Statement of Conformity
(2) Equipment and protective systems
intended for use in potentially
explosive atmospheres, Directive 2014/34/EU
(3) Statement of Conformity TÜV 14 ATEX 148929 X Issue: 03
Number:
(4) for the product: Fieldbus couplers/controllers resp. analog input/output modules
resp. digital input/output modules and communication supply and
segment modules type WAGO-I/O-SYSTEM *750-****/*
(5) of the manufacturer: WAGO GmbH & Co. KG
(6) Address: Hansastrasse 27
32423 Minden
Germany
Order number: 8003042573
Date of issue: See date of signature
(7) The design of this product and any acceptable variation thereto are specified in the schedule to this
EU-Type Examination Certificate and the documents therein referred to.
(8) TÜV NORD CERT GmbH certifies that the essential health and safety requirements for the design
and construction of this product for use in potentially explosive atmospheres in accordance with
Annex II of the Directive have been met.
The examination and test results are recorded in the confidential Assessment Report
No. 22 214 317045.
(9) Compliance with the Essential Health and Safety Requirements has been assured by compliance
with:
EN IEC 60079-0:2018/AC:2020-02 EN IEC 60079-7:2015/A1:2018 EN IEC 60079-15:2019
except in respect of those requirements listed at item 18 of the schedule.
(10) If the sign ”X” is placed after the certificate number, it indicates that the product is subject to the
Specific Conditions for Use specified in the schedule to this certificate.
(11) This statement of conformity relates only to the design, examination and tests of the specified
product in accordance to the Directive 2014/34/EU. Further requirements of the Directive apply to
the manufacturing process and supply of this equipment. These are not covered by this Statement
of Conformity.
(12) The marking of the product shall include the following:
II 3 G Ex ec nC IIC T4 Gc or II 3 G Ex ec IIC T4 Gc
See electrical data for details
TÜV NORD CERT GmbH, Am TÜV 1, 45307 Essen, notified by the central office of the countries for safety engineering
(ZLS), Ident. Nr. 0044, legal successor of the TÜV NORD CERT GmbH & Co. KG Ident. Nr. 0032
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Type code:
WAGO-I/O-SYSTEM z750-z3xx/* Fieldbus coupler
WAGO-I/O-SYSTEM z75y-z4xx/* Digital/Analog Input Modules
WAGO-I/O-SYSTEM z75y-z5xx/* Digital/Analog Output Modules
WAGO-I/O-SYSTEM z75y-z6xx/* Communication supply and segment Modules
WAGO-I/O-SYSTEM z750-z8xx/* Fieldbus controller
WAGO-I/O-SYSTEM z750-8xxx/* Controller PFC
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Electrical data:
Additionally assessed modules within the TÜV 14 ATEX 148929 X issue 03
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
0750-0366 FC EtherNet/IP G4 DLR
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC] = ±2.5 Un[VDC] = 5
Ethernet
2.7
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.3
In[A] = 0.48 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
0750-0527 (4DO 30V AC/DC 2.0A SSR)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 8 Un[VDC] 5
=
Un[VAC] = 30 Max I[A] per Ch. = 2 In[mA] = 57 1
Un[VDC] = 48
In[A] = 10
0750-0528 (4DO 30V AC/DC 2.0A SSR/ Isolated)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 8 Un[VDC] = 5
Un[VAC] = 30 Max I[A] per Ch. = 2 In[mA] = 57
1
Un[VDC] = 48
In[A] = 10
0750-0498 8AI TC/ adj.
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC]= 5
Un[VDC] = 24 8 Channel In[mA] = 100 0.6
In[A] = 10 Thermocouple
0750-1491 (2AI Resistor Bridge (Strain Gauge))
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC]= 5
Un[VDC] = 24 For the connection to In[mA] = 200 1
In[A] = 10 resistor bridge
0750-0600/0000-0001 (End Module with potentialgroup)
II 3 G Ex ec IIC T4 Gc
0750-0661/0000-0004 (4FDI 24V PROFIsafe)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 4 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 UIN[VDC] = 24 In[mA] = 120
In[mA] = 25 In[A] = 10 Max I[mA] per Ch. = 100
1
Terminals: 5 - 8
Max UIN[VDC] = 24
I[mA] = 3
0750-0662/0000-0004 (8FDI 24V PROFIsafe)
II 3 G Ex ec IIC T4 Gc
Terminals: 5-8, 13-16 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 UIN[VDC] = 24 In[mA] = 120
In[mA] = 35 In[A] = 10 Max I[mA] per Ch. = 100
1.5
Terminals: 1 - 4, 9-12
Max UIN[VDC] = 30
I[mA] = 3
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
0750-0666/0000-0004 (4FDI/2FDO 24V/10A PROFIsafe)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 4 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 UIN[VDC] = 24 In[mA] = 120
In[mA] = 30 In[A] = 10 Max I[mA] per Ch. = 100
Terminals: 5 - 8 2.5
Max UIN[VDC] =24 (@ 10A)
I[mA] = 3
Terminals: 9 - 16
Max I[A] per Ch. =10
0750-0667/0000-0004 (4FDI/4FDO 24V/2A PROFIsafe)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 4 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 UIN[VDC] = 24 In[mA] = 120
In[mA] = 35 In[A] = 10 Max I[mA] per Ch. = 100
Terminals: 5 - 8
2
Max UIN[VDC] = 24
I[mA] = 3
Terminals: 9 - 16
Max I[A] per Ch. = 2
0750-0677 (4PWM 24 VDC 0.2A.)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 24 In[mA] = 85 0.8
In[mA] = 20+Load In[A] = 10 In[A] per Channel = 0.2
0750-1652 (RS-232/485 Serial Interface)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 RS232 In[mA] = 145 0.8
In[A] = 10 Un[VDC] = ±15
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-306 ( DeviceNet )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 11 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 In[A] = 0,12 ∑ In[A] = 1.65
750-307 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-310 ( CC-Link )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-312 ( Modbus/RS 485/150-19200Bd )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-314 ( Modbus/RS 232/150-19200Bd )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-315 ( Modbus/RS 485/ 1,2-115,2kBaud )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-316 ( Modbus/RS 232/1,2-115,2kBaud )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-319 ( LonWorks )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-323 ( Profibus DP 12 MBd/ Digital )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 15 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-324 ( Interbus/ Digital )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB In, D-SUB Out Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-325 (CC-Link Coupler)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]= 5
MCS Un[VDC]=±2.5
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.2 3.5
In[A] = 0.6 (@ 24V) In[A] = 10 ∑ In[A] = 1.8
750-332 (FC BACnet/IP G4 2ETH SD)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Un[VDC] = 24 Ethernet In[A] = 0.45 3.8
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-333 ( Profibus DP/ V1 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 15 In[A] = 0.2 2.2
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.8
750-337 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-338 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-340 ( Profinet IO )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-341 ( ETHERNET TCP/IP 100MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-342 ( ETHERNET )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.2 2.2
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.8
750-343 ( Profibus DP )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.65
750-344 ( Interbus DP 500kBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 D-SUB In. D-SUB Out Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.65
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-345 ( Interbus DP 2MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 D-SUB In. D-SUB Out Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.65
750-346 ( DeviceNet )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 11 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) In[A] = 0.12 ∑ In[A] = 0.65
750-347 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.65
750-348 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.8
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.65
750-351 ( SERCOS III Fieldbus-Coupler 2-port 100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-352 (ETHERNET Fieldbus Coupler 10/100MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.3
In[A] = 0.28 (@ 24V) ∑ In[A] = 0.7
750-352/020-000 (ETHERNET TCP/IP 10/100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.1
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 0.7
750-354 (Fieldbus Coupler 100MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.4
In[A] = 0.26 (@ 24V) ∑ In[A] = 0.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-815 ( Modbus/RS 485/ 1,2-115,2kbaud )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-816 ( Modbus/RS 232/1,2-115,2kbaud )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-819 ( LonWorks )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-823 G4 Ethernet/IP ECO Controller 2ETH
II 3 G Ex ec IIC T4 Gc
Terminals: X3 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Ethernet In[A] = 0.4 3.3
In[A] = 0.5 (@ 24V) ∑ In[A] = 0.7
750-830 ( BACnet/IP )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45, RS232 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-832 Controller BACnet/IP G4 2ETH SD
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Un[VDC]= 24 Ethernet In[A] = 0.45 3.8
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-833 ( Profibus DP/ V1 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 15 In[A] = 0.2 2.2
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.8
750-837 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Series 231 (MCS) Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-838 ( CANopen )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.35 2.9
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.65
750-841 ( ETHERNET Controller 100MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-842 ( ETHERNET Controller )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.2 2.2
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.8
750-843 ( Fieldbus Controller TCP/IP 10MBit/s)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.2 2.2
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.8
750-849 ( KNX IP Fieldbus Controller 10/100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-852 (Ethernet ECO Coupler)
II 3 G Ex ec IIC T4 Gc
Terminals: X3 RJ45 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.4 2
In[A] = 0.3 (@ 24V) ∑ In[A] = 0.7
750-860 ( Linux Ethernet Controller )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-862 G4 Ethernet ECO Controller 2ETH
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: X3 Un[VDC]=±2.5 Un[VDC]= 5
Ethernet
3.3
Un[VDC] = 24 In[A] = 0.4
In[A] = 0.3 (@ 24V) ∑ In[A] = 0.7
750-863 ( Linux Ethernet Controller, RS-232 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45, RS232 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-871 ( ETHERNET TCP/IP 2Port )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-872 ( Fieldbus Controller for Telecontrol Applications 10/100MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45, D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 (RJ-45) In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 Un[VDC] = 15 (D-SUB) ∑ In[A] = 1.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-873 ( Ethernet TCP/IP & RS232 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45, D-SUB Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 (RJ-45) In[A] = 0.3 2.7
In[A] = 0.5 ( @ 24V ) In[A] = 10 Un[VDC] = 15 (D-SUB) ∑ In[A] = 1.7
750-880 (Fieldbus-Controller Ethernet 10/100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.50
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-881 (Fieldbus-Controller Ethernet 10/100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.50
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-882 (Fieldbus-Controller Ethernet 10/100 MBit/s )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.50
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-884 ( Application Controller BA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.50
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-885 (Ethernet MR/SD Fieldbus-Controller )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 RJ-45 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = ±2.5 In[A] = 0.45 3.50
In[A] = 0.5 ( @ 24V ) In[A] = 10 ∑ In[A] = 1.7
750-890 G4 Ethernet Controller 2ETH SD
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]=±2.5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC]= 24 Ethernet In[A] = 0.45 3.8
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-891 G4 Ethernet Controller 2ETH
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]=±2.5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC]= 24 Ethernet In[A] = 0.45 3.8
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-893 G4 Ethernet/IP Controller 2ETH
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]=±2.5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 Ethernet In[A] = 0.45 3.8
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-8100 (PFC100 CS3 ETH ECO)
II 3 G Ex ec IIC T4 Gc
Terminals: X3 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Ethernet In[A] = 0.5 3.9
In[A] = 0.5 (@ 24V) ∑ In[A] = 0.7
750-8101 (PFC100 CS3 ETH)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Un[VDC] = 24 Ethernet In[A] = 0.5 3.5
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-8102 (PFC100 CS3 ETH RS)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]= 5
Un[VDC]=±2.5
Un[VDC] = 24 Un[VDC] = 24 Ethernet In[A] = 0.55
3.8
In[A] = 0.55 (@ 24V) In[A] = 10 X3 RS ∑ In[A] = 1.7
Un[VDC]= 5
232/485
750-8202 PFC200 CS 2ETH RS
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]=±2.5 Un[VDC]= 5
Ethernet
X3 RS 3.0
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.45
232/485
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-8203 PFC200 CS 2ETH CAN
II 3 G Ex ec IIC T4 Gc
X1, X2 Un[VDC]=±2.5
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]= 5
Ethernet
3.0
Un[VDC] = 24 Un[VDC] = 24 X4CAN Un[VDC] = 5 In[A] = 0.45
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
750-8204 PFC200 CS 2ETH RS CAN
II 3 G Ex ec IIC T4 Gc
X1, X2 Un[VDC]=±2.5
Terminals:
1, 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]= 5
Ethernet
X3 RS Un[VDC] = 5
Un[VDC] = 24 Un[VDC]= 24 In[A] = 0.45 3.5
232/485
X4 Un[VDC] = 5
In[A] = 0.5 (@ 24V ) In[A] = 10 ∑ In[A] = 1.7
CAN
750-8206 PFC200 CS 2ETH RS CAN DPS
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]=±2.5 Un[VDC]= 5
Ethernet
X3 RS
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 5 In[A] = 0.45
232/485 4.0
In[A] = 0.5 ( @ 24V) In[A] = 10 X4 CAN Un[VDC] = 5 ∑ In[A] = 1.7
X5
Un[VDC] = 15
Profibus
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-8207 PFC200 CS 2ETH RS 3 G - WAGO-I/O-PRO + e!COCKPIT
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC] = ±2.5 Un[VDC]= 5
Ethernet
X3 RS 5.0
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 15 In[A] = 0.6
232/485
In[A] = 0.55 (@ 24V) In[A] = 10 GSM/Edge/UMTS/HSPA+ ∑ In[A] = 0.7
750-8208 PFC200 CS 2ETH RS CAN DPM
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]=±2.5 Un[VDC]= 5
Ethernet
X3 RS
Un[VDC] = 24 Un[VDC]= 24 Un[VDC] = 15 In[A] = 0.6
232/485 5.0
In[A] = 0.55 (@ 24V) In[A] = 10 X4 CAN Un[VDC] = 5 ∑ In[A] = 1.7
X5
Un[VDC] = 5
Profibus
750-8212 PFC200 CS 2ETH RS
II 3 G Ex ec IIC T4 Gc
X1, X2
Terminals: 1, 5 Terminals: 2, 3, 6, 7 Un[VDC]=±2.5 Un[VDC]= 5
Ethernet
5.0
Un[VDC] = 24 Un[VDC] = 24 X3 RS Un[VDC] = 15 In[A] = 0.6
In[A] = 0.5 (@ 24V) In[A] = 10 232/485 ∑ In[A] = 1.7
750-8213 PFC200 CS 2ETH CAN
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Terminals: 2, 3, 6, 7 X1, X2 Un[VDC]=±2.5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC]= 24 Ethernet In[A] = 0.6
5.0
X4 CAN Un[VDC] = 5
In[A] = 0.5 (@ 24V) In[A] = 10 ∑ In[A] = 1.7
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-400 ( 2 DI 24V DC, high-side switching, 3.0ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 3.7 0.4
In[A] = 10 I[mA] = 4.5
750-401 ( 2 DI 24V DC, high-side switching, 0.2ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 3.7 0.4
In[A] = 10 I[mA] = 4.5
750-402 ( 4 DI 24V DC, high-side switching, 3.0ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 7.5 0.8
In[A] = 10 I[mA] = 4.5
750-403 ( 4 DI 24V DC, high-side switching, 0,2ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 7.5 0.8
In[A] = 10 I[mA] = 4.5
750-404 ( Up/Down Counter )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 DI Terminals : 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 70
In[A] = 10 I[mA] = 5 0.9
DO Terminals : 4, 8
I[A] = 0.5
750-405 ( 2 DI 230V AC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VAC] = 230 U[VAC] = 79 - 253 In[mA] = 2 0.7
In[A] = 10 I[mA] = 6.5
750-406 ( 2 DI 120V AC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VAC] = 120 U[VAC] = 79 - 132 In[mA] = 2 0.7
In[A] = 10 I[mA] = 4.5
750-408 ( 4 DI 24V DC, low-side switching, 3.0 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 19 - 24 In[mA] = 5 0.9
In[A] = 10 I[mA] = 7
750-409 ( 4 DI 24V DC, low-side switching, 0.2 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 19 - 24 In[mA] = 5 0.9
In[A] = 10 I[mA] = 7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-410 ( 2 DI 24V DC, high-side switching, 3.0 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 30 In[mA] = 2.5 0.7
In[A] = 10 I[mA] = 8
750-411 ( 2 DI 24V DC, high-side switching, 0.2 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 30 In[mA] = 2.5 0.7
In[A] = 10 I[mA] = 8
750-412 ( 2 DI 48V DC, high-side switching)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 48 U[VDC] = 34 - 60 In[mA] = 2.5 0.6
In[A] = 10 I[mA] = 3.8
750-415 ( 4 DI 24V AC / DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VDC] = 11 - 30 In[mA] = 10
IDC[mA] = 7.5 1.4
U[VAC] = 11 - 27
IAC[mA] = 9.5
750-418 ( 2 DI 24V DC, high-side switching, diagnostic, acknowledgement)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 DI Terminals : 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 12
In[A] = 10 I[mA] = 3.7 0.8
DO Terminals : 4, 8
I[A] = 0.5
750-419 ( 2 DI 24V DC, high-side switching, diagnostic)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 DI Terminals : 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 12
In[A] = 10 I[mA] = 3.7 0.8
DO Terminals : 4, 8
I[A] = 0.5
750-421 ( 2 DI 24V DC, high-side switching, diagnostic)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 DI Terminals : 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 12
In[A] = 10 I[mA] = 3.7 0.8
DO Terminals : 4, 8
I[A] = 0.5
750-422 ( 4 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 9 0.7
In[A] = 10 I[mA] = 4
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-423 ( 4 DI 24V AC / DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VAC] = 24 U[VDC] = 11 - 30 In[mA] = 2
In[A] = 10 IDC[mA] = 7.5 1.4
U[VAC] = 11 - 27
IAC[mA] = 9.5
750-424 ( 2 DI Intruder Detection )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 24 In[mA] = 6 0.9
In[A] = 10 I[mA] = 16
750-425 ( 2 DI NAMUR )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 8.2 In[mA] = 5 0.6
In[A] = 10 I[mA] = 0 - 8.2
750-427 ( 2 DI 110V DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 110 U[VDC] = 70 - 137 In[mA] = 6 0.9
In[A] = 10 I[mA] = 2.5
750-428 ( 4 DI 42V AC / DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VDC] = 30 - 53 In[mA] = 5
IDC[mA] = 3.6 1.0
U[VAC] = 30 - 53
IAC[mA] = 6
750-429 ( 2 DI 60V DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 60 U[VDC] = 60 (-20% In[mA] = 2.5
0.6
...+25%)
In[A] = 10 I[mA] = 2.9
750-430 ( 8 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 17 1.0
In[A] = 10 I[mA] = 2.8
750-431 ( 8 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 17 1.0
In[A] = 10 I[mA] = 2.8
750-432 ( 4 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 5.5 0.8
In[A] = 10 I[mA] = 4.5
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-433 ( 4 DI 24V DC, 0,2ms / 2wire)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 5.5 0.8
In[A] = 10 I[mA] = 4.5
753-434 ( 8 DI 5-14V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VDC] = 5 - 14 U[VDC] = 7 – 15.4 In[mA] = 4 0.9
In[A] = 10 I[mA] = 0.06
750-436 ( 8 DI 24V DC, low-side switching, 3.0 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 13 0.9
In[A] = 10 I[mA] = 2.8
750-437 ( 8 DI 24V DC, low-side switching, 0.2 ms )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 13 0.9
In[A] = 10 I[mA] = 2.8
753-440 ( 4 DI 120 V AC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VAC] = 120V U[VAC] = 67 - 132 In[mA] = 15 1.1
In[A] = 10 I[mA] = 4.7
750-450 (4AI RTD, configurable )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 – 16 Un[VDC]= 5
Un[VDC] = 24 For the connection to the In[A] = 0.085
0.4
In[A] = 10 Pt-, Ni- or resistance
sensors
750-451 (8AI RTD, configurable )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC]= 5
Un[VDC] = 24 For the connection to the In[A] = 0.110
0.6
In[A] = 10 Pt-, Ni- or resistance
sensors
750-452 ( 2 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
I[mA] = 0 - 20 In[mA] = 70 0.6
Rinput[]= 220
750-453 ( 4 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 65 0.5
In[A] = 10 Rinput[]= 100
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-454 ( 2 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
I[mA] = 0 - 20 In[mA] = 70 0.6
Rinput[]= 220
750-455 ( 4 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 65 0.5
In[A] = 10 Rinput[]= 100
750-455/020-000 ( 4 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 4, 6, 8 Terminals: 1, 3, 5, 7 Un[VDC] = 5
Un[VDC] = 24 In[mA] = 0 - 20 In[mA] = 65 0.5
In[A] = 10 Rinput[Ω]= 100
750-456 ( 2 AI ± 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[V] = -10 - +10 In[mA] = 80 0.5
Rinput[k]= 570
750-457 ( 4 AI ± 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[V] = -10 - +10 In[mA] = 65 0.4
In[A] = 10 Rinput[k]= 100
750-458 (8AI TC/ Diagn./ adj)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC]= 5
Un[VDC] = 24 For the connection to the In[A] = 0.100 0.5
In[A] = 10 Thermocouple
750-459 ( 4 AI 0 - 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[V] = 0 - +10 In[mA] = 65 0.4
In[A] = 10 Rinput[k]= 100
750-461 ( 2 AI RTD, 750-461/020-000(2 AI NTC)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 3, 5, 6, 7 Un[VDC] = 5
Un[VDC] = 24 For the connection to a In[mA] = 80 0.5
In[A] = 10 PT100 thermocouple
750-463 ( 4- AI RTD for building automation )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 For the connection to a In[mA] = 50 0.3
In[A] = 10 PT100 thermocouple
750-464 ( 2-/ 4- AI RTD ), 750-464/020-000(4-AI NTC)
II 3 G Ex ec IIC T4 Gc
Terminals: Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 For the connection to a In[mA] = 50 0.3
In[A] = 10 PT100 thermocouple
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-465 ( 2 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 75 0.6
In[A] = 10 Rinput[]= 220
750-466 ( 2 AI 4-20mA S.E.)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 4 - 20 In[mA] = 75 0.6
In[A] = 10 Rinput[]= 220
750-467 ( 2 AI 0 - 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[V] = 0 - 10 In[mA] = 60 0.4
Rinput[k]= 130
750-468 ( 4 AI 0 - 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[V] = 0 - 10 In[mA] = 60 0.4
Rinput[k]= 133
750-469 ( 2 AI for Thermocouples )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Thermocouples In[mA] = 65 0.4
Rinput[M]= 1
750-470 ( 2 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 100 0.7
In[A] = 10 Rinput[]= 160
750-471 (4AI U/I Diff, PotFree)
II 3 G Ex ec IIC T4 Gc
Terminals: Terminals: 1 - 8 Un[VDC]= 5
Un[VDC] = 24 In[mA] = 0 - 20 In[mA] = 100 0.7
In[A] = 10 Rinput[Ω]= 130
750-472 ( 2 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals:1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 75 0.6
In[A] = 10 Rinput[]= 220
750-473 ( 2 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 100 0.7
In[A] = 10 Rinput[]= 160
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-474 ( 2 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 0 - 20 In[mA] = 75 0.6
In[A] = 10 Rinput[]= 220
750-475 ( 2 AI 0 - 1A AC/DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 I[A] = 0 - 1 In[mA] = 80 0.5
In[A] = 10 Rinput[m]= 22
750-475/020-000 ( 2 AI 0 - 5A AC/DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 I[A] = 0 - +5 In[mA] = 80 0.5
In[A] = 10 Rinput[m]= 2
750-476 ( 2 AI ± 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[V] = -10 - +10 In[mA] = 75 0.4
In[A] = 10 Rinput[k]= 130
750-477 ( 2 AI 0 - 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 U[V] = 0 - +10 In[mA] = 80 0.5
In[A] = 10 Rinput[k]= 120
750-478 ( 2 AI 0 - 10V AC/DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[V] = 0 - +10 In[mA] = 75 0.4
In[A] = 10 Rinput[k]= 130
750-479 ( 2 AI ± 10V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[V] = -10 - +10 In[mA] = 100 0.6
Rinput[M]= 1
750-480 ( 2 AI 0-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
I[mA] = 0 - 20 In[mA] = 80 0.7
Rinput[]= 270
750-482 ( 2- AI 4-20mA HART)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 5, 6 Un[VDC] = 5
Un[VDC] = 24 For the connection to In[mA] = 75
0.4
In[A] = 10 sensors with HART
Protocol
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-482/000-001 (2AI 4-20mA HART NE43)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5, 3, 7 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = 0 - 21 In[mA] = 25 1.6
In[mA] = 26+Load In[A] = 10
750-483 ( 2 AI 0 - 30V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[V] = 0 - 30 In[mA] = 80 0.5
Rinput[M]= 1
750-492 ( 2 AI 4-20mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 I[mA] = 4 - 20 In[mA] = 80 0.7
In[A] = 10 Rinput[]= 270
750-493 ( 3-Phasen-Power Measurement 1A )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VAC] = 99 - 302 In[mA] = 115 1.0
I[A] = 1
750-493/000-001 ( 3-Phasen-Power Measurement 5A )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VAC] = 99 - 302 In[mA] = 115 1.3
I[A] = 5
750-494 ( 3-Phasen-Power Measurement 1A )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VAC] = 99 - 302 In[mA] = 115 1.0
I[A] = 1
750-494/000-001 ( 3-Phasen-Power Measurement 5A )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
U[VAC] = 99 - 302 In[mA] = 115 1.3
I[A] = 5
750-494/000-005 (3-Phase Power Measurement Shunt)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[Vac] = 277 In[A] = 0.1 1
External Shunt
750-496 8AI 0/4-20mA
II 3 G Ex ec IIC T4 Gc
Terminals: 1 – 16 Un[VDC]= 5
Un[VDC] = 24 8Channel In[A] = 0.069
1.5
In[A] = 10 0/4 - 20mA
Rinput[Ω]= 220
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-497 (8AI 0-10V/ ±10V S.E.)
II 3 G Ex ec IIC T4 Gc
Terminals: Terminals: 1 - 8 Un[VDC]= 5
Un[VDC] = 24 Un[V] = ±10 In[mA] = 105 0.6
In[A] = 10 Rinput[kΩ]= >100
750-1400 ( 16 DI 24V DC Ribbon cable, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminal: 21, 22 Terminals: Connector Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 25 1.5
In[mA] = 50 I[mA] = 2.2 - 2.5
750-1402 ( 16 DI 24V DC Ribbon cable, low-side switching )
II 3 G Ex ec IIC T4 Gc
Terminal: 21, 22 Terminals: Connector Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 25 1.5
In[mA] = 50 I[mA] = 2.2 - 2.5
750-1405 ( 16 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 25 1.4
In[A] = 10 I[mA] = 2.1 - 2.4
750-1406 ( 16 DI 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 25 1.4
In[A] = 10 I[mA] = 2.1 - 2.4
750-1407 ( 16 DI 24V DC, low-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 25 1.4
In[A] = 10 I[mA] = 2.1 - 2.4
750-1415 ( 8 DI 24V DC, high-side switching, 2-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 32 In[mA] = 6 1.3
In[A] = 10 I[mA] = 4.3 - 4.6
750-1416 ( 8 DI 24V DC, high-side switching, 2-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 32 In[mA] = 6 1.3
In[A] = 10 I[mA] = 4.3 - 4.6
750-1417 ( 8 DI 24V DC, low-side switching, 2-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 12 0.8
In[A] = 10 I[mA] = 2.3 - 2.7
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-1418 ( 8 DI 24V DC, low-side switching, 2-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 12 0.8
In[A] = 10 I[mA] = 2.3 - 2.7
750-1420 ( 4 DI 24V DC, high-side switching, 3-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 32 In[mA] = 4 0.7
In[A] = 10 I[mA] = 4.3 - 4.6
750-1421 ( 4 DI 24V DC, high-side switching, 3-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 11 - 32 In[mA] = 4 0.7
In[A] = 10 I[mA] = 4.3 - 4.6
750-1422 ( 4 DI 24V DC, low-side switching, 3-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 7 0.4
In[A] = 10 I[mA] = 2.3 - 2.7
750-1423 ( 4 DI 24V DC, low-side switching, 3-conductor connection )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 32 In[mA] = 7 0.4
In[A] = 10 I[mA] = 2.3 - 2.7
750-1425 ( 8DI PTC )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC]= 5
Un[VDC] = 24 For the connection to a In[A] = 0.52 0.3
In[A] = 10 Pt-sensors
750-501 ( 2 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 3.5 0.6
In[mA] = 15 + Load In[A] = 10
750-502 ( 2 DO 24V DC, 2,0A )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 2 In[mA] = 3.5 1
In[mA] = 15 + Load In[A] = 10
750-504 ( 4 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 7 0.7
In[mA] = 15 + Load In[A] = 10
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-506 ( 2 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 7 1
In[mA] = 15 + Load In[A] = 10
750-507 ( 2 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 2 In[mA] = 15 1
In[mA] = 15 + Load In[A] = 10
750-508 ( 2 DO 24V DC 2,0A Diagnosis )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 2 In[mA] = 14 0.9
In[mA] = 7 + Load In[A] = 10
750-508/020-001 (2DO 24V DC 2.0A,30K WB)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 In[A] = 2 In[mA] = 14 0.9
In[mA] = 7+Load In[A] = 10
750-509 ( 2 DO 230V AC/DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 230 Max I[A] per Ch. = 0.3 In[mA] = 10 0.7
In[A] = 10
750-511 ( 2 DO Pulse Width Output Module 24V DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.1 In[mA] = 70 1
In[mA] = 15 + Load In[A] = 10
750-512 ( 2 DO 230V AC 2,0A/ Relay 2NO )
II 3 G Ex ec nC IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 230 Un[VDC] = 230 In[mA] = 100 1,3
In[A] = 10 Max I[A] per Ch. = 2
750-513 ( 2 DO Relay Output Module 230 V AC , 30 V DC )
II 3 G Ex ec nC IIC T4 Gc
Terminals: 1, 2, 5, 6 Un[VDC] = 5
Un[VDC] = 230 In[mA] = 70 1
Max I[A] per Ch. = 2
750-515 ( 4RO 250VAC 2A Pot-free Relay4NO )
II 3 G Ex ec nC IIC T4 Gc
Terminals: 1 – 8 Un[VDC]= 5
4Channel Relay In[A] = 0.095 1.1
250VAC/30VDC 2A
750-516 ( 4 DO 24V DC, low-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 7 1.4
In[mA] = 30 + Load In[A] = 10
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-517 ( 2 DO Relay Output Module 230V AC, 300V DC )
II 3 G Ex ec nC IIC T4 Gc
Terminals: 1 - 3, 5 - 7 Un[VDC] = 5
250V AC, 1A In[mA] = 90
0.7
300V DC, 0.15A
40V DC, 1A
750-522 ( 2 DO Solid state 230V AC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 230 Max I[A] per Ch. = 0.5 In[mA] = 40 1.5
In[A] = 10
750-530 ( 8 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0,5 In[mA] = 25 1.1
In[mA] = 15 + Load In[A] = 10
750-531 ( 4 DO 24V DC, 0,5A/ 2-Wire )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 11 1
In[mA] = 30 + Load In[A] = 10
750-532 ( 4 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 10 0.7
In[mA] = 13 + Load In[A] = 10
750-534 ( 8 DO 5 - 14V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 14 Un[VDC] = 5 - 14 Max I[A] per Ch. = 1 In[mA] = 20 0.8
In[mA] = 25 + Load In[A] = 10
750-536 (8 DO 24V DC, low-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 25 0.7
In[mA] = 12 + Load In[A] = 10
750-537 ( 8 DO 24V DC, high-side switching )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 50 1
In[mA] = 16 + Load In[A] = 10
753-540 (4 DO Solid state 230V AC)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 230 Max I[A] per Ch. = 0.25 In[mA] = 18 1.3
In[A] = 10
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-550 (2 AO 0-10V)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Un[VDC] = 5
Max UOutput [V]= 10 In[mA] = 65 0.4
Load impedance[k]= 5
750-552 (2 AO 0-20mA)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5, 4, 8 Un[VDC] = 5
Un[VDC] = 24 Max IOutput [mA]= 20 In[mA] = 70 1
In[A] = 10 Load impedance[]= 600
750-553 (4 AO 0-20mA)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5, 4, 8 Un[VDC] = 5
Un[VDC] = 24 Max IOutput [mA]= 20 In[mA] = 60
1.8
In[A] = 10 Load impedance[]= 600
750-554 (2 AO 4-20mA)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5, 4, 8 Un[VDC] = 5
Un[VDC] = 24 Max IOutput [mA]= 20 In[mA] = 70 1
In[A] = 10 Load impedance[]= 600
750-555 (4 AO 4-20mA)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5, 4, 8 Un[VDC] = 5
Un[VDC] = 24 Max IOutput [mA]= 20 In[mA] = 60 1.8
In[A] = 10 Load impedance[]= 600
750-556 (2 AO ±10V)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Max UOutput [V]= 10 In[mA] = 65 0.4
Load impedance[k]= 5
750-557 (4 AO ±10V)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
0.7
Un[VDC] = 24 Max UOutput [V]= 10 In[mA] = 125
In[A] = 10 Load impedance[k]= 5
750-559 (4 AO 0 - 10V)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Max UOutput [V]= 10 In[mA] = 125 0.7
In[A] = 10 Load impedance[k]= 5
750-560 (2 AO 0 - 10V)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Max UOutput [V]= 10 In[mA] = 16 1
In[A] = 10 Load impedance[k]= 1
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-562 (2 AO 0 - 10V / -10...+10V DC)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 U[V] = 0 - 10 In[mA] = 170
1
In[A] = 10 or U[V] = -10 - +10
Load impedance[k]= 5
750-563 (2 AO 0/4 - 20mA 6 - 18V )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5
Voltage op.mode Un[VDC] = 5
Un[VDC] = 24 U[V] = 6 - 18
In[A] = 10 Load impedance[k]= 1.8 In[mA] = 110 1.5
Current op. mode
I[mA]= 0 - 20
Load impedance[]= 500
750-564 (2DO 24V DC 2.0A, 30K WB)
II 3 G Ex ec IIC T4 Gc
Terminals: Terminals: 1, 5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = ±22 In[mA] = 55 1.4
In[mA] = 80+Load In[A] = 10 Un[V] = ±10
750-597 (8AO 0-10V/ ±10V S.E.)
II 3 G Ex ec IIC T4 Gc
Terminals: Terminals: 1, 5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 Un[V] = ±11 In[mA] = 61 1.6
In[mA] = 72 In[A] = 10 Rinput[kΩ]= >2
750-1500 (16 DO 24V DC Ribbon cable, high-side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Terminals: 21, 22 Terminals: Connector Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 40 2
In[mA] = 29 + Load In[A] = 8.1
750-1501 (16 DO 24V DC Ribbon cable, low-side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Terminals: 21, 22 Terminals: Connector Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 40 1.3
In[mA] = 11 + Load In[A] = 8.1
750-1502 (8 DI/DO 24V DC Ribbon cable, high side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Terminals: 21, 22 Terminals: Connector Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Digital Output In[mA] = 30
In[mA] = 16 + Load In[A] = 4.1 Max I[A] per Ch. = 0.5
1.8
Digital Input
U[VDC] = 11 - 32
I[mA] = 2.2 - 2.5
750-1504 (16 DO 24V DC, high-side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 24 Un[VDC] = 24 Terminals: 1 - 16 Un[VDC] = 5
2
In[mA] = 29 + Load In[A] = 10 Max I[A] per Ch. = 0.5 In[mA] = 40
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-1505 (16 DO 24V DC, low-side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 24 24 Terminals: 1 - 16 Un[VDC] = 5
1.3
In[mA] = 11 + Load In[A] = 10 Max I[A] per Ch. = 0,5 In[mA] = 40
750-1506 (8 DI/DO 24V DC, high side switching 0,5A)
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 24 Un[VDC] = 24 Terminals: 1 - 16 Un[VDC] = 5
In[mA] = 16 + Load In[A] = 4.1 Digital Output In[mA] = 30
Max I[A] per Ch. = 0.5
1.8
Digital Input
U[VDC] = 11 - 32
I[mA] = 2.2 - 2.5
750-1515 (8 DO 24V DC, high-side switching, 2-conductor connection 0,5A)
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 24 Un[VDC] = 24 Terminals: 1 - 16 Un[VDC] = 5
1
In[mA] = 15 + Load In[A] = 10 Max I[A] per Ch. = 0.5 In[mA] = 20
750-1516 (8 DO 24V DC, low-side switching, 2-conductor connection 0,5A)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max I[A] per Ch. = 0.5 In[mA] = 20 0.8
In[mA] = 8 + Load In[A] = 10
750-600 (End Module)
II 3 G Ex ec IIC T4 Gc
750-601 (24V DC Power Supply / Fuse)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 4, 5
Un[VDC] = 24 Supply with 24V DC 1.9
In[A] = 6.3 (@ 6.3A)
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-610 (Supply Module 24V DC)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 4, 5
1.9
Un[VDC] = 24 Supply with 24 VDC
(@ 6.3A)
In[A] = 6.3
750-611 (Supply Module 230V AC)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 4, 5
2.3
Un[VDC] = 230 Supply with 230 VAC
(@ 6.3A)
In[A] = 6.3
750-612 (Supply Module 230V AC/DC)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7
0.3
Un[VDC] = 230 Supply with 230 VAC
(@10A)
In[A] = 10
750-613 (Internal System Supply Module 24V DC)
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, Terminals: 1, 5 Un[VDC] = 5
7
1.2
Un[VDC] = 24 Un[VDC] = 24 In[A] = 0.2
In[A] = 10 In[A] = 0.5 ∑ In[A] = 2
750-614 (Field Side Connection Module)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8
0.3
Un[VDC/AC]= 230 Un[VDC/AC]= 230
(@ 10A)
In[A] = 10
750-615 (Supply Module 120V AC )
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 120 Terminals: 1, 2, 4, 5 2.3
In[A] = 6.3 Supply with 120VAC (@ 6.3A)
750-616 (Distance Module )
II 3 G Ex ec IIC T4 Gc
750-621 ( Distance Module (Power Cont.) )
II 3 G Ex ec IIC T4 Gc
750-622 ( Binary Spacer Module )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Un[VDC] = 5
Un[VDC] = 24 In[mA] = 10 0.1
In[A] = 10
750-623 ( 24V DC Power Supply 5-15V DC )
II 3 G Ex ec IIC T4 Gc
Terminals 1, 5 Terminals: 2, 6, 3, 7
Un[VDC] = 24 Un[VDC] = 5, 8, 10, 12,
1.7
15
In[mA] = 20 + Load Max I[A] = 0.5
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-624, 750-624/020-000 ( 24V DC Field Side Power Supply Filter (Surge) )
750-624/000-001, 750-624/020-001 (without powe jumper contacts )
II 3 G Ex ec IIC T4 Gc
Terminals: 2- 4, 6-8
0.4
Un[VDC] = 24
(@ 10A)
In[A] = 10
750-626, 750-626/020-000 ( 24V DC Power Supply Filter (Surge) )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 5
0.7
Un[VDC] = 24 Un[VDC] = 24
(@ 10A)
In[A] = 10 Max I[A] = 1.5
750-630 ( SSI Transmitter-Interface )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = 85 0.5
In[mA] = 3 In[A] = 10
750-635 ( Digital Impulse Interface )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 RS422 In[mA] = 45 0.3
In[A] = 10 Un[VDC] = 5
750-632, 750-632/000-001 (Proportional Valve Module)
II 3 G Ex ec IIC T4 Gc
DI Terminals: 1, 9
Terminals: 2,4,8,10,12, Un[VDC] = 24 Un[VDC]= 5
3,5,11,13,16 In[mA]=2.7
Un[VDC] =24 DO Terminals: 6, 7, 14, 2.2
15
In[mA] = 125
1.ch.op. In[A] = 1.4
2.ch.op. In[A] = 0.8
750-637 ( Incremental Encoder Interface )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 (Supply) Terminals: L, G, R Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 30 In[mA] = 110
In[mA] = 12 I[mA] = 7 Terminals: Ue,
Uo 2.5
Terminals: N1, N2 Terminals: A, A', B, B', Un[VDC] = 5
C, C'
Max I[A] = 0.5 Un[VDC] = 5 Max I[mA] = 300
750-637/000-001 ( Incremental Encoder Interface )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 (Supply) Terminals: L, G, R Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 30 In[mA] = 110
In[mA] = 12 I[mA] = 7
1,8
Terminals: N1, N2 Terminals: A, A', B, B',
C, C'
Max I[A] = 0.5 Un[VDC] = 30
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-638 ( 2-Channel Up/Down Counter 24V DC )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 30 In[mA] = 10 0.4
In[A] = 10 Rinput[k]= 5,4
750-640 ( RTC Module )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 U[VDC] = 24 In[mA] = 20 0.5
In[mA] = 11 In[A] = 10 I[mA] = 5
750-641 ( DALI/DSI Master Module)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 4, 5, 8 Un[VDC] = 5
0.5
Un[VDC] = 18 Max I[mA] = 200 In[mA] = 30
750-642 ( Radio Receiver Module )
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 5
0.5
In[mA] = 80
750-643 ( MP-Bus Master Module )
II 3 G Ex ec IIC T4 Gc
Terminals: 2, 3, 6, 7 Terminals: 1, 4, 5, 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = 15 0.7
In[A] = 10 In[mA] = 25
750-644 ( Bluetooth / RF Transceiver )
II 3 G Ex ec IIC T4 Gc
Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = 20 1
In[mA] = 35 In[A] = 10
750-645 ( 2-Channel Vibration Velocity/ Bearing Condition Monitoring VIB I/O)
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 5 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Un[VDC] = 24 In[mA] = 30 1.3
In[mA] = 40 + Load In[A] = 10 MaxI[A]= 0.5
750-650 ( Serial Interface RS-232 C )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
RS232 In[mA] = 55 0.4
Un[VDC] = 5
750-652 ( Serial Interface RS-232 / RS-485 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
RS232 In[mA] = 85 0.5
Un[VDC] = ±15
750-653 ( Serial Interface RS-485 )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
RS485 In[mA] = 65 0.4
Un[VDC] = 5
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-655 ( AS-Interface Master )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 U[VDC] = 26.5 - 31.6 In[mA] = 55 1.7
In[mA] = 3 In[A] = 10 I[mA] = 40
750-657 (4-Channel IO-Link Master)
II 3 G Ex ec IIC T4 Gc
Terminals: 2 - 5, 7, 8, Terminals: 1, 6, 9, 14 Un[VDC]= 5
10 - 13, 15, 16
1.2
Un[VDC] = 24 IO-Link Devices In[A] = 0.40
In[A] = 10
750-658 (CAN Gateway)
II 3 G Ex ec IIC T4 Gc
Terminals: 3, 6 Terminals: 1, 2, 5 Un[VDC]= 5
Un[VDC] = 24 CAM-Devices In[A] = 0.50 0.6
In[A] = 10
750-660/000-001 (8DI PROFIsafe V1.3 Module)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] =30 In[mA] = 40 1.4
In[mA] = 20 In[A] = 10 I[mA] = 2.2
750-661/000-003 (4FDI PROFIsafe V2 iPar)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] =30 In[mA] = 145 1.6
In[mA] = 20 In[A] = 10 I[mA] = 2.2
750-662/000-003 (8FDI PROFIsafe V2 iPar)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] =30 In[mA] = 148 1.9
In[mA] = 20 In[A] = 10 I[mA] = 2.2
750-665/000-001 ( 4DI and 4DO PROFIsafe V1.3 Module)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 -8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] = 30 In[mA] = 55
In[mA] = 38 In[A] = 10 I[mA] = 2.2
2.1
Terminals: 9 - 16
Max I[A] per Ch. = 0.5
Total out. current max. 2A
750-666/000-003 ( 4DI and 2DO PROFIsafe V2 Module )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 -8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] =30 In[mA] = 190
3
In[mA] = 30 In[A] = 10 I[mA] = 2.2
(@ 10A)
Terminals: 9 - 16
Max I[A] per Ch. =10
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-667/000-003 (4FDI and 4FDO PROFIsafe V2 iPar )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 -8 Un[VDC] = 5
Un[VDC] = 24 Un[VDC] = 24 Max UIN[VDC] =30 In[mA] = 180
In[mA] = 20 In[A] = 10 I[mA] = 2.2 2.7
Terminals: 9 - 16
Max I[A] per Ch. = 2
750-668/000-004 (4FAI 0/4-20mA Diff PROFIsafe)
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 8 Terminals: 1, 5 Un[VDC]= 5
Un[VDC] = 24 Un[VDC] = 24 In[mA] = 0 - 20 In[mA] = 120 2.2
In[mA] = 40+Load In[A] = 10 Rinput[Ω]= <300
750-669/000-003 (4FAI 0/4-20mA Diff PROFIsafe)
II 3 G Ex ec nC IIC T4 Gc
Terminals 17, 18 Terminals: 1 - 8 Input Un[VDC]= 5
Un[VDC] = 24 In[mA] = 2.2 In[mA] = 145
In[mA] = 50+Load Terminals: 9 - 16 Output 4.5
Un[V] = AC30, DC60
In[A] = 6
750-670 (Stepper Controller RS-422 / 24 V / 20 mA )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 98
In[A] = 10 I[mA] = 2.8
0.8
Terminals: 3, 4, 7, 8
Max I[mA] per Ch. = 30
Uout[V]= 5
750-671 (Stepper Controller 24 V / 1.5 A )
II 3 G Ex ec IIC T4 Gc
Terminals: 1, 2, 5 Un[VDC] = 5
Un[VDC] = 24 U[VDC] = 15 - 30 In[mA] = 85
In[A] = 10 I[mA] = 2.8 1.3
Terminals: 3, 4, 7, 8
Max I[A] per Ch. =1.5
750-960 ( Profibus Fieldbus Connector )
II 3 G Ex ec IIC T4 Gc
Terminals: 0.05
Un[VDC] = 5
In[mA] = 5
750-961 ( Fieldbus Connector Interbus IN )
II 3 G Ex ec IIC T4 Gc
750-962 ( Fieldbus Connector Interbus OUT )
II 3 G Ex ec IIC T4 Gc
750-963 ( CanOpen Fieldbus Connector )
II 3 G Ex ec IIC T4 Gc
Terminals:
Un[VDC] = 5 0.05
In[mA] = 5
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Power jumper
Input Interface Internal K-Bus ∑ Pv [W]
contacts
750-1605 ( 24V DC Field side connection Module 16+ )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16
0.3
Un[VDC] = 2
(@ 10A)
In[A] = 10
750-1606 ( 0V DC Field side connection Module 16- )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16
0.3
Un[VDC] = 24
(@ 10A)
In[A] = 10
750-1607 ( 24V / 0V DC Field side connection Module 8+ / 8- )
II 3 G Ex ec IIC T4 Gc
Terminals: 1 - 16
0,3
Un[VDC] = 24
(@ 10A)
In[A] = 10
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH
Thermal data:
The maximum permissible ambient temperature range is 0°C ≤ Ta ≤ +60°C
The maximum permissible ambient temperature range for modules with suffix extension /z*25-**** is
-20°C ≤ Ta ≤ +60°C
Note that the service temperature has to not exceed the defined ambient temperature and as stated in Specific Conditions
for Use the installation into the housing shall be carried out in such a way that the ambient temperature during the use is not
exceeded.
(16) Drawings and documents are listed in the Assessment Report No. 22 214 317045.
This certificate may only be reproduced without any change, schedule included.
Excerpts or changes shall be allowed by the TÜV NORD CERT GmbH