Professional Documents
Culture Documents
2 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Disclaimer of warranties and limitation of liability
This instruction booklet is published solely for information purposes In no event will Eaton be responsible to the purchaser or user in
and should not be considered all-inclusive. If further information is contract, in tort (including negligence), strict liability or otherwise
required, you should consult an authorized Eaton sales representative. for any special, indirect,incidental or consequential damage or loss
The sale of the product shown in this literature is subject to the whatsoever, including but not limited to damage or loss of use of
terms and conditions outlined in appropriate Eaton selling policies equipment, plant or power system, cost of capital, loss of power,
or other contractual agreement between the parties. This literature additional expenses in the use of existing power facilities, or claims
is not intended to and does not enlarge or add to any such contract. against the purchaser or user by its customers resulting from the
The sole source governing the rights and remedies of any purchaser use of the information, recommendations and description contained
of this equipment is the contract between the purchaser and Eaton. herein.
EATON www.eaton.com 3
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Contents
Description Page
Section 1: Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1 Preliminary comments and safety precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.1 Safety precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.2 Switchgear identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 General information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Power Xpert XGIS elements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.3.1 Standard features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
1.3.2 Ground bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1.3.3 Bracing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.4 Arc resistant features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.5 Optional features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
1.3.6 XGIS vertical section configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
1.4 Type XGIS gas insulated switchgear ratings (tables 2, and 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1.5 XGIS vertical section outlines and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.5.1 1250 ampere vertical section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1.5.2 2000 ampere vertical section. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
1.6 typical DC control schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1.7 SSIS conductor system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.7.1 SSIS bus in XGIS gas insulated switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1.7.2 Power cable conductors in XGIS switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Section 2: Safe practices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.1 Recommendations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
2.2 SF6 Gas handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Section 3: Receiving, handling and storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Section 4: Description and operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1 introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1.1 Three-position disconnect switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.1.2 Circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.2 Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.2.1 Three-position disconnect switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
4.2.2 Circuit breaker. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.2.3 Interface interlocks / interlocking check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.3 typical feeder circuit operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3.1 Sequence of operation for isolation of a feeder:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3.2 Sequence of operation for feeder grounding:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
4.3.3 Sequence of operation for main bus grounding on sectionalized bus arrangements. . . . . . . . . 38
4.3.4 Circuit breaker trip free operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Section 5: Inspection, maintenance, and testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.1 Logbook. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.2 Inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
5.3 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.3.1 SF6 Gas handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4 Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
5.4.1 Voltage test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
5.4.2 Current test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Setion 6: Renewal parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.1 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
6.2 Ordering instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
List of tables
4 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Description Page
Table 1. Three-position disconnect switch status display table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 2. Vertical section dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 3. Electrical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Table 4. Relevant standards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 5. Operating conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Table 6. Three-position disconnect switch/circuit breaker interlocking truth table. . . . . . . . . . . . . . . . . . . 38
Table 7. Recommended inspections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Table 8. Recommended renewal parts list. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
EATON www.eaton.com 5
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Read and understand these instructions before attempting Section 1: Introduction
installation, operation, or maintenance of this equipment. This
equipment must be installed and serviced only by qualified electrical 1.1 Preliminary comments and safety precautions
personnel. Retain this document for future use. This technical document is intended to cover most aspects associ-
ated with the installation and commissioning of Power XpertTM XGIS
gas insulated switchgear. It is provided as a guide for authorized
and qualified personnel only. Please refer to the specific WARNING
messages in paragraph 1.1.2 before proceeding past Section 1. If
further information is required regarding a particular installation,
IMPROPERLY INSTALLING OR MAINTAINING THESE PRODUCTS CAN application or maintenance activity, an Eaton representative should
RESULT IN DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE. be contacted.
READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE ATTEMPTING 1.1.1 Safety precautions
ANY UNPACKING, ASSEMBLY, OPERATION OR MAINTENANCE OF THE
CIRCUIT BREAKERS. All safety codes, safety standards and/or regulations must be strictly
observed in the installation, operation and maintenance of this
INSTALLATION OR MAINTENANCE SHOULD BE ATTEMPTED ONLY device.
BY QUALIFIED PERSONNEL. THIS INSTRUCTION BOOK SHOULD NOT
BE CONSIDERED ALL INCLUSIVE REGARDING INSTALLATION OR
MAINTENANCE PROCEDURES. IF FURTHER INFORMATION IS REQUIRED,
YOU SHOULD CONTACT EATON.
6 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.2 General information An option of the XGIS design is available that is certified to IP4X
requirements.
The purpose for this document is to provide instructions for opera-
tion and maintenance of Power Xpert XGIS gas insulated switchgear The XGIS design is not rated for outdoor service.
(referred to as Type XGIS gas insulated switchgear from this point
forward). These switchgear vertical sections employ state-of-the-art
gas insulation, shielded solid insulation, vacuum interrupters, and
modular plug-in technologies. Combined with laser welding technol-
ogy and a helium gas leakage testing process, this system provides
high reliability and a small installation footprint. They provide reliable
control and protection for electrical equipment and circuits, up to
38 kV.
EATON www.eaton.com 7
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
1.3 Power Xpert XGIS elements
Low-voltage
compartment
Three-position
disconnect switch
indicating lights
Low-voltage
panel
Meters
and Three-position
relays disconnect switch
view port
Tank pressue
gauge
VT disconnect switch
Three-position disconnect
switch operator
Three-position
disconnect switch
controls
Breaker control
switch and
indicating lights
Circuit breaker
operator
Charge spring
indicating light and
control switch
Cable terminations
8 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.3.1 Standard features The vacuum interrupter circuit breaker operating mechanism is
also mounted on the gas tank front panel, below the three-position
XGIS switchgear includes a three-position disconnect switch for disconnect switch’s operating mechanism. The circuit breaker mecha-
circuit isolation, and a vacuum interrupter circuit breaker. nism includes stored energy springs for breaker closing and opening.
The three-position disconnect switch and circuit breaker can each be The springs are charged either by an electric drive (normal mode)
operated electrically or manually. The circuit breaker can be charged, or using a manual charging handle mounted in the circuit breaker
closed or opened locally or remotely. The circuit breaker trip opera- operating mechanism front cover.
tion is initiated by external protective relays or other control devices. The circuit breaker operating mechanism includes mechanical indica-
The three-position disconnect switch is interlocked with the circuit tors for spring charged/discharged status and circuit breaker open/
breaker. closed status. These indicators are visible through cutouts in the
SF6 gas as an insulating medium circuit breaker mechanism front cover.
Sulfur Hexafluoride is an odorless, colorless, inert, non-toxic, non- The circuit breaker can be operated mechanically by buttons located
corrosive and non-flammable gas. It is thermally stable and must be on its front cover or electrically by pushbuttons mounted on the
heated to more than 500º Celsius (932º F) before it will decompose. vertical section door, or remotely.
The symmetry of the atoms in its molecular structure makes it The three-position disconnect switch and circuit breaker are both
extremely stable, with a very high dielectric strength. Its dielectric mechanically and electrically interlocked to prevent improper opera-
capability is approximated three times that of air at atmospheric tion during normal (electrical) and manual (mechanical) operation.
pressure. This means that equipment insulated with SF6 can be
much more compact than air-insulated equipment. Low-voltage control wiring is routed from the internal vertical section
terminal boards to an Eaton blue colored top hat, above the low-
Power Xpert XGIS vertical section characteristics voltage compartment. Control wiring from vertical section to vertical
An XGIS vertical section is divided into two functional areas: low- section in a lineup is routed through these top hats.
and medium-voltage. SF6 tank gauge
1.3.1.1 Low-voltage area The SF6 tank has a pressure gauge mounted on the tank upper
left front face, with a color-coded scale indicating safe, caution and
The XGIS vertical section front door is used to access the low-volt- danger pressure values. In addition, the gauge includes pressure
age section. This section houses low-voltage control and operating sensors with two contact outputs, for safe and low pressure levels.
mechanisms for the three-position disconnect switch and vacuum
interrupter circuit breaker.
The vertical section door has control devices mounted on it for:
• Circuit breaker open/closed switch and status indicating lights.
• Three-position disconnect switch status indicator lights and push-
buttons for three-position disconnect switch ground, open, and
close operations.
• Three-position disconnect switch (grounding function) status
indicators and pushbuttons for three-position disconnect switch
grounding open and close.
• Customer specific control devices.
• Customer specific protective device(s).
EATON www.eaton.com 9
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
SF6 Three-position disconnect switch position viewing port The tanks are laser-welded to be gas tight and have bushings on
their top surface and bottom front surfaces. These bushings accom-
To the right of the tank charging fitting, a viewing port is available to
modate connections for main bus and cables. The tank faces have
observe the three-position disconnect switch position. This port is
gasketed ports for three-position disconnect switch and circuit
available for mounting a camera if desired.
breaker mechanical drive mounting. If repairs are needed, a rear
access panel can be removed to access the devices inside the tank.
If repairs inside the tank are required, an Eaton service representa-
tive should be contacted.
The gas tank includes a fitting and gauge for gas pressure monitor-
ing, and another fitting for filling or evacuating the tank. Both fittings
are viewable in the low-voltage area, below the low-voltage control
DIN rails and wire channels.
A viewing port is mounted on the gas tank front face, beside the
tank pressure gauge and charging fitting, for viewing the three-
position disconnect switch position. This port can be fitted for a
Figure 5. Tank viewing port mounted camera.
The tank has an overpressure relief fitting mounted on the lower
Circuit breaker cycle counter part of the tank rear vertical face. The overpressure relief fitting will
The 1250A XGIS circuit breaker is rated for 10,000 load or no-load rupture at 2 bar absolute.
operations. The 2000A XGIS circuit breaker is rated for 2,000 load For the 2000 ampere vertical section design, a heatsink assembly
or no load operations. Each closing spring charging operation is is mounted on the rear of the tank, with fins extending out into the
recorded on the cycle counter mounted on the left side of the circuit back portion of the vertical section. This heatsink provides additional
breaker frame, and viewable through a window in the front cover. cooling for the busbar connections within the tank.
10 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
When a vacuum circuit breaker is furnished in the vertical section,
the three-position disconnect switch is mounted and connected to
the top of the circuit breaker assembly in the tank, and conductors
run from the breaker’s output terminals to the tank output bushings.
EATON www.eaton.com 11
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Circuit breaker
12 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
The circuit breaker assembly consists of three vacuum interrupters,
one per phase, housed in a molded frame. Input power connections
from the three-position disconnect switch couple to top center input
terminals mounted on each vacuum interrupter frame. The breaker
outputs are bused to cable compartment bushings.
The circuit breaker vacuum interrupter poles are actuated by a
stored-energy spring system, mounted in the breaker operating
mechanism. Under normal conditions, an electric motor drive
charges the springs with close and opening energy. For manual
operation, the mechanism is charged using a lever with gear reduc-
tion. The charging lever is located on front of the circuit breaker
operating mechanism.
The circuit breaker can be electrically or manually charged, and elec-
trically or manually opened or closed.
Push buttons (I, O) provided on the circuit breaker front panel are
used to trigger mechanical opening and closing of the breaker.
Electrical charging, opening and closing can be initiated either locally
or remotely via electrical controls as required for a given application.
The molded vacuum interrupter frame is attached to its operating
mechanism. The operating mechanism is located outside the sealed
tank. The molded vacuum interrupter frame assembly is located
inside the sealed tank. The interrupter operating shafts are attached
to the operating mechanism using sealed metal bellows that permit
shaft travel without compromising the tank gas seal.
EATON www.eaton.com 13
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
1.3.3 Bracing
Incoming SSIS buses are inherently braced by their mechanical
design. Output cables are clamped in place using cable cleats and
vertical section braces.
Operations
counter
Figure 15. Typical front views of XGIS vacuum circuit breaker mechanism with cover plate on and off.
Voltage transformers
Bus side voltage transformers (non-fused or fused) are mounted in
the XGIS vertical section in the voltage transformer compartment,
behind the busbar compartment, and are equipped with a front panel
accessible disconnect switch. The VT disconnect switch operator
either connects the VTs or grounds the VTs (there is no disconnect
position).
Cable side voltage transformers (non-fused or fused) can be
mounted in the XGIS vertical section in the voltage transformer
compartment, behind the busbar compartment, only when bus VTs
are not included in the same vertical section. These vertical sections
are equipped with a front panel accessible VT disconnect switch. The
VT disconnect switch operator either connects the VTs or grounds
them. If bus VTs are included in the same vertical section, then the
Figure 16. Cable cleats attached to cable compartment brackets. cable side VTs are mounted in the MV cable compartment on the
vertical section rear base if the VTs are non-fused, or outside the
1.3.4 Arc resistant features vertical section in the cable vault if the VTs are fused.
The XGIS design is arc resistant and offers designs with attachment NNote: If the system utilizes a ducted arc exhaust (required to achieve an arc
resistant rating), then a top mount VT cannot be installed in the same vertical
points for arc ducts at the sides or rear of the vertical section. If an
section to which the arc duct connects.
XGIS vertical section is configured for arc resistance, exhaust flaps
to integrate the vertical section into an arc resistant lineup prevent
the use of top-mounted voltage transformers in the vertical section
in which the arc duct attaches to the lineup.
Arc resistant lineups can be designed for arc gas exhaust from the
lineup left end, right end, or the rear of any vertical section.
14 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Figure 19. Fused remote voltage transformer (mounted in cable Figure 21. Example input voltage transformers.
vault).
EATON www.eaton.com 15
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Current transformers
Main bus CTs
Main bus CTs can be furnished on the horizontal bus in the space
above the gas tank, with the SSIS conductors passing through the
CTs before terminating at the tank input bushings. Main bus CT
dimensions will depend upon the CT ratio and design.
Main bus CTs are installed as part of the system installation process.
After the vertical sections have been put in place and attached to
their adjacent sections, SSIS bus sections and their connectors
connect to each vertical section main bus compartment bushings.
Cable connections
In the 1250 ampere rated XGIS vertical section, cable compart-
ment CTs can be furnished in single, double or triple transformers
per phase. The CTs mount on an output bus horizontal bushing.
Separable connectors connect cable to the bushing.
16 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Figure 29. 1250 ampere cable compartment with three CTs per
phase.
Figure 30. 2000 ampere cable compartment with one CT for two
bushings per phase.
EATON www.eaton.com 17
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Surge arresters
Surge arresters can be mounted in the cable compartment. Each
cable compartment bushing can accommodate up to three cable
connectors. When surge arresters are included, they replace one
of the power cable connectors, allowing a maximum of two power
cable connections per phase.
Figure 31. 2000 ampere cable compartment with two CTs for
two bushings per phase.
Bus connections
XGIS sections can be configured for output bus connections, so
that adjacent vertical section output bushings are directly connected
using SSIS bus. In that case, the output bushings are connected to
adapters connecting SSIS bus sections. Figure 33. Surge arrester.
Key interlocks
The XGIS design can be furnished with key interlocks.
1.3.6.1 Feeder/incoming
The feeder/incoming vertical section includes both the three-position
disconnect switch and the vacuum interrupter circuit breaker. It
includes SSIS main bus and cable connections. This section can
be furnished with fused VTs with a disconnect switch, cable CTs,
remote-mounted fused VTs or surge arresters.
18 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.3.6.2 Bus tie
The bus tie vertical section includes both the three-position discon-
nect switch and the vacuum circuit breaker. It is intended to
connect two separate buses. It can be furnished with a set of VTs
with the VT disconnect switch and bus CTs.
EATON www.eaton.com 19
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
1.3.6.3 Bus sectionalizer 1.3.6.4 Disconnector
The bus sectionalizer vertical section is intended to connect or The disconnector vertical section includes only the three-position
isolate buses without circuit breaker protection. It includes the three- disconnect switch. It is intended to connect or isolate direct connec-
position disconnect switch, but no circuit breaker. It can be furnished tions to the XGIS main bus. This section can be furnished with
with a set of VTs with the VT disconnect switch and bus CTs. fused VTs with a disconnect switch, cable CTs, remote-mounted
fused VTs or surge arresters.
Figure 36. Bus sectionalizer ANSI one-line. Figure 37. Disconnector ANSI one-line.
20 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.4 Type XGIS gas insulated switchgear ratings (tables 2, and 3)
EATON www.eaton.com 21
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Table 4. Relevant standards
Relevant standards
IEC 62271-100 High-voltage switchgear and controlgear - Part 100: Alternating current circuit breakers
IEC 62271-102 High-voltage switchgear and controlgear - Part 102: Hi-voltage alternating current three-position disconnect switches and earthing switches
IEC 62271-200 High-voltage switchgear and controlgears - Part 200: AC metal-enclosed switchgear and control gear for rated voltages above 1 kV and up to and
including 52 kV
IEC 60529 Degrees of protection provided by enclosures (IP code)
IEC 62271-1 High-voltage switchgear and controlgear - Part one: Common specifications
22 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.5 XGIS vertical section outlines and dimensions
1.5.1 1250 ampere vertical section
EATON www.eaton.com 23
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
1.5.2 2000 ampere vertical section
24 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
1.6 typical DC control schematics
Following are example schematic diagrams for an XGIS unit equipped with both three-position disconnect switch and circuit breaker. These
diagrams are representative and are for reference only.
EATON www.eaton.com 25
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
26 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
EATON www.eaton.com 27
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
28 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
EATON www.eaton.com 29
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
30 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
EATON www.eaton.com 31
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
1.7 SSIS conductor system
Solid Shielded Insulation System components provide modular
shielded busbar conductors protected by solid insulation. The system
includes shielded bus sections and coupling adapters that provide
mechanically robust installation that is impervious to environmental
conditions, and free from local electric field around the conductors.
The SSIS conductors and connecting adapters consist of three
concentric layers:
• The live conductor
• The insulating layer over the conductor, and
• The conductive shield outer layer
Figure 47 shows some example SSIS components and their
arrangement as bus sections and terminations. Bus sections start at
bus connection bushings (fitted in the tank) coupled to end or cross
adapters, extend using SSIS busbar, and terminate at bus connection
bushings connected to end or cross type adapters. Figure 50 shows
typical end and cross adapters utilized for main SSIS bus assembly.
For details, refer to the project specific drawings. Figure 48. Top view of XGIS tank showing tank bushings for
busbar connections.
The bushings are mounted on top of the gas tank and are connected
to the switching components in the tank Interior.
32 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
SSIS cross adapters are used to extend the bus between the adja- The installed cables are clamped in place using cable cleats mounted
cent vertical sections. on the cable compartment cable brackets.
The maximum number of cable connectors that can be accommo-
End adapter dated depends on the XGIS rating. Multiple connectors per phase
Bus CT are configured using tee or elbow type separable connectors as
shown in Figure 54. A surge arrester fitted behind an elbow type
connector can be used instead of a power cable when specified.
Cross adapter
The 2000 ampere XGIS uses dual cable bushings per phase for cable
connections (see Figure 53).
The separable connector design will change depending upon the
output cable dimensions. In every case, a maximum of three output
connections per phase can be made: up to one tee connector
and two coupling connectors, or one tee connector, one coupling
connector and a surge arrester (see Figure 54).
EATON www.eaton.com 33
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
34 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Section 2: Safe practices 2.2 SF6 Gas handling
2.1 Recommendations Do not handle the SF6 gas during general installation. If gas tank
filling or evacuation is required, it should be done by specialists
Type XGIS vacuum circuit breaker elements are equipped with high trained on SF6 processing.
speed operating mechanisms. They are designed with several built-in
interlocks and safety features to provide safe and proper operating SF6 removal and recharging will require a gas extraction pump and
sequences. charging system suitable for restoring rated gas tank pressure during
the refill.
Whenever SF6 is removed from the tank, the tank desiccant must
be replaced. This desiccant is specific to the XGIS switchgear. The
desiccant catalog number IS 87A1040H01. Figure 55 shows a bag of
desiccant placed in the tank bottom.
TO PROTECT PERSONNEL ASSOCIATED WITH INSTALLATION, OPERATION,
AND MAINTENANCE OF THESE SWITCHGEAR ELEMENTS, THE FOLLOWING
PRACTICES MUST BE FOLLOWED:
EATON www.eaton.com 35
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Section 4: Description and operation 4.1.2 Circuit breaker
4.1 introduction The circuit breaker springs’ charging mechanism is driven by an elec-
tric motor, with manual backup. The vacuum circuit breaker consists
XGIS gas insulated switchgear is a 38 kV system with designs for of three horizontal vacuum interrupter bottles, propelled by a single
main/feeder, bus tie, and bus sectionalizing units. It is configured for mechanism.
SSIS (solid shielded insulating system) main bus conductors and can
accommodate power cables with tee connector terminations. The The breaker position is indicated through a cutout window on the
units are designed for 1250 ampere and 2000 ampere applications. operating mechanism front cover and repeated by an indicating
light on the switchgear unit front door. Breaker positions are Open
The XGIS switchgear includes arc-resistant features including arc and Closed. The breaker spring charging system status is displayed
plenum, seals and gaskets for containment, gas deflectors, arc flaps, on the breaker operating mechanism front cover through a cutout
and arc exhaust ducts. window. The circuit breaker operating mechanism includes an opera-
Design options include tion cycle counter.
• Current transformers, For typical application configurations, please see Figure 27, Figure
28 and Figure 29. The low-voltage compartment is at the front of
• Voltage transformers (fused and unfused) with disconnect switch, the entire vertical section, , the pressure-relief channel is behind
• Cable side voltage transformers, either internal or cable-connected the vertical section, and all 3-phase medium-voltage elements are
remote voltage transformers, enclosed in the sealed SF6 tank.
• SSIS main bus connections, or The SF6 tank is made of laser-welded stainless steel plates and
contains the isolation and grounding three-position disconnect
• Cable connections (to a cable vault), for single or multiple cables
switch and may also contain a vacuum circuit breaker, depending on
per phase,
the application.
• Surge arresters.
The cable compartment is located underneath the tank and contains
Each of the designs uses a sealed pressurized tank to house its separable (plug-in type) connectors for installing lightning arresters
power switching components and their connections. The tank and power cables. The CTs are installed over the CT bushings.
contains SF6 (sulfur hexafluoride) gas at 1.2 to 1.3 bar, as the insulat-
ing medium.
4.2 Operation
Each XGIS switchgear unit is composed of 4.2.1 Three-position disconnect switch
• A low-voltage compartment (instruments, relays and operating Confirm that the circuit breaker is open (check the open/closed
mechanisms compartment), status indicator window for a green “0” indication). This will permit
the three-position disconnect switch manual access door to be
• A main bus compartment, opened to expose the manual drive screw port.
• A voltage transformer compartment,
• A pressurized sealed tank,
• A tank pressure gauge,
• A tank gas port,
• A tank pressure relief fitting,
• A power cable compartment.
36 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
EATON www.eaton.com 37
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Table 6. Three-position disconnect switch/circuit breaker interlocking truth table
Operations
4.3 typical feeder circuit operations 4.3.3 Sequence of operation for main bus grounding on sec-
tionalized bus arrangements (a bus and b bus tied together
It is assumed that a feeder is in the energized condition and the
operating sequences described below are of a general nature for using a bus tie breaker)
gas insulated switchgear. In all cases applicable safety and specific It is assumed that the tie circuit breaker is in the energized condi-
operating rules shall be observed. tion.
4.3.1 Sequence of operation for isolation of a feeder: Sequence of operation for grounding of main bus section A:
a. Open all breakers connected to bus “A.”
a. The feeder circuit breaker is switched to the open position. This
enables the three-position disconnect switch. b. Move all three-position disconnect switches on bus “A” to the
Open position and verify that state by viewing.
b. The feeder three-position disconnect switch is switched to the
open position. Verify this state by viewing. c. Disable closing of all bus “A” three-position disconnect switches.
c. The feeder circuit is now isolated on the cable side. d. Open the tie breaker between bus “A” and bus “B”.
e. Open bus “B” three-position disconnect switch of the bus tie
4.3.2 Sequence of operation for feeder grounding: circuit breaker. Verify this state by viewing.
a. Isolate the feeder using 4.3.1, above. f. Move the bus “B” three-position disconnect switch to the ground
b. Verify that the circuit is deenergized by means of an integrated position (this is possible only if all three-position disconnect
voltage detector / indicator. switches on the bus “A” feeders are in the open position). Verify
this state by viewing.
c. The three-position disconnect switch is switched to the ground
position. Verify this state by viewing. g. Close the tie circuit breaker.
d. Close the circuit breaker. h. Lock the tie circuit breaker in the closed position.
e. Lock the circuit breaker in its closed position. i. Bus “A” is now grounded.
f. The feeder is now grounded through the circuit breaker on the
line side.
38 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Sequence of operation for grounding of main bus section B: Section 5: Inspection, maintenance, and
a. Open all breakers connected to bus “B.” testing
b. Move all three-position disconnect switches on bus “B” to the 5.1 Logbook
open position and verify that state by viewing.
The user should keep a logbook with data with regards to the instal-
c. Disable closing of all bus “B” three-position disconnect switches.
lation, maintenance and repair of the XGIS switchgear. The informa-
d. Open the tie breaker between bus “A” feeder and bus “B” tion recorded should at least include the following:
feeder. • All important incidents occurring in and with the XGIS
e. Open bus “A” three-position disconnect switch of the bus tie • All faults
circuit breaker. Verify this state by viewing.
• All maintenance work carried out
f. Move the bus “A” three-position disconnect switch to the ground
position (this is possible only if all three-position disconnect • All repairs carried out
switches on the bus “B” feeders are in the open position). Verify • Note of contact with Eaton with regards to instructions and
this state by viewing. permissions if required of any changes or modifications/repairs
g. Close the tie circuit breaker. carried out.
h. Lock the tie circuit breaker in the closed position.
i. Bus “B” is now grounded.
5.2 Inspections
The XGIS switchgear should be inspected using a visual inspection
annually, a condition inspection every 5 years, and a maintenance
inspection when the given number of cycles is reached or at 10
years, whichever occurs first, per the table below.
EATON www.eaton.com 39
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
5.3 Maintenance
The XGIS is designed to be maintenance free for the service life of
the switchgear. If an issue arises requiring maintenance of compo-
nents in the SF6 tank, work must be done by an Eaton representa-
tive.
Under normal operating conditions, the breaker and switch mecha-
nisms should not require additional lubrication or maintenance for
the rated service life of the equipment. If lubrication is required,
Eaton recommends using Klueber ISOFLEX TOPAS NB 52. Apply
this lubricant to all bearing, sliding surfaces, joints, rollers, gearbox,
sprockets, and interlocking mechanisms.
All low voltage components should be maintained in accordance
with the relevant instruction manuals.
The Power Xpert XGIS product is designed such that no SF6 gas
handling should be required during installation and commissioning
of the gear. If gas tank filling or evacuation is required, it should be
done by specialists trained on SF6 processing.
SF6 removal and recharging will require a gas extraction pump and
charging system suitable for restoring rated gas tank pressure during Figure 59. XGIS gas tank desiccant.
the refill.
Whenever SF6 is removed from the tank, the tank desiccant must be 5.4 Testing
replaced. This desiccant is specific to the XGIS system and consists
of a bag, catalog number 87A1040H01, and should be purchased as XGIS switchgear is filled with the SF6 insulating gas in the factory
a spare part. Figure 59 shows a bag of desiccant placed in the tank and tested as a complete system.
bottom. Current and voltage tests may be conducted without removing
cables or discharging the insulating gas.
Those tests can be performed directly using an empty cable bushing
or by using the termination left for the lightning arrester (if applied).
For the voltage test, the voltage transformer and lightning arrester
must be isolated. Empty (unapplied) terminations must be covered
by insulating cable caps.
40 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
5.4.1 Voltage test Setion 6: Renewal parts
NNote: any empty VT sockets or exposed cable terminations must be blocked 6.1 General
by an insulated plug or cap.
For the details of XGIS switchgear renewal parts, refer to technical
Typical voltage tests that can be performed are: document TD022003EN.
• DC voltage ultra-low-frequency sine or square wave test on power Contact Eaton engineering services for more information.
cables.
• AC power frequency or impulse voltage withstand tests as Table 8. Recommended renewal parts list
desired Name Description Part Number
• Ac voltage system test can be performed using the voltage test B-line cleats
cable (see Figure 60). Separable cable T connector
Ssis bus components
Contact Eaton engineering services for more information.
Surge arrestor
Tank bushing
Current transformers
Voltage transformer, fused
Voltage transformer, unfused
VT fuses
EATON www.eaton.com 41
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Notes:
42 EATON www.eaton.com
Instructions for the operation and Instruction Booklet IB022017EN
maintenance of Power Xpert TM Effective February 2019
XGIS gas insulated switchgear
Notes:
EATON www.eaton.com 43
Instruction Booklet IB022017EN Instructions for the operation and
Effective February 2019 maintenance of Power Xpert TM
XGIS gas insulated switchgear
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
© 2019 Eaton
All Rights Reserved Eaton is a registered trademark.
Printed in USA
Publication No. IB022017EN / TBG 001430 All other trademarks are property
February 2019 of their respective owners.