Professional Documents
Culture Documents
Rajagopal and Thiyyakkandi (2021)
Rajagopal and Thiyyakkandi (2021)
Transportation Geotechnics
journal homepage: www.elsevier.com/locate/trgeo
Department of Civil Engineering, Indian Institute of Technology, Palakkad, Kerala 678623, India
Keywords: Back-to-Back Mechanically Stabilized Earth (MSE) walls have become an integral part of the transportation
Back-to-back MSE wall infrastructures, especially as ramps, bridge approaches, etc. The permeability, strength and constructability
Hybrid-fill attributes of well-graded granular soils have rendered them as the most suitable fill material for MSE walls.
Marginal fill However, the scarcity of such good materials compels the usage of locally available soil with high fine content
Finite element modelling
(marginal fill) having low permeability and high plasticity characteristics, which can cause excessive wall de
Matric suction
Rainwater infiltration
formation or even failure, if not adequately designed and constructed. This study focused on the assessment of
Fully coupled flow-deformation analysis overall performance of back-to-back MSE walls with a trapezoidal marginal fill zone surrounded by a near-
optimal amount of select fill (i.e., hybrid-fill) as an alternative to the wall with select fill only. The behaviour of
hybrid-fill wall at the end of construction and during heavy rainfall infiltration were investigated through finite
element modelling and compared with fully select fill and fully marginal fill walls. The study revealed that the
overall performance (i.e., horizontal and vertical deformations, reinforcement tension, and factor of safety) of
the hybrid-fill wall with 31–47% select fill is much better than that of fully marginal fill wall, especially during
the extreme rainfall infiltration scenario. The response of this hybrid configuration is even comparable with that
of fully select fill wall, suggesting the proposed hybrid-fill wall as a stable as well as cost-efficient alternative
system in locations where sufficient quantity of well-graded soil is not readily available.
Introduction permitted [1,16]. For back-to-back MSE walls, FHWA [16] has directed
to practice high quality select fill even in retained zone, provided the
Back-to-Back Mechanically Stabilized Earth (MSE) wall is a type of distance between the reinforced zones is less than half of the total
reinforced earth structure, widely used for transportation advancement height of wall. Similarly, IRC: SP-102 [36] has recommended select fill
projects like highway ramps and bridge-approach embankments. The completely for up to four-lane highways.
design of such structures is generally performed following the guide However, due to the shortage of such select fill materials in the
lines of Federal Highway Administration (FHWA) [16], American As locality and associated transportation cost and time, locally available
sociation of State Highway and Transportation Official (AASHTO) [1], marginal soils are often used as reinforced and retained backfill. It is
or British Standards (BS 8006-1) [21], in which foremost re evident from the existing literature that about 50% to 75% of total cost
commendations are given for the quality of backfill. As per the design is linked with backfill [40] and therefore, considerable cost reduction
guidelines of FHWA [16], AASHTO [1], BS 8006-1 [21] or Indian Road (20–30%) can be achieved by using in-situ or locally available soil in
Congress (IRC: SP-102) [36], well-graded granular soil or select fill is stead of bringing in high quality well-graded granular soil [23]. For
the most recommended backfill material for the reinforced zones, in instance, India is abundant of tropical soil due to its location and cli
which % fines and plasticity index (PI) should not exceed 15% and 6%, mate, and this soil is utilized as backfill material although not com
respectively. National Concrete Masonry Association (NCMA) [47] al plying with the select fill guidelines due to the scarcity of well-graded
lows the use of fill with fine content up to 35%, with appropriate granular material. Lateritic soil is one of the varieties of tropical soil,
provision for drainage. The backfill soils that are not meeting the formed by extensive deep weathering of gneiss, which covers major
guidelines of select fill are categorized as marginal fill. However, for portion of Kerala State, India (Western Ghats region) [49]. Due to its
retained zone of single-faced MSE wall, soil with % fines, liquid limit, ample availability in this region, lateritic soil is widely used as fill
and plasticity index not exceeding 50%, 40% and 20%, respectively, are material albeit it exhibits low permeability due to high fine content.
⁎
Corresponding author.
E-mail addresses: gopika795@gmail.com (G. Rajagopal), sudheesh@iitpkd.ac.in (S. Thiyyakkandi).
https://doi.org/10.1016/j.trgeo.2020.100445
Received 7 May 2020; Received in revised form 14 August 2020; Accepted 10 September 2020
Available online 17 September 2020
2214-3912/ © 2020 Elsevier Ltd. All rights reserved.
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
2
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
on such partial replacement of fill materials for back-to-back MSE walls. Table 1
This research focused on studying the effectiveness of potential hybrid- Geometric details of cases considered for the study.
fill combination, specifically, marginal soil core (trapezoidal cross- Cases W/H H (m) W (m) L (m) b h
section) surrounded by well-graded select fill, on improving the overall
infiltration characteristics and thus the performance of back-to-back Case A, L < H/2 1.7 4 6.8 1.2 0.4B – 1B 0.5H – 1H
6 10.2 1.8
MSE wall without altering the drainage properties of marginal fill.
10 17 3
Two-dimensional finite element (FE) program, PLAXIS 2D, was used Case B, L ≈ H/2 2 4 8 2.4 0.4B – 1B 0.5H – 1H
for the numerical modelling of MSE wall. The marginal fill for the study 6 12 3.6
was the typical lateritic soil collected from Palakkad district of Kerala 10 20 6
State, India and the select fill used was the freely draining sandy soil. Case C, L > H/2 3 4 12 6.4 0.6B – 1B 0.5H – 1H
6 18 9.6
Firstly, plastic analyses without considering suction were carried out to
10 30 16
identify the near-optimal geometric configuration immediately after
construction. Subsequently, rainwater infiltration was simulated con
sidering the effect of suction for the selected hybrid walls (from initial cases, the inclined face of trapezoidal zone was assumed parallel to the
analyses) to appraise its performance towards extreme seasonal Rankine’s failure line of select fill zone. Reinforcement length was fixed
changes. The reported rainfall data during the recent flood (2018) in (equals to 0.7H) and provided at a vertical spacing of 0.6 m on both
Kerala State [26] was adopted for infiltration analyses. The nearly op sides. The analyses of the following cases, (i) select fill in both reinforced
timal dimensions for the marginal core in terms of total width and and retained zones (fully select fill wall); (ii) marginal fill in both zones
height of the back-to-back MSE wall were established using the results (fully marginal fill wall); and (iii) select fill in reinforced zone and
of analyses. marginal fill in retained zone (retained-marginal fill wall), were also
carried out for comparison.
Proposed hybrid back-to-back MSE wall
Experimental characterization of hybrid core fill
Back-to-Back MSE wall with three heights (4 m, 6 m, and 10 m) and
three width-to-height (W/H) ratio (1.7, 2.0, and 3.0) were considered in The core fill material used for the numerical modelling of hybrid-fill
the study. Fig. 2 illustrates the schematic diagram of proposed hybrid-fill wall was typical lateritic soil from Palakkad district of Kerala State,
wall with trapezoidal core of marginal fill surrounded by well-graded India. A series of laboratory tests were carried out on this soil to ex
select fill. FHWA [16] highly recommends the usage of select fill even in amine the geotechnical properties, adopting ASTM test procedures. This
the retained zone if the spacing between the reinforced zones (L) is less includes sieve analysis and hydrometer analysis [10,12], Atterberg
than one-half of the wall height (H). Consequently, the present study limits test [8], standard Proctor test [11], direct shear test [7] and
investigated the following three back-to-back wall cases: (A) L < H/2; falling head permeability test [35]. The soil was classified as clayey
(B) L ≈ H/2; and (C) L > H/2. Note that W/H ratios of 1.7, 2.0 and 3.0 sand (SC), according to unified soil classification system (USCS) [6],
considered in this study are corresponding to Case A [L/(H/2) = 0.6], with liquid limit and plasticity index of 34% and 13%, respectively. As
Case B [L/(H/2) = 1.2] and Case C [L/(H/2) = 3.2], respectively. seen from particle size distribution curve (Fig. 3), 37% of particles pass
Table 1 lists the details of different geometric cases considered in the through #200 sieve. Hence, the soil properties show deviations from
study. A drainage layer of 0.3 m thickness, as recommended by FHWA the recommendations given by FHWA [16], AASHTO [1], BS 8006-1
[16], was provided behind the facing. The trapezoidal marginal core- [21] or IRC: SP-102 [36] for select fill. The summary of the experi
base-width (b) and height (h) are the two varying parameters in the mental results is given in Table 2.
proposed hybrid-fill system and are represented as a fraction of total In addition, to simulate the behaviour of hybrid-fill wall under
backfill width (B) and total wall height (H), respectively; i.e., b = αB and rainwater infiltration and depict its transition from unsaturated to fully
h = βH, where, α and β are variables ≤ 1. The analyses began with the saturated state, Soil Water Characteristic Curve (SWCC) for the hybrid
case of trapezoidal core with b = 1B and h = 1H and was repeated by core fill (lateritic soil) was required, which gives the relationship be
reducing b with a decrement of 0.1B (0.05B in some cases) until the stage tween matric suction and degree of saturation. Filter paper technique
where marginal fill is completely outside the reinforced zone. Similarly, h following ASTM D5298 – 16 [9] was adopted to determine the SWCC and
was reduced from maximum height (H) to half height of the wall (0.5H). is shown in Fig. 4. Several hydraulic models are available in literature for
About 200 models were simulated by varying W, H, b, and h; in all the fitting the experimental data into a smooth SWC curve; Brooks and Corey
3
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
100 where S, Sres and Ssat are the degree of saturation at given state, residual
Sample I state and fully saturated state, respectively; ga and gn are the SWCC fitting
90
Sample II parameters; pw and γw are the pore water pressure and unit weight of
80 water, respectively.
70 Relative permeability (i.e., ratio of permeability at given saturation
60 to saturated permeability) of the soil corresponding to the different
% Finer
20 (2)
10 where Se =
S Sres
, is the effective degree of saturation and gl is HCF
Ssat Sres
0 fitting parameter.
0.0001 0.001 0.01 0.1 1 10
Numerical Modelling
Particle Size (mm)
Fig. 3. Particle size distribution curve. Hybrid-fill wall – construction simulation
100
Experimental Data Validation of construction modelling procedure using full scale experimental
90 data
Degree of Saturation (%)
80 Fitted Curve
Firstly, the modelling procedure of MSE wall construction adopted
70 in this study was validated by simulating a full-scale study on single-
60 faced MSE wall constructed at Royal Military College of Canada
50 (RMCC) reported by Bathurst et al. [13]. Note that the single-faced MSE
wall data had to be used in this study as no full-scale study results on
40
back-to-back (double-faced) MSE walls were available in literature.
30 Hatami and Bathurst [32] have also utilized this experimental data for
20 the development and verification of their numerical model. The test
10 wall was constructed to a height of 3.6 m with 8° facing batter. Solid
0 masonry blocks (200 mm × 300 mm × 150 mm) and biaxial poly
0.1 1 10 100 1000 10000 100000 propylene geogrids with very low tensile strength (axial stiffness = 97
kN/m) was used as facing and reinforcement, respectively. The re
Matric Suction (kPa) inforcement was extended to a length of 2.52 m with 0.6 m vertical
spacing. Horizontal displacement was measured using displacement
Fig. 4. Soil Water Characteristic Curve of typical lateritic soil.
potentiometers mounted against the wall face; whereas, reinforcement
strain was measured with both strain gauges and extensometers. Ma
[20], van Genuchten [56], Fredlund and Xing [27] are some of the terial properties used for modelling were as per the actual experimental
widely used models. In the present study, van Genuchten - Mualem data [13,32], as given in Table 3. Soil layer with a lift thickness of
model, Eq. (1) [56] was used to fit the experimental data. 0.15 m was placed in each phase of staged construction. Rigid interface
was considered for geogrid and backfill; whereas an interface reduction
pw
gn (1 gn )/ gn factor of 0.7 was assumed for facing and backfill.
S = Sres + (Ssat Sres ) 1 + ga Fig. 5 shows the numerical model of the wall and Fig. 6 presents a
w (1) comparison of the FE results with the experimental results. As can be
Table 3
Backfill soil properties [13,32].
Parameters Unit weight, γ (kN/m3) Cohesion (kN/m2) Friction angle (°) Dilation angle (°) Young’s Modulus (kN/m2) Poisson’s ratio
4
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
Numerical
0.8
Hatami and Bathurst (2005) Strain guage
Strain (%)
0.5
4 Extensometer
0.2 Numerical
-0.1
0.0 0.5 1.0 1.5 2.0 Layer 4
3 (2.1 m above the base)
Distance from facing (m)
Elevation (m)
1.5
Strain (%)
1.1
2 0.7
0.3
-0.1
0.0 0.5 1.0 1.5 2.0 Layer 3
1 (1.5 m above the base)
Distance from facing (m)
1.0
Strain (%)
0.6
0 0.3
0 2 4 6 8 10 -0.1
Facing Displacement 0.0 0.5 1.0 1.5 2.0 Layer 2
(mm) (0.9 m above the base)
Distance from facing (m)
(a) (b)
Fig. 6. (a) Facing displacement; (b) Reinforcement strain [13,32].
Table 4 Table 5
Comparison of predicted and measured [13,32] facing displacements. Soil properties used for the FE modelling of proposed hybrid-fill wall.
Elevation (m) Measured displacement Predicted Difference (%) Soil properties Marginal fill Select fill Foundation soil
(Hatami and Bathurst displacement (mm)
[32]) (mm) Model Mohr- Mohr- Mohr-Coulomb
Coulomb Coulomb
3
0.3 2.3 2.9 26 Unit weight, γ (kN/m ) 17.4 * 16.8 18.85
0.9 3.7 4.5 21.6 Angle of internal friction, ϕ' (0) 31.5 44 45
1.5 5.1 5.4 5.8 Cohesion, c' (kN/m2) 2.6 1 15
2.1 5.6 5.5 1.8 Dilation angle, ψ (0) 0 11 15
2.7 5.4 4.4 18.5 Young’s modulus, E (kN/m2) 15,700 56,667 110,000
3.3 2.3 2.7 17.4 Poisson’s ratio, µ 0.3 0.25 0.3
Coefficient of permeability, k 0.04752 20 2
(m/day)
5
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
4 6 10 Select
Retained Marginal
H=4m 5 H=6m 8 b = 0.6B
3
Elevation (m) H = 10 m b = 0.7B
Elevation (m)
Elevation (m)
4 b = 0.8B
6 b = 0.85B
2 3 b = 0.9B
b = 1B
4 Marginal
2
1
1 2
0 0 0
0 5 10 15 0 7 14 21 28 35 0 40 80 120
Facing displacement Facing displacement Facing displacement
(mm) (mm) (mm)
Fig. 8. Variation in facing displacement with core-base-width, b (Case B; W/H = 2; h = 1H).
4 h = 0.5H
sponse of full-scale MSE wall with reasonable accuracy.
h = 0.7H
3 h = 0.9H
Performance of hybrid-fill wall immediately after construction
h = 1H
2 Analysis of proposed hybrid walls with varying dimensions (W, H, b,
Marginal
and h) were carried out to evaluate their performance immediately after
1 the construction and to identify a nearly optimal dimension for the
marginal trapezoidal core. An elastic-plastic deformation analysis using
0 plastic calculation type was adopted. Soil properties used for the
0 5 10 15 20 25 30 35 modelling are listed in Table 5. Properties of select fill used for the
modelling were taken from Bathurst et al. [13,32] and the same was
Facing displacement (mm) used as drainage layer as well with a permeability of 20 m/day. High
quality foundation soil (hard stratum) was assumed here to eliminate its
Fig. 9. Variation in facing displacement with core-height, h (Case C; W/H = 3;
influence on the overall behaviour of wall. The matric suction in the
H = 6 m and b = 0.9B).
marginal soil was ignored in the first series of analysis as it has positive
impact on the overall stability of the system and will be lost upon sa
seen from the Fig. 6, the facing displacement and mobilized re turation. However, after establishing the nearly optimal geometry of
inforcement strain from numerical analysis were in agreement with the the marginal core based on the initial analyses (i.e., ignoring suction), a
experimental data. Table 4 compares the experimental and numerical comparative study was also undertaken to investigate the performance
facing displacement values. Note that the facing displacement was of wall with the suction of marginal fill.
measured from the time of placement of each facing unit to the end of Simulation of the hybrid-fill wall model followed similar modelling
6
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
Settlement (mm)
0
Case A; W/H = 1.7
-40
Surface
-80
-120
-160
Distance from centre of wall (m)
0 2 4 6 8 10
Select
0
Settlement (mm)
Retained Marginal
Case B; W/H = 2
-40 b = 0.7B
Surface
b = 0.8B
-80 b = 0.9B
-120 b = 1B
Marginal
-160
Distance from centre of wall (m)
0 5 10 15
Settlement (mm)
0
Case C; W/H = 3
-40
Surface
-80
-120
-160
Fig. 10. Variation in surface settlement with core-base-width, b (H = 10 m; h = 1H).
0
h = 0.5H
-5
Surface
h = 0.7H
-10 h = 0.9H
-15 h = 1H
-20 Marginal
Fig. 11. Variation in surface settlement with core-height, h (Case C; W/H = 3; H = 4 m and b = 0.9B).
6 6 6
Case A; W/H = 1.7 Case B; W/H = 2 Select
Case C; W/H = 3
Retained Marginal
5 5 5 b = 0.57B
b = 0.7B
Elevation (m)
Elevation (m)
Elevation (m)
4 4 4 b = 0.8B
b = 0.85B
b = 0.9B
3 3 3 b = 1B
Marginal
2 2 2
1 1 1
0 0 0
0 5 10 15 0 5 10 15 0 5 10 15
Maximum mobilized Maximum mobilized Maximum mobilized
tension (kN/m) tension (kN/m) tension (kN/m)
Fig. 12. Maximum mobilized tension in reinforcement layer at different elevations (h = 1H).
7
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
10
Tension (kN/m)
Layer 5 (2.8 m above the base)
5
Marginal
0 Select
0 1 2 3 4 5 Hybrid
Distance from facing (m) Retained Marginal
15
Tension (kN/m)
6 Table 6
SWCC fitting parameters.
Marginal
5 Hydraulic properties Marginal fill Select fill Foundation soil
Select
Hybrid Ssat 1 1 1
4
Elevation (m)
Sres 0 0 0
Retained Marginal ga (m−1) 1.5 14.5 3
3 Marginal Theorectical gn 1.27 2.68 3
gl 0.5 0.5 0.5
Select Theorectical
2
technique to obtain the global factor of safety (FS) [19,30]. Deforma
1 tion responses, reinforcement load, lateral earth pressure distribution
and safety factor for each hybrid configuration were investigated. Si
mulated model of hybrid wall (Case B, H = 6 m, b = 0.9B and
0
h = 0.9H) is shown in Fig. 7.
0 10 20 30 40 50 Fig. 8 shows the variation of horizontal displacement along the fa
Lateral earth pressure (kN/m²) cing of wall (Case B; H = 4 m, 6 m, and 10 m) with core-base-width, b
for a constant h = 1H. As evident from the figure, the response of walls
Fig. 14. Lateral earth pressure behind the reinforced zone (Case C; W/H = 3;
with b < 0.9B was closer to that of a complete select fill wall. Similar
H = 6 m; b = 0.9B; h = 1H).
responses were noticed for Case A and Case C as well. The displacement
response of wall with “select fill in reinforced zone and marginal fill in
settings used for the validation. Initial phase (in-situ stress state) was retained zone” (Retained Marginal in Fig. 8) was essentially the same as
simulated by adopting k0 loading type. As construction progresses, each that of fully select fill wall. The variation of facing displacement with
layer of soil with a lift thickness of 0.2 m along with facing block marginal core-height (h) at a constant core-base-width of 0.9B (Case C
(200 mm height × 300 mm width) and reinforcement (axial stiffness and H = 6 m) is shown in Fig. 9. It is apparent from the figure that no
1100 kN/m) was placed. An interface reduction factor (Rinter) of 1 was much variation in horizontal displacement occurred with increase of h.
taken between geogrid and soil, and 0.7 between facing and soil as To compare the influence of hybrid-fill configuration on the settle
adopted in the validation. After the simulation of wall construction in ment response, variation in surface settlement of walls with different
stages, a safety analysis was performed using the ϕ-c reduction combinations of b and h were plotted. Fig. 10 shows surface settlement
Factor of Safety
8
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
6
Hybrid without Suction
5 Hybrid with Suction
Elevation (m)
4 Marginal without Suction
Marginal with Suction
3 Select without Suction
2 Select with Suction
Retained Marginal without Suction
1 Retained Marginal with Suction
0
0 10 20 30
Facing Displacement (mm)
Fig. 16. Effect of suction on facing displacement (Case C; W/H = 3; H = 6 m; b = 0.85B; h = 1H).
3.0
Factor of Safety
Without Suction
2.5
With Suction
2.0
1.5
1.0
Marginal Hybrid Retained Select
Marginal
Type of Backfill
Fig. 17. Effect of suction on factor of safety (Case C; W/H = 3; H = 6 m; b = 0.85B; h = 1H).
Table 7 in case of hybrid wall. It should be noted that the observed surface
Strength and hydraulic properties of soil and geotextile used for modelling settlement was only due to the vertical deformation of MSE fill as the
[5,51]. foundation soil was modelled as hard stratum. The similar settlement
Soil properties Backfill Geotextile responses were observed for other wall heights as well (H = 4 m and
6 m).
Maximum load mobilized in the reinforcement layers is another key
3
Unit weight, γ (kN/m ) 17.9 –
Angle of internal friction, ϕ' (0) 35 –
factor affecting the overall wall performance. Fig. 12 depicts the max
Cohesion, c' (kN/m2) 0 –
Dilation angle, ψ (0) 0 –
imum mobilized tension in the reinforcement layers for Case A, Case B,
Tensile strength (kN/m) – 12 and Case C walls with H = 6 m, h = 1H and varying b. From the figure,
Elongation at failure (%) – 83 it is clear that, the variation of maximum mobilized tension in each
Coefficient of permeability, k (m/sec) 4.9 × 10−7 0.00058 layer with core-base-width (b) was not significant when b ≤ 0.9B. In all
Ss 1 1
the cases, the response of retained marginal fill wall is similar to that of
Sres 0 0
ga (m−1) 1.118 19.62 fully select fill wall.
gn 1.11 3.03 Distribution of tension along the reinforcement of hybrid wall with
gl 0.5 0.5 b = 0.9B and h = 1H at two different elevations is illustrated in Fig. 13
(Case C; W/H = 3; H = 6 m). As evident from the figure, the hybrid
wall shows good agreement with the complete select fill wall and re
profiles for walls with varying b and a constant h = 1H (H = 10 m; tained-marginal fill wall, even though some portion of the reinforced
Case A, B, and C). Similarly, Fig. 11 presents the settlement profiles for zone was occupied by marginal fill.
different h keeping b constant (b = 0.9B). The variation of surface It is also important to study the variation of earth pressure dis
settlement with the increase in core-base-width (b) was more pro tribution for the proposed hybrid-fill wall as it can influence both ex
nounced at larger base width (> 0.9B); no considerable difference was ternal and internal stability of the wall. The variation of earth pressure
observed with the variation of b below 0.9B. In all the hybrid cases, the behind the reinforced zone of hybrid wall having b = 0.9B and h = 1H
observed surface settlement was less than that for complete marginal is presented in Fig. 14 along with that observed for fully select fill, fully
fill wall. As in the case of face displacement, the influence of core- marginal fill, and retained-marginal fill cases. Also shown in the figure
height (h) on surface settlement was minimal. An interesting observa are the Rankine’s active earth pressure distribution for fully select fill
tion was that the differential surface settlement for hybrid wall was and fully marginal fill walls. As expected, earth pressure distribution for
negligible even when compared to conventional select fill wall, though hybrid wall follows that for marginal wall, as the marginal soil occupies
the observed total surface settlement was higher. This is attributed to major portion behind the reinforced zone. Hence, for external stability
the increased deformation of the central region, which is marginal soil consideration (e.g., fixing the length of reinforcement), it is more
9
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
Fig. 18. Numerical model of test wall [5,51] simulated in PLAXIS 2D.
1.05 10
1.00 0
Porewater pressure (kPa)
-10
0.95
NVWC (Experimental)
-20
0.90 NVWC (Predicted)
θ/θs
appropriate to use earth pressure coefficient of marginal soil. From the analyses of hybrid-fill models under different sets of
Following the simulation of construction phase, a strength reduction geometric configurations discussed above, marginal core with a base-
analysis (ɸ-c reduction) implemented in PLAXIS 2D was adopted to width of 0.85B to 0.9B and height of 1H is found to be a satisfactory
determine the global safety factor (FS) of the system. The variation of FS configuration. In order to evaluate the relative performance of hybrid-
of hybrid model with normalized core-base-width (b/B) is shown in fill wall with the consideration of matric suction, additional analyses
Fig. 15 for 4 m, 6 m and 10 m high walls (Case C), along with FS for were carried out. The van-Genuchten model was used to simulate the
fully select fill, marginal fill and retained-marginal fill walls. As can be hydraulic parameters. Table 6 lists the SWCC parameters used for the
seen from the figures, FS of hybrid fill wall was closer to that of select modelling. Note that these parameters for the marginal fill were ob
fill wall as long as b ≤ 0.85B in comparison to the complete marginal tained by fitting the experimental results using Eq. (1). For select fill
fill wall. Though FS of hybrid fill wall (with b ≤ 0.85B) was less than and foundation soil these parameters were taken from Vahedifard et al.
the FS of retained-marginal fill wall, the difference was minimal. [55]. Water table was assumed at 2 m below the ground surface to
10
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
2 1440 min (Predicted) pore-water pressure; and χ – matric suction coefficient (assumed as
24500 min (Experimental) effective degree of saturation, Se). The program assumes pore air
1.5 24500 min (Predicted) pressure = 0 [19,28]. Here, (pa – pw) is defined as matric suction and
1 30300 min (Experimental) (pa pw ) is represented as effective suction.
30300 min (Predicted)
0.5
T krel sat S S pw
0 k ( pw + w g) n =0
wg Kw pw t (4)
0 0.3 0.6 0.9 1.2 1.5
Time (min)
where ρw – density of water; g – acceleration due to gravity; ksat – sa
Fig. 20. Variation in displacement along reinforcement layer 4 (1.05 m from turated permeability; n – soil porosity; Kw – bulk modulus of water; and
bottom) with infiltration.
S – degree of saturation.
Several studies on the response of MSE walls and soil slopes utilizing
introduce suction with respect to head. this analysis type have been reported in literature [31,55,60]. Hamdhan
Fig. 16 compares the effect of suction on the facing displacement of and Schweiger [31] have validated the adequacy of this analysis ap
selected hybrid-fill wall (b = 0.85B and h = 1H) with that of complete proach by carrying out the numerical modelling of a fully instrumented
select fill and marginal fill walls. As evident from the figure, the facing unsaturated soil slope subjected to rainfall. In the present study, the
displacement decreases in both hybrid-fill and fully marginal fill walls validation of this calculation type was conducted by simulating water
as suction imparts an apparent cohesion to the system. The maximum infiltration study on a full scale MSE wall carried out in Geosynthetics
facing displacement of the hybrid-fill wall is found to be still less than Laboratory of the Sao Carlos School of Engineering at the University of
that of marginal fill wall, although the degree of reduction is more Sao Paulo, Brazil [5,51].
pronounced in the latter. The global factor of safety (FS) of the walls The wall was constructed to a height of 1.65 m and a width of
with and without suction is presented in Fig. 17 for Case C (H = 6 m 1.55 m on a rigid concrete foundation. Clayey sand (SC) with % fines
and b = 0.85B). As expected, increased FS due to suction was more and plasticity index (PI) of 44% and 21%, respectively, were used as
evident in the case of complete marginal fill in comparison to the hy backfill. Non-woven needle-punched geotextile was used as reinforce
brid-fill case. However, the difference in FS between hybrid-fill and ment, and the same was wrapped around the backfill to form facing.
marginal fill walls was negligible. No noticeable reduction in facing Further, a protective coat of shotcrete (thickness: 0.05 m to 0.08 m) was
displacement and increase in FS was observed for fully select fill wall, as provided on the wrap-around facing of the wall. The reinforcement was
suction was nearly zero. extended to the whole width of the wall and was placed at a vertical
However, as mentioned previously, majority of the reported failures spacing of 300 mm. Infiltration was simulated using an irrigation
of fully marginal fill MSE walls were due to the reduction of suction and system with a uniform flow rate of 1.8 × 10−7 m/s installed over the
the induced pore water pressure by rainfall infiltration. Therefore, it wall. It consists of a series of pipes connected to a water reservoir,
was of great interest to investigate the performance of the hybrid-fill capable of maintaining a constant hydraulic head. A drainage layer of
wall under rainwater infiltration as well. thickness 0.15 m was provided on top of the wall to facilitate uniform
distribution of water. In addition, a uniform surcharge of 100 kPa was
applied on top using airbags and was maintained throughout the ex
Hybrid fill wall - Infiltration analysis
periment. Frequency domain reflection (FDR) sensors, piezometers,
extensometers, and LVDTs were used to monitor the volumetric water
Behaviour of hybrid-fill wall under rainfall infiltration was eval
content (θ), porewater pressure, reinforcement strain, and facing dis
uated by performing fully coupled flow-deformation analysis of the
placement of the test wall, respectively, during the progress of in
system. This calculation type, available in PLAXIS 2D, is capable of
filtration.
conducting both flow as well as deformation analyses simultaneously
The test wall was simulated using a plane strain model with 15-
[19,28].
noded triangular elements. Table 7 lists the strength as well as hy
draulic properties of both the backfill and non-woven geotextile [5,51].
Fully coupled flow-deformation analysis and Validation Unlike geogrid, non-woven geotextile exhibits high in-plane perme
In the fully coupled flow-deformation analysis, shear strength of ability characteristics, which helps the quick drainage of water. The
unsaturated soil is determined using Bishop’s effective stress, Eq. (3) hydraulic parameters of the reinforcement were incorporated by mod
[18] and transient flow through the soil is governed by the continuity elling interface elements and assigning the relevant properties. The
equation, Eq. (4) [28]. SWCC fitting parameters of backfill, non-woven geotextiles, and top
'
drainage layer (sand) were obtained by fitting the suction data [5]
=( pa ) + (pa pw ) (3) using van Genuchten model (Eq. (1)). The facing of the wall was
3.0 3.0
2.5 2.5
Displacement
Displacement
(mm)
1.5 1.5
1.0 1.0
0.5 0.5
0.0 0.0
0 10000 20000 30000 0 10000 20000 30000
Time (min) Time (min)
(a) (b)
Fig. 21. Variation in facing displacement with infiltration (a) 0.9 m above the base; (b) 0.6 m above the base.
11
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
6 6 6
EOC
5 5 5
After 10 days
Elevation (m)
4 4 4
Elevation (m)
Elevation (m)
After 20 days
3 3 3 After 30 days
2 After 61 days
2 2
After 61 days + 1 day
1 1 1 heavy rain
considered as permeable (i.e., seepage boundary condition) with a the behaviour of wall upon infiltration. The infiltration boundary
hydraulic conductivity of 1 × 10−10 m/s; whereas, impermeable condition was assigned at the top of the drainage blanket with a pre
boundary condition was adopted for the back side and bottom of the scribed intensity of 1.8 × 10-7 m/s to model the rainwater infiltration.
wall. The initial suction of the backfill was in the range of 45–60 kPa. Fig. 18 shows the numerical model of experimental wall simulated in
The required initial suction was simulated by inputting the corre PLAXIS 2D.
sponding degree of saturation. After modelling the construction of wall, Fig. 19 shows the predicted variation of normalized volumetric
a fully coupled flow-deformation analysis was performed to investigate water content (θ/θs; where, θs – volumetric water content at the fully
12
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
Settlement (mm)
Fully marginal
Surface
-15
-30
-45
EOC
Distance from centre of wall (m)
0 3 6 9 After 10 days
0
Settlement (mm)
After 20 days
Hybrid-fill
-15 After 30 days
Surface
After 61 days
-30
After 61 days + 1 day
-45 heavy rain
Retained-marginal
-15
Surface
-30
-45
Fig. 24. Variation in surface settlement during rainfall (Case C; W/H = 3; H = 6 m; b = 0.85B).
6 6 6
Fully marginal Hybrid-fill Retained-marginal
5 5 5 EOC
4 4 After 10 days
4
Elevation (m)
Elevation (m)
Elevation (m)
After 20 days
3 3 3
After 30 days
2 2 2 After 61 days
1 1 After 61 days +
1 1 day heavy rain
0 0 0
0 5 10 15 0 5 10 15 0 5 10 15
Max. Mobilized Max. Mobilized Max. Mobilized
Tension (kN/m) Tension (kN/m) Tension (kN/m)
Fig. 25. Variation in maximum mobilized tension during rainfall (Case C; W/H = 3; H = 6 m; b = 0.85B).
saturated state) and pore water pressure during infiltration along with between the proposed hybrid-fill wall, retained-marginal fill wall, and
the experimental results. Fig. 20 depicts the experimental and predicted fully marginal fill wall under typical rainfall in Kerala State, India. In
variation in horizontal displacement along a reinforcement layer lo case of hybrid-fill wall, 0.3 m thick select fill layer was considered on
cated 1.05 m above the base during water infiltration. Similarly, shown top (i.e., above marginal fill) to facilitate continuous and uniform dis
in Fig. 21 is the change in facing displacement (at 0.9 m and 0.6 m charge below road pavement. “Infiltration” boundary condition avail
above the base) as the infiltration progresses. As evident from able in PLAXIS was assigned at the top of the wall and ground surface
Figs. 19–21, the results of numerical simulation matched closely with with prescribed rainwater intensity for simulating the hydraulic
the measured data. The difference between the measured and predicted boundary condition. Effective suction, horizontal and vertical de
displacement values was within the range of 0 to 0.5 mm. This implies formation responses, reinforcement tension and safety factor variations
that fully coupled flow-deformation analysis available in PLAXIS 2D is during the several days of rainfall were studied in detail.
capable to simulate the behaviour of MSE wall under rainwater in Recent rainfall intensity data from the study report on “Kerala Flood
filtration with reasonable accuracy. of August 2018” by Central Water Commission, India [26] was used in
this research. The report includes the total monthly rainfall (in mm) for
Performance of hybrid-fill wall upon rainwater infiltration June and July 2018 and the rainfall data during the period of 1st to
A comparative performance evaluation study was carried out 19th of August 2018. There was a sudden raise in the intensity of
13
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
6 shows the surface deformation profile of fully marginal fill wall, hybrid-
Marginal
fill wall (b = 0.85B) and retained marginal fill wall (Case C and
Hybrid
5 H = 6 m) during rainwater infiltration. The upward deformation was
Retained Marginal
noticeable at the surface of the fill as the rainwater infiltration pro
gresses due to the reduction of suction in the marginal soil (Fig. 24).
4
Elevation (m)
2.6
2.4 Marginal
Factor of Safety
2.2 Hybrid
2.0 Retained Marginal
1.8
1.6
Case C; H = 6 m
1.4
1.2
EOC 10 days 20 days 30 days 61 days +1 day
heavy
Duration of Rainfall (days) rain
Fig. 27. Variation of global factor of safety during rainfall (b = 0.85B).
14
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
(i.e., W/H = 1.7, 2, and 3). The amount of select fill required for this Acknowledgments
configuration ranges from 31% to 47% for all the cases (different W and
H) considered in this study. It should be noted that the corresponding % The financial support provided to the first author by the Ministry of
of select fill for wall ‘with marginal soil in the retained zone only’ will Human Resource Development (MHRD), India, for completion of this
be varying from 44% to 81%. Since these findings are based on the work is greatly acknowledged.
results of finite element modelling, which has inherent limitations (e.g.,
material models, coupled flow deformation analysis, etc.) in simulating References
the exact field behaviour, validation of the findings through in
strumented experimental study (centrifuge or full-scale) is warranted [1] Aashto L. AASHTO LRFD bridge design specification. American Association of State
before its implementation. Highway and Transportation Officials, Washington DC; 2012.
[2] Abdi MR, Arjomand MA. Pullout tests conducted on clay reinforced with geogrid
encapsulated in thin layers of sand. Geotext Geomembranes 2011;29(6):588–95.
https://doi.org/10.1016/j.geotexmem.2011.04.004.
Conclusions [3] Abdi MR, Sadrnejad A, Arjomand MA. Strength enhancement of clay by en
capsulating geogrids in thin layers of sand. Geotext Geomembranes
2009;27(6):447–55.
The present study investigated the behaviour of a new hybrid back- [4] Adarsh S, Reddy MJ. Developing hourly intensity duration frequency curves for
to-back MSE wall, made of marginal fill in the central trapezoidal zone urban areas in India using multivariate empirical mode decomposition and scaling
and well-graded select fill in the remaining area, immediately after theory. Stoch Env Res Risk A 2018;32(6):1889–902. https://doi.org/10.1007/
s00477-018-1545-x.
construction and upon rainfall infiltration. The hybrid-fill core-base- [5] Albino UR, Portelinha FHM, Zornberg JG, Futai MM. Numerical simulation of in
width (b) was identified as one of the governing factors affecting the filtration into the fill of a wall reinforced with nonwoven geotextiles. Comput
overall wall performance, whereas, the core-height (h) has the least Geotech 2019;108:27–39.
[6] ASTM D2487-17. Standard Practice for Classification of Soils for Engineering
influence. The facing displacement and surface settlement of the hy Purposes (Unified Soil Classification System). ASTM International, West
brid-fill wall just after construction were found to be similar to that of a Conshohocken, PA; 2017.
fully select fill wall as long as core-base-width, b is ≤ 0.9B. Also, the [7] ASTM D3080 / D3080M-11. Standard Test Method for Direct Shear Test of Soils
Under Consolidated Drained Conditions. ASTM International, West Conshohocken,
differential surface settlement for the proposed hybrid-fill wall was less PA; 2011.
in comparison with both fully select fill and fully marginal fill walls, as [8] ASTM D4318-17e1. Standard Test Methods for Liquid Limit, Plastic Limit, and
the vertical deformation of the central marginal zone minimizes the Plasticity Index of Soils. ASTM International, West Conshohocken, PA; 2017.
[9] ASTM D5298-16. Standard Test Method for Measurement of Soil Potential (Suction)
non-uniformity. For the configurations with b ≤ 0.9B, mobilized ten Using Filter Paper. ASTM International, West Conshohocken, PA; 2016.
sion in the reinforcement layers was also comparable to that observed [10] ASTM D6913 / D6913M-17. Standard Test Methods for Particle-Size Distribution
in fully select fill wall. The FS of the hybrid-fill wall with b ≤ 0.85B and (Gradation) of Soils Using Sieve Analysis. ASTM International, West Conshohocken,
PA; 2017.
h = 1H was much greater than that of fully marginal fill wall, when the
[11] ASTM D698-12e2. Standard Test Methods for Laboratory Compaction
matric suction was ignored; whereas, incorporation of suction results in Characteristics of Soil Using Standard Effort (12400 ft-lbf/ft3 (600 kN-m/m3)).
a slightly higher FS for the fully marginal fill wall. Similarly, suction in ASTM International, West Conshohocken, PA; 2012.
marginal soil decreases the deformation response of both the marginal [12] ASTM D7928-17. Standard Test Method for Particle-Size Distribution (Gradation) of
Fine-Grained Soils Using the Sedimentation (Hydrometer) Analysis. ASTM
fill and hybrid-fill walls. However, larger displacement was still ob International, West Conshohocken, PA; 2017.
served for the fully marginal fill wall in comparison with the proposed [13] Bathurst RJ, Walters D, Vlachopoulos N, Burgess P, Allen TM. Full scale testing of
hybrid-fill wall. geosynthetic reinforced walls. Adv Transport Geoenviron Syst Using Geosynthetics
2000:201–17. https://doi.org/10.1061/40515(291)14.
The influence of rainfall infiltration on the horizontal and vertical [14] Balakrishnan S, Viswanadham B. Performance evaluation of geogrid reinforced soil
deformation, and reinforced tension of the proposed hybrid-fill wall walls with marginal backfills through centrifuge model tests. Geotext
was seen to be insignificant in contrast to the fully marginal fill wall. Geomembranes 2016;44(1):95–108.
[15] Balakrishnan S, Viswanadham B. Evaluation of tensile load-strain characteristics of
The variation of FS during rainfall was negligible in case of hybrid-fill geogrids through in-soil tensile tests. Geotext Geomembranes 2017;45(1):35–44.
wall as opposed to the fully marginal fill wall, even though its initial FS [16] Berg RR, Christopher BR, Samtani NC, Berg RR. Design of mechanically stabilized
was slightly higher due to suction. Based on the performance assess earth walls and reinforced soil slopes–Volume I (No. FHWA-NHI-10-024). Federal
Highway Administration, United States; 2009. https://www.fhwa.dot.gov/en
ment immediately after construction and upon rainfall infiltration, a gineering/geotech/pubs/nhi10024/nhi10024.pdf.
hybrid-fill configuration with core-base-width, b = 0.85B and core- [17] Bhattacherjee D, Viswanadham BVS. Numerical studies on the performance of hy
height, h ≈ 1H was found be acceptable and reasonably comparable to brid-geosynthetic-reinforced soil slopes subjected to rainfall. Geosynth Int
2015;22(6):411–27. https://doi.org/10.1680/jgein.15.00022.
the fully select fill wall with regard to deformation response, re
[18] Bishop AW, Blight GE. Some aspects of effective stress in saturated and partly sa
inforcement tension, and safety factor. The percentage of select fill (by turated soils. Geotechnique 1963;13(3):177–97. https://doi.org/10.1680/geot.
volume) required for this satisfactory hybrid-fill configuration ranges 1963.13.3.177.
from 31 to 47% for all the cases considered in this study. On the whole, [19] Brinkgreve RBJ, Kumarswamy S, Swolfs WM, Foria F, Waterman D, Chesaru A,
Bonnier PG. PLAXIS 2018. PLAXIS bv, the Netherlands; 2018.
this study suggests that the proposed hybrid-fill combination is a viable [20] Brooks R, Corey T. HYDRAU uc properties of porous media. Hydrology Papers.
fill option for back-to-back MSE wall in terms of strength, serviceability Colorado State University 1964;24:37.
and economy with minimum usage of select soil. [21] BS 8006-1. Code of practice for strengthened/reinforced soils and other fills. British
Standards Institution; 2010.
[22] Chen HT, Hung WY, Chang CC, Chen YJ, Lee CJ. Centrifuge modeling test of a
geotextile-reinforced wall with a very wet clayey backfill. Geotext Geomembranes
CRediT authorship contribution statement 2007;25(6):346–59. https://doi.org/10.1016/j.geotexmem.2007.01.003.
[23] Christopher BR, Stulgis RP. Low permeable backfill soils in geosynthetic reinforced
soil walls: state-of-the-practice in North America. Proc North Am Geo-synthetics
Gopika Rajagopal: Software, Validation, Formal analysis, Conf 2005:14–6.
Investigation, Resources, Writing - original draft, Visualization. [24] Christopher BR, Zornberg JG, Mitchell JK. Design guidance for reinforced soil
structures with marginal soil backfills. In: Proceedings of the Sixth International
Sudheesh Thiyyakkandi: Conceptualization, Methodology, Writing -
Conference on Geosynthetics, Atlanta, Georgia; 1998;2:797–804.
review & editing, Supervision, Project administration, Funding acqui [25] Collin JG. Lessons learned from a segmental retaining wall failure. Geotext
sition. Geomembranes 2001;19(7):445–54.
[26] CWC. Study report Kerala floods of August 2018. Central Water Commission,
Hydrological Studies Organisation, Hydrology (S) Directorate, Govt. of India; 2018.
[27] Fredlund DG, Xing A. Equations for the soil-water characteristic curve. Can Geotech
Declaration of Competing Interest J 1994;31(4):521–32. https://doi.org/10.1139/t94-061.
[28] Galavi V. Ground water flow, fully coupled flow deformation and undrained ana
lyses in PLAXIS 2D and 3D. Plaxis Report 2010.
The author declare that there is no conflict of interest.
15
G. Rajagopal and S. Thiyyakkandi Transportation Geotechnics 26 (2021) 100445
[29] Glendinning S, Jones CJ, Pugh RC. Reinforced soil using cohesive fill and electro histories and applications. Geosynth Int 1995;2(1):265–307. https://doi.org/10.
kinetic geosynthetics. Int J Geomech 2005;5(2):138–46. https://doi.org/10.1061/ 1680/gein.2.0011.
(ASCE)1532-3641(2005)5:2(138). [47] NCMA. Design manual for segmental retaining walls. 3rd Ed. Herndon VA: National
[30] Guler E, Hamderi M, Demirkan MM. Numerical analysis of reinforced soil-retaining Concrete Masonry Association; 2009.
wall structures with cohesive and granular backfills. Geosynth Int [48] Noorzad R, Mirmoradi S. Laboratory evaluation of the behavior of a geotextile re
2007;14(6):330–45. https://doi.org/10.1680/gein.2007.14.6.330. inforced clay. Geotext Geomembranes 2010;28(4):386–92.
[31] Hamdhan IN, Schweiger HF. Finite element method–based analysis of an un [49] Ollier CD, Rajaguru SN. Laterite of Kerala (India). Geogr Fis Din Quat
saturated soil slope subjected to rainfall infiltration. Int J Geomech 1989;12:27–33.
2013;13(5):653–8. https://doi.org/10.1061/(ASCE)GM.1943-5622.0000239. [50] Portelinha FHM, Bueno BS, Zornberg JG. Performance of geotextile reinforced soil
[32] Hatami K, Bathurst RJ. Development and verification of a numerical model for the wall in unsaturated poorly draining backfill soil conditions. In Proceedings of the
analysis of geosynthetic-reinforced soil segmental walls under working stress con 5th European geosynthetics congress. 2012. p. 455–65.
ditions. Can Geotech J 2005;42(4):1066–85. https://doi.org/10.1139/t05-040. [51] Portelinha FHM, Zornberg JG. Effect of infiltration on the performance of an un
[33] Helwany S, Reardon G, Wu J. Effects of backfill on the performance of GRS re saturated geotextile-reinforced soil wall. Geotext Geomembranes
taining walls. Geotext. Geomembranes 1999;17(1):1–16. 2017;45(3):211–26.
[34] Hossain MS, Kibria G, Khan MS, Hossain J, Taufiq T. Effects of backfill soil on [52] Raisinghani DV, Viswanadham BVS. Evaluation of permeability characteristics of a
excessive movement of MSE wall. J Perform Constr Fac 2012;26(6):793–802. geosynthetic-reinforced soil through laboratory tests. Geotext Geomembranes
https://doi.org/10.1061/(ASCE)CF.1943-5509.0000281. 2010;28(6):579–88. https://doi.org/10.1016/j.geotexmem.2010.01.001.
[35] Indian Standard, IS: 2720 (Part 17). Laboratory Determination of Permeability. [53] Raisinghani DV, Viswanadham BVS. Centrifuge model study on low permeable
Indian Standards Institution, New Delhi; 1986. slope reinforced by hybrid geosynthetics. Geotext Geomembranes
[36] IRC, SP. 102. In Guidelines for design and construction of reinforced soil walls. 2011;29(6):567–80. https://doi.org/10.1016/j.geotexmem.2011.07.003.
Indian Roads Congress, New Delhi; 2014. [54] Vahedifard F, Mortezaei K, Leshchinsky BA, Leshchinsky D, Lu N. Role of suction
[37] Iryo T, Rowe RK. Infiltration into an embankment reinforced by nonwoven geo stress on service state behavior of geosynthetic-reinforced soil structures. Transp
textiles. Can Geotech J 2005;42(4):1145–59. Geotech 2016;8:45–56.
[38] Jayanandan Midhula, Viswanadham BVS. Geogrid reinforced soil walls with mar [55] Vahedifard F, Tehrani FS, Galavi V, Ragno E, Agha Kouchak A. Resilience of MSE
ginal backfills subjected to rainfall: numerical study. Indian Geotech J 2019:1–14. walls with marginal backfill under a changing climate: Quantitative assessment for
[39] Kim WS, Borden RH. Numerical simulation of MSE wall behavior induced by sur extreme precipitation events. J Geotech Geoenviron 2017;143(9):04017056.
face-water infiltration. J Geotech Geoenviron 2013;139(12):2110–24. https://doi. https://doi.org/10.1061/(ASCE)GT.1943-5606.0001743.
org/10.1061/(ASCE)GT.1943-5606.0000927. [56] Van Genuchten MT. A closed-form equation for predicting the hydraulic con
[40] Koerner RM, Koerner GR. The importance of drainage control for geosynthetic re ductivity of unsaturated soils 1. Soil Sci Soc Am J 1980;44(5):892–8. https://doi.
inforced mechanically stabilized earth walls. J GeoEng 2011;6(1):3–13. org/10.2136/sssaj1980.03615995004400050002x.
[41] Koerner RM, Koerner GR. A data base, statistics and recommendations regarding [57] Viswanadham BVS, Razeghi HR, Mamaghanian J, Manikumar CHSG. Centrifuge
171 failed geosynthetic reinforced mechanically stabilized earth (MSE) walls. model study on geogrid reinforced soil walls with marginal backfills with and
Geotext Geomembranes 2013;40:20–7. https://doi.org/10.1016/j.geotexmem. without chimney sand drain. Geotext Geomembranes 2017;45(5):430–46. https://
2013.06.001. doi.org/10.1016/j.geotexmem.2017.06.005.
[42] Koerner RM, Koerner GR. An extended data base and recommendations regarding [58] Yoo C. Effect of rainfall on performance of reinforced earth wall. In: Han J,
320 failed geosynthetic reinforced mechanically stabilized earth (MSE) walls. Alzamora DE (eds) Geo-frontiers congress 2011. ASCE, GSP 211,
Geotext Geomembranes 2018;46(6):904–12. 2011;3:1852–1861. https://doi.org/10.1061/41165(397)189.
[43] Koerner RM, Soong TY. Geosynthetic reinforced segmental retaining walls. Geotext [59] Yoo C, Jung HY. Case history of geosynthetic reinforced segmental retaining wall
Geomembranes 2001;19(6):359–86. https://doi.org/10.1016/S0266-1144(01) failure. J Geotech Geoenviron 2006;132(12):1538–48. https://doi.org/10.1061/
00012-7. (ASCE)1090-0241(2006)132:12(1538).
[44] Liu H, Wang X, Song E. Long-term behavior of GRS retaining walls with marginal [60] Yubonchit S, Chinkulkijniwat A, Horpibulsuk S, Jothityangkoon C, Arulrajah A,
backfill soils. Geotext Geomembranes 2009;27(4):295–307. https://doi.org/10. Suddeepong A. Influence factors involving rainfall-induced shallow slope failure:
1016/j.geotexmem.2009.01.002. numerical study. Int J Geomech 2017;17(7):04016158. https://doi.org/10.1061/
[45] Mamaghanian J, Viswanadham BVS, Razeghi HR. Centrifuge model studies on (ASCE)GM.1943-5622.0000865.
geocomposite reinforced soil walls subjected to seepage. Geosynth Intl [61] Zornberg JG, Mitchell JS. Reinforced soil structures with poorly draining backfills.
2019;26(4):371–87. Part I: reinforcement interactions and functions. Geosynth Int 1994;2(1):103–47.
[46] Mitchell JK. Reinforced soil structures with poorly draining backfills part II: case
16