THE GENERAL NOTES ON THIS DRAWING AND THE DETAILS SHOWN ON THE DRGS INDEXED

APPLY UNLESS NOTED OTHERWISE ON THE DESIGN DRAWINGS

GENERAL MAIN ROADS DRAWINGS


G1. ALL STANDARD DETAILS MUST BE CHECKED BY A CIVIL M1. THESE STANDARD DRAWINGS ARE TO BE READ IN CONJUNCTION
ENGINEER TO DETERMINE THEIR CAPACITIES AND ADEQUACIES WITH THE FOLLOWING MAIN ROADS WA DRAWINGS.
FOR SPECIFIC APPLICATIONS.

G2. ALL WORKS SHALL BE UNDERTAKEN IN ACCORDANCE WITH 9531-1002 HAZARD MARKERS - SINGLE BOARD HAZARD MARKERS
THE LATEST EDITIONS OF CURRENT STANDARDS AND THEIR
AMENDMENTS, SPECIFICATIONS AND DRAWINGS AS SPECIFIED. 201131-0012 WARNING SIGN - ROAD TRAIN ENTERING 250m

G3. DISCREPANCIES WITHIN THE DOCUMENTATION SHALL BE 9331-0376 KERB TYPES


REFERRED TO THE COMPANY REPRESENTATIVE FOR
CLARIFICATION BEFORE PROCEEDING. 9331-0377 KERB TREATMENTS

G4. PRODUCTS EQUIVALENT TO THOSE SPECIFIED ON THE DESIGN 9931-0198 PAVEMENT MARKING - LINE TYPES
DRAWINGS MAY BE USED WITH THE APPROVAL OF THE
COMPANY REPRESENTATIVE. 200431-002 STOP AND GIVE WAY LINES

G5. ALL DIMENSIONS ARE IN METRES. 9548-106 LOCATION DETAILS FOR ONE POST SIGNS

G6. ALL LEVELS ARE IN METRES. 8720-0762 LOCATION DETAILS FOR TWO & THREE POST SIGNS

G7. VERTICAL DATUM IS AUSTRALIAN HEIGHT DATUM (AHD). 9630-1538 STOCK PROOF GRID (PFC & RHS) CONCRETE DETAILS

G8. HORIZONTAL DATUM IS GEOCENTRIC DATUM OF AUSTRALIA (GDA94). 9630-1539 STOCK PROOF GRID (PFC & RHS) REINFORCEMENT DETAILS

G9. ABBREVIATIONS ARE TO AS 1100 EXCEPT; 9630-1540 STOCK PROOF GRID (PFC & RHS) STEEL GRID FABRICATION DETAILS
TOC TOP OF CONCRETE WP WORK POINT
TOK TOP OF KERB C/W COMPLETE WITH 9630-1541 STOCK PROOF GRID (PFC & RHS) SIGNING & FENCING DETAILS
FGL FINISHED GROUND LEVEL U/S UNDERSIDE
IL INVERT LEVEL N/S NEAR SIDE 9630-1538 STOCK PROOF GRID (PFC & RHS) CONCRETE DETAILS
RL REDUCED LEVEL F/S FAR SIDE
EL ELEVATION LEVEL 201131-0064 SMALL BOX CULVERTS - MIN COVER 200mm - CONSTRUCTION DETAILS SHEET 1

EXCAVATION AND FILL 201131-0065 SMALL BOX CULVERTS - MIN COVER 200mm - CONSTRUCTION DETAILS SHEET 2

E1. EXCAVATION AND FOUNDATION PREPARATION SHALL COMPLY 201131-0066 SMALL BOX CULVERTS - MIN COVER 200mm - CONSTRUCTION DETAILS SHEET 3

NARY UNCHECKED
WITH SPECIFICATION HOLD.
201131-0084 SMALL BOX CULVERTS - MIN COVER 500mm - CONSTRUCTION DETAILS SHEET 1
E2. FILL MATERIAL TO BE IN ACCORDANCE WITH SPECIFICATION
HOLD. 201131-0085 SMALL BOX CULVERTS - MIN COVER 500mm - CONSTRUCTION DETAILS SHEET 2

E3. FILL AND PAVEMENTS TO BE COMPACTED IN ACCORDANCE 201131-0086 SMALL BOX CULVERTS - MIN COVER 500mm - CONSTRUCTION DETAILS SHEET 3
WITH SPECIFICATION HOLD.
200131-0061 RCP CULVERT
E4. BATTER SLOPES SHALL COMPLY WITH SPECIFIACTION HOLD.
200131-0062 PIPE DETAILS - BEDDING/BACKFILLING
E5. THE CONTRACTOR SHALL ENSURE THAT THE LOCATIONS OF
ALL EXISTING SERVICES IN THE VICINITY OF THE WORKS 200131-0063 RCP SKEW CULVERT DETAILS

MI
ARE IDENTIFIED PRIOR TO COMMENCEMENT OF EXCAVATIONS.

PRELI
200131-0064 CSP CULVERT DETAILS - SHEET 1

200131-0065 CSP CULVERT DETAILS - SHEET 2

200131-0066 CSP CULVERT DETAILS - SHEET 3

9531-0387 CULVERTS - ROCK PROTECTION


CIVIL STANDARDS DRAWING INDEX

STD-DC-002 ROADS - TYPICAL SECTIONS

STD-DC-003 OPEN DRAINS - TYPICAL SECTIONS


dgn

ON ONLY
ngs\Stdc001.

STD-DC-004 DRAINAGE PIT - DETAILS

STD-DC-005 FLOODWAYS - TYPICAL SECT10NS

NFORMATI
STD-DC-006 FLOODWAYS - MINOR ROADS
\Standard Drawi

STD-DC-007 TRENCHING DETAILS

STD-DC-008 SECURITY FENCING

STD-DC-009 STOCK FENCE DETAILS

I
STD-DC-010 TURKEY NEST TYPICAL PLAN & DETAILS
vi
\Proteus\Proteus Std Drgs\Ci l

DRG NUMBER TITLE

PROTEUS JOB No.


2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
23 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


NOTES AND DRAWING INDEX
email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
42:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-001
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
CL HAUL ROAD

FORMATION WIDTH - REFER DESIGN DRAWINGS

CUT FILL
UNCOMPACTED GENERAL FILL
BASECOURSE AS NOMINATED SUB-BASE AS NOMINATED TYPICAL TO ALL SAFETY BERMS
1.5 ON DESIGN DRAWING ON DESIGN DRAWING
1.5

75

75
2 1 2
2

1.

1.
1 -4% -4% 1 1
1

2
FOR DRAIN INVERT
1
LEVELS REFER TO
SUBGRADE
DESIGN DRAWINGS
GENERAL FILL

EXISTING/STRIPPED SURFACE

TYPICAL SECTION - HAUL ROAD


SCALE 1:100 0.5

UNCOMPACTED GENERAL FILL


CL ACCESS ROAD TYPICAL TO ALL SAFETY BERMS

75
1.5

0.
1
FORMATION WIDTH - REFER DESIGN DRAWINGS 2
1

1800 SHOULDER SEAL WIDTH (WHERE APPLICABLE) SHOULDER

0m
A’
GHT >1.
REFER DESIGN DRAWINGS

L ’
SURFACING AS

REFER DETAI
BASECOURSE AS
NOMINATED ON EXISTING/STRIPPED SURFACE
NOMINATED ON GENERAL FILL

LL HEI
DESIGN DRAWINGS DESIGN DRAWING
CUT
ED
DETAIL A
% SEAL -3% SE

F FI
-3 ALED
-4% UNSEALED -4% UNSEALED FILL -

I
6 UNSEALED ACCESS ROADS
1 FILL HEIGHT GREATER THAN 1.0 METRE

NARY UNCHECKED
300

2H:1V MAXIMUM DESIGN SPEED 60 km/hr


SUBGRADE GENERAL FILL TYPICAL FORMATION
SUB-BASE AS NOMINATED
ON DESIGN DRAWING REFER NOTE 6
EXISTING/STRIPPED SURFACE

NOTES
TYPICAL SECTION - UNKERBED ACCESS ROAD - SEALED
1. THIS DRAWING TO BE READ IN CONJUNCTION WITH
TYPICAL SECTION - UNKERBED ACCESS ROAD - UNSEALED - AS NOTED ALL RELEVANT DRAWINGS AND SPECIFICATIONS.

MI
2. ALL DIMENSIONS ARE METRES UNLESS NOTED

PRELI
OTHERWISE.

3. ALL WORKS TO BE IN ACCORDANCE WITH EARTHWORKS


SPECIFICATIONS HOLD AND ROADWORKS SPECIFICATION
CL ACCESS ROAD
HOLD.

4. REFER TO SPECIFICATION HOLD FOR SEAL TO BE


FORMATION WIDTH - REFER DESIGN DRAWINGS APPLIED TO ROADS AS DESIGNATED ON DESIGN
DRAWINGS.

1.0 MIN. SEAL WIDTH 1.0 MIN.


dgn

ON ONLY
5. PAVEMENT THICKNESS SHALL BE IN ACCORDANCE
WITH AUSTROADS STANDARDS.
ngs\stdc002.

0.2 0.2
6. FOR ROADS WITH DESIGN SPEED GREATER THAN
SURFACING AS 200mm BASECOURSE
MIN MIN 60km/hr EDGE PROTECTION FOR FILLS GREATER
NOMINATED ON UNLESS NOTED OTHERWISE
CUT DESIGN DRAWINGS
THAN 1.0m SHALL COMPLY WITH AUSTROADS

NFORMATI
TABLE DRAIN FILL STANDARDS.
2
REFER DRAIN
\Standard Drawi

1 3% 3%
DESIGN DRAWINGS
MAX -3% -3% MAX LEGEND
6
1
N

GENERAL FILL

I
3 MI

2H:1V
0.

GENERAL FILL BASECOURSE


FOR KERB DETAILS
EXISTING/STRIPPED SURFACE
vil

REFER MRWA STANDARDS SUB-BASE AS NOMINATED


\Proteus\Proteus Std Drgs\Ci

ON DESIGN DRAWING SUB-BASE

TYPICAL SECTION - KERBED ACCESS ROAD GENERAL FILL UNCOMPACTED


2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
50 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


ROADS - TYPICAL SECTIONS
email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
42:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
1:50 UNO A1
STD-DC-002
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
GENERAL NOTES
WINDROW FOR CATCH DRAINS
WINDROW FOR CATCH DRAINS
1. THIS DRAWING SHALL BE READ IN
NATURA CONJUNCTION WITH THE CONTRACT
L SURF
ACE NATURA DRAWINGS AND SPECIFICATIONS.
2 L SURF
ACE
ES
1 2
2
2. ALL DIMENSIONS ARE IN MILLIMETRES
VARI

ES
1 2 1
2
UNLESS NOTED OTHERWISE.

VARI
1 1 2
1
IL AS SHOWN 3. RIPRAP ROCK PROTECTION THAT IS

ES
ON DESIGN DRAWINGS IL AS SHOWN COARSER THAN THE SPECIFIED RIPRAP

VARI

ES
ON DESIGN DRAWINGS CLASS MAY ONLY BE USED WITH THE

VARI
WRITTEN APPROVAL OF THE COMPANY
WIDTH AS SHOWN REPRESENTATIVE. SHOULD THIS APPROVAL
DRAIN TYPE V1 BE GIVEN, THE RIPRAP PROTECTION
ON DESIGN DRAWINGS
THICKNESS SHALL BE CONSISTENT WITH
THE THICKNESS REQUIRED FOR THE
DRAIN TYPE T1 COARSER RIPRAP CLASS:

RIPRAP CLASS MINIMUM THICKNESS

750 LV ACCESS ROADS

750 LV ACCESS ROADS


FACING 500mm
LIGHT 750mm

1750 HAUL ROADS

1750 HAUL ROADS


1/4 TONNE 1000mm
1/2 TONNE 1250mm

EDGE OF FORMATION EDGE OF FORMATION


SAFETY BERM SAFETY BERM LEGEND

PAVEMENT OR HARDSTAND
FORMATION
1.5 1.5

NATURA 2 1 NATURA 2 1
L SURF L SURF GENERAL FILL UNCOMPACTED
ACE 1
ACE 1
ES

ES
2 2
VARI

VARI
1 1 RIPRAP

IL AS SHOWN IL AS SHOWN

ALL DEPTHS

ALL DEPTHS
ON DESIGN DRAWINGS ON DESIGN DRAWINGS
PAVEMENT OR PAVEMENT OR

>1000

>1000
HARDSTAND FORMATION HARDSTAND FORMATION
WIDTH AS SHOWN

ON DESIGN DRAWINGS
DRAIN TYPE V2
DRAIN TYPE T2

NARY UNCHECKED
PAVEMENT OR PAVEMENT OR
HARDSTAND FORMATION HARDSTAND FORMATION

1000 MAX
EDGE OF FORMATION EDGE OF FORMATION
NATURA NATURA
L SURF L SURF
ACE ACE
ES

ES
2 4 2
VARI

VARI
4
1 1 1 1

MI
PRELI
IL AS SHOWN IL AS SHOWN
1000 MAX

ON DESIGN DRAWINGS ON DESIGN DRAWINGS

WIDTH AS SHOWN
DRAIN TYPE V3
ON DESIGN DRAWINGS

RE
FE
DRAIN TYPE T3

R
dgn

NO

ON ONLY
TE
ngs\stdc003.

3
TYPICAL DRAIN PROFILES 1

RIPRAP

NFORMATI
ALL STONEWORK

1000
PLACED LOOSE
\Standard Drawi

FINISHED OR
EXISTING GROUND

I
REFER NOTE 3
GEOTEXTILE (BIDIM A34
1000 OR APPROVED EQUAL)
vi
\Proteus\Proteus Std Drgs\Ci l

TOE PROTECTION - TYPICAL DETAIL


2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
ph +61 8 6313 3200 fax +61 8 6313 3201
OPEN DRAINS - TYPICAL DETAILS
12 PM

email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
43:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-003
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
SEMI MOUNTABLE AND
MOUNTABLE KERB TYPE
S, M & A REFER DRG 1
EXPANSION JOINT TYP TO
LOCAL AUTHORITY STANDARD

KERB WIDTH TO BE MAINTAINED GALV HEAVY DUTY GRATE AND


AROUND SWEEP AND GRADED

PE
LID WITH BICYCLE SAFE GRATING.

NE OF PI
CEMENT MORTAR DOWN TO TOP OF FRAME 50 TYP RAISED 20mm TO SUIT ASPHALTIC
CORNERS ’F’ PAVING

CENTRELI

G’
FI
NISHED PAVEMENT LEVEL


IN THE CASE OF PITS
AT LOW POINTS
DEFLECTORS SHALL
ROAD PAVEMENT
BE OMITTED FROM

FLOW
100 MIN THICKNESS OF
DEFLECTOR SLAB
CEMENT STABILISED
PROVIDE MIN 20mm
ROAD BASE TYP
"MOUNTABLE PROFILES" MORTAR BED TO
CENTRELINE OF LINER SUIT FINAL LEVEL GENERAL COMPACTED FILL UNLESS
"BARRIER PROFILE" AND GRADE UNDER PAVEMENTS WHERE SELECTED
COMPACTED FILL SHALL EXTEND TO
PAVEMENT NOT UNDERSIDE OF PAVEMENT FORMATION
DEPRESSED FOR
BARRIER KERB FINISHED GROUND
OR UNDERSIDE OF
PAVEMENT FORMATION

G’

TYPICAL STEP IRON LOCATION
HAND FORMED CONCRETE
REFER NOTE 2
APRON - THICKNESS TO
GULLY PIT
MATCH DEPTH OF REPOSE OF
EXPANSION JOINT TYP TO
DEFLECTOR SLAB. TYPICAL SECTION MATERIAL OVERLAY ZONE
LOCAL AUTHORITY STANDARD
STEEL FLOAT FINISH DETAILS AS FOR MANHOLE UNO COMPACTED
SELECT FILL

300
BARRIER KERB TYPE BX
REFER DRG 2 SIDE ZONE
COMPACTED

D.
SIDE ENTRY PIT - TYPICAL PLAN

FLOW
SELECT FILL

O.

85

D’
EXTENT OF 300mm

0.


HAUNCH ZONE
ROCK SPALLING
MANHOLE - TYPICAL PLAN COMPACTED
SELECT FILL

100
’H’

D’
36
INSITU KERB PROFILE

0.

INSIDE FACE OF PRECAST AS NOTED HEAVY DUTY CIRCULAR BED ZONE
’B’ ’D’
UNITS SHALL BE FLUSH COVER TO MATCH OUTSIDE COMPACTED
300 PIPE 300 SELECT FILL
NER

DIAMETER OF LINER
2000 MIN
NE OF LI

FACE OF 150 THICK WITH O.D.


FACE OF KERB

HEAVY DUTY UNIVERSAL COMPACTED


UNIVERSAL FRAME 610 DIA REMOVABLE INSERT
FRAME AND COVER SUBGRADE
CENTRELI

NARY UNCHECKED
EDGE OF DEFLECTOR SLAB TYPICAL PIPE BEDDING DETAIL
FRAMES TO BE BEDDED
"E"mm BELOW NORMAL "D" REFERS TO NOMINAL PIPE DIAMETER

50
ON 12 THICK MORTAR
PAVEMENT LEVEL FINISHED
GROUND

VERGE SLOPES BUBBLE UP PIT - TYPICAL PLAN


AS INDICATED 100 NOM MORTAR
CHAMFER TO SUIT
HEAVY DUTY PAVEMENT AS TYPICAL
CONVERSION DETAILED
DEFLECTOR SLAB COMPACTED BACKFILL FOR
100 MINIMUM THICKNESS STANDARD STEPIRONS FULL DEPTH OF LINER

MI
SHALL BE BEDDED DIAMETER A NOM 300mm ROCK SPALLS NON TRAFFICABLE REINFORCED
’C’
ON 12 THICK MORTAR OF CEMENT STABILISED AT 340 CENTRES EXCAVATION
EXTENDING 2000 IN ALL CONCRETE LID WITH GALV

PRELI
ROAD BASE OR MASS
DIRECTIONS FROM EDGE HINGED GRATE
CONCRETE IF APPROVED
OF LID NOTES
DIAMETER A BY SUPERINTENDENT (TYP)
100 NOM MORTAR REFER NOTE 5
CHAMFER TO SUIT 1.REFER SPECIFICATION FOR COMPACTION

200
NOM
TYPICAL REQUIREMENTS.
COMPACTED SUBGRADE
MADE DAMP PRIOR MORTAR INSIDE AND
TO PLACEMENT 230 DIA SOAK HOLE OUTSIDE OF LINER 2.ALL MANHOLES, GULLYS AND SIDE ENTRY
OF SLAB BASE FILLED WITH NOM PITS GREATER THAN 1200mm DEEP SHALL
40mm AGGREGATE BE PROVIDED WITH STANDARD STEP IRONS
dgn

AT 340mm MAXIMUM CENTRES.

ON ONLY
30 NOM TYP
ngs\Stdc004.

450 DEEP SILT TRAP FOR 3.PIPE JOINTS WITHIN 1000mm OF MANHOLE,
MANHOLES ON 900 DIA GULLY OR SIDE ENTRY PIT SHALL BE
150 THICK MASS AND GREATER PIPE ONLY SEALED.
SIDE ENTRY PIT - TYPICAL SECTION CONCRETE BASE

NFORMATI
POURED INSITU 50
4.ALL PIPEWORK CONNECTIONS TO MANHOLE,
MANHOLE - TYPICAL SECTION GULLY OR SIDE ENTRY PIT SHALL BE
\Standard Drawi

’A’ KERB GROUTED TO PROVIDE A SMOOTH INTERNAL


PIPE SIZE ’B’ ’C’ ’D’ ’E’ ’F’ ’G’ ’H’
LINER DIA PROFILE FACE WITH 100 MIN THICKNESS OF CONCRETE
PIPE SIZE
’A’
A 830 70 270 25 300 800 900 LINER DIA AROUND OUTSIDE OF INCOMING PIPE.
225-375 1050 SM 710 90 410 15 140 450 800
225-375 1050 BUBBLE UP PIT - TYPICAL SECTION 5.REINFORCED CONCRETE PIPE SHALL BE

I
BX 590 60 540 0 0 450 650
A 900 0 270 25 300 800 900 CLASS 2 AND SHALL COMPLY WITH
450-600 1200 SM 800 0 410 15 140 450 800 450-600 1200 AS 4058.
BX 660 40 540 0 0 450 700
BUBBLE-UP PIT DETAIL
vil

900 1500
THIS DRG TO BE READ IN CONJUNCTION WITH
\Proteus\Proteus Std Drgs\Ci

DETAILS AS FOR MANHOLE UNO


INDEX AND CONCRETE NOTES ON
SIDE ENTRY PIT (S.E.P.) DETAILS MANHOLE DETAIL
DRG STD-DB-001
DETAILS AS FOR MANHOLE UNO
PROTEUS JOB No.
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
59 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


DRAINAGE PIT - DETAILS
email proteus@proteusgroup.com.au
CHK’D.
1 STD-DB-016 RETAINING WALLS, KERBS AND DRAINS SCALE DRG. No. REV.
43:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-004
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
VARIES AS SPECIFIED
GENERAL NOTES

PRAP
1.THIS DRAWING TO BE READ IN CONJUNCTION WITH ALL
UPSTREAM 3.0m FORMATION WIDTH 1.75m 1.5m RELEVANT DRAWINGS AND SPECIFICATIONS.

T OF RI
2.
ALL DIMENSIONS ARE METRES UNLESS NOTED OTHERWISE.
FILL TO DRAIN
AS REQUIRED FLOW
3.
FOR DETAILS ON DEPTH MARKERS, REFER TO AS1742.8.

MI
LI
DOWNSTREAM
EXI
STI
NG/STRI CL PAVEMENT
PPED SURFACE
FALL LEGEND
3
1 BASECOURSE
EXISTING/STRIPPED SURFACE

RIPRAP APRON AS SPECIFIED


VARIES (MIN 1V:50H) GENERAL FILL
(MIN. 500 THICK FACING CLASS)
UNCOMPACTED
PLACED ON BIDIM A34 GEOTEXTILE
CEMENT STABILISED BASECOURSE CONCRETE CUT OFF WALL
(MIN. 200 THICK) 3% BY WEIGHT WHERE SPECIFIED REFER DETAIL RIPRAP APRON AS SPECIFIED RIPRAP
(MIN. 500 THICK FACING CLASS)
PLACED ON BIDIM A34 GEOTEXTILE

FLOODWAY WITHOUT RELIEF CULVERT - UPSTREAM IN FILL - TYPICAL SECTION


PRAP

VARIES AS SPECIFIED
T OF RI

4.2m FORMATION WIDTH 1.75m 1.5m

UPSTREAM
1.2m MIN. 3.0m
MI

FLOW
LI

EXISTING/STRIPPED SURFACE
0.25m
VARIES (MIN 1V:50H) CL PAVEMENT

FALL DOWNSTREAM
3 0.1m OVERLAP
RIPRAP APRON AS SPECIFIED
1 SLOT FOR GUIDEPOST
(MIN. 500 THICK FACING CLASS) EXISTING/STRIPPED SURFACE (WHERE APPLICABLE) AS REQUIRED
PLACED ON BIDIM A34 GEOTEXTILE VARIES BITUMINOUS SURFACING

NARY UNCHECKED
(WHERE SPECIFIED)

CEMENT STABILISED BASECOURSE CONCRETE CUT OFF WALL


(MIN. 200 THICK) 3% BY WEIGHT WHERE SPECIFIED REFER DETAIL
RIPRAP APRON AS SPECIFIED
(MIN. 500 THICK FACING CLASS)
PLACED ON BIDIM A34 GEOTEXTILE
CEMENT STABILISED
FLOODWAY WITHOUT RELIEF CULVERT - UPSTREAM IN CUT - TYPICAL SECTION

N.
BASECOURSE

6m MI

MI
RIPRAP APRON

0.

PRELI
BIDIM A34 GEOTEXTILE
VARIES AS SPECIFIED

CONCRETE CUT OFF WALL DETAIL


3.0m FORMATION WIDTH 1.5m 1.5m SCALE 1:25

CL PAVEMENT FLOW

-3% -3% DOWNSTREAM


dgn

ON ONLY
UPSTREAM 3
ngs\stdc005.

1
EXISTING/STRIPPED SURFACE

EXISTING/STRIPPED SURFACE

NFORMATI
CEMENT STABILISED BASECOURSE CONCRETE CUT OFF WALL
RIPRAP APRON AS SPECIFIED (MIN. 200 THICK) 3% BY WEIGHT WHERE SPECIFIED REFER DETAIL
\Standard Drawi

(MIN. 500 THICK FACING CLASS) RIPRAP APRON AS SPECIFIED


PLACED ON BIDIM A34 GEOTEXTILE (MIN. 500 THICK FACING CLASS)
PLACED ON BIDIM A34 GEOTEXTILE

I
FLOODWAY WITH RELIEF CULVERT - TYPICAL SECTION
vi
\Proteus\Proteus Std Drgs\Ci l
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
37 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


FLOODWAYS - TYPICAL SECTIONS AND DETAILS
email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
44:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
1:50 UNO A1
STD-DC-005
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
B GENERAL NOTES
-

1. THIS DRAWING TO BE READ IN CONJUNCTION WITH ALL


RELEVANT DRAWINGS AND SPECIFICATIONS.

2. ALL DIMENSIONS ARE METRES UNLESS NOTED OTHERWISE.

3. FOR DETAILS ON DEPTH MARKERS, REFER TO AS1742.8.

N
SW ALE DRAI
A
MINOR ROAD
-

NARY UNCHECKED
TYPICAL FLOODWAY PLAN - MINOR ROADS
NOT TO SCALE

FLOODWAY TO BLEND INTO PROVIDE RIP-RAP APRON

SITE SWALE DRAINS REFER PLACED ON 510g/m‘


CRUSHED ROCK/GRAVEL
DESIGN DRAWINGS FOR GEOTEXTILE UNDERLAY
RUNNING COURSE CL ROAD
TO ANCHOR EDGE OF GEOWEB

MI
1m

LEVELS AND LOCATIONS


0.

PRELI
CL SWALE DRAIN 1.0m WIDTH OF MINOR ROAD
ROAD SURFACE

25m
MIN.

N
MI
3m

0.
2%
0.

2%

SAND/CLAY/GRAVEL
BLEND BASE COURSE 5.0m STRIP TOPSOIL AND EARTHWORK TO SUBGRADE.
dgn

ON ONLY
PROVIDE 510g/m‘ GEOTEXTILE UNDERLAY 250 THICK SAND/CLAY/GRAVEL
= =
ngs\stdc006.

TO GEOWEB CELL TYPE GW30V, 150 THICK. BLEND BASE COURSE


BACKFILL WITH 40mm NOM. SIZE GRAVEL.
40.0m NOM

GEOWEB ANCHORING TO BE 500mm MINIMUM LENGTH 12mm

NFORMATI
REBAR PINS WITH ’ATRA’ CLIPS AND TENDONS. SPACING PER
SECTION A MANUFACTURERS RECOMMENDATIONS.
\Standard Drawi

-
SECTION B
-

I
vi
\Proteus\Proteus Std Drgs\Ci l
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
ph +61 8 6313 3200 fax +61 8 6313 3201
FLOODWAYS - MINOR ROADS
01 PM

email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
45:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-006
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
300 MIN NON TRAFFIC AREA 150 WIDE ORANGE PVC
150 WIDE ORANGE PVC 600 MIN ROAD CROSSING DANGER MARKER TAPE
DANGER MARKER TAPE

GROUND LEVEL GROUND LEVEL GROUND LEVEL

ZONE C (NON TRAFFIC)


ZONE C (NON TRAFFIC)
OR
OR
ZONE D TOP 400 150 WIDE ORANGE PVC
ZONE D TOP 400

N.
AS PER DETAIL E

600
AS PER DETAIL E DANGER MARKER TAPE

MI
ZONE C (NON TRAFFIC)

70
OR

N.
900
ZONE D TOP 400

MI
ZONE A AS PER DETAIL E

80

70
250
ZONE A

80
250

TYP.

70
250 150 300
DETAIL A
TYP. MIN. MIN. ZONE A
-

80
T

NSTRUMENT

T
POW ER CONDUI

TE CONDUI
TELECOM CONDUIT ONLY

OR COMMS CONDUIT
250 150 300

TYP. MIN. MIN.

CONRTOL, I

TELECOM W HI

T
COMPACTION PARTICLE

POW ER CONDUI

T
TE CONDUI
ZONE MATERIAL DESCRIPTION
(MMDD) SIZE

NSTRUMENT
OR COMMS
BEDDING MATERIAL
ZONE A NOMINAL 7mm MAX

CONTROL

TELECOM
T
CLEAN IMPORTED OR EXCAVATED SAND

CONDUI

W HI
EXCAVATED SILTY SAND OR
ZONE B 90% 20mm MAX
IMPORTED SAND

I
EXCAVATED MATERIAL PREFERABLY
DETAIL B
ZONE C 90% 38mm MAX DETAIL C
SILTY SAND OR SANDY CLAY -
-
SAND/CLAY/GRAVEL BLEND
ZONE D
SUB BASE & ROAD BASE
94% 38mm MAX LV BURIED CONDUIT
HV BURIED CONDUIT

ZONE E 15MPa CONCRETE - -

NARY UNCHECKED
REFER DESIGN DRAWINGS REFER DESIGN DRAWINGS
FOR ROAD CONSTRUCTION DETAILS FOR ROAD CONSTRUCTION DETAILS

100

100
GROUND LEVEL GROUND LEVEL

ROAD BASE ROAD BASE

300

300
ZONE D ZONE D

MI
SAND/CLAY/GRAVEL BLEND SAND/CLAY/GRAVEL BLEND
N.

N.
ZONE C
400

500
MI

MI

PRELI
N.
600 MI
ZONE C

50
N.

N.
150

150
MI

MI
ZONE C

ZONE B
ZONE E

N.
150

MI
REINFORCING
MAX.
dgn

MESH
80

ON ONLY
ZONE B
ZONE A
ngs\stdc007.

MAX.
250 200 200 250 200 200

80
TYP. TYP.
ZONE A

NFORMATI
150 min 250 200 200
150 min
\Standard Drawi

FOR PIPING < DN90 TYP.

150 min

FOR PIPING < DN90

I
DETAIL D DETAIL E DETAIL F
- - -
vi
\Proteus\Proteus Std Drgs\Ci l

BURIED PIPING (NON TRAFFIC AREA) BURIED PIPING (ROAD CROSSING) BURIED PIPING (ROAD CROSSING)
PREFERRED DETAIL NON PREFERRED DETAIL
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
24 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


TRENCHING DETAILS
email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
45:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-007
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
’X’
NOTES
PROVIDE 2 INTERNAL GATE PIPES NOT ANGLE OF CRANK FOR
VERTICAL MEMBERS PER TO BE CRANKED CORNER POSTS TO
LEAF WHERE ’X’ IS > 6000 40 CLEAR BE 55 FROM THE 1 FOR TYPE OF SECURITY FENCING & GATES
BARBED WIRE 6 CAP PL VERTICAL TO MATCH (NORMAL, MEDIUM OR HIGH)
TYPICAL TOP STRAND OF
DN20x2.6 PIPE OTHER POSTS REFER TO THE DESIGN DRAWINGS
FENCE POST CAP TYP BARBED WIRE

35
2 ALL DESIGN, DETAIL AND CONSTRUCTION
OF FENCING SHALL COMPLY WITH
LACING BAR AS 1725 AND AS 2423.

MAX
3 SUPPORT

C’
BRACING L BRACING STAY
F


CABLES TYP 2 5 3 ALL POSTS TO BE SET VERTICAL.
5

=
STAY TYP BACK STAY REQUIRED ONLY x 140 I/S x (BACK STAY
5 5

NAL
WHERE WIDTH BETWEEN F 2 THE TOP OF THE FENCE IS TO FOLLOW
L SIMILAR)
THE GROUND PROFILE.

B’
GATE POSTS IS > 4000

A’ NOMI


4 POSTS AND GATE FRAMES SHALL BE

/S
DIAGONAL BRACES ONLY FABRICATED FROM PIPE TO AS 1074.

140 I
1
REQUIRED IF DIMENSION


1 HINGES 5 STAYS AND STRUTS SHALL BE CONNECTED

=
’X’ IS > 7000
TYPICAL TO POSTS USING BOLTED SPLIT FITTINGS.

6 SUPPORT AND BRACING CABLES - EACH


FGL CABLE SHALL COMPRISE 2 STRANDS OF

350

50
3.15mm DIA GALVANISED WIRE TWISTED

MAX
75 MAX
N

50
16 DIA BAR HAND

50 MI
TOGETHER DURING ERECTION.

TYP
HOLES C/W SECURITY

75
CHAIN AND TRIP 7 BARBED WIRE SHALL BE 2 STRANDS 1.6mm
DIA 150 TYPE CATCH DIA HIGH TENSILE BARBING GRADE WIRE
HIGH SECURITY 1 TWISTED TOGETHER. BARBS SHALL BE 4
FENCE ONLY - POINT TYPE AT 75-100mm CRS SECURED
STRAINER POSTS INTERMEDIATE POST GATE POST DOUBLE GATES GATE POST CORNER POST
TO POSTS WITH TIE WIRES.
REQUIRED AT EACH CHANGE OF INTERMEDIATE POSTS SHALL NORMAL AND (2 EQUAL LEAF GATES BETWEEN POSTS) HIGH SECURITY REQUIRED AT ALL CHANGES
DIRECTION OR GRADE GREATER BE SPACED EVENLY BETWEEN MEDIUM SECURITY 50x6FL WELDED IN DIRECTION OF THE FENCE 8 CHAINWIRE SHALL BE MANUFACTURED FROM
20 DIA LOCKABLE DROP BOLTS FIXED TO GATE
THAN 10 OR 60 000 GATE/CORNER AND/OR CONNECTORS (3 PLACES) 2.5mm DIA WIRE FOR NORMAL SECURITY &
C/W DN32x3.2 PIPE x 100 LONG KEEPERS SET
MAXIMUM SPACING STRAINER POSTS AT NOTE: DN50 AND DN80 POSTS 3.15mm DIA WIRE FOR MEDIUM AND HIGH
INTO CONCRETE (4 REQUIRED TO HOLD GATES IN
INTERVALS NOT AS DRAWN. DN100 POSTS FOR HIGH SECURITY SECURITY WITH A UNIFORM 50mm MESH,
BOTH OPEN AND CLOSED POSITIONS). FOR HIGH
L

EXCEEDING 4000 TO HAVE LACING BAR AND FENCE DIMENSIONS LACED TIGHTLY USING 2.80mm DIA SOFT
A

SECURITY GATES CLOSED POSITION KEEPERS


N

6 CAP PL AS FOR HIGH


N W I MI

REFER TO DETAIL ’1’ FENCING GRADE TIE WIRE TO EACH END


TO BE CAST INTO 300x150 CONCRETE BEAM
O

SECURITY GATE POSTS


E

POST, STRAINING POST, CORNER POST,


N

REFER DETAIL ’1’


1000
S BE S

GATE POST AND OUTER FRAME OF GATES


S
R

TABLE 1 - MISCELLANEOUS DIMENSIONS


D
C

STEEL SPIKE FOR 1000 AND TIED TO EACH SUPPORT


0

A
15

HIGH SECURITY CORNER, GATE OR


R

CABLE AT 450 CRS MAX FOR NORMAL &


R

SECURITY TYPE DIM ’A’ DIM ’B’ DIM ’C’


T
A
B

FENCE ONLY TYP STRAINER POSTS MEDIUM SECURITY AND 300 CRS MAX FOR
GATE PIPES NOT
3

REFER NOTE 16 NORMAL 1800 2230 250 HIGH SECURITY AND AT 500 CRS MAX TO
TO BE CRANKED
EACH INTERMEDIATE POST & INNER GATE
DN32x2.6 MEDIUM 2130 2560 250
DN32x2.6 MEMBERS. TOP & BOTTOM SELVEDGES OF
1 PIPE STRUT
PIPE STRUT HIGH 2640 3070 500 CHAINWIRE SHALL BE TWISTED & BARBED

500 MAX
1
500 MAX ON FENCES AND KNUCKLED ON GATES.

9 SUPPORT CABLES, CHAINWIRE AND


TABLE 2 - MISCELLANEOUS POSTS & FOOTINGS

NARY UNCHECKED
CHAINWIRE BARBED WIRE SHALL BE FIXED TO
FOOTING DEPTH THE OUTSIDE OF POSTS AND GATES.
POST TYPE SECURITY TYPE POST DIA FOOTING DIA
BELOW FGL
BRACING
TYPICAL FENCE POST 10 ALL GATE FITTINGS SHALL BE HEAVY
CABLES NORMAL, MEDIUM DN40x2.9 250 600
16 DIA BAR HAND HOLES DUTY GALVANISED.
SIDE VIEW TURNBUCKLES INTERMEDIATE
C/W LOCKABLE TYPE HIGH DN50x2.9 250 600
(EXCLUDING CORNER POST) SHOOT BOLT AND TRIP 11 POST CAPS SHALL BE MALLEABLE CAST
HINGES
TYPE CATCH TYPICAL BRACING & NORMAL, MEDIUM DN32x2.6 250 600 IRON OR PRESSED 3.2mm GALVANISED MILD
1 TYPICAL
BARBED WIRE BACK STAY STEEL DRIVE ON OR SCREW ON TYPE.
HIGH DN40x2.9 250 600
1 NOM
CORNER & NORMAL, MEDIUM DN50x3.6 250 750 12 GATES SHALL BE FULLY WELDED TO
STRAINER AS 1554.1 WITH A MINIMUM FILLET WELD

MI
75 MAX

75 MAX
HIGH DN80x4.0 300 900
N

N
50 MI

50 MI
OF 3mm. ALL WELDED OR DAMAGED
1

PRELI
NORMAL, MEDIUM DN32x2.6 - - AREAS SHALL BE PROTECTED WITH 2
1 LACING BAR COATS OF APPROVED ZINC RICH PAINT.
HIGH DN40x2.9 - -
REFER
3 NOTE 12 13 CONCRETE SHALL BE GRADE N20 OR
900 IF IN SAND (TABLE 2) BETTER TO AS 3600 AND COMPACTED
TYPE 1 TYPE 2
CHAINWIRE NORMAL AND AROUND POSTS LEAVING A 10mm FALL
HIGH SECURITY
MEDIUM SECURITY TABLE 3 - GATE FRAMES AWAY FROM THE POST. ALLOW CONCRETE
BRACED PANEL / TO CURE FOR AT LEAST 24 HOURS
BARBED WIRE RETURN STRAINER ASSEMBLY PERSONNEL GATES GATE TYPE SECURITY TYPE DIM ’X’ OUTER FRAME INNER MEMBERS BEFORE TENSIONING ANY WIRES.
REQUIRED AT ALL GATE POSTS AND TYPE 1 AND 2 TO BE PLACED BETWEEN 14 BOLTS SHALL BE GRADE 4.6 COMMERCIAL
dgn

REQUIRED WHERE THERE IS

ON ONLY
NORMAL, MEDIUM < 4m DN25x2.6 DN20x2.3
LACING BARS FOR GATE POSTS 2 STRAINER POSTS AS SHOWN OR GRADE BOLTS AND COMPLY WITH AS 1111.
INSUFFICIENT SPACE FOR
ngs\Stdc008.

BETWEEN GATE AND STRAINER POSTS DOUBLE NORMAL, MEDIUM > 4m DN32x2.6 DN25x2.6 BOLTS, NUTS AND WASHERS SHALL BE
BRACING STAYS
HIGH UP TO 8m DN40x2.9 DN32x2.6 HOT DIPPED GALVANISED.

PERSONNEL NORM,MED&HIGH - DN25x2.6 DN20x2.3 15 ALL FERROUS MATERIALS SHALL HAVE A


A

NFORMATI
BACK STAY COATING OF ZINC. THE COATING FOR WIRE
CHAINWIRE SUPPORT
- BACK STAY SHALL BE TYPE A HEAVILY GALVANISED.
CABLE
\Standard Drawi

200

50

GATE POST TABLE 4 - GATE POSTS & FOOTINGS


GROUND 16 HIGH SECURITY FENCES TO HAVE:
LEVEL FOOTING DEPTH 10 DIA x 50 LONG SHARPENED STEEL
DIM ‘X’ POST DIA FOOTING DIA
300

GATE TYPE SECURITY TYPE


BELOW FGL SPIKE ON TOP OF ALL POSTS AND
FENCE LINE FENCE LINE
GATE UPRIGHTS.

I
BRACING NORMAL, MEDIUM DN50x3.6 250 1000
CONCRETE CHAINWIRE SET INTO CONCRETE BEAM &
8

BRACING STAY
0

150 STAY TYP


BEAM CONCRETE BEAM BETWEEN NORMAL, MEDIUM > 4m TO 6m DN80x4.0 300 1000 ALL POST FOOTINGS, REFER DETAIL ’1’
= = ALL POST FOOTINGS DOUBLE
(EXCEPT BETWEEN GATE POSTS).
NORMAL, MEDIUM > 6m TO 8m DN100x4.5 400 1000
INCLUDING GATE POSTS
vil

HIGH UP TO 8m DN150x5.0 500 1200 THIS DRG TO BE READ IN CONJUNCTION WITH


SECTION DETAIL
\Proteus\Proteus Std Drgs\Ci

A 1 PLAN AT CORNER POST


- - PERSONNEL NORM,MED&HIGH - DN50x3.6 250 1000 INDEX AND CONCRETE NOTES ON
FOR CORNERS GREATER THAN 90 PLAN AT GATE POST
(BACK STAY NOT REQUIRED FOR DRG STD-DB-001
HIGH SECURITY FENCING DETAILS ONLY
CORNERS < 90)
PROTEUS JOB No.
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
04 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


SECURITY FENCING
email proteus@proteusgroup.com.au
CHK’D.
SCALE DRG. No. REV.
46:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
NTS A1
STD-DC-008
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
STRAINER POST @ 210m INCREMENTS

CORNER POST
DN100 GALV. PIPE WITH CAP
GATE POST
INTERMEDIATE POST @ 30m INCREMENTS INTERMEDIATE POST DN100 GALV. PIPE WITH CAP TYP
DN50 GALV. PIPE WITH CAP
WIRE PLACEMENT TO BE GOVERENED 3600 PROPRIETRY HINGED FARM GATE
BY HOLE LOCATION ON STAR PICKETS
TYPICAL DIMESIONS SHOWN START PICKET STRAINER POST BRACING STAY DN32 GALV. PIPE
POST DN100 GALV. PIPE WITH CAP 250 PARALLEL TO FENCE

4 ROWS OF 3.15 DIA 200mm PAD BOLT


PLAIN WIRE

285
1
35

1150 TYP
285
1200 NOM

14
10
1075

1800
305
GROUND LEVEL

590
75 TYP
600

600
750

1100
250 250

NOTE: INTERMEDIATE POSTS


5000 NOM 400
AT MAX 48m CTR

CORNER POSTS AND BRACING STAY TO BE


LOCATED AT ALL CHANGES OF DIRECTION IN
THE FENCELINE.
STRAINER ASSEMBLY LOCKED GATE
CORNER BRACING ASSEMBLY INTERMEDIATE POSTS

MINARY UNCHECKED
8 DIA HOLE DRILLED THROUGH
POST INLINE WITH WIRE

PRELI
SPACING LOCATION
NOTES

1. ALL DIMENSIONS IN MILLIMETRES, UNLESS SHOWN OTHERWISE.


DIMENSIONS SHOWN ARE TYPICAL.

2. ALL WIRE TO BE GALVANIZED FENCING WIRE TO AS 2423.

3. STEEL POSTS ARE STANDARD 1.8M STAR PICKETS, BLACK TAR


COATED OR GALVANIZED.
dgn

ON ONLY
4. BOLTS, NUTS AND WASHERS TO BE HOT-DIPPED TO AS 1214.
ngs\stdc009.

5. ALL GALV. PIPE TO CHS PER AS 1163, GALANISED PER AS 4680


DN100 - 4.5mm THICKNESS
DN50 - 3.6mm THICKNESS
DN32 - 3.2mm THICKNESS

NFORMATI
POST WIRE FASTENING DN25 - 3.2mm THICKNESS
\Standard Drawi

NTS
6. TWO GALVANISED FENCE DROPPERS 94cm LONG ARE TO BE
LOCATED EACH SPAN.

7. CONCRETE CLASS TO BE N32 PER REFERENCE DRAWING 1.

I
8. SECURING OF CHAINS BY WELDING OR SUITABLE GALVANISED
BOLT INTO A TAPPED HOLE, ALL WELDS TO BE COLD GALVANISED.
l

9. STRAIN WIRES IN ACCORDANCE WITH THE MANUFACTURES RECOMMENDATIONS.


vi
\Proteus\Proteus Std Drgs\Ci
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
DES’N.
ph +61 8 6313 3200 fax +61 8 6313 3201
STOCK FENCE DETAILS
31 PM

email proteus@proteusgroup.com.au
CHK’D.
1 STD-DB-001 CONCRETE STANDARDS NOTES & DRAWING INDEX SCALE DRG. No. REV.
46:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
1:20 A1
STD-DC-009
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.
Proteus Engineers Pty Ltd ABN 96 152 082 972 trading as Proteus EPCM Engineers
NORMAL SECURITY FENCE 1 TONNE RATED CAPACITY LUG
REFER DRG 3 REFER DRG 2
EMERGENCY EGRESS ROPE
REFER DETAIL 16 DIA BOW SHACKLE

/ / / / / /
SPLICE WITH HARD EYE

/
27 DIA POLYESTER ROPE

/
KNOTTED AT 1000 CENTRES
MAX
100NB STD WT PIPE

1200
300 300

C’

ANCHOR TRENCH
/

D’
1.5mm HDPE LINER
TOP OF BUND

400
510g/sqm GEOTEXTILE

600

600
FABRIC

/
/

B’
A 400 DIA


/

/
-
MASS CONCRETE

1000 DETAIL 1
1:20 -

EMERGENCY EGRESS ROPE DETAIL TYPICAL ANCHOR TRENCH DETAIL


/

SCALE 1:20

D’

HDPE LINER

/
/

C’

EXTRUSION WELD
ALL AROUND
OVERLAY USED CONVEYOR BELT

NARY UNCHECKED
ON HDPE LINER BELOW INLET FOR
LINER/BATTER PROTECTION

/
/

/ / / /

SET OUT POINT 1


EASTING SET OUT POINT 2
NORTHING EASTING
’C’ ’D’ ’A’ ’D’ ’C’ NORTHING HDPE PIPE

510g/sqm GEOTEXTILE FABRIC

MI
PLAN

PRELI
TYPICAL POND INLET DETAIL
LIFE RING WITH
MOUNTING POST SCALE 1:10

ON ONLY
dgn

J’
ngs\stdc010.

FREEBOARD ’

1.5mm HDPE LINER

NFORMATI
- COMPACTED EXCAVATED
MATERIAL TYP. REFER NOTE 2.
\Standard Drawi

’F’ RL ’G’ NOTES


TOP WATER LEVEL ’F’
1
1 1. FOR GENERAL NOTES REFER DRG 1.
’E’ ’E’

I
1 1
2. IMPORTED SELECT FILL TO BE USED FOR
RL ’H’ BUND CONSTRUCTION IF PROJECT ENGINEER
DETERMINES EXCAVATED MATERIAL IS
UNSUITABLE.
vi
\Proteus\Proteus Std Drgs\Ci l

SECTION A
1:100 -
2/07/2014

BY DATE
TITLE

DRAWN
CLIENT
E P C M E N G I N E E R S

A TETRA TECH COMPANY CHK’D.


PROJECT
CONSULTING ENGINEERS PROJECT MANAGERS CIVIL STANDARDS
3 STD-DB-008 CIVIL STANDARDS - SECURITY FENCING
DES’N.
20 PM

ph +61 8 6313 3200 fax +61 8 6313 3201


TURKEY NEST - TYPICAL PLAN & DETAILS
2 STD-DS-012 STEELWORK STANDARDS - LIFTING LUGS email proteus@proteusgroup.com.au
CHK’D.
1 STD-DC-001 CIVIL STANDARDS - GENERAL NOTES SCALE DRG. No. REV.
49:

This drawing must not be copied or reproduced in any form or used for any purpose
other than originally intended without written approval of PROTEUS EPCM ENGINEERS
1:200 A1
STD-DC-010
P:

No REF. DRG. No. TITLE REV BY DATE DESCRIPTION CHK’D APP’D


1:

APP’D.