JOB : Almajdoui Warehouse

HEAT LOAD CALCULATIONS


SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 116.87445
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 1.4
Cfm VENTILATION = 21 DEHUMIDIFIED AIR Cfm 675
Cfm/PERSON = 8
NO.OF PEOPLE = 4 TONS AS PER Cfm 1.7
Cfm VENTILATION = 32 TONNAGE REQUIRED 1.7 20251.13437
Cfm VENTILATION IN CAL. = 32 20.25113437
CFM PER SQFT 5.78
D.B. W.B. %RH GR/LB AREA PER TON 69
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
32 -1.28 0.12 0.68 -3
SOLAR GAIN-GLASS
NORTH 50 23 0.56 644 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 4* 215 860
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 857
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 43
S-E 0 12 0.56 0 ROOM LATENT HEAT 899
S-W 0 85 0.56 0
ROOM TOTAL HEAT 15270
SOLAR & TRANSMISSION GAIN
NORTH 60 16 0.34 326 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 32 36.6 0.88 1.08 1113
N-E 0 22 0.34 0 LAT 32 -1.28 0.88 0.68 -25
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1089
S-W 0 26 0.34 0 TOTAL 16359
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 491

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 1.4 16850


AGLS 50 36.6 1.13 2068
PART 374 31.6 0.45 5318
CEIL 117 31.6 0.45 1 1662 SENSIBLE HEAT FACTOR 0.94
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 675
32 36.6 0.12 1.08 152 TONS AS PER Cfm 1.7

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 4 * 245 980 GRAND TOTAL HEAT(BTU/HR/SQFT.) 144.17
APPL. 300 * 3.4 1020 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 122.96
LIGHTS 175 * 3.4 1.5 894 SQFT/PERSON 29.22
TONS PER SQFT 0.01
SUB TOTAL 13064 CFM PER SQFT 5.78
TONS/PERSON 0.35
LEAK LOSS +SAFETY FACTOR=10% 1306 DEHUMIDIFIED CFM/TON 480.75
ROOM SENSIBLE HEAT 14371 AREA PER TON 83.24
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 244.34787
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.8
Cfm VENTILATION = 45 DEHUMIDIFIED AIR Cfm 1364
Cfm/PERSON = 8
NO.OF PEOPLE = 8 TONS AS PER Cfm 3.4
Cfm VENTILATION = 64 TONNAGE REQUIRED 3.4 40928.00253
Cfm VENTILATION IN CAL. = 64 40.92800253
CFM PER SQFT 5.58
D.B. W.B. %RH GR/LB AREA PER TON 72
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
64 -1.28 0.12 0.68 -7
SOLAR GAIN-GLASS
NORTH 95 23 0.56 1224 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 8* 215 1720
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 1713
N-E 0 12 0.56 0
N-W 40 138 0.56 3091 SAFETY FACTOR=5% 86
S-E 0 12 0.56 0 ROOM LATENT HEAT 1799
S-W 0 85 0.56 0
ROOM TOTAL HEAT 30843
SOLAR & TRANSMISSION GAIN
NORTH 114 16 0.34 620 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 64 36.6 0.88 1.08 2226
N-E 0 22 0.34 0 LAT 64 -1.28 0.88 0.68 -49
N-W 48 18 0.34 294
S-E 0 30 0.34 0 SUB TOTAL 2177
S-W 0 26 0.34 0 TOTAL 33020
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 991

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.8 34011


AGLS 135 36.6 1.13 5583
PART 418 31.6 0.45 5944
CEIL 244 31.6 0.45 1 3475 SENSIBLE HEAT FACTOR 0.94
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1364
64 36.6 0.12 1.08 304 TONS AS PER Cfm 3.4

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 8 * 245 1960 GRAND TOTAL HEAT(BTU/HR/SQFT.) 139.19
APPL. 600 * 3.4 2040 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 118.86
LIGHTS 367 * 3.4 1.5 1869 SQFT/PERSON 30.54
TONS PER SQFT 0.01
SUB TOTAL 26403 CFM PER SQFT 5.58
TONS/PERSON 0.35
LEAK LOSS +SAFETY FACTOR=10% 2640 DEHUMIDIFIED CFM/TON 481.36
ROOM SENSIBLE HEAT 29044 AREA PER TON 86.21
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 179.08265
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.5
Cfm VENTILATION = 33 DEHUMIDIFIED AIR Cfm 1297
Cfm/PERSON = 8
NO.OF PEOPLE = 4 TONS AS PER Cfm 3.2
Cfm VENTILATION = 32 TONNAGE REQUIRED 3.2 38924.40275
Cfm VENTILATION IN CAL. = 33 38.92440275
CFM PER SQFT 7.25
D.B. W.B. %RH GR/LB AREA PER TON 55
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
33 -1.28 0.12 0.68 -3
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 4* 215 860
EAST 0 12 0.56 0
WEST 65 0 163 0.56 5933 SUB TOTAL 857
N-E 0 12 0.56 0
N-W 35 138 0.56 2705 SAFETY FACTOR=5% 43
S-E 0 12 0.56 0 ROOM LATENT HEAT 899
S-W 0 85 0.56 0
ROOM TOTAL HEAT 28521
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 78 26 0.34 690 SENS 33 36.6 0.88 1.08 1142
N-E 0 22 0.34 0 LAT 33 -1.28 0.88 0.68 -25
N-W 42 18 0.34 257
S-E 0 30 0.34 0 SUB TOTAL 1117
S-W 0 26 0.34 0 TOTAL 29638
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 889

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.5 30527


AGLS 100 36.6 1.13 4136
PART 374 31.6 0.45 5318
CEIL 179 31.6 0.45 1 2547 SENSIBLE HEAT FACTOR 0.97
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1297
33 36.6 0.12 1.08 156 TONS AS PER Cfm 3.2

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 4 * 245 980 GRAND TOTAL HEAT(BTU/HR/SQFT.) 170.47
APPL. 300 * 3.4 1020 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 154.24
LIGHTS 269 * 3.4 1.5 1370 SQFT/PERSON 44.77
TONS PER SQFT 0.01
SUB TOTAL 25111 CFM PER SQFT 7.25
TONS/PERSON 0.64
LEAK LOSS +SAFETY FACTOR=10% 2511 DEHUMIDIFIED CFM/TON 510.03
ROOM SENSIBLE HEAT 27622 AREA PER TON 70.40
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 146.03623
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.0
Cfm VENTILATION = 27 DEHUMIDIFIED AIR Cfm 1019
Cfm/PERSON = 8
NO.OF PEOPLE = 4 TONS AS PER Cfm 2.5
Cfm VENTILATION = 32 TONNAGE REQUIRED 2.5 30580.20181
Cfm VENTILATION IN CAL. = 32 30.58020181
CFM PER SQFT 6.98
D.B. W.B. %RH GR/LB AREA PER TON 57
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
32 -1.28 0.12 0.68 -3
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 4* 215 860
EAST 0 12 0.56 0
WEST 60 0 163 0.56 5477 SUB TOTAL 857
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 43
S-E 0 12 0.56 0 ROOM LATENT HEAT 899
S-W 0 85 0.56 0
ROOM TOTAL HEAT 22600
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 72 26 0.34 636 SENS 32 36.6 0.88 1.08 1113
N-E 0 22 0.34 0 LAT 32 -1.28 0.88 0.68 -25
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1089
S-W 0 26 0.34 0 TOTAL 23689
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 711

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.0 24399


AGLS 60 36.6 1.13 2481
PART 407 31.6 0.45 5788
CEIL 146 31.6 0.45 1 2077 SENSIBLE HEAT FACTOR 0.96
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1019
32 36.6 0.12 1.08 152 TONS AS PER Cfm 2.5

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 4 * 245 980 GRAND TOTAL HEAT(BTU/HR/SQFT.) 167.08
APPL. 300 * 3.4 1020 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 148.60
LIGHTS 219 * 3.4 1.5 1117 SQFT/PERSON 36.51
TONS PER SQFT 0.01
SUB TOTAL 19728 CFM PER SQFT 6.98
TONS/PERSON 0.51
LEAK LOSS +SAFETY FACTOR=10% 1973 DEHUMIDIFIED CFM/TON 501.33
ROOM SENSIBLE HEAT 21701 AREA PER TON 71.82
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 578.01448
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 4.2
Cfm VENTILATION = 106 DEHUMIDIFIED AIR Cfm 2007
Cfm/PERSON = 8
NO.OF PEOPLE = 10 TONS AS PER Cfm 5.0
Cfm VENTILATION = 80 TONNAGE REQUIRED 5.0 60203.60143
Cfm VENTILATION IN CAL. = 106 60.20360143
CFM PER SQFT 3.47
D.B. W.B. %RH GR/LB AREA PER TON 115
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
106 -1.28 0.12 0.68 -11
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 10 * 215 2150
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 2139
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 107
S-E 0 12 0.56 0 ROOM LATENT HEAT 2246
S-W 0 85 0.56 0
ROOM TOTAL HEAT 44968
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 106 36.6 0.88 1.08 3686
N-E 0 22 0.34 0 LAT 106 -1.28 0.88 0.68 -81
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 3605
S-W 0 26 0.34 0 TOTAL 48573
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 1457

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 4.2 50030


AGLS 0 36.6 1.13 0
PART 1276 31.6 0.45 18145
CEIL 578 31.6 0.45 1 8219 SENSIBLE HEAT FACTOR 0.95
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 2007
106 36.6 0.12 1.08 503 TONS AS PER Cfm 5.0

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 10 * 245 2450 GRAND TOTAL HEAT(BTU/HR/SQFT.) 86.56
APPL. 1500 * 3.4 5100 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 73.91
LIGHTS 867 * 3.4 1.5 4422 SQFT/PERSON 57.80
TONS PER SQFT 0.01
SUB TOTAL 38839 CFM PER SQFT 3.47
TONS/PERSON 0.42
LEAK LOSS +SAFETY FACTOR=10% 3884 DEHUMIDIFIED CFM/TON 481.34
ROOM SENSIBLE HEAT 42722 AREA PER TON 138.64
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 52.57308
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 0.8
Cfm VENTILATION = 10 DEHUMIDIFIED AIR Cfm 410
Cfm/PERSON = 8
NO.OF PEOPLE = 2 TONS AS PER Cfm 1.0
Cfm VENTILATION = 16 TONNAGE REQUIRED 1.0 12305.10142
Cfm VENTILATION IN CAL. = 16 12.30510142
CFM PER SQFT 7.80
D.B. W.B. %RH GR/LB AREA PER TON 51
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
16 -1.28 0.12 0.68 -2
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 2* 215 430
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 428
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 21
S-E 0 12 0.56 0 ROOM LATENT HEAT 450
S-W 0 85 0.56 0
ROOM TOTAL HEAT 9182
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 16 36.6 0.88 1.08 557
N-E 0 22 0.34 0 LAT 16 -1.28 0.88 0.68 -12
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 544
S-W 0 26 0.34 0 TOTAL 9726
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 292

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 0.8 10018


AGLS 0 36.6 1.13 0
PART 330 31.6 0.45 4693
CEIL 53 31.6 0.45 1 748 SENSIBLE HEAT FACTOR 0.95
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 410
16 36.6 0.12 1.08 76 TONS AS PER Cfm 1.0

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 2 * 245 490 GRAND TOTAL HEAT(BTU/HR/SQFT.) 190.55
APPL. 450 * 3.4 1530 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 166.09
LIGHTS 79 * 3.4 1.5 402 SQFT/PERSON 26.29
TONS PER SQFT 0.02
SUB TOTAL 7938 CFM PER SQFT 7.80
TONS/PERSON 0.42
LEAK LOSS +SAFETY FACTOR=10% 794 DEHUMIDIFIED CFM/TON 491.32
ROOM SENSIBLE HEAT 8732 AREA PER TON 62.97
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 121.69852
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 1.2
Cfm VENTILATION = 22 DEHUMIDIFIED AIR Cfm 583
Cfm/PERSON = 8
NO.OF PEOPLE = 2 TONS AS PER Cfm 1.5
Cfm VENTILATION = 16 TONNAGE REQUIRED 1.5 17478.20176
Cfm VENTILATION IN CAL. = 22 17.47820176
CFM PER SQFT 4.79
D.B. W.B. %RH GR/LB AREA PER TON 84
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
22 -1.28 0.12 0.68 -2
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 2* 215 430
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 428
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 21
S-E 0 12 0.56 0 ROOM LATENT HEAT 449
S-W 0 85 0.56 0
ROOM TOTAL HEAT 12852
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 22 36.6 0.88 1.08 776
N-E 0 22 0.34 0 LAT 22 -1.28 0.88 0.68 -17
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 759
S-W 0 26 0.34 0 TOTAL 13611
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 408

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 1.2 14019


AGLS 0 36.6 1.13 0
PART 528 31.6 0.45 7508
CEIL 122 31.6 0.45 1 1731 SENSIBLE HEAT FACTOR 0.97
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 583
22 36.6 0.12 1.08 106 TONS AS PER Cfm 1.5

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 2 * 245 490 GRAND TOTAL HEAT(BTU/HR/SQFT.) 115.20
APPL. 150 * 3.4 510 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 101.92
LIGHTS 183 * 3.4 1.5 931 SQFT/PERSON 60.85
TONS PER SQFT 0.01
SUB TOTAL 11276 CFM PER SQFT 4.79
TONS/PERSON 0.58
LEAK LOSS +SAFETY FACTOR=10% 1128 DEHUMIDIFIED CFM/TON 498.68
ROOM SENSIBLE HEAT 12403 AREA PER TON 104.17
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 88.223596
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 0.9
Cfm VENTILATION = 16 DEHUMIDIFIED AIR Cfm 471
Cfm/PERSON = 8
NO.OF PEOPLE = 2 TONS AS PER Cfm 1.2
Cfm VENTILATION = 16 TONNAGE REQUIRED 1.2 14116.05702
Cfm VENTILATION IN CAL. = 16 14.11605702
CFM PER SQFT 5.33
D.B. W.B. %RH GR/LB AREA PER TON 75
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
16 -1.28 0.12 0.68 -2
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 2* 215 430
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 428
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 21
S-E 0 12 0.56 0 ROOM LATENT HEAT 450
S-W 0 85 0.56 0
ROOM TOTAL HEAT 10467
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 16 36.6 0.88 1.08 563
N-E 0 22 0.34 0 LAT 16 -1.28 0.88 0.68 -12
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 550
S-W 0 26 0.34 0 TOTAL 11017
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 331

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 0.9 11348


AGLS 0 36.6 1.13 0
PART 429 31.6 0.45 6100
CEIL 88 31.6 0.45 1 1255 SENSIBLE HEAT FACTOR 0.96
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 471
16 36.6 0.12 1.08 77 TONS AS PER Cfm 1.2

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 2 * 245 490 GRAND TOTAL HEAT(BTU/HR/SQFT.) 128.62
APPL. 150 * 3.4 510 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 113.54
LIGHTS 132 * 3.4 1.5 675 SQFT/PERSON 44.11
TONS PER SQFT 0.01
SUB TOTAL 9107 CFM PER SQFT 5.33
TONS/PERSON 0.47
LEAK LOSS +SAFETY FACTOR=10% 911 DEHUMIDIFIED CFM/TON 497.58
ROOM SENSIBLE HEAT 10017 AREA PER TON 93.30
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 187.8459
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.6
Cfm VENTILATION = 34 DEHUMIDIFIED AIR Cfm 1294
Cfm/PERSON = 8
NO.OF PEOPLE = 6 TONS AS PER Cfm 3.2
Cfm VENTILATION = 48 TONNAGE REQUIRED 3.2 38833.62943
Cfm VENTILATION IN CAL. = 48 38.83362943
CFM PER SQFT 6.89
D.B. W.B. %RH GR/LB AREA PER TON 58
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
48 -1.28 0.12 0.68 -5
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 6* 215 1290
EAST 0 12 0.56 0
WEST 80 0 163 0.56 7302 SUB TOTAL 1285
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 64
S-E 0 12 0.56 0 ROOM LATENT HEAT 1349
S-W 0 85 0.56 0
ROOM TOTAL HEAT 28907
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 96 26 0.34 849 SENS 48 36.6 0.88 1.08 1670
N-E 0 22 0.34 0 LAT 48 -1.28 0.88 0.68 -37
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1633
S-W 0 26 0.34 0 TOTAL 30540
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 916

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.6 31456


AGLS 80 36.6 1.13 3309
PART 440 31.6 0.45 6257
CEIL 188 31.6 0.45 1 2671 SENSIBLE HEAT FACTOR 0.95
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1294
48 36.6 0.12 1.08 228 TONS AS PER Cfm 3.2

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 6 * 245 1470 GRAND TOTAL HEAT(BTU/HR/SQFT.) 167.46
APPL. 450 * 3.4 1530 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 146.70
LIGHTS 282 * 3.4 1.5 1437 SQFT/PERSON 31.31
TONS PER SQFT 0.01
SUB TOTAL 25052 CFM PER SQFT 6.89
TONS/PERSON 0.44
LEAK LOSS +SAFETY FACTOR=10% 2505 DEHUMIDIFIED CFM/TON 493.82
ROOM SENSIBLE HEAT 27558 AREA PER TON 71.66
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 201.64494
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.7
Cfm VENTILATION = 37 DEHUMIDIFIED AIR Cfm 1355
Cfm/PERSON = 8
NO.OF PEOPLE = 6 TONS AS PER Cfm 3.4
Cfm VENTILATION = 48 TONNAGE REQUIRED 3.4 40654.12032
Cfm VENTILATION IN CAL. = 48 40.65412032
CFM PER SQFT 6.72
D.B. W.B. %RH GR/LB AREA PER TON 60
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
48 -1.28 0.12 0.68 -5
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 6* 215 1290
EAST 0 12 0.56 0
WEST 85 0 163 0.56 7759 SUB TOTAL 1285
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 64
S-E 0 12 0.56 0 ROOM LATENT HEAT 1349
S-W 0 85 0.56 0
ROOM TOTAL HEAT 30199
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 102 26 0.34 902 SENS 48 36.6 0.88 1.08 1670
N-E 0 22 0.34 0 LAT 48 -1.28 0.88 0.68 -37
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1633
S-W 0 26 0.34 0 TOTAL 31832
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 955

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.7 32787


AGLS 85 36.6 1.13 3515
PART 451 31.6 0.45 6413
CEIL 202 31.6 0.45 1 2867 SENSIBLE HEAT FACTOR 0.96
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1355
48 36.6 0.12 1.08 228 TONS AS PER Cfm 3.4

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 6 * 245 1470 GRAND TOTAL HEAT(BTU/HR/SQFT.) 162.60
APPL. 450 * 3.4 1530 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 143.07
LIGHTS 302 * 3.4 1.5 1543 SQFT/PERSON 33.61
TONS PER SQFT 0.01
SUB TOTAL 26227 CFM PER SQFT 6.72
TONS/PERSON 0.46
LEAK LOSS +SAFETY FACTOR=10% 2623 DEHUMIDIFIED CFM/TON 495.99
ROOM SENSIBLE HEAT 28849 AREA PER TON 73.80
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 237.98497
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 3.2
Cfm VENTILATION = 44 DEHUMIDIFIED AIR Cfm 1587
Cfm/PERSON = 8
NO.OF PEOPLE = 8 TONS AS PER Cfm 4.0
Cfm VENTILATION = 64 TONNAGE REQUIRED 4.0 47611.89588
Cfm VENTILATION IN CAL. = 64 47.61189588
CFM PER SQFT 6.67
D.B. W.B. %RH GR/LB AREA PER TON 60
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
64 -1.28 0.12 0.68 -7
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 8* 215 1720
EAST 0 12 0.56 0
WEST 100 0 163 0.56 9128 SUB TOTAL 1713
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 86
S-E 0 12 0.56 0 ROOM LATENT HEAT 1799
S-W 0 85 0.56 0
ROOM TOTAL HEAT 35586
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 120 26 0.34 1061 SENS 64 36.6 0.88 1.08 2226
N-E 0 22 0.34 0 LAT 64 -1.28 0.88 0.68 -49
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 2177
S-W 0 26 0.34 0 TOTAL 37763
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 1133

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 3.2 38896


AGLS 100 36.6 1.13 4136
PART 484 31.6 0.45 6882
CEIL 238 31.6 0.45 1 3384 SENSIBLE HEAT FACTOR 0.95
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1587
64 36.6 0.12 1.08 304 TONS AS PER Cfm 4.0

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 8 * 245 1960 GRAND TOTAL HEAT(BTU/HR/SQFT.) 163.44
APPL. 600 * 3.4 2040 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 141.97
LIGHTS 357 * 3.4 1.5 1821 SQFT/PERSON 29.75
TONS PER SQFT 0.01
SUB TOTAL 30715 CFM PER SQFT 6.67
TONS/PERSON 0.41
LEAK LOSS +SAFETY FACTOR=10% 3072 DEHUMIDIFIED CFM/TON 489.63
ROOM SENSIBLE HEAT 33787 AREA PER TON 73.42
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 210.43801
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 2.1
Cfm VENTILATION = 39 DEHUMIDIFIED AIR Cfm 925
Cfm/PERSON = 8
NO.OF PEOPLE = 9 TONS AS PER Cfm 2.3
Cfm VENTILATION = 72 TONNAGE REQUIRED 2.3 27758.52745
Cfm VENTILATION IN CAL. = 72 27.75852745
CFM PER SQFT 4.40
D.B. W.B. %RH GR/LB AREA PER TON 91
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
72 -1.28 0.12 0.68 -8
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 9* 215 1935
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 1927
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 96
S-E 0 12 0.56 0 ROOM LATENT HEAT 2024
S-W 0 85 0.56 0
ROOM TOTAL HEAT 21722
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 72 36.6 0.88 1.08 2504
N-E 0 22 0.34 0 LAT 72 -1.28 0.88 0.68 -55
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 2449
S-W 0 26 0.34 0 TOTAL 24172
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 725

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 2.1 24897


AGLS 0 36.6 1.13 0
PART 649 31.6 0.45 9229
CEIL 210 31.6 0.45 1 2992 SENSIBLE HEAT FACTOR 0.91
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 925
72 36.6 0.12 1.08 342 TONS AS PER Cfm 2.3

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 9 * 245 2205 GRAND TOTAL HEAT(BTU/HR/SQFT.) 118.31
APPL. 450 * 3.4 1530 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 93.61
LIGHTS 316 * 3.4 1.5 1610 SQFT/PERSON 23.38
TONS PER SQFT 0.01
SUB TOTAL 17908 CFM PER SQFT 4.40
TONS/PERSON 0.23
LEAK LOSS +SAFETY FACTOR=10% 1791 DEHUMIDIFIED CFM/TON 445.98
ROOM SENSIBLE HEAT 19698 AREA PER TON 101.43
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 172.24424
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 1.6
Cfm VENTILATION = 32 DEHUMIDIFIED AIR Cfm 793
Cfm/PERSON = 8
NO.OF PEOPLE = 4 TONS AS PER Cfm 2.0
Cfm VENTILATION = 32 TONNAGE REQUIRED 2.0 23785.82132
Cfm VENTILATION IN CAL. = 32 23.78582132
CFM PER SQFT 4.60
D.B. W.B. %RH GR/LB AREA PER TON 87
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
32 -1.28 0.12 0.68 -3
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 4* 215 860
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 857
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 43
S-E 0 12 0.56 0 ROOM LATENT HEAT 899
S-W 0 85 0.56 0
ROOM TOTAL HEAT 17779
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 32 36.6 0.88 1.08 1113
N-E 0 22 0.34 0 LAT 32 -1.28 0.88 0.68 -25
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1089
S-W 0 26 0.34 0 TOTAL 18867
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 566

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 1.6 19433


AGLS 0 36.6 1.13 0
PART 627 31.6 0.45 8916
CEIL 172 31.6 0.45 1 2449 SENSIBLE HEAT FACTOR 0.95
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 793
32 36.6 0.12 1.08 152 TONS AS PER Cfm 2.0

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 4 * 245 980 GRAND TOTAL HEAT(BTU/HR/SQFT.) 112.82
APPL. 450 * 3.4 1530 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 98.00
LIGHTS 258 * 3.4 1.5 1318 SQFT/PERSON 43.06
TONS PER SQFT 0.01
SUB TOTAL 15345 CFM PER SQFT 4.60
TONS/PERSON 0.40
LEAK LOSS +SAFETY FACTOR=10% 1534 DEHUMIDIFIED CFM/TON 489.59
ROOM SENSIBLE HEAT 16879 AREA PER TON 106.36
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 555.97945
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 3.8
Cfm VENTILATION = 102 DEHUMIDIFIED AIR Cfm 1840
Cfm/PERSON = 8
NO.OF PEOPLE = 5 TONS AS PER Cfm 4.6
Cfm VENTILATION = 40 TONNAGE REQUIRED 4.6 55209.38631
Cfm VENTILATION IN CAL. = 102 55.20938631
CFM PER SQFT 3.31
D.B. W.B. %RH GR/LB AREA PER TON 121
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
102 -1.28 0.12 0.68 -11
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 5* 215 1075
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 1064
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 53
S-E 0 12 0.56 0 ROOM LATENT HEAT 1118
S-W 0 85 0.56 0
ROOM TOTAL HEAT 40296
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 102 36.6 0.88 1.08 3546
N-E 0 22 0.34 0 LAT 102 -1.28 0.88 0.68 -78
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 3468
S-W 0 26 0.34 0 TOTAL 43763
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 1313

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 3.8 45076


AGLS 0 36.6 1.13 0
PART 1386 31.6 0.45 19709
CEIL 556 31.6 0.45 1 7906 SENSIBLE HEAT FACTOR 0.97
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 1840
102 36.6 0.12 1.08 483 TONS AS PER Cfm 4.6

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 5 * 245 1225 GRAND TOTAL HEAT(BTU/HR/SQFT.) 81.08
APPL. 600 * 3.4 2040 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 70.47
LIGHTS 834 * 3.4 1.5 4253 SQFT/PERSON 111.20
TONS PER SQFT 0.01
SUB TOTAL 35617 CFM PER SQFT 3.31
TONS/PERSON 0.75
LEAK LOSS +SAFETY FACTOR=10% 3562 DEHUMIDIFIED CFM/TON 489.92
ROOM SENSIBLE HEAT 39178 AREA PER TON 148.01
JOB : Almajdoui Warehouse
HEAT LOAD CALCULATIONS
SPACE Warranty Office DATE 26/02/2023
TIME 00:00
shaharukh
DESIGN DATA
AREA: = 231.39103
HT.OF THE AREA: = 11
LIGHTING (WATTS/SQFT) = 1.5 HEAT LOAD SUMMARY
NO.OF AIR CHANGE REQUIRED = 1 GRAND TOTAL HEAT 1.8
Cfm VENTILATION = 42 DEHUMIDIFIED AIR Cfm 864
Cfm/PERSON = 8
NO.OF PEOPLE = 3 TONS AS PER Cfm 2.2
Cfm VENTILATION = 24 TONNAGE REQUIRED 2.2 25909.57229
Cfm VENTILATION IN CAL. = 42 25.90957229
CFM PER SQFT 3.73
D.B. W.B. %RH GR/LB AREA PER TON 107
OUTSIDE 112 74 - 63
INSIDE 75 - 50 64.7
DIFF. 37 - - -1.3

SUN GAIN BYPASS O.A. LATENT LOAD


AREA or T.DIFF. FACTOR BTU CFM G.DIFF BYPASS FACTOR BTU
42 -1.28 0.12 0.68 -4
SOLAR GAIN-GLASS
NORTH 0 23 0.56 0 INTERNAL LATENT LOAD
SOUTH 0 12 0.56 0 PEOPL 3* 215 645
EAST 0 12 0.56 0
WEST 0 0 163 0.56 0 SUB TOTAL 641
N-E 0 12 0.56 0
N-W 0 138 0.56 0 SAFETY FACTOR=5% 32
S-E 0 12 0.56 0 ROOM LATENT HEAT 673
S-W 0 85 0.56 0
ROOM TOTAL HEAT 19059
SOLAR & TRANSMISSION GAIN
NORTH 0 16 0.34 0 OUTSIDE AIR HEAT
SOUTH 0 29 0.34 0
EAST 0 30 0.34 0 CFM G.DIFF bb FACTOR
WEST 0 26 0.34 0 SENS 42 36.6 0.88 1.08 1476
N-E 0 22 0.34 0 LAT 42 -1.28 0.88 0.68 -32
N-W 0 18 0.34 0
S-E 0 30 0.34 0 SUB TOTAL 1443
S-W 0 26 0.34 0 TOTAL 20502
ROOF 0 46 0.12 0 0
HEAT GAIN SAFETY FACTOR @ 3% 615

OTHER TRANSMISSION GAIN GRAND TOTAL HEAT (TONS) 1.8 21117


AGLS 0 36.6 1.13 0
PART 682 31.6 0.45 9698
CEIL 231 31.6 0.45 1 3290 SENSIBLE HEAT FACTOR 0.96
FLOR 0 31.6 0.5 1 0 SELECTED A.D.P. 52.6
DEHUMIDIFIED RISE 19.712
BYPASS O.A. SENSIBLE LOAD
CFM T.DIFF. FACTOR DEHUMIDIFIED AIR Cfm 864
42 36.6 0.12 1.08 201 TONS AS PER Cfm 2.2

INTERNAL SENSIBLE LOAD CHECK RESULTS.


PEOPLE 3 * 245 735 GRAND TOTAL HEAT(BTU/HR/SQFT.) 91.26
APPL. 300 * 3.4 1020 ROOM SENSIBLE HEAT(BTU/HR/SQFT.) 79.46
LIGHTS 347 * 3.4 1.5 1770 SQFT/PERSON 77.13
TONS PER SQFT 0.01
SUB TOTAL 16715 CFM PER SQFT 3.73
TONS/PERSON 0.59
LEAK LOSS +SAFETY FACTOR=10% 1671 DEHUMIDIFIED CFM/TON 490.78
ROOM SENSIBLE HEAT 18386 AREA PER TON 131.49
Area Ton CFM
Project manager 117 1.3 500
Project manager 117 1.3 500
Sales & Busines 245 2.8 1120
Finance 180 2 800
Admin 145 1.8 720
workstation 578 4.4 1760
Kitchen 53 0.5 200
Kitchen Passage 120 0 0
Lounge 88 0 0
Server 1 400
6000

6000

Area Ton CFM


Manager 1 188 2 750
2 200 2 750
3 238 2.3 850
Meeting 210 1.7 600
Engg 173 1.3 500
workstation 2 556 4 1500
Reception 232 1.5 600
5550
440 6000
440 1160
1000
800
516.7464
1263.158 440
143.5407
0
0
600
5203.445

1
0.717703

6000 1200 520


2600 0.433333 920 680
3400 0.566667

You might also like