Voltage Rating :
3 x 220/380VAC.50 or 60Hz
Current Rating :
1.5(6A)
Features 5 (20A)
• Three phase 4 wires 10(40A)
• Single or Multi Tarif 20(80A)
• Class 1.0 accuracy Accuracy :
• Low starting current 1.0 Class
• Permanent display Standard Refer :
• Pulse output IEC6136, IEC60512
• Modbus RTU Surge Test :
• IEC61036 & IEC60512 6KV, 1.2/50micro sec.
• Protection IP20 Insulation :
2.5KVms, 1 min. Between voltage inputs & meter
Application FCC Test :
• Tenant office building 10V/m. 80-1000MHz
• Food concessions campus Over Voltage :
• Entertainment facilities 120% of rated voltage
• Shopping mall Power Consumption :
• Airport <4VA/phase
• Utility metering Expected Life :
• Commercial building >50,000 hours
Display :
Overview 7 digits of LCD display, loop different data; Time, Date,
The HEM three phase electronic type kWh meter is Total Kwh, Spike, Peak, Flat, Valley.
the latest development revenue meter. The meter has Starting Current :
been designed to meet the modern standard of elec- 20mA
trical utilities. High metering security is designed to Resolution :
against ilegal abstraction and fraud. 0.1kWh
Protection from mechanical, magnetic or electri- Pulse Output :
cal interference is built into the products as an anti- 6A:6400; 20A:1600; 40A:800; 80A:400pulse/kWh
fraud, the meter runs forward regardless of the energy Phase Lost Detection :
direction. Three LED indicate the status of each phase
The high accuracy, wide operating range and very Temperature :
low starting current makes it the ideal choice. The SMT -20 to 60deg.C<=95%
(Surface Mount Technology) design and construction Communication :
guarantee a long and service free life. Modbus RTU,
Beside HEM300 is well protected against tropical Baudrate 9600bps
conditions by means of a gasket seal located between Mounting type :
the base and terminal cover. The energy register is of 35mm Surface DIN rail mounting
the well-proven digital type of LCD, incorporating 7 Size :
digits. The design of the register ensure easy reading 126(H)x89(W)x74(D)mm
of the meter and permanent display. Weight :
Automatic meter reading function is provided by 710g
it is electronic pulse output or through Modbus RTU
protocol port connections. The register value is always
maintained with meter’s display.
Dimension
(Unit : mm) Front view Side view

Three Phase kWh Meter Pulse R S T Rev

35.5
91
89

45
F1 F2 F3 F4

126 46
69
74

Wiring Diagram
3-phase without CT

1 3 5 N L1 L1’ L2 L2’ L3 L3’ 7 8 9 10 11 12

R
A B + - + -
S
Load RS485 Time IMP E IMP
T
N

3-phase with CT

1 3 5 N L1 L1’ L2 L2’ L3 L3’ 7 8 9 10 11 12


* * *
R
A B + - + -
S
RS485 Time IMP E IMP
T
N

Ordering Information
HEM300 - - -

10A,20A,40A,80A or etc

DC - Direct Connect
CT - External CT

E - Single Tariff
F - Multi Tariff