1 X 6 mm2 CU / LSHF / LSHF 1.0/1.0 kV (1.5 kV DC) Solar Cable
Sr. Description Unit Details
1. Size No. x mm2 1x6 2. Description - CU/LSHF/LSHF 3. Reference Standard - BS EN 50618 4. Ambient Temperature range - Maximum conductor temperature (insulation & 5. 120 (For 20 000 Hours) Sheath) 6. Rated Voltage kV 1.0/1.0 kV AC -1.5kV DC 7. Number and nominal diameter of wires - As per BS EN 60228 8. Shape of conductor - Flexible Annealed tin-coated flexible copper 9. Conductor material - as per BS EN 60228, class-5. Halogen free cross-linked flame 10. Insulation material - retardant compound (HFFR). 11. Nominal thickness of insulation mm 0.70 Halogen free cross-linked flame 12. Outer sheath material retardant compound (HFFR) 13. Outer sheath Color Black 14. Nominal thickness of outer sheath mm 0.80 15. Max. conductor DC Resistance at 20°C 3.39 16. Max. conductor AC Resistance at 90°C 4.3226 Current rating:* 17. Single Cable Free in Air A 70 18. Single Cable on a surface A 67 19. Two Loaded Cable touching ,on a surface A 57 20. Approximate overall diameter mm 6.0 21 Approximate Cable net weight kg/km 90 22 Drum Cutting length with (±5% tolerance.) m 1000 23 Minimum Bending Radius mm 36 Assessment of halogens in accordance with BS EN 24. 50525-1:2011 Annex B Weathering /UV Resistance as per BS EN 50618 25. Annex E. 26. Ozone Resistant as per BS EN 50396 Elongation at Break as per BE EN 60811-501 & BS 27. EN 60811 -401 28 Acid Resistant As per BS EN 60811-404 *Laying Conditions: Ambient air temperature of 60 ºC, In case of different laying conditions, appropriate correction (derating) factors from Table A.4 of BS EN 50618