Sat 4208 Al T Mar Me 003 00
Sat 4208 Al T Mar Me 003 00
Contract No.:
MAR MATERIAL APPROVAL REQUEST
4208
Project Name: PMCS Riyadh Airports
Reference No.: SAT-4208-AL-T-MAR-ME-0003-00 Date: 29-Sep-21
Contract Title: PBB T3 & T4
Works Package WP12
TO: PMCS EGIS FROM: CONTRACTOR SATCO
Description of Material (One item only per form): As per Specification Alternative
Title: Submitting data sheets and catalogues for PBB Substation NOVEC System SAMPLE
Description:
YES NO
Attach all relevant technical literature marked to identify relevant descriptions, current test certificate, samples, etc.
Attach a certificate stating compliance with Contract requirements.
Highlight any element of contractual non-compliance in this submittal.
References: Planned Dates for Applicable Submittal for: Date
Drawing Ref. No.: Attached 1. O & M Manual
Specification No.: 2. RAC Training
BOQ Ref. No.: 3. Specified/recommended spare parts
International Standards: 4. Warranties and Guarantees
Ref:
Manufacturer / Supplier:
Company Name: Raychem Locally Manufactured:
Address: Production Period:
Delivery Ex-Works:
Total Delivery Time:
Local Agent: Overland:
Sea Freight:
Total Freight:
PROGRAMME CONTRACTOR’S AUTHORIZED SIGNATURE
Date Required on Site:
ENGINEER’S COMMENTS
1- Product catalogue reviewed only. 2-Follow manufacturer recommendations.
3. Its contractor responsibility to make sure mentioned product comply approved
design criteria, NFPA requirement and project specifications.
4. Contractor is responsible for complying all fire safety requirement as per saudi
civil defence. ( final approval is subject to Saudi civil defence approval)
Signed by: Signed by:
5. commentsEngineering
attached.Manager Resident Engineer
DOCUMENT STATUS:
Code A – Approved Work may proceed. Code B – Approved with comments, resubmit, work may proceed
Code C - Revise and resubmit. Work may not proceed. Code D – Rejected, Not applicable
IMPORTANT: Permission to proceed on behalf of RAC does not constitute acceptance or approval by RAC of design, calculations,
analysis, tests, methods of materials developed or selected by the Contractor and does not relieve him from compliance with his
contractual obligations.
PMC
Stamp
Contract No.
DOC Submittals
Project Name: PMCS Riyadh Airports
Works Package
PBB TR3& TR4
Name
Reference No.: SAT-4208-TR3-SL-SD-M-FF-M03-003-000-00 Date: 8-May-21
PMC/Contractor: Revision: 00
TO: Egis FROM: SATCO Contractor
Type:
Design Change Order Schedule Update Samples Reports
Shop Drawings As-Built Method Statement Others:
Discipline:
Special Airport Civil/Structure Electrical VDGS General
Projects MEP Others:
DESCRIPTION OF THE SUBMITTAL (): Reply Required By: -
Subject: NOVEC Firefighting System Shop Drawings and Calculation Reports for PBB Substation Rooms
ATTACHMENTS:
Anand Sundaram
02 June,2021
ENGINEERED SYSTEM
DESIGN AND INSTALLATION MANUAL
(UL/FM VERSION)
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
CONTENTS DATE: 2010-03
Warranty������������������������������������������������������������������� 86
Disclaimers and Limitations�� ��������������������������������� 86
SECTION 11 - APPENDICES
APPENDIX A - Temperature Correction Chart
������������������������������������������������������������������������� 88
APPENDIX B - Hughes Program Printout������� 89
APPENDIX C - NOVEC™ 1230 Material Safety
Data Sheet (MSDS) �� ������������������������������������ 99
APPENDIX D - NOVEC™ 1230 Liquid Level
Indicator Charts�������������������������������������������� 105
APPENDIX E - Dual Supply System
Components�������������������������������������������������� 122
Table 26: Primary and Secondary Supply System
Components.�� ���������������������������������������������� 122
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 1 - INTRODUCTION DATE: 2010-03
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 1 - INTRODUCTION DATE: 2010-03
NOVEC™ 1230 Agent Characteristics • Less visual obscurity and minimal risk to
personnel.
NOVEC™ 1230 is a clean agent containing no particles
or oily residues. It is produced under ISO 9002 guidelines • Low toxicity.
to strict manufacturing specifications ensuring product • Most effective when used with automatic detection
purity. NOVEC™ 1230 leaves no residue or oily deposits to introduce NOVEC™ 1230 with a 10 second
on delicate electronic equipment, and can be removed discharge.
from the protected space by ventilation.
• The ability to prevent re-ignition providing
NOVEC™ 1230 is thermally and chemically stable, concentration levels are maintained.
but without the extremely long atmospheric lifetimes
associated with some other clean agents. The atmospheric NOVEC™ 1230 is stored as a liquid in approved DOT
lifetime of NOVEC™ 1230 has been determined to be or TPED containers and is super-pressurised with dry
5 days (Reference 3M™). The US EPA SNAP does not nitrogen to 25 bar @ 21 °C (360 psi @ 70 °F).
consider NOVEC™ 1230 to be a long lived substance
when discharged, and as such has placed no restrictions on
its use. (Environmental Protection Agency’s Significant WARNING
New Alternatives Program). NOVEC™ 1230 shall not be used on fires involving
the following materials unless they have been
Typical areas that may be protected by a SAPPHIRE® tested to the satisfaction of the authority having
system are detailed below; the list is by no means jurisdiction:
exhaustive:
• Certain chemicals or mixtures of chemicals, such
as cellulose nitrate and gunpowder, that are capable
Bank Vaults of rapid oxidation in the absence of air.
Libraries
Rare Book Stores • Reactive metals such as lithium, sodium,
Electronic Data Processing potassium, magnesium, titanium, zirconium,
Telephone Exchanges uranium and plutonium.
Studios
Communication Centres • Metal hydrides.
Transformer and Switchrooms
• Chemicals capable of undergoing autothermal
Control Rooms
decomposition, such as certain organic peroxidase
Test Laboratories and hydrazine.
Flammable Liquid Stores
Table 1.
Agent Physical Properties FK-5-1-12
Chemical structure CF3CF2C(O)CF(CF3)2
Chemical name Dodecafluoro-2-methylpentan-3-one
Molecular weight 316.04
Boiling point 49.0 °C (120.2 °F)
Freezing point -108.0 °C (-162.4 °F)
Critical temperature 168.7 °C (335.6 °F)
Critical pressure 1865 kPa (270.4 psi)
494.5 cc/mole
Critical volume
(0.0251 cu ft./lbm.)
Critical density 639.1 kg/m³ (39.91 lb./ft³)
(Reference: NFPA 2001, 2008 edition)
Table 2.
Table 3: Toxicology/Environmental
NOVEC™ 1230
Environmental
Ozone Depletion (ODP) 0
Toxicology
Acute Exposure LC50 >10.0%
Cardiac Sensitization
10.0%
No Observed Adverse Effect Level (NOAEL)
Lowest Observed Adverse Effect Level (LOAEL) >10.0%
(Reference: NFPA 2001, 2008 edition)
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
This section describes the individual components that The 4.5, 8, 16, 32, 52, 106, 147 and 180 litre containers
comprise a complete system. Some items are optional are manufactured in accordance with DOT 4BW500 or
depending on the application, and are indicated as such. 4BW450, and the 343 litre container in accordance with
DOT 4BW450.
SAPPHIRE® Container
The container assembly consists of a container fitted Material: Carbon Steel
with a valve and internal syphon tube, factory filled 4BW500
with NOVEC™ 1230, and super-pressurised with dry Hydraulic test pressure: 69.0 bar (1000 psi)
nitrogen to 25 bar @ 21 °C (360 psi @ 70 °F). Containers Working Pressure: 34.5 bar (500 psi)
sharing the same manifold shall be equal in size and fill
4BW450
density. Containers are finished in red and are available
Hydraulic test pressure: 62.1 bar (900 psi)
in various sizes. A nameplate is fixed to the container
Working Pressure: 31.0 bar (450 psi)
displaying the agent weight, tare weight, gross weight, fill
density, charge date and fill location. Paint Specification: Red epoxy polyester or
red polyester powder
coated
Figure 1 - SAPPHIRE® Container
The 8, 16, 32, 52, 106 and 147 litre containers are
also available manufactured in accordance with EN
13322-1.
Table 4a: DOT Container - valve Table 5a: TPED Container - valve
equivalent lengths. equivalent lengths.
Part No. Equivalent Lengths Part No. Equivalent Lengths
(Nominal Volume) (m) (Nominal Volume) (m)
303.207.010 (4.5 litre) 6.096 303.207.020 (8 litre) 6.096
303.207.001 (8 litre) 6.096 303.207.021 (16 litre) 6.096
303.207.002 (16 litre) 6.096 303.207.022 (32 litre) 6.096
303.207.003 (32 litre) 6.096 303.207.023 (52 litre) 10.668
303.207.004 (52 litre) 10.668 303.207.024 (106 litre) 10.668
303.207.005 (106 litre) 10.668 303.207.025 (147 litre) 10.668
303.207.006 (147 litre) 10.668
303.207.007 (180 litre) 10.668
303.207.008 (343 litre) 25.91
10
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
The container label details the weight of NOVEC™ 1230 Material: Aluminum
contained, empty weight, fill density and charge date.
Once the label is applied to the container surface, and to Adhesive: Pre-applied 3M adhesive 9485
avoid possible tampering it can not be removed intact.
Certification: UL Recognised
THIS CONTAINER IS FILLED WITH 3M NOVEC™ FLUID THE DATE OF MANUFACTURE IS ON THE CONTAINER
(DODECAFLUORO-2-METHYLPENTAN-3-ONE) AND IS
SUPERPRESSURIZED TO 25 BAR (360 PSI)
SUITABLE FOR USE IN AMBIENT TEMPERATURES OF
AT 21°C (70°F) WITH DRY NITROGEN
-18°C TO 54°C (0°F TO +130°F)
PART NO.:
AGENT WEIGHT: KG (lb) 16, 32 AND 52 LITRE CONTAINERS
TARE WEIGHT: KG (lb) MUST BE TRANSPORTED AND STORED
Tyco Safety Products IN THE VERTICAL POSITION
GROSS WEIGHT: KG (lb)
Burlingham House,
FILL DENSITY: KG/L (lb/ft 3) Gapton Hall Industrial Estate,
Great Yarmouth, Norfolk, NR31 0NN FACTORY TESTED TWICE
CHARGE DATE: Tel no. +44 (0)1493 417600 DOT SERVICE PRESSURE
FILL LOCATION: Fax no. +44 (0)1493 417700 STAMPED ON THE CONTAINER
12
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Technical Information
80 mm (3”)Valve
Body: Brass UNS-C36000
Rating: 52 bar (760 psi) @ 50 °C (122 °F)
Thread: 0.9375-16UN-3A
Hole Orientation: 90° to Body
Torque: 68 Nm (50 Ibs.ft)
Overall Size : 33.3mm (L) x 18mm (Dia)
(1.3125” (L) x 0.71” (Dia))
Weight: 0.088 kg (0.195 lbs)
14
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Figure 7 - Alternate Low Pressure Switch (Part No. 305.209.007) Figure 8 - Alternate Low Pressure Switch (Part No. 305.209.007)
Option #1 Option #2
Fixing Brackets
The bracket assembly consists of one back channel and a Technical Information
nut and bolt with two bracket half straps. To securely hold
Material: Mild Steel
the container in position during the system discharge, two
bracket assemblies are required per container. The only Coating: Black Polyethylene powder-Plascoat LDPE
exceptions are the 4.5 and 8 litre containers which only Mounting: Unistrut Channel
require one. Weight: 0.34 kg (0.75 lbs) (Part No. 311.205.020)
0.30 kg (0.66 lbs) (Part No. 311.205.013)
Each strap is notched for insertion into the back channel 0.46 kg (1.01 lbs) (Part No. 311.205.014)
allowing the container to be properly aligned. The bracket 0.71 kg (1.56 lbs) (Part No. 311.205.019)
assembly is designed to be mounted to a rigid vertical
surface with the container assembly resting fully on the
floor.
Length of Back
Part Number Container Size
Figure 9 - Fixing Bracket (Strap Style) Channel
mm (in)
311.205.020 4.5 litre 400 (15.75”)
178 mm dia. (7”)
16
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Figure 10 - Manual Actuator (Part No. 304.209.002) Figure 11 - Pneumatic Actuator (Part No. 304.209.004)
Figure 12 - Electrical Actuator - Suppression Diode (Part No. Figure 13 - Electrical Actuator - Bridge Rectifier (Part No.
304.205.010) 304.209.001)
18
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
20
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Figure 17 - 80mm (3”) Valve Single Tank Adaptor Figure 18 - Manifold Check Valve
Manifold
Manifolds are fabricated sections of steel pipework. They enable multiple containers to be connected to a common pipe
network. They may also be used in systems where main / reserve containers arrangements are required.
Technical Information
Material: ASTM A106 Gr B / BS 3601 Schedule 80
Inlet: NPT socket
Outlet: BSP Taper / NPT Taper / 6” Flange
Test Press. 90 bar (1305 psi)
Finish: Primed, Ready to paint on site.
Table 6: Manifolds
Inlet to Inlet to Inlet to End
Part No. of Manifold Container Overall EndThread
End Cap Inlet Connection
No. Inlets Pipe Size Size Length Connection
Distance Distance Distance
mm mm mm mm
307.209.022 2 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 650 (25.6”) BSPT
307.209.023 3 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 1000 (39.4”) BSPT
307.209.024 4 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 1350 (53.1”) BSPT
307.209.001 2 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 650 (25.6”) NPT
307.209.002 3 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 1000 (39.4”) NPT
307.209.003 4 65mm (2.5”) 150 (6”) 350 (14”) 150 (6”) 4.5 L to 32 L 1350 (53.1”) NPT
307.209.025 2 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 808 (31.8”) BSPT
307.209.026 3 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 1316 (51.8”) BSPT
307.209.027 4 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 1824 (71.8”) BSPT
307.209.028 5 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 2332 (91.8”) BSPT
307.209.029 6 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 2840 (111.8”) BSPT
307.209.004 2 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 808 (31.8”) NPT
307.209.005 3 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 1316 (51.8”) NPT
307.209.006 4 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 1824 (71.8”) NPT
307.209.007 5 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 2332 (91.8”) NPT
307.209.008 6 80mm (3”) 150 (6”) 508 (20”) 150 (6”) 52 L to 180 L 2840 (111.8”) NPT
22
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Technical Information
Material: Carbon Steel to
ASTM A105 / ASTM A350 LF2
Dimensions: ANSI B16.11 / BS3799
Pressure Rating: 3000lb
24
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Construction of Manifolds
For customers wishing to manufacture their own
manifolds they must be constructed as detailed
below, and use the manifold inlets specified on Page 24,
(Figure 20 and Table 7).
Table 8: Manifolds
Inlet Inlet
No. of End Overall Container Socket
to End Cap to Inlet
Inlets Connection Length Size Part No.
Distance Distance
mm mm mm
2 2½ in. BSPT / 2½ in. NPT 650 (25.6”) 150 (6”) 350 (14”) 4.5 L to 32 L 17036
3 2½ in. BSPT / 2½ in. NPT 1000 (39.4”) 150 (6”) 350 (14”) 4.5 L to 32 L 17036
4 2½ in. BSPT / 2½ in. NPT 1350 (53.1”) 150 (6”) 350 (14”) 4.5 L to 32 L 17036
2 3 in. BSPT / 3 in. NPT 808 (31.8”) 150 (6”) 508 (20”) 52 L to 180 L 17037
3 3 in. BSPT / 3 in. NPT 1316 (51.8”) 150 (6”) 508 (20”) 52 L to 180 L 17037
4 3 in. BSPT / 3 in. NPT 1824 (71.8”) 150 (6”) 508 (20”) 52 L to 180 L 17037
5 3 in. BSPT / 3 in. NPT 2332 (91.8”) 150 (6”) 508 (20”) 52 L to 180 L 17037
6 3 in. BSPT / 3 in. NPT 2840 (111.8”) 150 (6”) 508 (20”) 52 L to 180 L 17037
2 4 in. BSPT / 4 in. NPT 808 (31.8”) 150 (6”) 508 (20”) 52 L to 180 L 17038
3 4 in. BSPT / 4 in. NPT 1316 (51.8”) 150 (6”) 508 (20”) 52 L to 180 L 17038
4 4 in. BSPT / 4 in. NPT 1824 (71.8”) 150 (6”) 508 (20”) 52 L to 180 L 17038
5 4 in. BSPT / 4 in. NPT 2332 (91.8”) 150 (6”) 508 (20”) 52 L to 180 L 17038
6 4 in. BSPT / 4 in. NPT 2840 (111.8”) 150 (6”) 508 (20”) 52 L to 180 L 17038
3 6 in. Flange 1366 (53.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
4 6 in. Flange 1874 (73.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
5 6 in. Flange 2382 (93.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
6 6 in. Flange 2890 (113.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
7 6 in. Flange 3398 (133.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
8 6 in. Flange 3906 (153.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
9 6 in. Flange 4414 (173.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
10 6 in. Flange 4922 (193.8”) 150 (6”) 508 (20”) 52 L to 180 L 17467
26
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Figure 24 - Male Adaptor Figure 25 - Male Pilot Hose Connector (Part No. 309.013.007)
28
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
30
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
SECTION SECTION
2 - SYSTEM
2 - COMPONENTS
SYSTEM COMPONENTS
Discharge Nozzle
HYGOOD
HYGOOD
NOVEC™ 1230 is distributed within the protected area by
the discharge nozzle which is sized to ensure the correct
flow of agent for the risk. Nozzles are available with seven
Discharge
or eightDischarge
Nozzle
ports to allow for Nozzle
180° or 360° horizontal discharge Figure 21 - 7Figure
& 8 Port
21Nozzle
- 7 & 8 Brass
Port Nozzle
Configuration
Brass Configuration
patterns. Ports are drilled in 0.1 mm (0.004 in) increments
FM-200® is distributed
FM-200® iswithin distributed
the protected
within the area protected
by the area by the
to the specified system design. Nozzles are supplied 10mm as (3/8") 10mm
BSP (3/8")
Nozzle: BSP Nozzle:
Part No. 3381/2
Part No. 3381/2
discharge nozzle
discharge
whichnozzleis sizedwhich
to ensure
is sized
thetocorrect ensure the correct
15mm (1/2") 15mm
BSP (1/2")
Nozzle: BSP Nozzle:
Part No. 3391/2
Part No. 3391/2
standard in Brass as BSPP or NPT with Stainless Steel
flow of agent for
flow the
ofrisk��
agent Nozzles
for the are
risk��available
Nozzleswith are available
seven with 20mmseven
(3/4") 20mm
BSP (3/4")
Nozzle: BSP Nozzle:
Part No. 3401/2
Part No. 3401/2
as an option.
or eight portsortoeight
allowports
for 180
to allow
o or 360 foro 180
horizontal
o or 360dis- o horizontal
25mmdis-
(1") 25mmBSP (1")
Nozzle:BSP Nozzle:
Part No. 3411/2
Part No. 3411/2
charge patterns��
charge
Portspatterns��
are drilledPortsin are
0��1mm
drilled
(0��0in040��in)
1mmin-(0��032mm (1 1/4")
04 in) in- 32mm
BSP (1
Nozzle:
1/4") BSP Nozzle:
Part No. 3421/2
Part No. 3421/2
crements to the
crements
specified
to the system
specified
design��system nozzles BSP40mm
BSP design�� (1 1/2")
nozzles 40mm
BSP (1
Nozzle:
1/2") BSP Nozzle:
Part No. 3431/2
Part No. 3431/2
are supplied are
as standard
supplied in as Brass
standard andinStainless
Brass and Steel 50mm
Stainless Steel(2") 50mm
BSP (2")
Nozzle: BSP Nozzle:
Part No. 3441/2
Part No. 3441/2
with NPT as optional��
with NPT as optional��
Technical Information
Material: Brass / Stainless Steel
Thread Type: BSPP / NPT
Drill Incrementation: 0.1 mm
Nozzle Type:
Technical Information
Technical Information16 Port 360° / 7 Port 180°
Max. Distance from Ceiling: 300mm
Material:
Max. AgentMaterial:
per Nozzle: Brass 100
/ Stainless
Brass
kg (220 Steel
/ Stainless Steel
lbs)
Orientation: Pendant / Upright
FM-200® Installation
FM-200®Guide/11100/02.08.05/Issue
Installation Guide/11100/02.08.05/Issue
3.3 3.3 25 25
Novec™ 1230 (UL/FM)
14A-11T
02
2010-03 SECTION 2 - SYSTEM COMPONENTS
32
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
Figure 31 - Door Notice (Part No. 314.207.002) Figure 32 - Manual Release Sign (Part No. 314.207.003)
NOVEC™
CAUTION! 1230
Fluid
Do NOT enter unless RELEASE
Manual
extinguishing system Control Point
is locked off.
NOVEC™ When alarm sounds NOVEC™
1230 evacuate hazard area. 1230
FLUID FLUID
After NOVEC™ 1230 Fluid
discharge do NOT CAUTION!
Technical Information
CAUTION!
Material 2 mm (0.08 in) Craylon
This area is protected
with NOVEC™ 1230 Fire Finish Gloss, scratch resistant
Protection Fluid. Overall Size: 212mm (L) x 75mm (W)
When alarm sounds
(8.35” (L) x 2.95” (W))
NOVEC™ or upon gas discharge Weight: 0.011 kg (0.024 lbs)
1230 evacuate hazard area
FLUID immediately.
After discharge
do NOT
re-enter until
thoroughly ventilated.
Technical Information
Material 2 mm (0.08” ) Craylon
Finish Gloss, scratch resistant
Overall Size: 210mm (L) x 210mm (W)
(8.27” (L) x 8.27” (W))
Weight: 0.025 kg (0.055 lbs)
34
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 2 - SYSTEM COMPONENTS DATE: 2010-03
System Design
There are two main elements of system design. The first The NOVEC™ 1230 cupburner value* is 4.5% for
is the risk assessment; determining the type of protection commercial grade Heptane, and an extinguishing
required, considerations such as ventilation, openings concentration of 3.5% for Class A materials.
and restrictions; equipment location. etc. The second is
calculating the quantity of NOVEC™ 1230 required, Calculations to determine minimum design concentration:
including floor and/or ceiling voids, positioning of nozzles,
electrical requirements, etc. Cupburner or fire test concentration x safety factor.
All systems are designed in accordance with NFPA Safety factor: Class A = 1.2
2001. Class B = 1.3
Class C = Class A
Hazard Analysis
For Class A (Determined by fire test) -
The first, and one of the most important, exercises in
3.5 x 1.2 = 4.2%
planning a SAPPHIRE® extinguishing system is the
hazard survey. The information derived from the survey For Class B (Commercial grade Heptane)-
should include risk assessment, environmental conditions, 4.5% x 1.3 = 5.85%
personnel considerations, system operation both in normal
conditions and after a discharge, access and construction For Class B (Other class B fuels)-
limitations, dimensions, volumes, and any special cupburner x 1.3 = design concentration
requirements. For Class C -
SAPPHIRE® systems are suitable for use in normal Use at least design concentration for Class A
commercial and industrial environments. The minimum surfaces fires (4.2%)
design concentration for Class A & C fires is 4.2% but For systems with only manual actuation -
differs for Class B fires. To determine other recommended cupburner x 1.3 = design concentration but not
design concentrations for Class B flammable liquids, refer less than 9.0%
to the methodology within NFPA 2001, 2008 edition.
All design concentration calculations are based on Rugged environments, and those requiring
extinguishing concentrations plus 20% safety factor for intrinsically safe or flameproof equipment, require special
Class A & C and 30% safety factor for Class B. consideration and should be discussed fully with the
technical support centre before finalising a system design.
All agent quantities are calculated at minimum NOVEC™ 1230 is suitable for use with the following
design temperature to determine agent quantity. materials:
Maximum achieved concentration should be calculated
at the maximum anticipated enclosure temperature, and
Class A Fires involving solid materials usually of
compared to NOAEL / LOAEL values, see table 3.
an organic nature, in which combustion
normally takes place with the formation of
glowing embers.
Class B Fires involving flammable liquids or
liquefiable solids and flammable gases.
Class C Fires involving energized electrical
equipment where the electrical
nonconductivity of the extinguishing
media is of importance
36
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 3 - SYSTEM DESIGN DATE: 2010-03
• Class D Combustible metals. Each enclosed space is considered as a risk area and
requires at least one nozzle. A floor void, ceiling void,
• Chemicals capable of auto-thermal recomposition. cable duct, etc., is treated as a separate adjacent area and
• Chemicals capable of rapid oxidation. requires simultaneous discharge to occur.
• Enclosures with hot surfaces (>400 °C) (752 °F) Ceiling obstructions such as beams that are less than
300 mm (12”) below the slab need not be considered.
Hazard Structure Obstructions greater than 300 mm (12”) can affect the
distribution of agent and may require additional nozzles.
The protected enclosure shall be bounded by rigid Consult the technical support centre if in doubt.
elements of building construction. The ceiling should be
not less than 0.3 m (1. ft) above the hazard. To determine the volume refer to the site drawings,
ensuring that the scale is accurate and that heights are
During agent discharge, the hazard enclosure will denoted, or make a sketch of the area adding dimensions
experience a pressure change. Consideration should be and any relevant details. Calculate the volume of each
given to mitigating these pressure changes. area.
38
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 3 - SYSTEM DESIGN DATE: 2010-03
Manifolds
It may be necessary to manifold agent containers to
provide the required amount of agent for a hazard, or to
make available the proper increments of agent weight for
the protection of multiple hazards.
Whenever containers are manifolded, the following
rules must be observed.
Agent Distribution
Distribution piping will be installed only with approved
piping as indicated in Section 5.
Pipe size reductions may be made by using reducing
tees or reducing bushings or reducing couplings.
40
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 3 - SYSTEM DESIGN DATE: 2010-03
HYGOOD
Maximum Limits (Elevation) in Pipe Work. SECTION
SECTION 3
3 -- SYSTEM
SYSTEM DESIGN
DESIGN
Examples:
Maximum Limits in Pipe Work.
If nozzles are only located above the container outlet, then the maximum elevation difference between the container
Examples:
outlet Figure
and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 9.1 m 25a -See
(30 ft).
Maximum
Maximum
Figure 35. Limits in Pipe Work.
Limits in Pipe Work.
Examples: Figure 25a -
Examples: Figure 35 - Nozzles Located Above the Container Outlet Figure 25a -
4.5 m (15 ft)
9.1 m (30 ft) 9.1 m (30 ft)
9.1 m (30 ft)
If nozzles are located both above and Note: If a system design violates these
below the container outlet, then the maximum distance limits, contact the technical support centre
Note: Ifhas
to determine what action a system design violates
to be taken.
between the furthest horizontal pipe runs, or discharge these limits, contact Macron Safety
If nozzles
nozzles (whicheverIfisnozzles are
further)are located
shall both
not exceedabove and
9��1mand
(30
located both above Systems to determine what action
below
ft)�� Seethe container
figure 25c�� outlet, then the maximum distance
below the container outlet, then the maximum distance Note:
has If ataken��
to be system design violates
between the furthest horizontal pipe runs, or discharge Note: If a system design violates
between the furthest horizontal pipe runs, or discharge these limits, contact Macron Safety
nozzles
© 2010 (whichever
Tyco Safetyis Products
further) shall not exceed 9��1m (30 these limits, contact Macron Safety41
nozzles (whichever is further) shall not exceed 9��1m (30 Systems to determine what action
ft)�� See figure 25c�� Systems to determine what action
ft)�� See figure 25c�� has to be taken��
34 has to be taken��
FM-200 Installation Guide/11100/02.08.05/Issue
®
3.3
SECTION
Nozzle 3 - SYSTEM
Discharge DESIGN
Radius HYGOOD
System Design Procedure
The following procedure must be followed when designing
The maximum discharge radius is 6.9 m (22.6ft) for a SAPPHIRE® systems.
360° nozzle and 10.9 m (35.8ft) for a 180° nozzle.
•System
DetermineDesign Procedure
Figure 26 - Nozzle Discharge Radius
hazard material and required design
concentration.
The following procedure must be followed when design-
Figure 38 - Nozzle Discharge Radius
•ing Identify
FM-200individual
®
systems��enclosure volumes and deduct any
impermeable volumes where appropriate.
• Determine hazard material and required design
• Determine hazard altitude and correction factor.
concentration��
6.9 m
8��7m •• Calculate
Identify quantity of NOVEC™
individual 1230 perand
enclosure volumes enclosure,
deduct
atany
minimum design temperature.
impermeable volumes where appropriate��
•• Determine
Determinecontainer size andand
hazard altitude fillcorrection
density. factor��
Computer Room:
120.7m 3 543.3 m³
(4262.6ft 3
) 41 xx16 port
7 port nozzles
nozzle
(19237.1 ft³)
Computer Room:
Floor Void: 63.36 m³ 2 x 16 port nozzles
(2275.4 ft³)
543.3m3 (19237.1ft ) 3
4 x 8 port nozzles
Nozzle placement and piping arrangements for the
Floor Void:
example are shown in Figure 45.
Figure 39 - Side Tee Split limits. Figure 40 - Bull Tee Split limits.
90-65%
Minimum length
of 10 x nominal 30-70%
pipe diameter
w
Flo Minimum length
w of 10 x nominal
Flo
pipe diameter
Minimum length
of 10 x nominal
pipe diameter 10-35% 70-30%
Figure 41 - Side tee orientation “correct” Figure 42 - Side tee orientation “incorrect”
w
Flo
w
Flo
Figure 43 - Bull tee orientation “correct” Figure 44 - Bull tee orientation “incorrect”
Incorrect Tee
Correct Tee Splits
Splits
w
Flo
w
Flo
NOTE: Incorrect orientation of side and bull tee could result in separation of the NOVEC™ 1230 from the Nitrogen (due to NOVEC™ 1230
greater density). The design would also be outside the parameters permitted by the calculation software. See figures 42 and 44.
Design Example - Calculations When the minimum quantity of NOVEC™ 1230 has
been calculated the weight is compared to the available
Minimum Agent Quantity is based on the hazard volume agent container size. The container size must be equal to
at the minimum anticipated temperature and concentration or greater then the weight of agent (see Table 4 & 5).
required. To determine the minimum agent quantity the
following equation is used: With the appropriate container selected, the previous
equation can be rearranged to determine the concentration
W = (V/S)* (C/100-C) based on the actual weight as containers are filled to the
nearest kg.
C= 100 WS
W = Weight of agent required (kg)
WS + V
V = Hazard volume (m³)
To calculate the required agent for each hazard volume as
S = Specific Vapour Volume (m³/kg) a percentage of the total agent required;
44
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
HYGOOD
ISSUE No. 02
SECTION 3 - SYSTEM DESIGN SECTION
DATE: 3 - SYSTEM DESIGN
2010-03
The minimum
Switch Room: enclosure
4262��concentrations
6/23499��7 = 18��can
14%beofcalculated
Agent After determining
After determiningthe theminimum
minimum weight andand
weight concentration,
concentra-
based on the actual container fill (21 °C minimum design the maximum concentration can be determined
tion, the maximum concentration can be determined by by
Computer Room: 19237��1/23499��7 = 81��9% of Agent
temperature). recalculating the equation based on the maximum
recalculating the equation based on the maximum tem-
Floor Void: 2275��4/2275��4 = 100% of Agent temperature
perature anticipated
anticipated in eachinenclosure
each enclosure 27 °C
270C (800F) maxi-
maximum design temperature. This calculation is required
mum design temperature�� This calculation is required to
Switch C = to switch
100 xRoom
92.2 x :0.072154 = 5.22% to determine
Actual agent determine if if
thethemaximum
maximumconcentration
concentrationisisbelow
below the
the
Room: (92.2 x 0.072154) + 120.8 NOAEL limit for normally occupied areas.
NOAEL limit for normally occupied areas��
0��1814 x 3 x 276 = 150��2 lbs
Piping Practices
Due to the two phase flow of NOVEC™ 1230, certain
piping practices must be adhered to. Mainly that the flow
split must be on the horizontal plane. There are two types
of tee used in SAPPHIRE® systems, a through /side tee
and a bull tee. Both have limitations on the minimum and
maximum allowable flow splits which are detailed on
page 43.
It should also be noted that system designers shall
allow a minimum of 10 times the nominal pipe diameter
around tee splits before any change of direction.
System designers should aim to design as far as
possible balanced pipe networks, use minimum lengths
of pipe, use minimum numbers of elbows, maximize pipe
volume before the 1st tee and incorporate similar pipe run
lengths to nozzles.
46
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 4 - FLOW CALCULATIONS DATE: 2010-03
Introduction
In determining the quantity of NOVEC™ 1230 required Example:
for a particular application, it is important to assess the
hazard area correctly. The following information will
need to be determined as discussed in Section 3. Hazard Volume: 280 m³
Room Temperature: 20 °C
1. Hazard Volume.
Agent Concentration: 5.3%*
2. Minimum Room Temperature. Flooding Factor: 0.77861
3. Hazard Type.
Quantity of NOVEC™ 1230 required: 0.77861 x 280
4. Height above sea-level. =218.0 kg
The Hazard volume can be determined by calculating
the room volume and deducting any impermeable
volumes that may be contained within the area. The Note: Specific Vapour Volume data shown in Tables
anticipated temperature of the Hazard area will normally 10 and 11 are experimentally derived values and the
be advised by the client. The agent concentration is specific vapour volume equation (S) has a correlation
dependant upon the type of hazard being protected and coefficient of 0.99. However the equation can be
hazard altitude. The quantity of NOVEC™ 1230 can used to give a close approximation of required agent
be calculated by using the flooding factors (Table 10. quantities.
metric / 11. imperial) or by using the formula (NOVEC™
1230 Equation Calculations) and then multiplying by the
altitude correction factor (Table 12).
48
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 4 - FLOW CALCULATIONS DATE: 2010-03
where S = 0.0664 + 0.000274 t (°C) • 0.5 kg/l (31.2 lbs/ft³) - 1.2 kg/l (74.9 lbs/ft³) fill
density.
or (S= 0.9856 + 0.002441 t °F) • Max. liquid arrival time imbalance of 1.0 seconds.
• Maximum liquid run out time of 2.0 seconds.
t = Design Temperature in Hazard Area °C (°F)
• Maximum nozzle height is 4.3 m (14.0 ft)
C = Required NOVEC™ 1230 Design Conc. (% by
• Minimum of 10% agent in pipe before first tee.
volume) at Design Temperature (t).
• Maximum of 20 nozzles per system.
• Maximum of 10 enclosures per system.
Engineered Systems
• The ratio between the nozzle area and the pipe cross
Engineered systems are based on a Hydraulic Flow
sectional area immediately preceding the nozzle is
Program developed by Hughes Associates Inc. The
limited to a minimum of 0.20 (20%) and a maximum
program predicts the two phase flow of NOVEC™ 1230
of 0.80 (80%).
and nitrogen through a pipe network. Information detailing
the enclosure is entered and the program calculates the (For extended discharge consult the technical support centre)
required pipe sizes, nozzle drill sizes, average nozzle
pressures and discharge time. For further information on
Table 13 : Max. & Min. Flow Rates
the Flow Program, refer to the Hughes Flow Program
User’s Manual.
Pipe Size mm Minimum Maximum
(in) flow rate flow rate
As system design calculations are critical to the kg/s (lb/s) kg/s (lb/s)
success of the extinguishing system, only trained 15(½) 0.454 (1.00) 1.361 (3.00)
personnel are permitted to perform system calculations.
20 (¾) 0.907 (2.00) 2.495 (5.50)
If in the future, other companies wish to use the program,
25 (1) 1.588 (3.50) 3.855 (8.50)
representatives will be required to attend a formal training
session. All system calculations are conducted ‘in house’ 32 (1¼) 2.722 (6.00) 5.67 (12.50)
or by authorised suppliers. 40 (1½) 4.082 (9.00) 9.072 (20.00)
50 (2) 6.35 (14.00) 13.61 (30.00)
NOTE: The calculation method has been designed 65 (2½) 9.072 (20.00) 24.95 (55.00)
for specific types of fittings, pipes, and pipe inside 80 (3) 13.61 (30.00) 44.92 (99.00)
diameter. When these limitations are not maintained, 100 (4) 24.95 (55.00) 56.7 (125.00)
there is a risk that the system will not supply the 125 (5) 40.82 (90.00) 90.72 (200.00)
required quantity of extinguishing agent. 150 (6) 54.43 (120.00) 136.1 (300.00)
Note: This information is for Schedule 40 pipe, and serves as
an estimate only.
Pipe and nozzle sizes need to be confirmed by the
computer programme.
50
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
General Information
All installation shall be carried out by an approved Installation drawings shall be submitted for approval to
contractor with the correct equipment and previous the appropriate authority prior to system installation.
experience of gaseous extinguishing systems. The supplier On receipt, unpack the supplied items and ensure
can provide this service or provide a list of their factory that the components comply with the packing list and
trained installation contractors. Installation instructions installation drawings.
are described under the following main headings, and in
the order of installation. The container weight is checked at the factory prior
to dispatch, and recorded on the label attached to the
• Container Installation
container. If there is any doubt regarding the weight, or
• Piping and Nozzles leakage is suspected, the container should be weighed to
confirm there is no weight loss.To check agent weight in
• Actuation Controls 106, 147, 180 and 343 litre containers with an installed
liquid level measuring device, see Maintenance Section of
• Ancillary Equipment this manual. Determine the container storage temperature
and refer to the Temperature Correction Chart to check the
pressure within the container (see Appendix A).
• Completion Procedures
• Agent Quantities.
• Nozzle Data.
• Container Data.
Actuation Cap
25 mm (1”) Plastic Part No. 12569
DISCHARGE
HOSE OR
PIPE PIPE
UNION
COUPLING SINGLE
TANK
ADAPTOR
ELBOW
ELBOW
52
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
750 mm
300 mm
1. Fix the two back vertical channels to the wall at the CHECK VALVE
appropriate height using suitable anchor type bolts LOCKING GRUB
(see table 17). SWIVEL NUT SCREW
54
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
1) Abbreviations:
BW - butt welded / CD - cold drawn / HFS - hot finished seamless / CFS - cold finished seamless / S - seamless
2) Where schedule numbers are given, these determine the minimum wall thickness in accordance with BS1600.
Where the specified pipe is not obtainable in these dimensions, the next larger thickness should be used.
56
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
Note: Cautionary information indicating the calculation Table 22: Hanger Spacing
method has been investigated for specific types of fittings,
type of pipe and pipe inside diameter. Also that when the Pipe Maximum Spacing
specified limitations are not maintained there is the risk Size mm m
that the system will not supply the required quantity of
15 (1/2”) 1.5 (5 ft)
extinguishing agent. The Flow Program contains pipe
20 (3/4”) 1.8 (6 ft)
and fittings options together with Equivalent Length
25 (1”) 2.1 (7 ft)
information for UK / US pipe and fittings.
32 (1¼”) 2.4 (8 ft)
Pipe Hangers 40 (1½”) 2.7 (9 ft)
50 (2”) 3.4 (11 ft)
Pipe hangers must be spaced according to the size of pipe 65 (2½”) 3.5 (11.5 ft)
(see table 22).
80 (3”) 3.7 (12 ft)
100 (4”) 4.3 (14 ft)
• Hangers must be placed within 300 mm (12”) of the 150 (6”) 5.2 (17 ft)
discharge nozzle (see Figure 51).
(Reference: BS IS0 14520-1:2000)
• Hangers must be placed between elbows that are
more than 600 mm (24”) apart (see Figure 52).
• Hangers must be fixed to a structure capable of
supporting the Pipework.
Nozzles
All nozzles require the installation of a dirt trap comprising
1 side tee, 2 nipples, and 1 pipe cap. Fit the nozzle to the
nipple on the dirt trap and check the nozzle orifice to
ensure proper orientation. Dirt trap lengths should be no
more than 10 times nominal pipe diameter.
A false ceiling comprising loose tiles must have the
tiles retained within a 2 m (6.5 ft) radius of the nozzle,
to prevent movement during system discharge. Nozzles
should be installed a maximum of 300 mm (12”) below
the ceiling.
58
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
Actuation Installation
The method of actuation depends on the system Figure 54 - Actuator Non-Fire Position
configuration and any specific contract requirements and
can be broken down as follows:
• Single Container Actuation
• Multiple Container Actuation
If no other actuators are to be installed ensure that the Figure 55 - Electrical Actuator Location
protective cap on the actuator is retained in position.
The electrical signal from the detection and/or control The electrical signal from the detection and/or control
equipment is connected in accordance with the wiring equipment is connected in accordance with the wiring
diagram detailed in Figure 56 when all other installations diagram detailed in Figure 57 when all other installations
have been completed. have been completed.
Figure 56 - Electrical Actuator Wiring Diagram - Suppression Figure 57 - Electrical Actuator Wiring Diagram - Bridge
Diode Rectifier
- + 1
2 1
2
3
PLUG CONNECTOR
This Electrical Actuator is fitted with a suppression diode This Electrical Actuator is fitted with a bridge rectifier
in parallel to the coil as indicated. Connect +ve from as indicated. Connect +ve from control panel to either
control panel to terminal 1 and -ve from control panel terminal 1 or 2 with the reverse for the -ve supply from
to terminal 2, on plug connector. End of line monitoring control panel, on plug connector. End of line monitoring
device (if required) to be fitted on site. device (if required) to be fitted on site.
Before this system is put into operation, the removable Before this system is put into operation, the removable
solenoid can be checked by firing the system. To do this, solenoid can be checked by firing the system. To do this,
REMOVE THE ELECTRICAL ACTUATOR from the REMOVE THE ELECTRICAL ACTUATOR from the
valve. With power to the actuator, the pin should be firmly valve. With power to the actuator, the pin should be firmly
in the down position. Ensure that the electrical actuator is in the down position. Ensure that the electrical actuator is
reset prior to fitting on to the conatainer valve. FAILURE reset prior to fitting on to the conatainer valve. FAILURE
TO RESET THE ACTUATOR WILL RESULT IN THE TO RESET THE ACTUATOR WILL RESULT IN THE
POTENTIALLY HAZARDOUS DISCHARGE OF THE POTENTIALLY HAZARDOUS DISCHARGE OF THE
CONTAINER. CONTAINER.
60
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
Figure 58 - Manual Actuator Non-Fire Position Figure 60 - Pneumatic Actuator Non-Fire Position
62
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
Ancillary Equipment
Discharge Pressure Switch
On single container installations the pressure switch should On multi-container installations the pressure switch should
be located close to the valve assembly and connected with be located close to the last slave container and connected
a pilot hose from the pressure port outlet on the valve to by pilot hose to the tee connector on the pneumatic actuator
the connector on the pressure switch (see Figure 63). (see Figure 64).
Figure 63 - Discharge Pressure Switch Installation (Single Figure 64 - Discharge Pressure Switch Installation (Multiple
Container System) Container System)
Connectionstoto
Connections Pyrochem
Pyrochem PCR-100
PCR-100
• Pre
PreChecks
Checksand Visual
and Inspections.
Visual Inspections��
Connections to Pyrochem PCR-100 • Pre Checks and Visual Inspections��
NOTE: Program output circuit 4 as a supervisory input circuit. •• Final
FinalConnections.
Connections��
NOTE:
See Program
Pyrochem output manual
PCR-100 circuit 4for
as programming
a supervisory input
details. • Final Connections��
NOTE: Program outputPCR-100
circuit 4 manual
as a supervisory input •• Hand
circuit. See Pyrochem for programming
circuit. See Pyrochem PCR-100 manual for programming Handover
overProcedures.
Procedures��
details. • Hand over Procedures��
details.
CAUTION:
Low Pressure Switch CAUTION:
47 K EOL The completion of the installation system,
CAUTION:
Resistor commissioning
The completion tests
of and hand-over may
the installation occur
system,
The completion
before the area is of the installation
ready use. In system,
for hand-over themay
event
commissioning tests and
ofcommissioning
delay before
occur between tests and hand-over
thehand-over and for
area is ready
may
the use��
risk area
In
occur
being before the
available area is ready
for protection, thenforthe
use�� In
system
the event of delay between hand-over and
the event
must be areaof delay
left between
in a ‘safe’ hand-over
condition to and
avoid
the risk being available for protection,
the risk
accidental area being
discharge. available
The for protection,
then the system must be system
left in amust
'safe'only
con-be
Connections
Connectionstoto
Pyrochem FMM-101
Pyrochem or FMM-1
FMM-101 or Module thenoperative
made the system must
once thebe leftfor
area in aprotection
'safe' con-has
Connections to Pyrochem FMM-101 or dition to avoid accidental discharge�� The
FMM-1 Module dition
been to avoid
completed accidental
and be discharge��
is operational. The
FMM-1 Module system must only made operative once
system must only be made operative once
the area for protection has been completed
NOTE: Program the addressable module as supervisory. See the area for protection has been completed
NOTE: Program the addressable module as supervisory. and is operational��
Pyrochem
NOTE: PCR-400
Program themanual for programming
addressable module details.
as supervisory. and is operational��
See Pyrochem PCR-400 manual for programming details.
See Pyrochem PCR-400 manual for programming details.
64
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 5 - INSTALLATION DATE: 2010-03
• All pipe connections must be tight. • Verify all pneumatic actuator pistons are in the fired
position.
• Nozzles to be the proper type, correctly placed, and
properly orientated. • Check for leaks. There must be less than 10% loss in
pressure within 1 minute).
• Check model and weight markings on container
nameplates to verify that correct containers and • Provide 34 bar (493 psi) pressure to the master
charges have been installed as required. container valve pilot hose.
• Verify that all warning and instruction plates are • Verify all pneumatic actuator pistons are in the fired
mounted where required. position.
• Check for leaks. There must be less than 10% loss in
Electrical Checks pressure within 1 minute).
The electrical systems may include interfaces with many Before replacing the pneumatic actuators, ensure that
other systems for alarm, indication, actuation, shutdown, all pistons are fully reset (see Figure 60). After reinstalling
etc. For complex electrical systems the scope and operating the pneumatic actuators, reconnect the pilot hose to the
requirements will be described in other documents. master container valve adaptor (see Figure 62).
Electrical checks are given below for a basic system using
electrical actuation of the container valve; Final Connections
Hand-over Procedures
The entire system shall be thoroughly inspected to make
sure that it is complete and that all tests required during
installation have been properly carried out. In addition, the
following items are particularly important.
1. A container should be refilled or replaced when it
shows a loss in agent quantity of more than 5% or a
loss in pressure (adjusted for temperature) of more
than 10%. (Operating pressure of unit at 25 bar at
21 °C, 360 psi at 70 °F). Refer to Appendix A for
pressures at other container temperatures.
2. Check container weight information label against
system requirement. If there is any doubt or if there
has been a loss of weight, then the container must be
weighed.
3. Make sure the system is armed and the actuating
systems are operational.
66
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 6 - INTEGRITY TESTING DATE: 2010-03
Preparation. All doors outside the area that are required to The gauges are zeroed by taking them to full scale
be open for the test are wedged open with suitable notices deflection and holding for approximately ten seconds,
posted to advise personnel. Where voids are protected by after which the gauges are gently tapped and zeroed.
NOVEC™ 1230, tiles are removed to ensure a uniform
air flow. Enclosure Evaluation
The enclosure is put in the state it would be in prior Static Pressure Measurements. With the door fan
to a discharge, e.g. ventilation system shut down, dampers equipment fully installed and set up, but with all openings
closed, etc. closed, a measurement of any pressure difference
between the enclosure and the relief area is made. If the
Note. Equipment within the enclosure that does not affect
measurement is unduly high its causes are ascertained and
the integrity may be left running even if it will be shut
if possible permanently reduced or eliminated.
down in the event of a discharge, preventing unnecessary
disruption and inconvenience. Total Enclosure Leakage Method. Using an adequate
range on one fan, or a number of fans, a pressure difference
Ventilation. Air conditioning and/or forced ventilation
of between column pressure and column pressure plus
can affect the system performance and the quantity of
30% is created. The pressure difference, and the air flow
agent required.
required to generate this, is then recorded. This is carried
out for both pressurisation and depressurisation modes.
(i) Self-contained air conditioning unit The total equivalent leakage area and the predicted
retention time is calculated.
A self-contained unit conditions the air within the
enclosure and does not rely on a fresh air supply, or draw Suspended Ceiling Leakage Neutralisation Method.
air from other parts of the building. If the hazard has a This procedure is used to improve the accuracy of the
self-contained unit and it is located within the area without predicted retention time where a reasonable air-tight
an outside air supply, no additional agent is required. It is ceiling exists, whether or not the ceiling is protected with
not necessary to shut down the unit prior to a discharge NOVEC™ 1230.
as the mixing effect is beneficial. However if the air-
conditioning unit is left running, a depleting concentration Note. Leak paths through the ceiling may be temporarily
rather than a descending NOVEC™ 1230/air interface sealed.
will be formed. The concentration will be depleted due to
leakage. Therefore overgassing the enclosure may help to The volumes above and below the false ceiling are
obtain the required ten minute retention time at minimum depressurised to the same extent but using separate fans.
concentration. This is confirmed by using cool chemical smoke to check
that no air is flowing through the false ceiling.
(ii) Central air conditioning unit
Readings of the pressure difference between the
A central air conditioning unit relies on air from outside enclosure, relief area, and the air flow through the fan(s)
and is often linked by ducts to other parts of the building, used to depressurise the room and false ceiling are made,
therefore, prior to a discharge, the unit should be shut down and then the procedure is repeated in the pressurisation
and/or dampers operated to close the ducts. Sufficient time mode. The below ceiling leakage area is then calculated
must be allowed for the plant to stop, or dampers to close, and used in conjunction with the ELA to predict a revised
before discharge occurs. retention time.
68
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 6 - INTEGRITY TESTING DATE: 2010-03
---------------------------------------------------------- ----------------------------------------------------------
RETROTEC DISCHARGE SIMULATION VER. HA5.1 FAN TEST READINGS & DATA
RETENTION TIME PREDICTION MODEL
---------------------------------------------------------- ----------------------------------------------------------
----------------------------------------------------------
Equivalent Leakage Area (ELA m²): 0.0050
Hole in Ceiling (m²): 0.0025 RM= 1.639 PC= 13.7
Hole in Floor (BCLA m²): 0.0025 A T= 0.003 ALL- 0.002
This Room PASSES the Test as the Predicted Retention Time is 10.1 minutes for C3= 3.019 C 4= 0.000
the agent/air interface to drop below the minimum protected height. GD= 7.260 K 1- 1.8850
AR= 9.374 T= 605.679
Witnessed By: PA= 13.7 FA= 0.500
X_ ___________________________________ CF= 1.000 K 2= 0.0046
EL= 0.000 TD = 20.000
Software Conforms to 1992 NFPA 12A/2001 TCD Room Integrity Procedure.
Page 2 Of 2 Licensed to: MARCRON SAFETY SYSTEMS (UK) LIMITED
Maximum Allowable ELA (m²): 0.005
Registration # : 207
Interface Height @ 10 minutes: 2.903
----------------------------------------------------------
Page 1 Of 2 Licensed to: MARCRON SAFETY SYSTEMS (UK) LIMITED
Registration # : 207
70
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 7 - SYSTEM OPERATION DATE: 2010-03
72
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 8 - MAINTENANCE DATE: 2010-03
Introduction
This section provides user inspection and maintenance Weekly Check of System Components
guidance for SAPPHIRE® Engineered Systems. A
Make a visual inspection of the system components,
log book will be provided to record all inspections,
distribution piping and nozzles. Check the immediate
maintenance, measurements and actions taken. The
vicinity of all equipment to ensure that no accidental
continued capability for effective performance of an
damage or tampering has occurred.
SAPPHIRE® Total Flooding Fire Suppression System
depends on fully adequate maintenance procedures, with
Weekly General Check
periodic testing. Reference NFPA 2001 section 7-1 to 7-6
and ISO 14520-1. Inspect the hazard area, access routes, container storage
area, floor voids and areas above suspended ceilings
User’s Programme of Inspection to ensure housekeeping is good and that no refuse has
The installer should provide the user with an inspection accumulated. Ensure that access to the system container
programme for the system and components. The assemblies and local remote controls is unobstructed.
programme shall include instructions on the action to be
taken in respect of faults. The user’s inspection programme Monthly Check of Notices
is intended to detect faults at an early stage to allow
Inspect system and protected spaces to ensure that warning
rectification before the system may have to operate.
signs, safety precautions and operating instructions are
A suitable programme is as follows:- posted and clearly visible.
Inspect the hazard area against the original layout to Check that all personnel who may have to operate
ensure that there have been no changes that might affect the equipment or system are properly trained and are
the proper performance of the fire protection system. authorized to do so, and in particular that new employees
Changes might include: have been instructed in its use.
• Contents of area.
• Use of area.
• Openings in area.
• Floor/ceiling voids.
• Partitioning.
Test and service all electrical detection and alarm systems • Record weight of container on record tag.
as recommended in NFPA as well as any other standard • Replace containers in bracketing and remove anti-
accepted to the authority having jurisdiction. recoil caps.
6 Monthly Container Check • Reconnect discharge piping / discharge hoses and all
control heads, pressure actuators, pressure actuation
Externally inspect containers for signs of damage or pipe or tubing and flexible electric connectors.
unauthorised modifications. Check container labels are
securely fixed and legible. Check container brackets and Using the Liquid Level Measuring Device
fittings.
The liquid level measuring device is used to determine
6 Monthly Contents Check the liquid NOVEC™ 1230 level in 106, 147, 180 and
343 litre container assemblies. During a maintenance
Examine the container pressure gauge reading and refer to examination, the measuring device will enable a service
the temperature correction chart. If the container pressure representative to convert a linear measurement to agent
corrected to temperature is below 10% of the stated weight in order to determine if the tank has any weight loss.
pressure it must be replaced or recharged. This measurement is accomplished without removing the
NOVEC™ 1230 tank from the fire suppression system.
Verification of the content of NOVEC™ 1230 in
the containers may be achieved through either liquid
level detection or container weighing. If containers show
a extinguishant loss of more than 5% or a pressure loss
(adjusted for temperature) of more than 10%, the container
should be refilled or replaced.
74
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 8 - MAINTENANCE DATE: 2010-03
READ LEVEL
HERE
MEASURING
TAPE
Notice. The container module temperature can be 6. Compare the weight from the table to the weight of
determined by measuring the ambient temperature at charge stamped on the container nameplate. If the
the container location. The container must be stored measurement shows a net weight loss of more than
at this temperature for at least 24 hours to obtain an 5%, the tank must be weighed to verify the liquid level
accurate liquid level reading. measurement. If the weight loss still exceeds 5% of the
weight of charge, the container requires recharging.
Example: Using the Container Weight Conversion 6 Monthly Control Valve & Actuator Check
Table
Check all manual and pneumatic actuators for free
movement of the piston. Replace whole unit where
A semi-annual weight check is being performed on
appropriate. Check all control valves for correct manual
a 180 litre (450lb) SAPPHIRE® tank filled with 137 kg
function and automatic valves additionally, for correct
(301 lbs.) of NOVEC™ 1230. The temperature of the
automatic function.
container is 16 °C (60 °F). The liquid level measuring
device reading is 52.0 cm. (20½ in.) 6 Monthly Pipe Network Check
Find the 52.0 cm (20½ in.) line on the left side of
Externally check pipework to determine its conditions.
the 180 litre (450lb) container table and read horizontally
Replace or pressure test and repair as necessary pipework
across the table to the 16 °C (60 °F) column. Then, by
showing corrosion or mechanical damage.
reading the weight of NOVEC™ 1230 at the level/
temperature column intersection, it is determined that the
6 Monthly Nozzle Check
weight of NOVEC™ 1230 is 130.7 kg. (288.2 lbs.)
Inspect nozzles for dust and debris, clean out where
To determine if this is within the 5% weight loss
necessary.
tolerance, multiply the weight of charge (taken from the
container nameplate) by 0.95 to determine the minimum
6 Monthly Enclosure Check
weight of NOVEC™ 1230 required in this container:
137 kg x 0.95 = 130 kg (301 lb. x 0.95 = 286 lb.) Carry out a full visual check of the enclosure for integrity
and confirm the dimensions and the configuration of the
Because the measured weight of NOVEC™ 1230, hazard are as the original drawings or previous visit. If
130.7 kg, (299.2 lb.) is more than the minimum required drawings are not available and this is the first visit then
NOVEC™ 1230 weight of 130 kg (286 lb.), the weight of dimensions should be taken and passed to the engineering
NOVEC™ 1230 is within the 5% weight loss tolerance. department together with the quantity of agent to enable a
calculation to be carried out to ensure the correct quantity
If the measured weight had been less than the 5% of gas has been used.
weight loss tolerance, the container should be weighted to
verify the liquid level measurement. If the weight loss still 12 Monthly Hose Check
exceeds 5% of the weight of charge, the container must All system hoses should be examined for damage. If visual
be recharged. examination shows any deficiency, the hose shall
be replaced.
Personnel Training
76
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 8 - MAINTENANCE DATE: 2010-03
b. For master/slave system complete the following iv) Ensure actuator is reset before refitting, using the
steps to check the slave actuation system:- reset tool provided.
1. Disconnect pneumatic valve actuators from the d. For master/slave system, remove the appropriate
slave container valves. port plug and reconnect the pilot actuation line to
the slave port on the back of the master valve.
2. Disconnect the pilot loop from the master container
valve and install the appropriate plug. e. Reset pressure switches after the test has been
completed.
3. Introduce 4 bar (58 psi) pressure into the pilot
actuation line to the pneumatic actuators. (1) An approved distributor is carrying out the
maintenance on the detection system.
4. Check that the pistons in the pneumatic valve
actuators have fully operated. (2) If the servicing of the detection system is being
carried out at the same time as the mechanical
5. Check for leaks. There must be less than 10% loss service by another nominated body.
in pressure within 1 minute).
Specialised Maintenance Duties
6. Vent pressure in the pilot actuation line and re-set
all of the actuators.
Container Hydrostatic Pressure Testing
7. Introduce 34 bar (493 psi) pressure into the pilot
In countries where NFPA 2001 applies the following
actuation line to the pneumatic actuators.
criteria are used for hydrostatic pressure testing :
8. Check that the pistons in the pneumatic valve Containers only need hydrostatic pressure testing after
actuators have fully operated. discharge. Systems under local jurisdiction may have
other rules of hydrostatic pressure testing, please follow
9. Check for leaks. There must be less than 10% loss these rules.
in pressure within 1 minute).
Finally
10. Vent pressure in the pilot actuation line and re-set Carry out a final visual inspection of the system and
all of the actuators. the protected area to ensure that all equipment has been
reinstalled and reconnected properly. Ensure that any
c. To check the electrical actuation system (for single associated control/indication panel is displaying normal
container systems only electrical actuators are operation. Complete the site log book, recording work
fitted): carried out and parts used. Inform the responsible person
that the work is complete and that the system is back
i) Remove electrical actuators from valve on-line.
assembles.
1. Check that the container is empty. 11. If valve has been removed from neck ring, replace
neck seal : (This is to pre-dome burst disc if required)
2. Remove valve, syphon tube grub screw and syphon
tube from container. Siphon tube for 343 litre container 25 mm (1”) valve Neck O-ring (Part No. 12853)
stays in the container collar, (This operation only needs
50 mm (2”) valve Neck O-ring (Part No. 12855)
to be undertaken if the burst disc needs replacing).
80 mm (3”) valve- Neck O-ring (Part No.570294)
3. Unscrew top cap by removing locking grub screw
located behind safety cap chain fixing screw. Once that 12. The outlet adapter may require to be replaced, if this
has been taken off the schrader should also be removed. is so the outlet will need to be removed and threads
(80 mm (3”) valve does not use a grub screw, external cleaned. Apply Loctite 648 to the thread of the new
type valve cap). outlet adapter and screw fully home. Re-fit anti-recoil
cap.
All O-ring seals must be lubricated using PTFE silicone
grease. In the event that the pressure gauge or pressure switch
needs to be replaced:
4. O-ring seal for the top cap has to be removed :
13. Remove to reveal grub screw. Check the grub screw
25 mm (1”) valve O-ring (Part No.12869)
setting, this should be initially tighten fully and then
50 mm (2”) valve O-ring (Part No.17035) loosen by 1/2 a turn.
80 mm (3”) valve O-ring (Part No.570295) 14. Apply PTFE tape to replacement components and
refit.
5. Remove shuttle from valve body and dispose.
15. Remove 53.4 bar (775 psi) burst disc assy if damaged
6. Locate replacement suttle assembly : from burst disc port and replace with a new assy.
25 mm (1”) valve shuttle (Part No. 16855). 25 mm (1”) and 50 mm (2”) valve:
50 mm (2”) valve shuttle(Part No.19490). M18 assembly, torque to 20 Nm, (Part No. 20915)
78
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 9 - RECHARGING PROCEDURE DATE: 2010-03
PLASTIC CAP
SCHRADER VALVE
TOP CAP
SHUTTLE O-RING
SHUTTLE
BOTTOM CAP
1/8” PLUG
PRESSURE SWITCH
SCHRADER VALVE
CAP
SHUTTLE O-RING
SHUTTLE
BOTTOM CAP
CHAIN SCREW
BODY O-RING
ANTI-RECOIL
CAP
GAUGE
INSERT
PRESSURE SWITCH
PRESSURE GAUGE SCHRADER
VALVE
COLLAR O-RING
80
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION:
14A-11T
ISSUE No. 02
HYGOOD
SECTION 9 - RECHARGING PROCEDURE DATE: 2010-03
Section 9 - RECHARGING PROCEDURE
82
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 9 - RECHARGING PROCEDURE DATE: 2010-03
16. Remove fill hose and filling adapter, leak test the
outlet and attach anti-recoil cap. Note : When leak testing
outlet with spray, do not look directly into port, examine
quickly from an angle.)
17. Reset scales and note down gross weight.
18. Make certain all safety caps are in place, schrader
protection cap Part No. 12569.
19. Attach label to container stating the following
information. Job number, Customer, Project, Container
size, Fill weight, Gross weight, Date filled, Type of
agent.
20. Place container in bonded area for leak monitoring
for at least 24 hours prior to dispatch.
21. After 24 hours a Leak Test on the container is
conducted - see section on Container / valve assy leakage
test.
22. Insert fill information on to container label.
Note: Filling can only be carried out by UL approved fill stations using containers assembled and tested by the O.E.M.
84
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 9 - RECHARGING PROCEDURE DATE: 2010-03
1. After 24 hours standing, the valve pressure gauge Details of the procedure and equipment required are
should be checked for pressure loss (refer to temperature available from the Original Equipment Manufacturer
correction chart to adjust for temperature change). The (O.E.M) on request.
container and valve assembly should then be checked for
leakage using the Halotek leak detector unit.
Container Leak Test
2. Testing should take place in an area free of
NOVEC™ 1230 contamination. Carefully probe the container/valve assembly at all probes
and openings. Ensure that the probe is not brought into
3. Take the Halotek unit & calibration gas and within direct contact with any objects as this can lead to spurious
the NOVEC™ 1230 free environment, calibrate the unit. results and ensure that the dwell time of the probe is
sufficiently long (more than 5 seconds) to ensure any
4. Adjust the Halotek leak detector to gain a steady
leak is detected. Any significant and repeatable increase
audible pulse, in free air, of about 2 to 4 pulses per
of the audible pulse rate should be taken as an indication
second.
of a leak and the container and valve assembly should be
5. Conduct a stability check by leaving the Halotek unit rejected.
for approximately 3 minutes in a clean air environment. If
Once the leakage source has been rectified, the
the pulse rate is observed to stay within the range of 2 to 4
container and valve assembly should be subjected to a
pulses per second, proceed to the repeatability check.
further leak test using the Halotek unit.
If the stability check is inconclusive, repeat
stability check in an alternative clean environment. If
stability problems persist, contact R&D department for
instruction.
6. The leak standard of 0.13 oz/year should be
conditioned to a temperature of 20 °C +/-5 °C (68 °F ±
9 °F) for at least 24 hours.
7. Conduct a calibration repeatability test.
8. Remove the cap from the leak standard, screw the
calibration nozzle into the outlet of the bottle and open the
hand valve fully.
9. Place the Halotek probe into the calibration nozzle.
Within 5 seconds the pulse rate should start to increase
and be a continuous tone within 15 seconds.
10. Remove the probe from the nozzle and position
the Halotek unit away from the gas source. The pulse rate
should revert back to the original rate of 2 to 4 pulses per
second within 15 seconds.
11. Repeat test a further two times. If repeatability
test indicates that the unit is functioning within the set
parameters, proceed to the container leak test.
Warranty
Following the commissioning of the system, all equipment
will be covered by the company’s twelve month parts
warranty (excluding parts accidentally or maliciously
damaged by others). For further information, refer to the
company’s ‘Terms and conditions’ document.
86
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
SECTION 11 - APPENDICES DATE: 2010-03
40
35
Pressure (bar, absolute)
30
25
20
15
10
0
-20 0 20 40 60 80 100
88
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX B - HUGHES PROGRAM PRINTOUT DATE: 2010-03
SAPPHIRE®
Calculation Program
Computer printout
Example Calculation
Consolidated Report
9 pages
Consolidated Report
Customer Information
Project Data
Project Name: Computer Addition
Designer: John Doe
Number: ABC-3
Account: 123-45
Location: 2nd Floor
Description: Protection of new computer equipment
Page: 1 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
90
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX B - HUGHES PROGRAM PRINTOUT DATE: 2010-03
clarify
Consolidated Report
Enclosure Information
Enclosure Number: 1
Name: Front Computer Room
Enclosure Temperature...
Minimum: 20.0 C
Maximum: 20.0 C
Maximum Concentration: 4.220 %
Design Concentration... clarify
Adjusted: 4.220 %
Minimum: 4.200 %
Minimum Agent Required: 61.0 kg
Width: 0.00 m
Length: 0.00 m
Height: 0.00 m
Volume: 100.00 cubic m
Non-permeable: 0.00 cubic m
Total Volume: 100.00 cubic m
Adjusted Agent Required: 61.3 kg
Number of Nozzles: 1
Page: 2 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
clarify
Consolidated Report
Enclosure Information
Enclosure Number: 2
Name: Rear Computer Room
Enclosure Temperature...
Minimum: 20.0 C
Maximum: 20.0 C
Maximum Concentration: 4.224 %
Design Concentration...
Adjusted: 4.223 % cl clarify
Minimum: 4.200 %
Minimum Agent Required: 122.0 kg
Width: 0.00 m
Length: 0.00 m
Height: 0.00 m
Volume: 200.00 cubic m
Non-permeable: 0.00 cubic m
Total Volume: 200.00 cubic m
Adjusted Agent Required: 122.7 kg
Number of Nozzles: 2
Page: 3 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
92
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX B - HUGHES PROGRAM PRINTOUT DATE: 2010-03
Consolidated Report
Agent Information
Pipe Network
Part 1 - Pipe Pipe
Description Start End Type Diameter Length Elevation
Main Cyl. X 1 0 1 80 mm 1.47 m 1.47 m
Adaptor 1 2 80 mm 0.13 m 0.00 m
Flex Hose 2 3 80 mm 0.41 m 0.00 m
Pipe 3 4 40T 40 mm 0.50 m 0.00 m
Pipe 4 5 40T 40 mm 2.00 m 2.00 m
Pipe 5 6 40T 40 mm 3.00 m 0.00 m
Pipe 6 7 40T 32 mm 2.00 m 0.00 m
Pipe 7 8 40T 25 mm 2.50 m 0.00 m
Pipe/E1-N1 8 9 40T 25 mm 0.50 m -0.50 m
Pipe 7 10 40T 25 mm 2.00 m 0.00 m
Page: 4 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Consolidated Report
Part 1 - Pipe Pipe
Description Start End Type Diameter Length Elevation
Pipe/E2-N2 10 11 40T 25 mm 0.50 m -0.50 m
Pipe 6 12 40T 32 mm 2.50 m 0.00 m
Pipe/E2-N1 12 13 40T 32 mm 0.50 m -0.50 m
Part 3 - Nozzles
Start End Flow Name Size Type Nozzle Area
0 1 184.0 kg
1 2 184.0 kg
2 3 184.0 kg
3 4 184.0 kg
4 5 184.0 kg
5 6 184.0 kg
6 7 122.6 kg
7 8 61.3 kg
8 9 61.3 kg E1-N1 25 mm 180-BR (NPT) 445.32 square mm
7 10 61.3 kg
10 11 61.3 kg E2-N2 25 mm 180-BR (NPT) 425.75 square mm
Page: 5 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
94
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX B - HUGHES PROGRAM PRINTOUT DATE: 2010-03
Consolidated Report
Part 3 - Nozzles
Start End Flow Name Size Type Nozzle Area
6 12 61.4 kg
12 13 61.4 kg E2-N1 32 mm 180-BR (NPT) 465.33 square mm
Parts Information
'Other' Items:
1 - 80 mm Flexible Discharge Hose (Part: 306.205.006)
1 - 80 mm Flared to NPT Valve Adapter (Part: 309.002.014)
Page: 6 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Consolidated Report
1 - 32 mm
2 - 40 mm
List of Tees:
1 - 32 mm
1 - 40 mm
System Acceptance
Enclosure Number: 2
Enclosure Name: Rear Computer Room
Minimum Design Concentration: 4.200%
Adjusted Design Concentration: 4.223%
Predicted Concentration: 4.230%
Maximum Expected Agent Concentration: 4.230% (At 20.0 C)
Page: 7 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
96
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX B - HUGHES PROGRAM PRINTOUT DATE: 2010-03
Consolidated Report
Drawing View: 1
Drawing View: 5
Page: 8 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Consolidated Report
Drawing View: 9
Page: 9 of 9
Calculation Date/Time: Sunday, June 29, 2008, 12:18:46 PM
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
98
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX C - NOVEC™ 1230 DATA SHEET DATE: 2010-03
(MSDS)
(5 PAGES)
2 HAZARDS IDENTIFICATION
---------------------------------------------
Risk Phrases:
R52/53 Harmful to aquatic organisms. May cause long-term adverse effects in the aquatic environment.
3 COMPOSITION/INFORMATION ON INGREDIENTS
-----------------------------------------------------------------------------
Ingredient name and classification CAS number Percentage
-------------------------------------------------- ------------------- -----------------
1,1,1,2,2,4,5,5,5-Nonafluoro-4-(trifluoromethyl)-3-pentanone 756-13-8 > 99.9
3M Classification: R52/53
4 FIRST-AID MEASURES
-------------------------------------
4.3 Inhalation:
If signs/symptoms develop, remove person to fresh air. If signs/symptoms persist, get medical attention.
4.4 Ingestion:
No need for first aid is anticipated.
100
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX C - NOVEC™ 1230 DATA SHEET DATE: 2010-03
5 FIRE-FIGHTING MEASURES
--------------------------------------------
- Ventilation:
Keep container in a well-ventilated area.
- Incompatible Materials/Conditions:
Store out of direct sunlight.
Store away from heat.
8.3.5 Ingestion:
Not applicable.
102
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX C - NOVEC™ 1230 DATA SHEET DATE: 2010-03
11 TOXICOLOGICAL INFORMATION
-----------------------------------------------------
12 ECOLOGICAL INFORMATION
------------------------------------------------
12.3 Persistence/Biodegradability:
Not determined.
13 DISPOSAL CONSIDERATIONS
-----------------------------------------------
14 TRANSPORT INFORMATION
---------------------------------------------
Transport Details:
Please see the Annex to this document in which all transportation information is given.
15 REGULATORY INFORMATION
-----------------------------------------------
Symbol(s):
None.
Risk Phrases:
R52/53 Harmful to aquatic organisms. May cause long-term adverse effects in the aquatic environment.
Safety Phrases:
S61 Avoid release to the environment. Refer to special instructions/safety data sheets.
Disclosable Ingredients:
1,1,1,2,2,4,5,5,5-Nonafluoro-4-(Trifluoromethyl)-3-Pentanone.
16 OTHER INFORMATION
--------------------------------------
The information on this Safety Data Sheet is based on our experience and is correct to the best of our knowledge at the date of publication, but we do not accept
any liability for any loss, damage or injury resulting from its use (except as required by law). The information may not be valid for any use not referred to in this Data
Sheet or use of the product in combination with other materials. For these reasons, it is important that customers carry out their own test to satisfy themselves as to
the suitability of the product for their own intended applications.
104
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
(16 PAGES)
106
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
108
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
110
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
112
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
114
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
116
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
118
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
120
EQUIPMENT: Novec™ 1230 (UL/FM)
PUBLICATION: 14A-11T
ISSUE No. 02
APPENDIX D - LIQUID LEVEL INDICATOR CHARTS DATE: 2010-03
122