UPY-B31040-01MO (B) Owner Manual Binder - 1
UPY-B31040-01MO (B) Owner Manual Binder - 1
Owner Manual
(1 of 1)
Yard/Customer : Astilleros Balenciaga
Hull no. : NB452-NB453
Customer reference :
Order No. : 53032- & 53033
Document name : UPY-B31040-01MO
Revision :B
Author : TB
Date First Issue : 06.07.2015
Comments : As built Hull 453
Introduction to Owner Manual 1
PRODUCT, Layout 7
PRODUCT, Wiring 8
10
PRODUCT, Software
11
Document Summary
The Operator Manual describes issue for operation and maintenance of the system delivered by
Ulmatec Pyro.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-D11001-04SX (A) Pyro Energy Management System - Introduction To Owner Manual.Docx Page 1 of 4
CONTENTS
1 Abbreviations .................................................................................................................................. 3
2 Ulmatec Pyro ................................................................................................................................... 3
2.1 Office Address ......................................................................................................................... 3
2.2 Mail & Web Address ................................................................................................................ 3
2.3 Telephone & Fax ...................................................................................................................... 3
2.4 VAT Identification Number ...................................................................................................... 3
3 Order Spare Parts ............................................................................................................................ 4
3.1 Project Specific Information .................................................................................................... 4
3.2 Component Specific Information ............................................................................................ 4
3.3 Spare Part List .......................................................................................................................... 4
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-D11001-04SX (A) Pyro Energy Management System - Introduction To Owner Manual.Docx Page 2 of 4
1 Abbreviations
UPY Ulmatec Pyro AS
2 Ulmatec Pyro
Ulmatec Pyro AS
Gamlem
6280 Søvik
NORWAY
Mail: pyro@ulmatec.no
Web: www.ulmatec.no
Telephone : +47 70 20 98 70
Fax : +47 70 20 98 90
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-D11001-04SX (A) Pyro Energy Management System - Introduction To Owner Manual.Docx Page 3 of 4
3 Order Spare Parts
Note: Information regarding yard, hull, and project is located on the front page of the Owner Manual or
on a label located on each product.
Information regarding plant and location is located in the cable/piping diagram and on the label
located on each product.
Note: information regarding Component and Production Number is located on the unit label.
For some product you will also find enclosed a recommended spare part list.
The list includes recommendation for 2 and 5 years spare parts.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-D11001-04SX (A) Pyro Energy Management System - Introduction To Owner Manual.Docx Page 4 of 4
Index divider: Section 2 N
Index divider: Section 3 N
Index divider: Section 5 N
Certificate No:
A-14229
File No:
TYPE APPROVAL CERTIFICATE 855.40
Job Id:
262.1-001812-6
This is to certify:
That the Automatic Oil Fired Water Heater
Issued to
Ulmatec Pyro AS
SØVIK, Norway
Application :
The approval is for system design principle only.
This Certificate is subject to terms and conditions overleaf. Any significant change in design or construction may render this Certificate invalid.
The validity date relates to the Type Approval Certificate and not to the approval of equipment/systems installed.
Product description
Type: PYRO Automatic Oil fired and electric Water Heater
Approval conditions
The following documentation of the actual application is to be submitted to the shipyard in each case:
- Reference to this Type Approval Certificate
The Type Approval covers hardware and software listed under Product description.
As long as the units are covered by the Type Approval, a product certificate according to Pt.4 Ch.9 Sec.1
A 202 will not be required. Correct configuration and set up for each delivery to be tested during
commissioning after installation.
Data sheets:
Landis & Gyr data sheet 7153 E Oil burner control LAL Series.
Alternative wiring diagrams may be accepted provided they include the following:
- Burner controller type LOA24, LAL 1.25 or LAL 2.25.
- Alarm and shut off of fuel oil supply by means of normally closed contacts, upon
following conditions:
- Low water level
- Flame and ignition failure
- Water temperature high
- Potential free common alarm output contacts to main alarm system.
Periodical assessment
The scope of the periodical assessment is to verify that the conditions stipulated for the type are
complied with, and that no alterations are made to the product design or choice of systems, software
versions, components and/or materials.
The main elements of the assessment are:
· Ensure that type approved documentation is available
· Inspection of factory samples, selected at random from the production line (where practicable)
· Review of production and inspection routines, including test records from product sample tests and
control routines
· Ensuring that systems, software versions, components and/or materials used comply with type
approved documents and/or referenced system, software, component and material specifications
· Review of possible changes in design of systems, software versions, components, materials and/or
performance, and make sure that such changes do not affect the type approval given
· Ensuring traceability between manufacturer’s product type marking and the type approval certificate
Periodical assessment is to be performed at least every second year and at renewal of this certificate.
END OF CERTIFICATE
Revision History
Revision: Description: Date: Sign:
A First Issue 06.02.2013 ASK
B New standard software for FFH 11.04.2013 TS
C Changed pump control setting 19.09.2013 TS
D Added configuration for LNG burner 04.10.2013 TS
E Added Alarm list 10.12.2013 TS
F Added instructions for Program download from USB-Memory 29.01.2014 TS
G Added operator guidelines for FFH without PLC 26.02.2014 ASK
H Changed setting for pumps 01.04.2014 TS
I Changed instructions for pumps 07.04.2014 TS
J Changed pump control, and safety function 28.08.2014 TS
K Safety functions to separate alarms 17.10.2014 TS
L ModBus control & Recipes 02.03.2014 TS
Document Summary
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 1 of 22
CONTENTS
1 ABBREVIATIONS ........................................................................................................................................ 3
2 OPERATOR GUIDELINES, PLC CONTROL SYSTEM ......................................................................... 3
2.1 MAIN MENU .............................................................................................................................................. 3
2.1.1 SUB-MENU DESCRIPTION ............................................................................................................. 4
2.1.2 MENU OVERVIEW............................................................................................................................ 5
2.2 OPERATING MENU .................................................................................................................................. 6
2.2.1 INFORMATION DISPLAYED ........................................................................................................... 6
2.2.2 FUEL FIRED HEATER, ON – OFF .................................................................................................. 7
2.2.3 PUMPS MAN - AUTO ....................................................................................................................... 7
2.2.4 LOW-TEMP MODE ........................................................................................................................... 7
2.2.5 HIGH-TEMP MODE ......................................................................................................................... 7
2.2.6 ALARM............................................................................................................................................... 8
2.2.7 HELP ................................................................................................................................................. 8
2.2.8 MAIN .................................................................................................................................................. 8
2.3 SETTING MENU ........................................................................................................................................ 9
2.3.1 SETTING LOW / HIGH TEMP MODE.............................................................................................. 9
2.3.2 SETTING PUMPS .............................................................................................................................. 9
2.3.3 SETTING FOR PUMP PRESSURE ALARMS AND AUTOMATIC START/STOP ............................ 9
2.3.1 EXPORT USER RECIPES TO USB MEMORY STICK .....................................................................10
2.3.2 IMPORT USER RECIPES FROM USB MEMORY STICK ...............................................................10
2.3.3 ENABLE / DISABLE MODBUS REMOTE CONTROL ....................................................................11
2.3.4 RESET TO DEFAULT SETTING ......................................................................................................11
2.3.5 HELP ................................................................................................................................................11
2.3.6 MAIN .................................................................................................................................................11
2.4 OPERATIONAL INFO MENU..................................................................................................................12
2.4.1 RUN HOURS INDICATION .............................................................................................................12
2.4.2 FUEL CONSUMPTION FOR FFH ..................................................................................................12
2.4.3 RESET RUN HOURS ........................................................................................................................12
2.4.4 HELP ................................................................................................................................................12
2.4.5 MAIN .................................................................................................................................................12
2.5 SERVICE MENU .......................................................................................................................................13
2.5.1 CONFIGURATION ...........................................................................................................................13
2.5.2 SERVICE SETTINGS ........................................................................................................................14
2.5.3 EXPORT FAT CONFIGURATION AND SERVICE SETTINGS TO USB MEMORY STICK ...........15
2.5.4 EXPORT HAT CONFIGURATION AND SERVICE SETTINGS TO USB MEMORY STICK ...........15
2.5.5 IMPORT FAT CONFIGURATION AND SERVICE SETTINGS FROM USB MEMORY STICK .....15
2.5.6 IMPORT HAT CONFIGURATION AND SERVICE SETTINGS FROM USB MEMORY STICK .....15
2.6 EXAMPLE TYPICAL MENU OPERATION. ...........................................................................................16
2.6.1 STARTING THE FUEL BURNER .....................................................................................................16
2.7 DOWNLOAD NEW SOFTWARE FROM USB MEMORY STICK .........................................................17
3 OPERATOR GUIDELINES, RELAY CONTROL SYSTEM ..................................................................18
3.1 LAYOUT CONTROL CABINET. .............................................................................................................18
3.2 SWITCHES IN THE FRONT OF THE CONTROL CABINET. ................................................................18
4 MAINTENANCE AND PERIODICAL TESTING ....................................................................................20
4.1 WEEKLY MAINTENANCE .....................................................................................................................20
4.2 MONTHLY MAINTENANCE ..................................................................................................................20
4.3 MAINTENANCE EVERY 6 MONTH.......................................................................................................20
4.4 MAINTENANCE EVERY YEAR .............................................................................................................21
5 RECOMMENDED SPARE PARTS ............................................................................................................22
5.1 FUEL BURNER .........................................................................................................................................22
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 2 of 22
5.2 SENSOR & SAFETY VALVES.................................................................................................................22
5.3 CONTROL CABINET ...............................................................................................................................22
1 ABBREVIATIONS
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 3 of 22
2.1.1 SUB-MENU DESCRIPTION
• OPERATING MENU
Allow the operator to control the fuel burner, pumps, electric heating and view the alarm list.
• SETTING MENU
Allow the operator to adjust set-point for the burner, pumps, electric heating.
o Service Settings
Settings at comissioning
These settings are done at Harbour Acceptance Test (HAT).
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 4 of 22
2.1.2 MENU OVERVIEW
MAIN MENU OPERATING MENU ALARMS
SETTING MENU
SERVICE CONFIGURATION
SERVICE SETTING
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 5 of 22
2.2 OPERATING MENU
-
Allow the user to set the Fuel Fired Heater Off and On.
- :
Allow the user to set the pumps in Manual or Auto.
- Pressure indication:
Water pressure is indicated on each side of the circulation pump.
- Low temp mode temperature setting and actual temperature are displayed.
Grey = Off, Green = On.
- High temp mode temperature setting and actual temperature are displayed.
Grey = Off, Green = On.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 6 of 22
2.2.2 FUEL FIRED HEATER, ON – OFF
ON
Burner operates according to the temperature settings specified in the selected TEMP MODE.
The heating elements will operate according to the temperature settings specified in the selected TEMP
MODE.
OFF
All functions is set to OFF
AUTO
Pumps starts according to pump pressure, and other pump settings.
The fuel fired heater will operate at the setting specified in the LOW-TEMP MODE
The fuel fired heater will operate at the setting specified in the HIGH-TEMP MODE
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 7 of 22
2.2.6 ALARM
Safety Stop alarm is triggered when, emergency stop, low water level, burner open or high
temperature is activated. Some fuel fired heaters has only a combined alarm for the safety
function. The safety stop alarms will set the FFH to OFF, and the pumps to MAN with all pumps
in stop position.
After a reset of this alarm, the FFH must be manually set back to ON, and the pumps to AUTO.
2.2.7 HELP
2.2.8 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 8 of 22
2.3 SETTING MENU
Electric heating sections has a default hysteresis at +/- 1 °C (Can be adjusted by service)
Stop heating temperature is valid for both nozzle.
- Select recipe you want to save, or make a new by typing in recipe name.
- All settings will be saved in a report and a recipe in the USB memory stick.
- Put the memory stick with the new recipe into the back of the panel (see picture 1)
- The recipe you want to replace, must be removed from the internal memory in the panel.
- Then the recipe can be imported from the memory stick by pressing the import button.
- After importing recipe, you must load the recipe from the internal memory in the panel to your system.
NOTE: only deleted recipes will be updated with the ones on the memory stick.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 10 of 22
2.3.3 ENABLE / DISABLE MODBUS REMOTE CONTROL
Press button to enable/disable MODBUS remote control
When enabled, the button is yellow, and these values can be controlled from MODBUS
- Setpoints
- Heater ON/OFF
- Temperature mode HIGH/LOW
When remote control is enabled, the text “Remote control enabled. To disable, go to settings” is shown on
the local control panel.
2.3.5 HELP
2.3.6 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 11 of 22
2.4 OPERATIONAL INFO MENU
2.4.4 HELP
2.4.5 MAIN
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 12 of 22
2.5 SERVICE MENU
Service menu is password protected and intended for service operator
2.5.1 CONFIGURATION
2.5.1.2 SENSORS
Set scale for analog sensors
Select order specific sensors
2.5.1.8 HELP
2.5.2.8 HELP
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 14 of 22
2.5.3 EXPORT FAT CONFIGURATION AND SERVICE SETTINGS TO USB
MEMORY STICK
All configurations and service settings will be saved to a USB memory stick connected at the back of the
panel. (picture 1, page 10). Press yes to replace the recipes
- Put the memory stick with the new recipes into the back of the panel. (picture 1, page 10)
- Press delete old recipes
- Press yes to delete
- Press Import, and all deleted recipes will be loaded from the memory stick to the internal memory in the
panel
- Next popup appears
- Press load FAT service setting and configuration recipe
- Put the memory stick with the new recipes into the back of the panel. (picture 1, page 10)
- Press delete old recipes
- Press yes to delete
- Press Import, and all deleted recipes will be loaded from the memory stick to the internal memory in the
panel
- Next popup appears
- Press load HAT service setting and configuration recipe
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 15 of 22
2.6 EXAMPLE TYPICAL MENU OPERATION.
2.6.1 STARTING THE FUEL BURNER
: On the OPERATIING MENU
Activate LOW-TEMP MODE or HIGH TEMP MODE and oil burner ON.
Set pumps to AUTO
: The burner begins its starting cycle (approx.60.sec.).
: The burner fan starts the burning chamber preparing period (30.sec.). The air flap will open.
: The ignition transformer is activated. The fuel oil solenoid valve opens, and the flame occurs.
: The photo-cell activates and surveys the flame.
: On two step burners, nozzle 2 will open after 15sec. The air flap will open to nozzle 2 set-point.
: The water heater will now operate automatically on the thermostat, normally adjusted to 65°C for
LOW-TEMP MODE and 90°C for HIGH TEMP MODE.
The temperature for nozzle 2 should be adjusted approx. 5°C lower than nozzle 1.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 16 of 22
2.7 DOWNLOAD NEW SOFTWARE FROM USB MEMORY STICK
Program updates can be downloaded to the PLC and the Control Panel from an USB Memory Stick.
Load files sent from Ulmatec Pyro to an USB Memory Stick.
These files must be on the memory stick. The file fcu.fx may have a different name (*.fx)
Put the memory stick into the USB-port at the back of the control panel, and disconnect the power.
Reconnect the power, and the menus below will appear.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 17 of 22
3 OPERATOR GUIDELINES, RELAY CONTROL SYSTEM
- COMMON ALARM
Alarm for High Temp, Low water level, Ignition/Flame Failure and Motor circuit breaker circulation
pump
- BURNER OFF/AUTO:
To stop the fuel burner this switch shall be set to position OFF.
To start the fuel burner the switch shall be set to position AUTO.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 18 of 22
- CIRCULATION PUMP
The system is normally delivered with two circulation pump.
Each pump has a separate switch for start/stop of the pump.
In most cases only one of the pumps has to run to cover the energy requirement.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 19 of 22
4 MAINTENANCE AND PERIODICAL TESTING
4.1 WEEKLY MAINTENANCE
Checkpoints:
Description Personal requirement
Functionality test, Circulation pump Owner
Functionality test, Hot water circulation pump Owner
Functionality test, Fuel transfer pump Owner
Functionality test, Electric heating Owner
Functionality test, Fuel heating Owner
Functionality test, Fuel burner. Owner
Functionality test, Verify reading from exhaust gas temperature sensor Owner
Functionality test, Verify reading from fuel flow meter. Owner
Inspection, The water level shall be checked. If necessary, refill water. Owner
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 20 of 22
4.4 MAINTENANCE EVERY YEAR
Checkpoints:
Description Personal requirement
Replace the fuel nozzle Ulmatec service engineer
Safety function, Flame control when starting Ulmatec service engineer
Safety function, Flame control when running Ulmatec service engineer
Safety function, Safety temperature switch Ulmatec service engineer
Safety function, Water Low level switch Ulmatec service engineer
Safety function, Safety pressure valve Ulmatec service engineer
Failure modes, power supply Ulmatec service engineer
Failure modes, Interfaces Ulmatec service engineer
Failure modes, Protection circuits Ulmatec service engineer
Inspection, Expansion tank (air pressure) Ulmatec service engineer
Inspection, Circulation pump Ulmatec service engineer
Inspection, Hot water circulation pump Ulmatec service engineer
Inspection, Fuel transfer pump Ulmatec service engineer
Inspection, Electric heating Ulmatec service engineer
Inspection, Fuel heating Ulmatec service engineer
Inspection, Fuel burner. Ulmatec service engineer
Inspection, Check through the inspection glass when the burner is running. Ulmatec service engineer
If it is coke residue in combustion chamber the unit need to be cleaned.
Inspection, Check ceramic plates on the burner plate Ulmatec service engineer
Control system, SW updates Ulmatec service engineer
Control system, Verify system setting Ulmatec service engineer
Control system, Electrical Installation Ulmatec service engineer
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 21 of 22
5 RECOMMENDED SPARE PARTS
5.1 FUEL BURNER
Checkpoints:
Description Number of units
Photocell 1 pc
Ignition transformer. 1 pc
Nozzle 1 pc of each type
Ignition cable 1 pc
Ignition electrode 1 pc
Burner motor 1 pc
Baffle plate 1 pc
Oil pump 1 pc
Oil tube (oil pump) 1 pc
Servo motor (2 x nozzle) 1 pc
Air fan 1 pc
Coil for solenoid valve 2 pc
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PO (L) Fuel Fired Heater_Operators Guidelines.Docx Page 22 of 22
Index divider: Section 11
Document Type: Document Name:
PRODUCT-
Modbus Description UPY-G00001-01PA
Document Title: Date First Issue: Revision:
Fuel Fired Heater 23.01.2014
Author:
Arne Skotte H
Revision History
Revision: Description: Date: Sign:
D Changed high temp low level to Safety Stop Alarm 29.09.2014 TS
Includes High temp, Low Level, Open Burner, and Emergency
Stop
E Changed Modbus description 07.10.2014 TS
F Added three alarms, and common alarm 24.10.2014 TS
G Changed configuration of order 23.02.2015 TS
H Added read/write information 02.03.2015 TS
Configurable station number
Added address for remote control enabled, address 11701 ??
Added GUIEnableRemoteControl, GUIFFHControl, and
GUITempMode
Modbus Description
Configuration of order
Optional
- Configuration of actual order is found in project drawing UPY-Bxxxxx-11OT
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G00001-01PA (H) Modbus Description_Front Page.Docx Page 1 of 1
UPY-G00000-01PA Fuel Fired Heater, Modbus Description
Description Variable name Type ModBusAdress Read ModBusAdress Write Value Comment
Alarm Safety Stop (HT/LL/Open Burner/E.stop) AlarmHighTempLowLevel Bit 11501 - NO -
Alarm ignition failure AlarmIgnitionFailure Bit 11502 - NO -
Alarm high diff pressure pump unit AlarmHighDiffPressure Bit 11503 - NO -
Alarm low diff pressure pump unit AlarmLowDiffPressure Bit 11504 - NO -
Alarm PLC AlarmPLC Bit 11505 - NC -
Alarm circulation pump no. 1 AlarmCircPump1 Bit 11506 - NO -
Alarm circulation pump no. 2 AlarmCircPump2 Bit 11507 - NO -
Alarm circulation pump no. 3 AlarmCircPump3 Bit 11508 - NO -
Alarm electric heating element section no. 1 AlarmElHeatSection1 Bit 11509 - NO -
Alarm electric heating element section no. 2 AlarmElHeatSection2 Bit 11510 - NO -
Alarm electric heating element section no. 3 AlarmElHeatSection3 Bit 11511 - NO -
Alarm electric heating element section no. 4 AlarmElHeatSection4 Bit 11512 - NO -
Alarm sanitary pump AlarmSanitaryPump Bit 11513 - NO -
Alarm fuel oil transfer pump AlarmTransferPump Bit 11514 - NO -
Warning standby pump started WarningStandByPumpStarted Bit 11515 - NO -
Alarm emergency stop AlarmEmergencyStop Bit 11516 - NO -
Sensor alarm water temperature FFH AlarmSensorWaterTemp Bit 11517 - NO -
Sensor alarm exhaust temperature AlarmSensorExhaustTemp Bit 11518 - NO -
Sensor alarm pressure into pump unit AlarmSensorPressureIn Bit 11519 - NO -
Sensor alarm pressure out from pump unit AlarmSensorPressureOut Bit 11520 - NO -
Alarm burner motor AlarmBurnerMotor Bit 11521 - NO -
Alarm low water level AlarmLowWaterLevel Bit 11522 - NO -
Alarm safety tempertaure switch AlarmSafetyTempSwitch Bit 11523 - NO -
Alarm LNG heater AlarmLNGHeater Bit 11524 - NC -
Alarm Common AlarmCommon Bit 11525 - NO -
Run signal circulation pump no. 1 CircPumpOn1 Bit 11601 - 0-1 0 when running
Run signal circulation pump no. 2 CircPumpOn2 Bit 11602 - 0-1 0 when running
Run signal circulation pump no. 3 CircPumpOn3 Bit 11603 - 0-1 0 when running
Run signal electric heating section no. 1 ElheatingOn1 Bit 11604 - 0-1 0 when running
Run signal electric heating section no. 2 ElheatingOn2 Bit 11605 - 0-1 0 when running
Run signal electric heating section no. 3 ElheatingOn3 Bit 11606 - 0-1 0 when running
Run signal electric heating section no. 4 ElheatingOn4 Bit 11607 - 0-1 0 when running
Run signal sanitary water pump SanitaryPumpOn Bit 11608 - 0-1 0 when running
Run signal fuel oil transfer pump TransferPumpOn Bit 11609 - 0-1 0 when running
Run signal fuel hater (standby) FuelHeaterOn Bit 11610 - 0-1 0 when running
Run signal burner motor BurnerMotorOn Bit 11611 - 0-1 0 when running
Setpoint alarm high diff pressure pump unit SPAlarmMaxDiffPressure INT 47531 47531 0-10bar Scaling: 0,01
Setpoint alarm low diff pressure pump unit SPAlarmMinDiffPressure INT 47532 47532 0-10bar Scaling: 0,01
Setpoint runtime extra pumps SPPumpTimer INT 47533 47533 0-10h -
Time between check if extra pump is necessary GUIStatusTimeCheckPriority INT 47534 47534 0-120s -
Setpoint high el. Heating section no. 1 SPElHeaterHighTemp1 INT 47535 47535 0-100 -
Setpoint high el. Heating section no. 2 SPElHeaterHighTemp2 INT 47536 47536 0-100 -
Setpoint high el. Heating section no. 3 SPElHeaterHighTemp3 INT 47537 47537 0-100 -
Setpoint high el. Heating section no. 4 SPElHeaterHighTemp4 INT 47538 47538 0-100 -
Setpoint low el. Heating section no. 1 SPElHeaterlowTemp1 INT 47539 47539 0-100 -
Setpoint low el. Heating section no. 2 SPElHeaterlowTemp2 INT 47540 47540 0-100 -
Setpoint low el. Heating section no. 3 SPElHeaterlowTemp3 INT 47541 47541 0-100 -
Setpoint low el. Heating section no. 4 SPElHeaterlowTemp4 INT 47542 47542 0-100 -
Setpoint high start nozzle no. 1 SPStartNozzle1HighTemp INT 47543 47543 0-100 -
Setpoint low start nozzle no. 1 SPStartNozzle1LowTemp INT 47544 47544 0-100 -
Setpoint high start nozzle no. 2 SPStartNozzle2HighTemp INT 47545 47545 0-100 -
Setpoint low start nozzle no. 2 SPStartNozzle2LowTemp INT 47546 47546 0-100 -
Setpoint high stop burner SPStopBurnerHightemp INT 47547 47547 0-100 -
Setpoint low stop burner SPStopBurnerLowtemp INT 47548 47548 0-100 -
Setpoint hysteresis el-heating SPHysteresisElHeating INT 47549 47549 0-100 -
Total run hours circulation pump no. 1 TotTimeCircPump1 DINT 47811 - 0-> -
Total run hours circulation pump no. 2 TotTimeCircPump2 DINT 47813 - 0-> -
Total run hours circulation pump no. 3 TotTimeCircPump3 DINT 47815 - 0-> -
Total run hours sanitary pump TotTimeSanitaryPump DINT 47817 - 0-> -
Total run hours fuel oil transfer pump TotTimeTransferPump DINT 47819 - 0-> -
Total run hours FFH TotTimeFFH DINT 47821 - 0-> -
Run hours after reset circulation pump no. 1 TimeCircPump1 DINT 47823 - 0-> -
Run hours after reset circulation pump no. 2 TimeCircPump2 DINT 47825 - 0-> -
Run hours after reset circulation pump no. 3 TimeCircPump3 DINT 47827 - 0-> -
Run hours after reset sanitary pump TimeSanitaryPump DINT 47829 - 0-> -
Run hours after reset fuel oil transfer pump TimeTransferPump DINT 47831 - 0-> -
Run hours after reset FFH TimeFFH DINT 47833 - 0-> -
Temp mode selected GUITempMode Bit 1801 1801 0-1 0=Low - 1=High
Fuel Fired Heater On/ OFF GUIFFHControl Bit 1802 1802 0-1 Heater ON/OFF
Index divider: Section 12
Document Type: Document Name:
PRODUCT –
Harbour Acceptance Test (HAT) UPY-G01001-01PH
Document Title: Date First Issue: Revision:
HAT, Heat Generator – Fuel Fired Heater 12.03.2014
Author: -
Arne Skotte
Project No:
…………………………………………………………………………….
Yard:
…………………………………………………………………………….
Hull Number:
…………………………………………………………………………….
Customer Reference:
…………………………………………………………………………….
Location:
…………………………………………………………………………….
Test Date:
…………………………………………………………………………….
Ulmatec Pyro AS
Service Engineer: …………………………………………………………………………….
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 1 of 13
CONTENTS
2 ABBREVIATIONS ...................................................................................................................................... 3
3 SAFETY ....................................................................................................................................................... 3
4 GENERAL INFORMATION, SYSTEM HAT ......................................................................................... 4
4.1 PURPOSE SYSTEM HAT ............................................................................................................................. 4
4.2 TEST REQUIREMENT................................................................................................................................... 4
4.3 HAT COMMISSION TEST............................................................................................................................ 4
4.4 TEST CONFIGURATION ............................................................................................................................... 4
4.5 SPECIAL TOOLS ......................................................................................................................................... 4
5 PRE-COMMISSION ................................................................................................................................... 5
5.1 ARRANGEMENT DRAWING......................................................................................................................... 5
5.2 SYSTEM INSTALLATION ............................................................................................................................. 5
5.3 MOUNTING FUEL FIRED HEATER ............................................................................................................... 5
5.4 TECHNICAL INSTALLATION FUEL FIRED HEATER. ..................................................................................... 5
5.5 CIRCULATION PUMP (LOCAL UNIT) ........................................................................................................... 6
5.6 EXPANSION TANK...................................................................................................................................... 6
5.7 CONTROL SYSTEM, FUEL FIRED HEATER .................................................................................................. 7
5.7.1 Visual Inspection:............................................................................................................................ 7
5.7.2 Software Updates: ........................................................................................................................... 7
5.7.3 Supply Burner Motor and Circulation Pump .................................................................................. 7
5.7.4 Electric Heating Coil ...................................................................................................................... 7
5.7.5 Circulating pump............................................................................................................................. 7
5.7.6 Sanitary hot water circulation pump ............................................................................................... 7
5.7.7 Fuel transfer pump .......................................................................................................................... 8
5.7.8 Fuel Heating.................................................................................................................................... 8
5.7.9 Burner motor ................................................................................................................................... 8
5.7.10 System Operation, HMI pump control ........................................................................................ 8
5.7.11 System Operation, HMI heating element control ....................................................................... 8
5.7.12 System Operation, System Setting............................................................................................... 8
5.7.13 Operation, Fuel Burner .............................................................................................................. 8
5.7.14 System Operation – Start Oil Burner......................................................................................... 9
5.7.15 System Operation – Setting Menu............................................................................................... 9
5.7.16 System Operation – Pump Menu .............................................................................................. 10
5.8 ORDER SOFTWARE BACKUP ..................................................................................................................... 10
5.9 COMMENTS AND SIGNATURE: .................................................................................................................. 10
6 HARBOUR ACCEPTANCE TEST (HAT) ............................................................................................. 11
6.1 SAFETY FUNCTION – TEMPERATURE SWITCH .......................................................................................... 11
6.2 SAFETY FUNCTION – FLAME CONTROL WHEN STARTING ....................................................................... 11
6.3 FAILURE MODES – CONTROL SYSTEM .................................................................................................... 11
6.4 SAFETY FUNCTION – FLAME CONTROL WHEN RUNNING ....................................................................... 12
6.5 SAFETY FUNCTION – WATER LOW LEVEL SAFETY SWITCH ..................................................................... 12
6.6 COMMENTS AND SIGNATURE: .................................................................................................................. 12
7 PUNCH LIST ............................................................................................................................................. 13
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 2 of 13
2 Abbreviations
HAT Harbour Acceptance Test
FAT Factory Acceptance Test
UPY Ulmatec Pyro AS
DNV Det Norske Veritas
HMI Human Machine Interface
S/N Serial Number
3 Safety
Ensure that all personnel involved in the commission of the equipment have the required knowledge regarding:
- System architecture.
- Product included in the scope of supply.
- Commission procedure.
- Local safety rules.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 3 of 13
4 General information, System HAT
The HAT (quayside) test shall be verified by the Ulmatec service engineer and the customer for each test:
If a test is not valid it shall be marked “NA” (Not Applicable).
Any other comments shall be marked in the “Comment Field”.
If a comment requires any correction it shall be noted on the “punch list”.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 4 of 13
5 Pre-Commission
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 5 of 13
5.5 Circulation pump (Local unit)
Checkpoints:
Description Verified √,
Not Applicable NA
Specify location:
----------------------------------------------------------------------------
IMPORTANT Check that all valves are open and the pump is not running dry.
Check for visual damage.
Mounted so that service is possible.
Unit fasten to the foundation according to specification.
Bled the pump before operating.
Observe that there is no leakage from the unit or the piping.
Verify that the pump runs in the correct direction.
Verify the pressure before the pump is correct : Bar
------------------
Verify the pressure after the pump is correct : Bar
------------------
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 6 of 13
5.8 Control System, Fuel Fired Heater
5.8.1 Visual Inspection:
Checkpoints:
Description Verified √,
Not Applicable NA
Check for visual damage.
Mounted so that service is possible.
Cabinet earth screw earthed connected to ship chassis.
Cable mounted according to specification.
Cable screen earthed according to the cable diagram.
Cabinet mounted according to environmental specification
(temperature, humidity and IP protection)
Power supply according to specification and from specified source.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 7 of 13
5.8.7 Fuel transfer pump
Checkpoints:
Description Verified √,
Not Applicable NA
Operate the pump and observe that the rotation direction is correct.
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 8 of 13
5.8.14 System Operation – Start Oil Burner
Checkpoints:
Description Verified √,
Not Applicable NA
Start the Fuel Burner from the HMI,
“Fuel burning” Auto -and “High Temp Mode” On.
Burner start cycle for approx. 60 second.
Burner fan starts for burning chamber ventilation (approx. 25 sec.)
Ignition transformer is activated, fuel oil solenoid open and flame occurs.
Can be observed from the inspecting opening.
The photo cell activates and surveys the flame.
On two-step burner nozzle 2 will open after 15 sec. if thermostat nozzle 2 is closed.
Air flap will open to nozzle 2 set point.
The fuel fired heater will operate automatically on the thermostat
setting for “High Temp Mode”.
Change the temperature to “Low Temp Mode” and observe that the fuel fired heater
operate automatically on the thermostat setting for “Low Temp Mode”.
Use an external pressure gauge to measure the nozzle pressure: Bar
_________
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 9 of 13
5.8.16 System Operation – Pump Menu
Checkpoints:
Description Verified √,
Not Applicable NA
For each circulation pump adjust following:
- Start requirement, differential pressure in Bar.
See order documentation (lowest pressure pump curve): ________Bar
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
Signature:
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 10 of 13
6 HARBOUR ACCEPTANCE TEST (HAT)
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 11 of 13
6.4 Safety Function – Flame Control when running
Checkpoints:
Description Verified √,
Not Applicable NA
The heater plant is running at normal working temperature.
Withdraw the photocell from socket (false flame failure).
Photocell shall be kept in dark.
The power supply to the burner shall be cut after a time delay of 5 sec.
The burner tries one restart after a time delay of approx. 2 min
The "FLAME FAILURE", lights up.
External and internal alarm is issued.
Note: The electric heating element shall still be on.
Refit the photocell in socket and fuel fired heater is restarted by pushing
“Reset Burner Control”.
Alternatively the water level pressure switch could be checked with a pressure pump
on the test- flange connection.
External alarm is issued.
Remove the water low level alarm level to normal value, and the heater restarts.
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
………………………………………………………………………………………………………………….
Signature:
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345
UPY-G01001-01PH (-) Fuel Fired Heater - HAT.Docx Page 12 of 13
7 PUNCH LIST
All action that required correction shall be noted in the punch list
Punch Punch Description:
Number
10
ULMATEC PYRO AS
Gamlem, 6280 Søvik, Norway
Tel.: +47 70 20 98 70 Pyro@ulmatec.no www.ulmatec.no Reg. No. 966 300 345