Professional Documents
Culture Documents
Cbi 2803648 A
Cbi 2803648 A
Output Current In
Output Voltage (Vn) / Nominal Power (W) 36 / 48 VDC / 270W (jumper selection)
7 A @36VDC / 5A @48VDC
Efficiency (at 50% of rated current) ≥ 91 %
Turn-On delay after applying input voltage 1.5 sec. (max)
Start up with Strong Load (capacitive load) Yes, Unlimited
Dissipation power load max 30 W
PROTECTION
Short-circuit protection Yes
Over Load protection Yes
Over Voltage Output protection Yes (typ. 90 VDC)
LOAD Over Temperature protection Yes
For the latest on Altech Power Supply specifications please visit www.altechcorp.com/power.
162
CBI2803648A
DC UPS
Jumper for Battery Type Selection
The Altech DC-UPS system is built to optimize power
management. The available power is automatically allocated Open
between load and battery, supplying power to the load is the first Lead
1 2 3 4 6 7
priority. For high inrush applications the charging power will Sealed
reroute automatically to the load. In this case the maximum Lead Low
available current on the load output is two times the value of the 1 2 3 4 6 7 1 2 3 4 5 6 7 8 9 10
Sealed – + – +
device rated current.
Lead High
1 2 3 4 6 7 ADJ. MAINS LOW BATTERY
The Battery Care concept based on algorithms that achieve rapid Gel
OR OR BATTERY
BACKUP REPLACEMENT
Environment
Insulation voltage (IN/OUT) 3000 VAC
Insulation voltage (input / ground) 1605 VAC
Insulation voltage (Output / ground) 500 VAC
Protection Class (EN/IEC 60529) IP20
Pollution Degree Environment 2
Connection TB, Screw Terminal 2.5 mm² (24-14 AWG)
Protection class (Ground Connected) Class I
Dimensions (WxHxD) 115x115x135 mm
2.95x4.53x5.32 in
Weight (approx.) 0.85 kg (1.9 Lbs)
Altech Corp.® • 35 Royal Road • Flemington, NJ 08822-6000 • Phone (908)806-9400 • FAX (908)806-9490
163