You are on page 1of 11

MEP WORKS BILL OF QUANTITY

Project : Villa Debora


Location :Pererenan, Badung Bali

Total
No. Item Pekerjaan Sat Vol Harga
( Rp )
A SUMMARY
MEP

1 ELEKTRIKAL Ls 1

2 LIGHTNING PROTECTION Ls 1

3 PLUMBING Ls 1

4 AIR CONDITIONING ( AC ) Ls 1

5 VAC ( VENTILATION AIR CONDITIONING ) Ls 1

6 POOL Ls 1

TOTAL

Diajukan oleh,

……………………………..
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
A ELECTRICAL WORKS
A.1 PLN CONNECTION, ELECTRICAL PANELS AND FEEDER CABLES.
Supply, install and testing :
1 Low Voltage Main Distribution Panel (MDP) - include include Interlock, ATS & AMF module, metering Unit 1
and all accessories required as design drawings
2 Grounding , R maximum = 5 Ohm Set 1
3 Power Panel, Polyester Cabinet and all accessories required as design drawings (IP. 40 Indoor & IP
65 Outdoor) :
- PP - LIFT Unit 1
- LP - 2 Unit 1
- LP - 1 Unit 1
- PP - AC G Unit 1
- LP - G Unit 1
- PP - PUMP Unit 1
- PP - POOL Unit 1
- PP - AC 2 Unit 1
- PP - AC 1 Unit 1
Electrical Feeder cables, to include cable clamp, conduit & sparring pipe, cable lug and all accessories
required :

1 From KWH PLN to Main Distribution Panel (MDP) ; NYY 4 x 50 mm2 Mtr' 13
2 From Genset to Main Distribution Panel (MDP) ; NYY 4 x 35 mm2+ NYA 35 mm2 Mtr' 43
3 From MDP to :
- PP - LIFT NYY 4 x 2.5 mm2 + NYA 2.5 mm2 Mtr' 46
- LP-2 (2nd FLOOR) NYY 4 x 4 mm2 + NYA 4 mm2 Mtr' 47
- LP-1 (1st FLOOR) NYY 4 x 4 mm2 + NYA 4 mm2 Mtr' 7
- PP - AC G (AC GROUND FLOOR) NYY 4 x 16 mm2 + NYA 16 mm2 Mtr' 58
- LP G (GROUND FLOOR) NYY 4 x 2.5 mm2 + NYA 2.5 mm2 Mtr' 48
- PP - PUMP NYY 4 x 2.5 mm2 + NYA 2.5 mm2 Mtr' 54
- PP - POOL NYY 4 x 4 mm2 + NYA 4 mm2 Mtr' 61
4 From LP - 2 to :
- Solarhart 1,2 & 3 NYY 3 x 4 mm2 Lot 160
- Pompa Air Panas 1 & 2 NYY 3 x 4 mm2 Lot 966
5 From PP - AC G to :
- PP - AC 2 (2nd FLOOR) NYY 4 x 2.5 mm2 + NYA 2.5 mm2 Mtr' 50
- PP - AC 1 (1st FLOOR) NYY 4 x 4 mm2 + NYA 4 mm2 Mtr' 37
- Outdor VRV NYY 4 x 6 mm2 Lot 8
- IU G/1 NYY 3 x 2.5 mm2 Lot 8
- IU G/2 NYY 3 x 2.5 mm2 Lot 8
6 From PP - AC 2 to :
- OU2/1 NYY 3 x 4 mm2 Lot 22
- OU2/2 NYY 3 x 4 mm2 Lot 26
- OU2/3 NYY 3 x 4 mm2 Lot 36
- OU2/4 NYY 3 x 4 mm2 Lot 43
- OU/IU 2/1 NYY 3 x 4 mm2 Lot 16
- OU/IU 2/2 NYY 3 x 4 mm2 Lot 12
- OU/IU 2/3 NYY 3 x 4 mm2 Lot 9
- OU/IU 2/4 NYY 3 x 4 mm2 Lot 10
7 From PP - AC 1 to :
- IU1/1 NYY 3 x 2.5 mm2 Lot 22
- IU1/2 NYY 3 x 2.5 mm2 Lot 26
- IU1/3 NYY 3 x 2.5 mm2 Lot 36
- IU1/4 NYY 3 x 2.5 mm2 Lot 30
8 From PP - PUMP to :
- Panel Control Pompa NYY 4 x 2.5 mm2 + NYA 2.5 mm2 Lot 13
- Shallow Well Pump NYFGY 3 x 2.5 mm2 Lot 41
- Sewage Treatment Plan NYFGY 3 x 1.5 mm2 Lot 27
9 From PP - LIFT to :
- Panel Control Lift NYY 4 x 6 mm2 + NYA 10 mm2 Lot 42
- Panel Control Lift NYY 3 x 2.5 mm2 Lot 42

A.2 ELECTRICAL CABLE TRAY


#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
1 Tray Cable dim 300 x 100 mm Lot 54
2 Tray Cable dim 200 x 100 mm Lot 87
3 Tray Cable dim 150 x 100 mm Lot 16

B.1 CABLE INSTALLATION


Supply, install and testing :
1 Lighting cable installation internal, NYM 3x2.5 mm2 in HIC Clipsal 20mm. Point 279
2 Lighting cable installation external, NYY 3x2.5 mm2 Point 85
3 Pool Lighting cable installation, NYYHY 2x4 mm2 Point 18
4 GPO cable installation, NYM 3x2.5 mm2 in HIC Clipsal 20mm. Point 118
5 Exhaust Fan cable installation internal, NYM 3x2.5 mm2 in HIC Clipsal 20mm. Point 16
6 Ceiling Fan cable installation, NYM 3x2.5 mm2 in HIC Clipsal 20mm. Point 9

B.2 LIGHTING FIXTURE, CEILING FAN etc.


Supply, install and testing :
1 Indoor Lighting Nos 213
2 Hanging Lamp Nos 10
3 Outdoor Lighting Nos 85
4 Pool Lamp Nos 18
5 Strip Light Mtr 289
6 Ceiling Fan Nos 9

B.3 ELECTRICAL ACCESSORIES


Supply, install and testing :
1 Single Switch Nos 43
2 Double Switch Nos 31
3 Hotel Single Switch Nos 6
4 Hotel Double Switch Nos 25
5 Fan Speed Controler Nos 9
6 Dimmer Nos 1
7 Single GPO Shuko type , 100W, 1phase Nos 54
8 Double GPO Shuko type , 2x100W, 1phase Nos 37
9 Single GPO Floor type , 100W, 1phase Nos -
10 Duble GPO Floor type , 2x100W, 1phase Nos 9
11 Single GPO Floor type for Lamp Nos 10
12 Single GPO Shuko type for Hair Dryer 500W Nos 8

2 ELECTRONIC WORKS
A.1 DATA & IP TV WORK
Supply, install and testing :
1 Data & IP TV Equipmet such as : Lot 1
Cable SUTP CAT. 6 in + HIC from Router Modem to Data Server/MDR
- 1 unit Main Data Rack (MDR) for Data connection & IP Camera connection, include all accessories
required :
- 2 x Switch HUB 8 Port - Gigabit
-2 x Switch HUB 16 Port - Gigabit
- 1 x Switch HUB 24 Port - Gigabit
- 1 x UPS Back up power 1200 VA
5 DATA Access Point Unit 9

DATA & IP TV INSTALLATION WORK


1 DATA- distribution cable installation UTP Cat 6 in HIC Clipsal dia 20 mm. for 7 unit data Socket Outlet Mtr 138

2 Acces Point - distribution cable installation UTP Cat 6 in HIC Clipsal dia 20 mm for 9 unit Data Acces Mtr 346
Point .
3 IP TV- distribution cable installation UTP Cat 6 in HIC Clipsal dia 20 mm. for 4 Unit IPTV Socket Outlet Mtr 179

4 DATA / LAN Socket outlet Unit 7


6 TV Socket outlet Unit 4

A.2 IP CAMERA SYSTEM


Supply, install and testing :
1 IP Camera Equipmet such as : Lot 1
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
- 1 unit NVR 24 Channel + PoE & 2 x Monitor
- 1 unit Hardrive 4 TB
- 1 unit UPS Back up power 1200 VA

IP CAMERA INSTALLATION WORK


2 IP Camera day & night c/w support & acc Unit 13
1 IP Camera Cabling Installation SUTP Cat 6 + HIC Clipsal dia 20 mm for 13 Unit IP Camera mtr 532

A.3 TELEPHONE WORK


Supply, install and testing :
1 Telephone Equipmet such as : Lot 1
- 1 unit PABX; installed capacity max 3 COL - 8 Extension
- 1 unit Main Distribution Frame (MDF) ; c/w 20 pair Krone LSA terminal, Polyester Cabinet IP 54; to
include surge arrestor 10" and cabling from and to PABX
- 1 unit UPS Back up power 1200 VA
- 1 unit Single Line Telephone handset

TELEPHONE INSTALLATION WORK


1 TELEPHONE cable installation ITC 2x2x0.6mm² in HIC Clipsal dia 20 mm. Point 4
2 TELEPHONE Socket outlet Unit 4

B ELECTRONIC CABLE TRAY


Supply, install and testing :
1 Tray Cable dim 300 x 100 mm mtr 13
1 Tray Cable dim 200 x 100 mm mtr 57
2 Tray Cable dim 150 x 100 mm mtr 66

TOTAL
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
B LIGHTNING PROTECTION SYSTEM
1 Lightning Protection HeadRadius 50m unit 1
2 Lightining Pole on the top of building 3 mtrs high unit 1
3 Down Conductor NYY 70 Sqmm + HIC mtr 38

TOTAL
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
C PLUMBING & MECHANICAL WORKS
A.1 CLEAN WATER MAIN EQUIPMENT
Supply, install and testing :
1 Shallow Well Construction included chasing PVC AW Class dia 5" of 40 meters depth Unit 1
2 Shallawell Pump cap : 50 Lpm / 30 meter Head / 750 Watt Set 1
3 Pacage Booster Pump cap. 250 ltr/mnt,30 meters head,2.900 Rpm,power 3,5 KW,Operation parallel Set 1
alternate c/w Pressure tank
4 Floating Valve dia. 1" for Clean Water tank Nos 2
5 PPR/equivalent class PN-10, DN 32 mm Mtr' 24
6 PPR/equivalent class PN-10, DN 32 mm From PDAM Meter & Shallow well Pump to Clean Water Mtr' 82
Tank
7 PPR/equivalent class PN-10, DN 40 mm + DN 32 mm From the Pump into the Shallow Well Mtr' 24

8 Foot valve Ø 65 mm Nos 2


9 Foot valve Ø 32 mm Nos 1

B.1 COLD WATER


Supply, install and testing :
1 PPR/equivalent class PN-10, DN 50 mm Mtr' 19
2 PPR/equivalent class PN-10, DN 40 mm Mtr' 40
3 PPR/equivalent class PN-10, DN 32 mm Mtr' 90
4 PPR/equivalent class PN-10, DN 25 mm Mtr' 110
5 PPR/equivalent class PN-10, DN 20 mm Mtr' 128
6 Gate valves dia. 2 1/2 " Nos 1
7 Gate valves dia. 1/2 " Nos 1
8 Gate valves dia. 1 " Nos 1

B.2 HOT WATER


Supply, install and testing :
1 Solarhard Cap.200 litre c/w accessories Unit 3
2 Hot Water tank 500 litre c/w accessories Unit 1
3 Hot Water Pump cap. 60 litre/mnt ; head 15m,2.900 Rpm,power 700 Watt,operation 1 unit on and 1 Unit 2
unit stand by c/w thermocouple & thermostat sensor set
4 Hot Water Pump Return Unit 1
5 PPR/equivalent class PN-20, DN 40 mm Mtr' 6
6 PPR/equivalent class PN-20, DN 32 mm Mtr' 104
7 PPR/equivalent class PN-20, DN 25 mm Mtr' 102
8 PPR/equivalent class PN-20, DN 20 mm Mtr' 110
9 Gate valves dia. 1/2" Nos 10
10 Gate valves dia. 3/4" Nos 3
11 Gate valves dia. 1" Nos 1
12 Stainer dia. 1/2" Nos 3
13 Gate valves dia. 1 1/2" Nos 4
14 Check valves dia. 1 1/2" Nos 2
15 Flaxible Joint dia. 1 1/2" Nos 4
16 Strainer dia. 1 1/2" Nos 2
17 Header Ø 40 mm Unit 2

B.3 SEWAGE WATER PLUMBING


Supply, install and testing :
1 Sewage Treatment Plant Tank cap. 4m3/day Unit 1
2 PVC AW dia. 150 mm Mtr' 24
3 PVC AW dia. 100 mm Mtr' 79
4 PVC AW dia. 80 mm Mtr' 5
5 PVC AW dia. 65 mm Mtr' 34
6 PVC AW dia. 50 mm Mtr' 70
7 PVC AW dia. 40 mm vent Mtr' 21
8 PVC AW dia. 32 mm vent Mtr' 36
9 PVC AW dia. 25 mm vent Mtr' 50
10 Vent cup dia. 25mm Nos 3
11 Vent cup dia. 32 mm Nos 3
12 Clean Out dia. 100 mm, PVC Nos 8
13 Clean Out dia. 50 mm, PVC Nos 2
14 Absortion tank Nos 1
B.4 WASTE WATER PLUMBING
Supply, install and testing :
1 PVC AW dia. 100 mm Mtr' 27
2 PVC AW dia. 80 mm Mtr' 74
3 PVC AW dia. 50 mm Mtr' 75
4 PVC AW dia. 40 mm Mtr' 43
3 PVC AW dia. 32 mm vent Mtr' 14
4 PVC AW dia. 25 mm vent Mtr' 19
6 Floor Waste Gully dia. 2" Nos 20
7 Smart Drain Nos 20
8 P.Trap dia. 80mm Nos 1
9 Clean Out dia. 100mm, PVC Nos 1
8 CO Ø 80 mm Nos 3
10 Absortion Pit Nos 1

B.5 STORM WATER DRAINAGE PLUMBING


Supply, install and testing :
1 PVC AW dia. 200 mm Mtr' 51
2 PVC AW dia. 150 mm Mtr' 41
3 PVC AW dia. 100 mm Mtr' 123
4 PVC AW dia. 80 mm Mtr' 94
5 PVC AW dia. 50 mm Mtr' 61
7 Absorption Pit Unit 1
8 Bak Kontrol 400 x 400 Unit 5
3 Roof Drain dia. 80 mm Nos 20
4 Roof Drain dia. 100 mm Nos 1

TOTAL
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
D AIR CONDITIONING WORK
Supply, install and testing :
1 Outdoor VRV Cap. 124.000 BTUH Unit 1
2 Indoor Unit & Outdoor Unit Ceilling Canceled type Air Conditioner,capacity = 18.000 BTU/H . Unit 1

3 Indoor Unit Ceiling Mounted Duct type Air Conditioner,capacity = 19.100 BTU/H . Unit 2
4 Indoor Unit Ceiling Mounted Duct type Air Conditioner,capacity = 24.200 BTU/H . Unit 2
5 Indoor Unit & Outdoor Unit Ceilling Canceled type Air Conditioner,capacity = 28.000 BTU/H . Unit 2

6 Indoor Unit & Outdoor Unit Ceilling Canceled type Air Conditioner,capacity = 36.000 BTU/H . Unit 1

7 Indoor Unit Ceiling Mounted Duct type Air Conditioner,capacity = 40.000 BTU/H . Unit 1
8 Thermostat c/w STP AWG #18 cable control to indoor unit Set 5
9 Thermostart installation STP AWG #18 cable control c/w HIC Ø 20 mm² Point 4
10 Refnet Branch Joint Unit 4
11 NYY cable Ø 4 x 2.5 mm² control cable indoor to outdoor unit lot 4
12 Refrigerant piping, refnet joint & all accessories required with Aeroflex insulation 19 mm wall thickness mtr 55
for each pipe Size 3/4 " x 1 1/8 "
13 Refrigerant piping, refnet joint & all accessories required with Aeroflex insulation 19 mm wall thickness mtr 53
for each pipe Size 3/8 " x 7/8 "
14 Refrigerant piping, refnet joint & all accessories required with Aeroflex insulation 19 mm wall thickness mtr 99
for each pipe,Size 3/8 " x 5/8 "
15 Refrigerant piping, refnet joint & all accessories required with Aeroflex insulation 19 mm wall thickness mtr 16
for each pipe,Size 1/4 " x 1/2 "
16 Drain piping PVC AW dia. 3/4" with Aeroflex insulation 13 mm wall thickness mtr 114
17 Supply & Return Air Plenum Box c/w insulation Set 18
18 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 3
installation, Size 450 x 250 mm
19 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 4
installation, Size 400 x 250 mm
20 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 35
installation, Size 300 x 250 mm
21 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 12
installation, Size 250 x 250 mm
22 Supply & install Supply air duct box as drawing c/w Hanger, bolt ,and other accessories normally Unit 10
installation, Size 1.000 x 150 mm
23 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally Unit 4
installation,Size 1.000 x 150 mm
24 Supply & install Supply air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 25
installation,Flaxible duct Size 150 mm
25 Supply & install air linier Size 1.000 x 150 mm,Alluminium allow paints as architects request Unit 2

26 Supply & install return air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 100
installation, Size 300 x 250 mm
27 Supply & install return air duct as drawing c/w Hanger, bolt ,and other accessories normally mtr 12
installation, Size 250 x 250 mm
28 Supply & install return air duct box as drawing c/w Hanger, bolt ,and other accessories normally Unit 16
installation, Size 1.000 x 150 mm
29 Supply & install Return air grille Size 1.000 x 150 mm,Alluminium allow paints as architects request Unit 14

30 Supply & install Return air grille Size 650 x 150 mm,Alluminium allow paints as architects request Unit 3

31 Supply & install air Grille Size 650 x 150 mm,Alluminium allow paints as architects request Unit 2

32 Supply & install air linier Size 1.000 x 150 mm,Alluminium allow paints as architects request Unit 12

33 Supply & install Fresh air flexible c/w fresh grille lot 9

TOTAL
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
E EXHAUS FAN WORK
1 Exhaust Fan 150 CFM,power 0.030 KW,220 V/1Ph/50Hz,1400 Rpm,50 PA Ceiling type c/w Unit 2
Pipe Connection & grill
2 In Line duct Fan 500 CFM,power 0.300 KW,220 V/1Ph/50Hz, 1400 Rpm,60 PA. Unit 1

3 Exhaust Fan 80 CFM,power 0.030 KW,220 V/1Ph/50Hz,1400 Rpm,50 PA Ceiling type c/w Unit 4
Pipe Connection & grill
4 Exhaust Fan,power 100 CFM,0.040 KW,220 V/1Ph/50Hz,1400 Rpm,50 PA Ceiling type c/w Unit 7
Pipe Connection & grill
5 Exhaus air duct as drawing c/w Hanger, bolt ,and other accessories normally installation,size mtr 18
200 x 200 mm
6 Exhaus Air Grille size 200 x 200 mm Unit 3

TOTAL
#REF!
#REF!
#REF!

Harga Total
No. Item Pekerjaan Sat Vol Satuan Harga
( Rp ) ( Rp )
F MAIN SWIMMING POOL
Plumbing Equipment
1 Pool Water Circulation pump 1.5 HP unit 2
2 Sand Fliter unit 2
3 Salt Chlorinator Deleted
4 Hair Catcher unit 2
5 Anti Vortex Main Drain w/ hydrostatic relief valve & collector tube unit 3
6 Wall Inlet Nozzle Ajustable unit 12
7 Floor Inlet Nozzle Ajustable unit 8
8 Vacum Inlet unit 2
9 PVC Ball Valve 3" unit 2
10 PVC Ball Valve 2" unit 28
11 PVC Non return valves 2" unit 4
12 PVC Union Joint unit 12
13 Foot Valve 3" unit 2
14 Check valve 3/4" unit 2
15 Gate valve 3/4" unit 2
16 Floating valve 3/4" + gate valve unit 2
17 Stainless Steel Leaf Screen unit 2
Plumbing & Electric Installation
18 PVC AW dia. 3" mtr 26
19 PVC AW dia. 2" mtr 487
20 Suction & Discharge Header unit 4
21 Pool Equipment Power installation titik 2
22 Pool Light Installation titik 2

Total

You might also like