Prodotto: Single Phase Automatic
Fuel Pump Control
1. Working modes ........................................................................................................ 3
2. Technical specifications ......................................................................................... 4
3. Dimensions .............................................................................................................. 5
4. Connections ............................................................................................................. 6

ii USER MANUAL
 OFF: all off (used with external remote switch)

 MAN: the fuel level is maintained constant at MAX STOP

 Activation: pump command is activated with 2 seconds delay (t1) from fuel
solenoid activation.

 Deactivation: fuel solenoid command is deactivated with 5 seconds delay


(t2) from pump command.

 AUTO: the fuel level is maintained between MIN START and MAX STOP (the pump
starts when the level is lower than MIN. START and stops at MAX STOP level)

 Activation: pump command is activated with 2 seconds delay (t1) from fuel
solenoid activation.

 Deactivation: fuel solenoid command is deactivated with 5 seconds delay


(t2) from pump command.

USER MANUAL 3
BLOCKS: MAX ALARM: stops the pump both in manual and automatic modes

CHARACTERISTICS: - Supply voltage 12 or 24VDC


- Fuel pump engine max voltage 250Vac
- Max engine current 10A at 250Vac (6.3 A with default fuse)
- Safety solenoid voltage 12 or 24V (same that supply voltage)
- Max solenoid current 3A

PROTECTIONS: - 5x20mm glass fuse as protection for the pump engine


- Self-restoring integrated fuse as protection for the solenoid
- Protection against the supply voltage inversion

CONNECTIONS: J1 connector – power supply 12 or 24V


J2 connector – supply 230Vac
J3 connector – connections to level contacts
J4 connector – level contacts outputs (to others devices)
J5 connector – fuel pump engine
J6 connector – remote command switch
J7 connector – security fuel solenoid

NOTES: In order to use a remote switch, the internal switch must left in OFF position.
The supply inputs for the security solenoid command are pin X (positive 12-24V) and
20 (ground 0V) of the connector J1: connect the X pin to a positive which is present
only when the engine is running and with a proper current rate.

SIGNALLING LEDS: ON PUMP: fuel pump running


MAX ALARM: level higher than the maximum (with block)
MAX STOP: maximum level (pump stop)
MIN. START: minimum level (pump start)
RESERVE: fuel reserve
EMPTY: fuel end

4 USER MANUAL
USER MANUAL 5
6 USER MANUAL
This document is owned by SICES s.r.l.. All rights reserved. SICES s.r.l. reserves the right to modify
this document without prior notice.
SICES has made any effort to ensure that the information herein provide are correct; in any case
SICES does not assume any liability for the use these information.
The disclosure by any means of this document to third parties is not allowed.