You are on page 1of 3

CISCA Prepares New Recommendations for

Seismic Restraint
By Lee Cumming, Chair, CISCA Seismic Steering Committee
Kelly Merz, ANCO Engineering, Inc.
Carl A. Wangman, CISCA Executive Vice President
and Judith Iacuzzi, CISCA Marketing/Communications Manager

With the support of the National tee anticipate that the Code for Zones the balance of 1990 and during 1991.
Science Foundation, the Ceilings and 3-4 will be modified as the testing and The current UBC Standard 47-18
Interior Systems Construction Asso- committee review continues through covers metal ceiling suspension used
ciation (CISCA) for the past seven
years has been conducting tests to
determine whether the current Uni-
form Building Code requirements for
suspended T-Bar ceiling seismic re-
straint is effective. The CISCA Seis-
mic Committee has recommended
changes to the Uniform Building Code,
particularly affecting Zones 0, 1 and
2.
CISCA originally researched and
drafted the first Standard for life safety
in seismic areas in 1972. This was
incorporated in the UBC in 1978.
More recently, CISCA officials, work-
ing with engineers at ANCO Engi-
neering, Inc., in Culver City, Califor-
nia, decided to review the original
standards, testing them for effective-
ness. The result of this recent research
is that CISCA now recommends clari-
fication of and changes in the UBC
for Zones 0-2. An article describing
CISCA’s new recommendations for
Zones O-2 appears in the November
issue of Interior Construction maga-
zine.
One of the issues identified by the
CISCA Seismic Committee is the need
for industry education on current UBC
Standards for seismic restraint of
ceilings. The following comments
review recommendations in the cur-
rent Standard, which does not distin-
guish between zones. The comments
are intended to clarify currently rec-
ommended procedures for Zones 3
and 4; however, like Zones 0-2, CISCA
leadership and the Seismic Commit-

46 November 1990/Construction Dimensions


primarily to support acoustical tile or figuration of ceiling system members Trapeze suspensions shall be a mini-
acoustical lay-in panels as follows: or assemblies and their connections mum of back-to-back 1-1/4 inch cold-
are such that calculations of their rolled channels for spans exceeding
1. SCOPE allowable load-carrying capacity can- 48 inches.
not be made in accordance with es- 2. Perimeter Hangers:
Suspended ceilings which are de- tablished methods of analysis, their The terminal ends of each cross
signed and constructed to support performance shall be established by runner and main runner shall be
ceiling panels or tiles, with or without test. supported independently a maximum
lighting fixtures, ceiling mounted air Evaluation of test results shall be of eight inches from each wall or ceil-
terminals or other ceiling mounted made on the basis of the mean values ing discontinuity with No. 12 gauge
services shall comply with the require- resulting from tests of not fewer than wire or approved wall support.
ments of this standard. three identical specimens, provided 3. Lateral Force Bracing:
Exceptions: the deviation of any individual test Where substantiating design cal-
1. Ceiling area of 144 square feet result from the mean value does not culations are not provided, horizon-
or less surrounded by walls which exceed plus or minus 10%. The allow- tal restraints shall be effected by four
connect directly to the structure above able load-carrying capacity as deter- No. 12 gauge wires secured to the
shall be exempt from the lateral load mined by test shall not exceed one main runner within two inches of the
design requirements of these stan- half of the mean ultimate test value. cross runner intersection and splayed
dards. 3. Substantiation: 90 degrees from each other at an angle
2. Ceilings constructed of lath and Each ceiling system manufacturer not exceeding 45 degrees from the
plaster or gypsum board, screw or nail shall furnish lateral loading capacity plane of the ceiling. A strut fastened
attached to suspended members that and displacement or elongation char- to the main runner shall be extended
support a ceiling on one level extend- acteristics for their systems, indicat- to and fastened to the structural
ing from wall to wall. ing the following: members supporting the roof or floor
a. Maximum bracing pattern and above. The strut shall be adequate to
2. MINIMUM DESIGN LOADS minimum wire sizes. resist the vertical component induced
b. Tension and compression force by the bracing wires. These horizon-
1. Lateral Forces: capabilities of main runner splices, tal restraint points shall be placed 12
Such ceiling systems and their cross runner connections and expan- feet on center in both directions with
connections to the building structure sion devices. the first point within six feet from
shall be designed and constructed to All tests shall be conducted by an each wall. Attachment of the restraint
resist a lateral force specified in Chap- approved testing agency. wires to the structure above shall be
ter 23 of the Uniform Building Code. adequate for the load imposed.
Connection of lighting fixtures to 3. INSTALLATION Lateral force bracing membranes
the ceiling system shall be designed shall be spaced to not interface with
for a lateral force of 100% of the 1. Vertical Hangers: horizontal piping or duct work that is
weight of the fixture. Suspension wires shall not be not provided with bracing restraints
2. Grid Members, Connectors and smaller than No. 12 gauge spaced at for horizontal forces. Bracing wires
Expansion Devices: four feet on center or No. 10 gauge at shall be attached to the grid and to the
The main runners and cross run- five feet on center along each main structure in such a manner that they
ners of the ceiling system and their runner unless calculations justifying can support a design load of not less
splices, intersection connectors and the increased spacing are provided. than 200 pounds or the actual design
expansion devices shall be designed Each vertical wire shall be attached load, whichever is greater, with a safety
and constructed to carry a mean ulti- to the ceiling suspension member and factor of two.
mate test load of not less than 180 to the support above with a minimum 4. Perimeter Members:
pounds or twice the actual load, which- of three turns. Any connection device Unless perimeter members are a
ever is greater, in tension with a 5- at the supporting construction shall structural part of the approved sys-
degree misalignment of the members be capable of carrying not less than tem, wall angles or channels shall be
in any direction, and in compression. 100 pounds. considered as aesthetic closers and
In lieu of 5-degree misalignment, the Suspension wires shall not hang shall have no structural value assessed
load may be applied with a 1-inch more than one in six out-of-plumb to themselves or their method of at-
eccentricity on a sample not more unless countersloping wires are pro- tachment to the wall. Ends of main
than 24 inches long each side of the vided. Wires shall not attach to or runners and cross members shall be
splice. The connections at splices and bend around interfering material or tied together to prevent their spread-
intersections all shall be of the me- equipment. A trapeze or equivalent ing.
chanical interlocking type. device shall be used where obstruc- 5. Attachment of Members to the
Where the composition or con- tions preclude direct suspension. Perimeter:

48 November 1990/Construction Dimensions


To facilitate installation, main shall be positively attached to the tion of modifying the current recom-
runners and cross runners may be ceiling suspension main runners or to mendations so that life safety can be
attached to the perimeter member at cross runners with the same carrying provided in a cost-effective manner.
two adjacent walls with clearance capacity as the main runners. The final approval process includes
between the wall and the runners Terminals or services weighing 20 review by the International Confer-
maintained at the other two walls or pounds but not more than 56 pounds, ence of Building Officials (ICBO) who
as otherwise shown or described for in addition to the above, shall have publish the Uniform Building Code,
the approved system. two No. 12 gauge hangers connected the Building Officials and Code Ad-
from the terminal or service to the ministrators International (BOCA)
4. LIGHTING FIXTURES ceiling system hangers or to the struc- who publish the National Building
ture above. These wires may be slack Code, and the Southern Building Code
Only “intermediate” and “heavy Terminals or services weighing Congress International (SBCCI), who
duty” ceiling systems as defined in more than 56 pounds shall be sup- publish the Standard Building Code.
Paragraph B may be used for the ported directly from the structure CISCA will continue to provide in-
support of lighting fixtures. above by approved hangers. formation on developments in this
All lighting fixtures shall be posi- critical area.
tively attached to the suspended ceil- 6. PARTITIONS
ing system. The attachment device
shall have a capacity of 100% of the Where the suspended ceiling sys-
lighting fixture weight acting in any tem is required to provide lateral
direction. support for permanent or relocatable
When “intermediate” systems are partitions, the connection of the par-
used, No. 12 gauge hangers shall be tition to the ceiling system, the ceiling
attached to the grid members within system members and their connec-
three inches of each comer of each tions, and the lateral force bracing
fixture. Tandem fixtures may utilize shall be designed to support the reac-
common wires. tion force of the partition from pre-
Where “heavy duty” systems are scribed loads applied perpendicular
used, supplemental hangers are not to the face of the partition. These
required if a 48-inch modular hanger partition reaction forces shall be in
pattern is followed. When cross run- addition to the loads described in
ners are used without supplemental Section 47.1811 of the Uniform Build-
hangers to support lighting fixtures, ing Code. Partition connectors, the
these cross runners must provide the suspended ceiling system and the lat-
same carrying capacity as the main eral form bracing shall all be engi-
runner. neered to suit the individual partition
Lighting fixtures weighing less than application and shall be shown or
56 pounds shall have, in addition to defined in the drawing or specifica-
the requirements outlined above, two tions.
No. 12 gauge hangers connected from
the fixture housing to the structure 7. DRAWINGS AND SPECIFICA-
above. These wires may be slack. TIONS
Lighting fixtures weighing 56
pounds or more shall be supported The drawings shall clearly identify
directly from the structure above by all systems and shall define or show
approved hangers. all supporting details, lighting fixture
Pendant-hung lighting fixtures shall attachment, lateral force bracing,
be supported directly from the struc- partition bracing, etc. Such definition
ture above using No. 0 gauge wire or may be by reference to this standard,
approved alternate support without or approved system, in whole or in
using the ceiling suspension system part. Deviations or variations must
for direct support. be shown or defined in detail.
Conclusion
5. MECHANICAL SERVICES CISCA officials, working with
ANCO Engineers, will review the
Ceiling mounted air terminals or above stated standards during the
services weighing less than 20 pounds course of 1990-1991 with the inten-

You might also like