Professional Documents
Culture Documents
AS 2067/amdt 1/2010-02-24
AS 2067/amdt 1/2010-02-24
STANDARDS AUSTRALIA
Amendment No. 1
to
AS 2067—2008
Substations and high voltage installations exceeding 1 kV a.c.
CORRECTION
The 2008 edition of AS 2067 is amended as follows; the amendment(s) should be inserted in the appropriate
place(s).
SUMMARY: This Amendment applies to the Preface, Clauses 1.2, 1.3.4, 1.3.20, 1.3.30, 1.3.31, 1.3.44, 1.3.51,
1.3.62, 2.1.1, 2.2.4.1, 2.2.6, 3.1, 3.2, 3.3, 3.4, 4.1.1, 4.2.2, 4.2.3, 5.1.4, 5.2.7, 5.5.2.1, 6.7.3, 6.7.4, 6.7.8, 6.7.9,
6.7.13, 6.7.14, 7.3.2, Paragraph B2.1, Appendices C and E, Tables 3.1 and 3.2, 6.1, A1 and Figures 5.1, 5.2,
5.3, 6.7.
Published on 24 February 2010.
AMDT Preface
No. 1
FEB In the fourth paragraph, replace ‘20007’ with ‘2007’.
2010
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT
Clause 2.1.1
No. 1 In the sixth paragraph, beginning ‘Unless the installation’ insert the word ‘solely’ after
FEB
2010 ‘operate’.
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT
Clause 3.4
No. 1 Delete the third paragraph and replace with—
FEB
2010
‘The minimum clearances in air between phases or between conductors of the same phase
that are separable electrically from each other shall be at least 15% greater than the values
given in Column 6 of Table 3.1 (for voltages up to and including U m = 245 kV).’
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
TABLE 3.1
ROD TO STRUCTURE/PLATE GEOMETRY (VOLTAGE RANGE 1 AND VOLTAGE RANGE II)
1 2 3 4 5 6 7 8 9 10 11 12
Rated short Safety clearances for operational
Rated Rated
duration Minimum Minimum purposes and maintenance work
Highest lightning switching Non- Ground
Nominal power phase-to- phase-to- Section Horizontal Vertical
voltage impulse impulse flashover safety
voltage frequency earth phase safety work safety work safety
(see note 6) withstand withstand distance clearance
withstand clearance clearance clearance clearance clearance
voltage voltage
voltage (N + G) (N + 1900) (N + 1340)
(kV r.m.s) (kV r.m.s) (kV r.m.s) (kV peak) (kV peak) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Un Um N G S H V
Up to 3.3 Up to 3.6 10 40 60 70 65 2440 2505 1965 1405
6.6 7.2 20 60 90 105 100 2540 2000 1440
11 12 28 75 120 140 130 2570 2030 1470
28 (95) (160) 185 175 2615 2075 1515
22 24 50 125 220 255 240 2680 2140 1580
50 (145) (280) 325 310 2750 2210 1650
33 36 70 170 320 370 350 2790 2250 1690
70 (200) (380) 440 420 2860 2320 1760
66 72.5 140 325 630 725 695 3135 2595 2035
110 123 185 450 900 1035 990 3430 2890 2330
230 550 1100 1265 1210 3650 3110 2550
132 145 230 550 1100 1265 1210 3650 3110 2550
275 650 1300 1495 1430 3870 3330 2770
220 245 360 850 1700 1955 1800 4240 3700 3140
395 950 1900 2185 2015 4455 3915 3355
460 1050 2100 2415 2225 4665 4125 3565
275 300 380 950 750 1900 2185 2015 4455 3915 3355
450 1050 850 2400 2760 2545 4985 4445 3885
330 362 450 1050 850 2400 2760 2545 4985 4445 3885
520 1175 950 2900 3335 3075 5515 4975 4415
500 550 620 1425 1050 3400 3910 3605 6045 5505 4945
680 1550 1175 4100 4715 4345 6785 6245 5685
NOTE: Refer to Notes following Table 3.2.
AMDT Table 3.2
No. 1
FEB Delete Table 3.2 and the following Notes and replace with the following:
2010
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
TABLE 3.2
CONDUCTOR TO STRUCTURE GEOMETRY, U m >245 kV (VOLTAGE RANGE II)
1 2 3 4 5 6 7 8 9 10 11 12
Rated short Safety clearances for operational
Rated Rated
duration Minimum Minimum purposes and maintenance work
Highest lightning switching Non- Ground
Nominal power phase-to- phase-to- Section Horizontal Vertical
voltage impulse impulse flashover safety
voltage frequency earth phase safety work safety work safety
(see note 6) withstand withstand distance clearance
withstand clearance clearance clearance clearance clearance
voltage voltage
voltage (N + G) (N + 1900) (N + 1340)
(kV r.m.s) (kV r.m.s) (kV r.m.s) (kV peak) (kV peak) (mm) (mm) (mm) (mm) (mm) (mm) (mm)
Un Um N G S H V
275 300 380 950 750 1700 1955 1800 2440 4240 3700 3140
450 1050 850 1900 2185 2015 4455 3915 3355
330 362 450 1050 850 1900 2185 2015 4455 3915 3355
520 1175 950 2200 2530 2330 4770 4230 3670
500 550 620 1425 1050 2600 2990 2755 5195 4655 4095
680 1550 1175 3100 3565 3285 5725 5185 4625
NOTES TO TABLES 3.1 AND 3.2
1 The clearances in Table 3.1 and 3.2 are based on the climatic conditions described in Clause 2.4.
2 The phase-to-earth clearances given in Column 6 of Table 3.1 are for unfavourable configurations of live and earthed parts, i.e. the ‘rod-structure’ arrangement, and may be
used for determining clearances to earth from live parts of any configuration.
3 The phase-to-earth clearances given in Column 6 of Table 3.2 for U m >245 kV r.m.s. are for ‘conductor-structure’ configurations normally employed at the higher voltages.
(For background information on electrode configurations, refer to CIGRE Technical Brochure 72-1992, Guidelines for the evaluation of dielectric strength of external
insulation, and to AS 1824.2.)
4 The higher values shown in parentheses in Column 4 are included to cover those distribution installations that may be exposed to higher than normal overvoltages or where a
higher level of safety or withstand is required. For other installations the lower values are preferred.
5 The values shown in parentheses in Column 6 correspond to the rated lightning impulse withstand voltages shown in parentheses in Column 4.
6 For U m <36 kV r.m.s., it may be desirable to increase the phase-to-earth and phase-to-phase clearances where the presence of birds or vermin could cause a hazard or for
constructional or other reasons.
7 The non-flashover distances given in Column 8 include a margin of 10% up to an air clearance of 1300 mm in Column 6 and 6% for 1400 mm and above to allow for variations
in construction dimensions. This margin may be deleted when the conditions for carrying out the work are adequate to ensure that the minimum phase-to-earth air clearance is
observed in all cases.
8 If considered desirable, the section safety clearance given in Column 10 may be increased to 3000 mm as a minimum for air clearances up to 380 mm, in Column 6.
AMDT Clause 4.1.1
No. 1
FEB Delete Item (a) and replace with—
2010
‘(a) Safe physical arrangement when properly assembled, installed and connected to
supply.’
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT Figure 5.1
No. 1
FEB Delete the caption and replace with—
2010
X
S
S
X N
N
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT Clause 5.5.2.1
No. 1
FEB
Delete the last paragraph and replace with—
2010
‘Pipelines and other equipment, if allowed in substations, shall be designed so that the
electrical installation is not affected, even in the event of damage to the pipe or other
equipment.’
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT Figure 6.7
No. 1
FEB Delete the figure and replace with—
2010
AMDT Appendix A
No. 1
FEB 1 Delete Table A1 and replace with the following:
2010
TABLE A1
TYPICAL TOUCH VOLTAGE LIMITS
Time (msec) Touch voltages
C1 C2
10 355 808
20 351 790
50 339 742
100 319 676
150 297 619
200 270 563
300 205 436
400 137 306
500 93 214
700 67 136
1000 56 109
2000 49 94
5000 45 85
10000 43 82
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
2 Delete the text after Table A1 and replace with—
‘The values for the two curves C1 and C2 used in Figure A2 are shown in Table A1.
Formulae by which the specified voltage limits may be calculated are as follows:
C1 Special locations—High public contact likelihood with negligible additional
series impedance
a + ct + et 2 + gt 3 + it 4 + kt 5
Vt =
1+ bt + dt 2 + ft 3 + ht 4 + jt 5
where
t = clearing time in milliseconds
a = 358.8444
b = −3.8399e-03
c = −1.7939
d = 3.7036e-06
e = 3.4832e-03
f = 1.4786e-08
g = −2.6211e-06
h = −4.8406e-11
i = −4.4354e-10
j = 5.2568e-14
k = 2.1260e-12
C2 Normal locations—Normal public contact likelihood with typical mix of
additional series impedance
a + ct + et 2 + gt 3 + it 4
Vt =
1+ bt + dt 2 + ft 3 + ht 4
where
t = clearing time in milliseconds
a = 828.10
b = 8.0916e-04
c = −1.3631
d = −6.2782e-06
e = 6.2308e-04
f = 1.5372e-08
g = 1.5046e-06
h = 1.3723e-11
i = 1.0909e-09’
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
AMDT Paragraph B2.1
No. 1
FEB Delete Item (b) and replace with—
2010
‘(b) has combined HV and LV (common) earthing; and’
AMDT Appendix C
No. 1
FEB Delete the entire Appendix and replace with the following:
2010
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
APPENDIX C
FIRE RISK ZONES FOR DISTRIBUTION SUBSTATIONS
(Informative)
For all figures below, the fire protection requirements of the Building Code of Australia
apply together with (if combustible liquid-containing electrical equipment is employed) the
Appendix H requirements of AS 1940—2004. The examples are for distribution substations
having transformers with less than 1000 l of oil per transformer.
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C2 NON-FIRE-RATED SUBSTATION IN AN AREA INCORPORATING HV
EQUIPMENT WITH COMBUSTIBLE LIQUID DIELECTRIC
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C3 NON-FIRE-RATED SUBSTATION IN AN AREA INCORPORATING DRY-
TYPE HV EQUIPMENT (SWITCHGEAR AND/OR TRANSFORMERS) OR HV EQUIPMENT
WITH NON-COMBUSTIBLE DIELECTRIC
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C4 ADJACENT NON-FIRE-RATED SUBSTATION IN AN AREA
INCORPORATING HV EQUIPMENT WITH COMBUSTIBLE DIELECTRIC
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C5 ATTACHED OR ADJACENT SUBSTATION WITH FIRE-RATED WALLS AND
ROOF AND NON-FIRE-RATED DOORS AND VENTS
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C6 INDOOR SUBSTATION WITH PUBLIC ACCESS ABOVE
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C7 OPEN TOP SUBSTATION WITH FIRE-RATED WALLS AND NON-FIRE-
RATED DOORS
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.
FIGURE C8 NON-FIRE-RATED SUBSTATION IN A COMMERCIAL/INDUSTRIAL AREA
INCORPORATING HV EQUIPMENT WITH COMBUSTIBLE LIQUID DIELECTRIC AND
FIRE-RATED BLAST WALL
AMDT Appendix E
No. 1
FEB Delete the entire Appendix.
2010
Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.