PRESENTATION:

A dose of LOWPAT- LIQUID is presented in a container of 25 kg of liquid, necessary for the treatment of one electrode.

A) APPLICATION IN INSTALLATION WITH A SINGLE ELECTRODE

The procedure is extremely simple, since LOWPAT-LIQUID comes ready to be shaken in its own covered container and
added to the electrode installed in the ground without any additional manipulation.

INSTRUCTIONS FOR USE ACCORDING TO THE TYPE OF ELECTRODE

We recommend in all cases to measure the resistance before carrying out the treatment, and once it has been carried
out, which allows us to verify the effectiveness of the treatment in our case.

1) IN SOLID PICA

Around the head of the electrode to be treated, make a hole (with a capacity of about 10 litres) or a chest for the
liquid to penetrate into the ground. Shake LOWPAT-LIQUID and add as it filters into the soil, until completing the
COMPLETE treatment (25 Kg.)

2) IN CONDUCTORS BURIED HORIZONTALLY

Once the conductive electrode is installed in the trench, cover it with earth or other filling (without stones) about 10 cm.
shake and apply LOWPAT -LIQUID by addition along the buried electrode The
length to be treated with a dose of LOWPAT-LIQUID will be between 3 and 4 meters
Machine Translated by Google

3) IN VERTICALLY BURIED PLATES

-
After installing the plate and cover it with earth or other filling up to 1-2 cm. of its top edge, add LOWPAT
LIQUID, along its edge, so that it is well distributed throughout the electrode environment.

When you have strained all the liquid, finish covering, compacting and measuring

4) IN DEEP ELECTRODE (DRILLING-WELLS)

In this case we will proceed alternating the 25 Kg. of LOWPAT - LIQUID every 50 Kg. of solid fill material or in mush, (eg
bentonite, powdered coal, graphite, arable land or the land itself extracted from the drilling without stones)

Thus, once the drilling is complete, we will add 25 kg of LOWPAT-LIQUID, then 50 kg of fill, then 25 kg of LOWPAT-LIQUID and
so on until the well is filled. In the most superficial area, always add (touch it or not) 25 kg of LOWPAT-LIQUID. Fill and compact
carefully without leaving holes in the perforation

When installing LOWPAT-LIQUIDO in drilling there are 3 special situations that must be controlled

1) Presence of caves and/or large cavities


2) Presence of water currents
3) Presence of totally compact rock

In any of these cases, contact the Cirprotec Technical Department Tel. (+34) 93 733 16 84 - Fax (+34) 93 733 27 64

25Kg LOWPAT -LIQUIDO

50 Kg. Papilla or filling

25Kg LOWPAT-LIQUIDO

50 Kg. Papilla or filling

25Kg LOWPAT -LIQUIDO

B) APPLICATION OF LOWPAT-LIQUID IN AN INSTALLATION WITH MORE THAN ONE ELECTRODE

If it is necessary to treat more than one electrode, once the first one has been treated, as seen in A). Proceed to treat the second
electrode, taking into account that this must be at a distance of about 7 to 9 meters, since at this distance, the effective
performance of the treatments is maximized. At shorter distances, the treatments themselves would be equally effective. , but
when joining them to the circuit, lower than expected decreases would be seen

NOTE: For greater durability of the treatments, add 2 containers of LOWPAT-LIQUID to each electrode (instead of the usual
one).