SYNCRONIZING GENERATOR G1 & G2
STEP ITEM PICTURE DESCRIPTION
Supply tnb only for “AUTO
1 OFF SUPPLY TNB
MODE’
Diesel fuel
CHECK ENGINE Engine oil
2 GENERATOR Battery
Belting & etc
Reset OCR & EF relay
protection
CHECK PANEL &
3 PROTECTION
All selector switch in ‘OFF’
position
All breaker in ‘OFF’ position
GENERATOR
4 SELECTOR
Manual (MAN)
G1 or G2
GEN. SWITCH
5 SELECTOR
Depend which generator will
be ‘MAIN’ generator
MODE SELECTION
6 SELECTOR
Manual (MAN)
SYNCRONIZING GENERATOR G1 & G2
Select ‘ON’ position for engine
7 D.C. Control
ready to start
Push green ‘START’ button
8 ‘START’ Button hold until engine generator
running
Check and make sure voltage
and frequency in demand
condition
Volt Meter & Adjust at ‘SET SPEED’
9 Frequency Meter (Governor) to set FREQUENCY
generator
Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator
NEUTRAL Push green button to ‘CLOSE’
10 CONTACTOR ‘CLOSE’ contactor for neutral
Button generator
SYNCRONIZING GENERATOR G1 & G2
Push green button for close
11 MCCB ‘CLOSE’ button MCCB generator for give
supply to user
Push ‘ON’ ACB to give supply
12 ACB ESSENTIAL
for bussbar
Pull to ‘ON’ MCCB to give
MCCB to MSP (Main
13 Supply Panel)
supply for Main Supply Panel
(MSP)
Pull to ‘ON’ MCCB Capacitive
MCCB
Push green button to give
14 Capacitive Load Bank
supply CAPACITIVE LOAD
Panel
BANK PANEL
Pull to ‘ON’ MCCB Inductive
MCCB
Push green button to give
15 Inductive Load Bank
supply INDUCTIVE LOAD BANK
Panel
PANEL
SYNCRONIZING GENERATOR G1 & G2
‘ON’ button Push 1 green button for ‘ON’
16 Capacitive Capacitive Load
Push 2 green button for ‘ON’
17 ‘ON’ button Inductive
Inductive Load
Make sure power factor
meter in 0.85 at PF Meter
MSP
18 Power Factor Meter
SYNCRONIZING GENERATOR G1 & G2
ADD LOAD AND SYNCHORONIZING GENERATOR
G1 or G2
Depend which generator will
GEN. SWITCH
19 SELECTOR
be ‘FOLLOWER’ generator
For Indication at
‘SYNCHRONIZING PANEL’
MODE SELECTION
20 SELECTOR
Manual (MAN)
Select ‘ON’ position for engine
21 D.C. Control
ready to start
Push green ‘START’ button
22 ‘START’ Button hold until engine generator
running
SYNCRONIZING GENERATOR G1 & G2
Check and make sure voltage
and frequency in demand
condition following generator
‘MAIN’
Volt Meter &
23 Frequency Meter
Adjust at ‘SET SPEED’
(Governor) to set FREQUENCY
generator
Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator
NEUTRAL Push green button to ‘CLOSE’
24 CONTACTOR ‘CLOSE’ contactor for neutral
Button generator
Indicator Synchronize Scope
in ‘Clock wise’ direction
Indicator lamp until to ‘DARK
LAMP’
SYNCHRONIZING
25 PANEL
All must same for FOLLOWER
Generator follow the MAIN
Generator
Voltage, Frequency, Voltage
Angle, Voltage Sequence
Push green button for close
MCCB generator to
26 MCCB ‘CLOSE’ button synchronized generator
FOLLOWER to generator
MAIN
SYNCRONIZING GENERATOR G1 & G2
Push red button for open
MCCB generator for safety
from Neutral Return / Reverse
27 MCCB ‘OPEN’ button Power
Only the smallest capacity
generator will open the
Neutral Contact
ADD Load
Push 1 more green button for
27 ‘ON’ button
‘ON’ Capacitive Load
Capacitive
ADD Load Push 2 more green button for
28 ‘ON’ button Inductive ‘ON’ Inductive Load
Make sure power factor
29 Power Factor Meter meter in 0.85 at PF Meter
MSP
SYNCRONIZING GENERATOR G1 & G2
REDUCE LOAD AND SPLIT GENERATOR
Reduce Load
Push 1 red button for ‘OFF’
30 ‘OFF’ button
Capacitive Load
Capacitive
Reduce Load
Push 2 red button for ‘OFF’
31 ‘OFF’ button
Inductive Load
Inductive
Push red button for open
MCCB generator for divorce
32 MCCB ‘OPEN’ button
generator FOLLOWER to
generator MAIN
NEUTRAL Push red button to ‘OPEN’
33 CONTACTOR ‘OPEN’ contactor for neutral
Button generator
SYNCRONIZING GENERATOR G1 & G2
Check and make sure voltage
and frequency in demand
condition
Volt Meter & Adjust at ‘SET SPEED’
34 Frequency Meter (Governor) to set FREQUENCY
generator
Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator
Select ‘OFF’ position for
35 D.C. Control
engine to STOP
MODE SELECTION
36 SELECTOR
‘OFF’ Position
REMOVE ALL LOAD AND STOP GENERATOR
Remove Load
Push 1 red button for ‘OFF’
37 ‘OFF’ button
Capacitive Load
Capacitive
SYNCRONIZING GENERATOR G1 & G2
Remove Load
Push 2 red button for ‘OFF’
38 ‘OFF’ button
Inductive Load
Inductive
Push red button for open
39 MCCB ‘OPEN’ button
MCCB generator
NEUTRAL Push red button to ‘OPEN’
40 CONTACTOR ‘OPEN’ contactor for neutral
Button generator
Check and make sure voltage
and frequency in demand
condition
Volt Meter & Adjust at ‘SET SPEED’
41 Frequency Meter (Governor) to set FREQUENCY
generator
Adjust at ‘SET VOLTAGE’ (AVR)
to set VOLATGE generator
SYNCRONIZING GENERATOR G1 & G2
Select ‘OFF’ position for
42 D.C. Control
engine to STOP
MODE SELECTION
43 SELECTOR
‘OFF’ Position
GENERATOR
44 SELECTOR & GEN. ‘OFF’ Position
SWITCH
FINNISH