You are on page 1of 1

Technical Data Sheet

1 X 6 mm2 CU / LSHF / LSHF 1.0/1.0 kV (1.5 kV DC) Solar Cable

Sr. Description Unit Details


1. Size No. x mm2 1x6
2. Description - CU/LSHF/LSHF
3. Reference Standard - BS EN 50618
4. Ambient Temperature range -
Maximum conductor temperature (insulation &
5. 120 (For 20 000 Hours)
Sheath)
6. Rated Voltage kV 1.0/1.0 kV AC -1.5kV DC
7. Number and nominal diameter of wires - As per BS EN 60228
8. Shape of conductor - Flexible
Annealed tin-coated flexible copper
9. Conductor material -
as per BS EN 60228, class-5.
Halogen free cross-linked flame
10. Insulation material -
retardant compound (HFFR).
11. Nominal thickness of insulation mm 0.70
Halogen free cross-linked flame
12. Outer sheath material
retardant compound (HFFR)
13. Outer sheath Color Black
14. Nominal thickness of outer sheath mm 0.80
15. Max. conductor DC Resistance at 20°C 3.39
16. Max. conductor AC Resistance at 90°C 4.3226
Current rating:*
17. Single Cable Free in Air A 70
18. Single Cable on a surface A 67
19. Two Loaded Cable touching ,on a surface A 57
20. Approximate overall diameter mm 6.0
21 Approximate Cable net weight kg/km 90
22 Drum Cutting length with (±5% tolerance.) m 1000
23 Minimum Bending Radius mm 36
Assessment of halogens in accordance with BS EN
24.
50525-1:2011 Annex B
Weathering /UV Resistance as per BS EN 50618
25.
Annex E.
26. Ozone Resistant as per BS EN 50396
Elongation at Break as per BE EN 60811-501 & BS
27.
EN 60811 -401
28 Acid Resistant As per BS EN 60811-404
*Laying Conditions: Ambient air temperature of 60 ºC, In case of different laying conditions, appropriate correction (derating)
factors from Table A.4 of BS EN 50618

CLASSIFICATION: INTERNAL