Hoja de Datos - Tanque Skimmer
Revisión: 02 Fecha Rev: 02-Dic-2022
(10-TR-5226)
Disciplina: PRO Tipo Documento: DTS
23 DESIGN AND TESTING Purchaser to Review Design Prior to Ordering Material? Yes No
24 Maximun Design Temperature 60°C Design Metal Temperature -9 °C
25 Design Pressure (Max/min) 160 (mmCA) / -25 (mmCA) External Pressure 0.9226 bara
26 Maximum Fill Rate 13.25 m3/hr Maximum Emptying Rate 13.25 m3/hr
27 Design Liquid Level 5160 mm Residence time 8 hours
28 Corrosion Allowance Shell 3.0 mm Roof 3.0 mm
31 Design Pressure
52
Este documento es propiedad de TotalEnergies EP Bolivie. No debe ser archivado, reproducido o revelado sin la autorización escrita de la COMPAÑÍA.
BO-INC-65-IPEC-351013_rev02
TotalEnergies EP Bolivie Doc. Ref.: BO-INC-65-IPEC-351013
CTR Referencia: NA
69 13. Tank Bottom Plate Thickness According to API 650 (mm) Lap Butt Sea
75 15. Intermediate Wind Girder? Yes No 16. Top Wind Girder for Use as Walkway Yes No
76
77
17. Roof Type Supported Self Supported Floating (internal)
117
118 Earthing Lugs Qty 2 Specification According to API 650 Latest edition and GS EP ELE 031
Este documento es propiedad de TotalEnergies EP Bolivie. No debe ser archivado, reproducido o revelado sin la autorización escrita de la COMPAÑÍA.
BO-INC-65-IPEC-351013_rev02
TotalEnergies EP Bolivie Doc. Ref.: BO-INC-65-IPEC-351013
CTR Referencia: NA
139 Other
140
141 25. Walkway (Note 6) Width (Note 2) mm Length (Note 2) mm
142 26.Drawoff Sump Basic Standard API 650 Special
143 27.Bolted Door Sheet? Yes No (Appendix (tanks Only) Raised Flush
144
145 28. Internal Piping Swing Line No (Note 2) Suction Line No (Note 2)
146
147 29. Accesories Pressure Vacuum Valve Yes No By Others
150 Slotter Diffusers YES (Note 2) Fireproofing Water Spray Ring Yes No By Others
166 M1 1 914x1219/ 36x48 API 650 Cleanout door L9 1 50.8/2 150# RF Reserve
167 M2 1 914x1219/ 36x48 API 650 Cleanout door U1 1 101.6/4 150# RF Auxiliar nozzel
168
Este documento es propiedad de TotalEnergies EP Bolivie. No debe ser archivado, reproducido o revelado sin la autorización escrita de la COMPAÑÍA.
BO-INC-65-IPEC-351013_rev02
TotalEnergies EP Bolivie Doc. Ref.: BO-INC-65-IPEC-351013
CTR Referencia: NA
170 NOTES
171 1.- Acording to BO-INC-65-IPEC-402001 Base del Diseño Estructural y Civil
172 2.- To be confirmed/completed by manufacturer during detail design. All calculations shall be submitted for the company approval.
173 3.- Slope oriented to drain sump.
174 4.- The manufacturer Shall comfirm the system according to GS EP COR 352 / GS EP COR 354
175 5.- According to BO-INC-65-IPEC-532002 ''FILOSOFÍA DE DISEÑO DE PROTECCIÓN CATÓDICA '
176 6.- The Tank shall be provided with walkway and handrail around roof periphery that allows access to all nozzles, valves and instruments
177 in the roof.
178 7.- With internal pipe, elbow and sump.
179 8.- Carbon steel bolting shall be zinc plated and bichromated according to ASTM F 1941M and ASTM B 633 (class Fe/Zn-12.SC3), and
180 coated according to GS EP COR 352.
181 9.- For further information see following references:
182 - BO-INC-65-IPEC-107004 "MEMORIA DE CÁLCULO DE TANQUES - TRATAMIENTO DE AGUA DE PRODUCCIÓN"
183 - BO-INC-65-IPEC-351004 "ESPECIFICACIONES TECNICAS PARA TANQUE SKIMMER (10-TR-5226)"
184 10. - Klingersil C4430 or similar for cleanout doors, gasket for internal pipping acording to Class B03.
185 11. For Tank Detail Design, review earth pressure capacity. See document BO-INC-65-IPEC-752002 Informe Geotecnico.
186 12. Tank shall be design according to API 650 and GS EP PVV 312.
187 13. According to class B03 of document GS EP PVV 112.
188
189
Este documento es propiedad de TotalEnergies EP Bolivie. No debe ser archivado, reproducido o revelado sin la autorización escrita de la COMPAÑÍA.
BO-INC-65-IPEC-351013_rev02
TotalEnergies EP Bolivie Doc. Ref.: BO-INC-65-IPEC-351013
CTR Referencia: NA
REFERENCE DRAW
BANDEJA DE 2"
U5
DISTRIBUCION
SUPERIOR LLL: 4600 mm
1:20 LLLL: 4500 mm
DIFUSOR
RANURADO U4 2"
F2
2"
5400 mm
2" U3
N1
6" 2"
BANDEJA DE
DISTRIBUCION L9
CIEGO
1:20 INFERIOR
4"
DIFUSOR
U1
RANURADO
M2 M1 6" 400 mm
36" x 48" 36" x 48"
N2
4" 4"
N8 N9-N13
1:120 1:120
5500mm
DETALLE A
50 mm
360 mm
270 mm
Notes
2.- The constructor should validate the dimensions as well as the distrubution of the connections of the tank.
Este documento es propiedad de TotalEnergies EP Bolivie. No debe ser archivado, reproducido o revelado sin la autorización escrita de la COMPAÑÍA.
BO-INC-65-IPEC-351013_rev02