SYNCRONIZING GENERATOR G1 & G2

STEP ITEM PICTURE DESCRIPTION

 Supply tnb only for “AUTO


1 OFF SUPPLY TNB
MODE’

 Diesel fuel
CHECK ENGINE  Engine oil
2 GENERATOR  Battery
 Belting & etc

 Reset OCR & EF relay


protection
CHECK PANEL &
3 PROTECTION
 All selector switch in ‘OFF’
position
 All breaker in ‘OFF’ position

GENERATOR
4 SELECTOR
 Manual (MAN)

 G1 or G2
GEN. SWITCH
5 SELECTOR
 Depend which generator will
be ‘MAIN’ generator

MODE SELECTION
6 SELECTOR
 Manual (MAN)
SYNCRONIZING GENERATOR G1 & G2

 Select ‘ON’ position for engine


7 D.C. Control
ready to start

 Push green ‘START’ button


8 ‘START’ Button hold until engine generator
running

 Check and make sure voltage


and frequency in demand
condition
Volt Meter &  Adjust at ‘SET SPEED’
9 Frequency Meter (Governor) to set FREQUENCY
generator
 Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator

NEUTRAL  Push green button to ‘CLOSE’


10 CONTACTOR ‘CLOSE’ contactor for neutral
Button generator
SYNCRONIZING GENERATOR G1 & G2

 Push green button for close


11 MCCB ‘CLOSE’ button MCCB generator for give
supply to user

 Push ‘ON’ ACB to give supply


12 ACB ESSENTIAL
for bussbar

 Pull to ‘ON’ MCCB to give


MCCB to MSP (Main
13 Supply Panel)
supply for Main Supply Panel
(MSP)

 Pull to ‘ON’ MCCB Capacitive


MCCB
 Push green button to give
14 Capacitive Load Bank
supply CAPACITIVE LOAD
Panel
BANK PANEL

 Pull to ‘ON’ MCCB Inductive


MCCB
 Push green button to give
15 Inductive Load Bank
supply INDUCTIVE LOAD BANK
Panel
PANEL
SYNCRONIZING GENERATOR G1 & G2

‘ON’ button  Push 1 green button for ‘ON’


16 Capacitive Capacitive Load

 Push 2 green button for ‘ON’


17 ‘ON’ button Inductive
Inductive Load

 Make sure power factor


meter in 0.85 at PF Meter
MSP

18 Power Factor Meter


SYNCRONIZING GENERATOR G1 & G2

ADD LOAD AND SYNCHORONIZING GENERATOR

 G1 or G2
 Depend which generator will
GEN. SWITCH
19 SELECTOR
be ‘FOLLOWER’ generator
 For Indication at
‘SYNCHRONIZING PANEL’

MODE SELECTION
20 SELECTOR
 Manual (MAN)

 Select ‘ON’ position for engine


21 D.C. Control
ready to start

 Push green ‘START’ button


22 ‘START’ Button hold until engine generator
running
SYNCRONIZING GENERATOR G1 & G2

 Check and make sure voltage


and frequency in demand
condition following generator
‘MAIN’
Volt Meter &
23 Frequency Meter
 Adjust at ‘SET SPEED’
(Governor) to set FREQUENCY
generator
 Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator

NEUTRAL  Push green button to ‘CLOSE’


24 CONTACTOR ‘CLOSE’ contactor for neutral
Button generator

 Indicator Synchronize Scope


in ‘Clock wise’ direction
 Indicator lamp until to ‘DARK
LAMP’
SYNCHRONIZING
25 PANEL
 All must same for FOLLOWER
Generator follow the MAIN
Generator
 Voltage, Frequency, Voltage
Angle, Voltage Sequence

 Push green button for close


MCCB generator to
26 MCCB ‘CLOSE’ button synchronized generator
FOLLOWER to generator
MAIN
SYNCRONIZING GENERATOR G1 & G2

 Push red button for open


MCCB generator for safety
from Neutral Return / Reverse
27 MCCB ‘OPEN’ button Power
 Only the smallest capacity
generator will open the
Neutral Contact

ADD Load
 Push 1 more green button for
27 ‘ON’ button
‘ON’ Capacitive Load
Capacitive

ADD Load  Push 2 more green button for


28 ‘ON’ button Inductive ‘ON’ Inductive Load

 Make sure power factor


29 Power Factor Meter meter in 0.85 at PF Meter
MSP
SYNCRONIZING GENERATOR G1 & G2

REDUCE LOAD AND SPLIT GENERATOR

Reduce Load
 Push 1 red button for ‘OFF’
30 ‘OFF’ button
Capacitive Load
Capacitive

Reduce Load
 Push 2 red button for ‘OFF’
31 ‘OFF’ button
Inductive Load
Inductive

 Push red button for open


MCCB generator for divorce
32 MCCB ‘OPEN’ button
generator FOLLOWER to
generator MAIN

NEUTRAL  Push red button to ‘OPEN’


33 CONTACTOR ‘OPEN’ contactor for neutral
Button generator
SYNCRONIZING GENERATOR G1 & G2

 Check and make sure voltage


and frequency in demand
condition
Volt Meter &  Adjust at ‘SET SPEED’
34 Frequency Meter (Governor) to set FREQUENCY
generator
 Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator

 Select ‘OFF’ position for


35 D.C. Control
engine to STOP

MODE SELECTION
36 SELECTOR
 ‘OFF’ Position

REMOVE ALL LOAD AND STOP GENERATOR

Remove Load
 Push 1 red button for ‘OFF’
37 ‘OFF’ button
Capacitive Load
Capacitive
SYNCRONIZING GENERATOR G1 & G2

Remove Load
 Push 2 red button for ‘OFF’
38 ‘OFF’ button
Inductive Load
Inductive

 Push red button for open


39 MCCB ‘OPEN’ button
MCCB generator

NEUTRAL  Push red button to ‘OPEN’


40 CONTACTOR ‘OPEN’ contactor for neutral
Button generator

 Check and make sure voltage


and frequency in demand
condition
Volt Meter &  Adjust at ‘SET SPEED’
41 Frequency Meter (Governor) to set FREQUENCY
generator
 Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator
SYNCRONIZING GENERATOR G1 & G2

 Select ‘OFF’ position for


42 D.C. Control
engine to STOP

MODE SELECTION
43 SELECTOR
 ‘OFF’ Position

GENERATOR
44 SELECTOR & GEN.  ‘OFF’ Position
SWITCH

FINNISH