Layout of a rainwater drainage system is given. Design sewer BE by using the


following information:
Project return period: Tr = 10 yr
Time of concentration for all areas = 10 min
The maximum allowable velocity in the sewers: 4 m/s
Flow duration in channels between two successive manholes: 2 min
The Manning roughness coefficient n = 0.016
The slope of BE: 4%
Commercial pipe with 25 mm increments
i= 90(Tr/tc)0.5
Tr: return period (yr)
Tc: time of concentration (min)

1
9.06.2023

2
9.06.2023

3
9.06.2023

A sanitary sewer system as shown will be design for the


year 2030. It is assumed that 80% of the supplied water
will return to the sewer system. The population of the
town at 1990 and 2000 are 51000 and 63500 respectively.
A heavy storm would yield a contribution of 1.0 lit/s/ha of
rainfall. A constant groundwater infiltration of 0.4 lit/s/ha
to the system is expected.
The minimum and maximum flow velocity are 0.6 m/s and
3.5 m/s respectively. Design pipe CD. PFmax=3.8; PFdry=2.1;
SCD=0.05; n = 0.016; qmean=122.5 lit/day.cap

4
9.06.2023

5
9.06.2023