You are on page 1of 86

APF221384

G 160 VSD
Instruction book
Atlas Copco

G 160 VSD
APF221384

Instruction book
Original instructions

COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and
drawings.

This instruction book is valid for CE as well as non-CE labelled machines. It meets the
requirements for instructions specified by the applicable European directives as
identified in the Declaration of Conformity.

2017 - 09

www.atlascopco.com
Instruction book

Table of contents

1 Safety precautions..........................................................................................................5

1.1 SAFETY ICONS................................................................................................................................... 5

1.2 GENERAL SAFETY PRECAUTIONS............................................................................................................5

1.3 SAFETY PRECAUTIONS DURING INSTALLATION........................................................................................... 6

1.4 SAFETY PRECAUTIONS DURING OPERATION.............................................................................................. 7

1.5 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR........................................................................... 8

1.6 DISMANTLING AND DISPOSAL...............................................................................................................10

2 General description...................................................................................................... 11

2.1 INTRODUCTION.................................................................................................................................11

2.2 AIR AND OIL SYSTEM.........................................................................................................................12

2.3 COOLING AND CONDENSATE SYSTEM.................................................................................................... 14

2.4 SMARTBOX AND SMARTLINK.................................................................................................... 15

3 Elektronikon® Graphic controller............................................................................... 18

3.1 ELEKTRONIKON CONTROL SYSTEM....................................................................................................... 18

3.2 DIGITAL OUTPUT CONTACTS................................................................................................................20

3.3 ICONS USED.................................................................................................................................... 22

3.4 MAIN SCREEN..................................................................................................................................26

3.5 CONTROLLER MENU STRUCTURE..........................................................................................................30

3.6 WEB SERVER.................................................................................................................................. 34

3.7 PROGRAMMABLE SETTINGS.................................................................................................................41

4 Installation.....................................................................................................................43

4.1 INSTALLATION REMARKS.....................................................................................................................43

4.2 DIMENSION DRAWING........................................................................................................................ 44

4.3 INSTALLATION PROPOSAL................................................................................................................... 47

4.4 MAIN FUSES AND SUPPLY CABLES (SECTION & MAXIMUM LENGTH) ............................................................ 49

2 APF221384
Instruction book

4.5 QUALITY OF SAFETY COMPONENTS.......................................................................................................51

4.6 INSTALLATION INSTRUCTIONS FOR CUBICLE FAN...................................................................................... 51

4.7 PICTOGRAPHS................................................................................................................................. 52

5 Operating instructions................................................................................................. 54

5.1 INITIAL START-UP..............................................................................................................................54

5.2 BEFORE STARTING............................................................................................................................56

5.3 STARTING....................................................................................................................................... 57

5.4 DURING OPERATION.......................................................................................................................... 58

5.5 CHECKING THE DISPLAY.....................................................................................................................59

5.6 STOPPING.......................................................................................................................................60

5.7 TAKING OUT OF OPERATION................................................................................................................61

5.8 USE OF AIR RECEIVER....................................................................................................................... 62

6 Maintenance.................................................................................................................. 63

6.1 PREVENTIVE MAINTENANCE SCHEDULE..................................................................................................63

6.2 MOTORS.........................................................................................................................................64

6.3 OIL SPECIFICATIONS..........................................................................................................................65

6.4 OIL CHANGE....................................................................................................................................65

6.5 OIL FILTER CHANGE.......................................................................................................................... 68

6.6 STORAGE AFTER INSTALLATION........................................................................................................... 69

6.7 SERVICE KITS.................................................................................................................................. 69

7 Adjustments and servicing procedures..................................................................... 70

7.1 AIR FILTERS.................................................................................................................................... 70

7.2 COOLERS....................................................................................................................................... 71

7.3 SAFETY VALVE.................................................................................................................................72

8 Problem solving............................................................................................................74

8.1 PROBLEM SOLVING........................................................................................................................... 74

APF221384 3
Instruction book

9 Technical data...............................................................................................................76

9.1 READINGS ON DISPLAY...................................................................................................................... 76

9.2 REFERENCE CONDITIONS................................................................................................................... 76

9.3 LIMITS............................................................................................................................................77

9.4 SETTINGS OF SAFETY VALVE...............................................................................................................77

9.5 SETTINGS OF OVERLOAD RELAYS, FUSES AND CIRCUIT BREAKERS.............................................................. 77

9.6 COMPRESSOR DATA..........................................................................................................................77

10 Pressure equipment directives................................................................................... 79

11 Documentation..............................................................................................................81

4 APF221384
Instruction book

1 Safety precautions

1.1 Safety icons

Explanation

Danger to life

Warning

Important note

1.2 General safety precautions


1. The operator must employ safe working practices and observe all related work safety
requirements and regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter
of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized,
trained, specialized personnel. The personnel should apply safe working practices by use of
personal protection equipment, appropriate tools and defined procedures.
4. The compressor is not considered capable of producing air of breathing quality. For air of
breathing quality, the compressed air must be adequately purified according to the
applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks:
• Stop the machine
• Press the emergency stop button
• Switch off the voltage
• Depressurize the machine
• Lock Out - Tag Out (LOTO):
• Open the power isolating switch and lock it with a personal lock
• Tag the power isolating switch with the name of the service technician.
• On units powered by a frequency converter, wait 10 minutes before starting any
electrical repair.
• Never rely on indicator lamps or electrical door locks before maintenance work, always
disconnect and check with measuring device.

If the machine is equipped with an automatic restart after voltage failure function and if
this function is active, be aware that the machine will restart automatically when the
power is restored if it was running when the power was interrupted!

6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at
people. Never use the air to clean dirt from your clothes. When using the air to clean
equipment, do so with extreme caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and
accessories shall be replaced if unsuitable for safe operation.
8. It is prohibited to walk or stand on the unit or on its components.

APF221384 5
Instruction book

9. The Variable Speed Drive is equipped with a Safe Torque Off function, triggered by the
emergency stop button. The Safe Torque Off function has the immediate effect that the drive
can not supply any torque-generating energy. The drive is reliably torque-free. This state is
monitored internally in the drive.

The Safe Torque Off function does not disconnect the voltage of the main and auxiliary
circuits from the drive. Maintenance work on electrical parts of the drive or the motor can
only be carried out after isolating the drive system from the main supply!

10. If compressed air is used in the food industry and more specifically for direct food contact, it
is recommended, for optimal safety, to use certified Class 0 compressors in combination
with appropriate filtration depending on the application. Please contact your customer center
for advice on specific filtration.

1.3 Safety precautions during installation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during installation


1. The machine must only be lifted using suitable equipment in accordance with the applicable
safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is
strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and
deceleration must be kept within safe limits. Wear a safety helmet when working in the area
of overhead or lifting equipment.
2. The unit is designed for indoor use. If the unit is installed outdoors, special precautions must
be taken; consult your supplier.
3. In case the device is a compressor, place the machine where the ambient air is as cool and
clean as possible. If necessary, install a suction duct. Never obstruct the air inlet. Care must
be taken to minimize the entry of moisture at the inlet air.
4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting
the pipes.
5. Air hoses must be of correct size and suitable for the working pressure. Never use frayed,
damaged or worn hoses. Distribution pipes and connections must be of the correct size and
suitable for the working pressure.
6. In case the device is a compressor, the aspirated air must be free of flammable fumes,
vapors and particles, e.g. paint solvents, that can lead to internal fire or explosion.
7. In case the device is a compressor, arrange the air intake so that loose clothing worn by
people cannot be drawn in.
8. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to
expand under heat and that it is not in contact with or close to flammable materials.
9. No external force may be exerted on the air outlet valve; the connected pipe must be free of
strain.
10. If remote control is installed, the machine must bear a clear sign stating: DANGER: This
machine is remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and depressurized and that the
electrical isolating switch is open, locked and labelled with a temporary warning before any
maintenance or repair. As a further safeguard, persons switching on or off remotely

6 APF221384
Instruction book

controlled machines shall take adequate precautions to ensure that there is no one checking
or working on the machine. To this end, a suitable notice shall be affixed to the start
equipment.
11. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is
available and that the exhausted air does not recirculate to the compressor air inlet or
cooling air inlet.
12. The electrical connections must correspond to the applicable codes. The machines must be
earthed and protected against short circuits by fuses in all phases. A lockable power
isolating switch must be installed near the compressor.
13. On machines with automatic start/stop system or if the automatic restart function after
voltage failure is activated, a sign stating "This machine may start without warning" must be
affixed near the instrument panel.
14. In multiple compressor systems, manual valves must be installed to isolate each
compressor. Non-return valves (check valves) must not be relied upon for isolating pressure
systems.
15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure must be protected by a pressure relieving device or devices as
required.
16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be
accidentally touched by personnel in normal operation must be guarded or insulated. Other
high temperature piping must be clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to
be protected by a safety device with set pressure according to the maximum cooling water
inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
19. If the device is a dryer and no free extinguishing system is present in the air net close to the
dryer, safety valves must be installed in the vessels of the dryer.

Also consult following safety precautions: Safety precautions during operation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.4 Safety precautions during operation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during operation


1. Never touch any piping or components of the machine during operation.
2. Use only the correct type and size of hose end fittings and connections. When blowing
through a hose or air line, ensure that the open end is held securely. A free end will whip
and may cause injury. Make sure that a hose is fully depressurized before disconnecting it.

APF221384 7
Instruction book

3. Persons switching on remotely controlled machines shall take adequate precautions to


ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes,
vapors or particles.
5. Never operate the machine below or in excess of its limit ratings.
6. Keep all bodywork doors shut during operation. The doors may be opened for short periods
only, e.g. to carry out routine checks. Wear ear protectors when opening a door.
On machines without bodywork, wear ear protection in the vicinity of the machine.
7. People staying in environments or rooms where the sound pressure level reaches or
exceeds 80 dB(A) shall wear ear protectors.
8. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not
rubbing
• No leaks occur
• All fasteners are tight
• All electrical leads are secure and in good order
• Safety valves and other pressure relief devices are not obstructed by dirt or paint
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in
good repair, free of wear or abuse
• Air cooling filters of the electrical cabinet are not clogged
9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a
workroom, take precautions against air pollution and possible contamination of the breathing
air.
10. On water-cooled compressors using open circuit cooling towers, protective measures must
be taken to avoid the growth of harmful bacteria such as Legionella pneumophila bacteria.
11. Do not remove any of, or tamper with, the sound-damping material.
12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure shall be protected by a pressure relieving device or devices as
required.
13. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book
must be respected. Local regulations remain applicable if they are more strict.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.5 Safety precautions during maintenance or repair


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

8 APF221384
Instruction book

Precautions during maintenance or repair


1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes,
etc.).
2. Use only the correct tools for maintenance and repair work.
3. Use only genuine spare parts for maintenance or repair. The manufacturer will disclaim all
damage or injuries caused by the use of non-genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached
to the starting equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
7. Close the compressor air outlet valve and depressurize the compressor before connecting
or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all
sources of pressure and relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
precautions against toxic vapors of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
covering the parts and exposed openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
completely purged, e.g. by steam cleaning, before carrying out such operations. Never weld
on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is
overheated, the machine shall be stopped but no inspection covers shall be opened before
sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil
vapor when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure
vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they
function properly. They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating
pressures, temperatures and time settings are correct. Check that all control and shut-down
devices are fitted and that they function correctly. If removed, check that the coupling guard
of the compressor drive shaft has been reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of
the oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture
from entering them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on
the bodywork and in the air inlet and outlet systems of the compressor, is in good condition.
If damaged, replace it by genuine material from the manufacturer to prevent the sound
pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate
bowls.
21. Only if applicable, the following safety precautions are stressed when handling
refrigerant:
• Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.

APF221384 9
Instruction book

• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin
with water. If liquid refrigerant contacts the skin through clothing, never tear off or
remove the latter; flush abundantly with fresh water over the clothing until all refrigerant
is flushed away; then seek medical first aid.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.6 Dismantling and disposal

Dismantling
Once the end of life of the machine is reached, please follow next steps:
1. Stop the machine.
2. Check all safety precautions mentioned in the previous chapters to secure safe handling
(e.g. LOTO, cool-down, depressurize, discharge, ...).
3. Separate the harmful from the safe components (e.g. drain oil from oil containing parts).
4. Refer to the disposal topic mentioned below.

Disposal
Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts,
etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the
local recommendations and environmental legislation.
Electric and electronic components are subject to the EU Directive 2012/19/EC for Waste
Electrical and Electronic Equipment (WEEE). As such, these parts must not be disposed of at a
municipal waste collection point. Refer to local regulations for directions on how to dispose of this
product in an environmentally friendly manner.

10 APF221384
Instruction book

2 General description

2.1 Introduction

General

General view

Description of G VSD compressors


G VSD (Variable Speed Drive) compressors are single-stage, oil-injected, air-cooled screw
compressors directly driven by an electric motor. The compressors deliver pulsation-free air. By
continuously matching the speed of the drive motor to the air net pressure, the compressor
optimizes energy consumption and reduces the operating pressure band.
The following features are available as an option:

SMARTBOX
When ordering the compressor, it is possible (except for Japan and Korea) to choose the free
SMARTBOX option which is mounted in the electrical cabinet. The SMARTBOX allows read-out
of the compressor parameters on a login-protected web site called SMARTLINK. The connected
antenna is mounted on the outside of the electrical cabinet. (Refer to the SMARTBOX and
SMARTLINK section.)

APF221384 11
Instruction book

2.2 Air and oil system

Flow diagrams

Flow diagram of air-cooled VSD compressor

Drawing Reference Description


(1) Customer installation
(2) Atlas Copco installation

12 APF221384
Instruction book

Drawing Reference Description


(3) Condensate drain of the dryer
(4) Condensate drain of the compressor
(5) Energy recovery circuit (optional)
(6) Air inlet
(7) Air outlet
* Refer to your Atlas Copco Customer Centre for detailed info

Position of components

Air flow
Air drawn through filter (AF) is compressed in compressor element (E). Compressed air and oil
are discharged through check valve (CV) to air receiver/oil separator (AR) where oil is separated
from the compressed air. The air is blown through minimum pressure valve (Vp) to air cooler
(Ca).
On Pack compressors, the cooled air is discharged through the condensate trap and the outlet
towards the air net.
Check valve (CV) prevents blow-back of compressed air.
Minimum pressure valve (Vp) prevents the receiver pressure from dropping below a minimum
pressure. The valve has a built-in check valve.

APF221384 13
Instruction book

Oil system
Air pressure forces the oil from receiver (AR) through oil cooler (Co), filters (OF) and oil stop
valve (Vs) to compressor element (E) and the lubrication points.
Oil stop valve (Vs) prevents the compressor elements from flooding with oil when the compressor
is stopped.
Valve (Bv) by-passes oil cooler (Co) when starting the compressor from a cold condition, so
ensuring rapid warming of the oil to normal working temperature.
In air receiver (AR) most of the oil is removed from the air centrifugally. Almost all of the
remaining oil is removed by the separator element.

2.3 Cooling and condensate system

Condensate drain system

Condensate drains

Reference Designation
Dac Automatic condensate drain, compressor
Dmc Manual condensate drain

A condensate trap is installed downstream of the air cooler to prevent condensate from entering
the air outlet pipe. The trap is provided with a WSD for automatically draining condensate and
with a manual drain valve.
This condensate can contain small amounts of oil and should be processed according to local
environmental legislation.

Cooling system
On air-cooled compressors, the air and oil coolers are cooled by fans.

14 APF221384
Instruction book

2.4 SMARTBOX and SMARTLINK

General
The machine comes with a SMARTBOX mounted in the electrical cabinet.

The SMARTBOX allows read-out of a number of parameters of the machine on a user login-
protected web site called SMARTLINK. The connected antenna is mounted on the outside of the
machine.

Safety precautions
It is important to follow all regulations regarding the use of radio equipment, in particular
regarding the possibility of radio frequency (RF) interference. Please follow the safety advice
given below carefully.
• Respect restrictions on the use of radio equipment in fuel depots, chemical plants or other
explosive environments.
• Avoid SMARTBOX operation close to inadequately protected personal medical devices such
as hearing aids and pacemakers. Consult the manufacturers of the medical device to
determine if it is adequately protected.
• Avoid SMARTBOX operation close to other electronic equipment which may also cause
interference if the equipment is inadequately protected. Observe any warning signs and
manufacturer recommendations.
• Respect a distance from the human body of at least 20 cm (8 inch) during SMARTBOX
operation.
• Do not operate the SMARTBOX in areas where cellular modems are not advised without
proper device certifications. These areas include environments where cellular radio can
interfere, such as explosive atmospheres, medical equipment, or any other equipment which
may be susceptible to any form of radio interference. The modem can transmit signals that
could interfere with this equipment.

SMARTLINK
The machine is SMARTLINK-ready.
SMARTLINK is Atlas Copco’s web-based platform to monitor compressed air installations. It is
available in 3 product levels:
• SMARTLINK Service
SMARTLINK Service rules out all uncertainties. Scheduling maintenance visits becomes as
simple and easy as it should be; the service log book is always just one click away and the
online link with Atlas Copco allows to request and quickly receive quotes for spare parts or
additional services.

APF221384 15
Instruction book

This product level is free of charge and available for 3 years following the machine
purchase.
• SMARTLINK Uptime
SMARTLINK Uptime keeps your compressors up and running. By e-mail and/or text, you
receive all relevant machine indications (warnings and shutdowns) in advance. Based on
this information, you can then take all necessary actions and measures to avoid the risk of a
breakdown.
This product level is available as a free of charge 3-month trial.
• SMARTLINK Energy
SMARTLINK Energy safeguards the performance of your equipment. It enables you to
continuously monitor and analyze the energy efficiency of the compressor room. You decide
which performance indicators, benchmarks and reports are created. You can make accurate
and immediate improvements when needed. The results can be used for energy monitoring
according to ISO50001.
This product level is available as a free of charge 3-month trial.
Once a SMARTLINK level is chosen, gaining access is the next step. To gain access at least one
machine SMARTLINK-ready component (compressor, dryer, ...) is required. Follow the next
steps:
• Gather the information about the SMARTLINK-ready machine(s) (e.g. picture of the data
plate; invoice,…)
• Go to the SMARTLINK web site http://www.atlascopco.com/smartlink
• Click on the left button in the screen below.

• Use the data of the SMARTLINK–ready machine to register as a user.

16 APF221384
Instruction book

• You will receive an e-mail with login credentials.


• Go to the SMARTLINK web site http://www.atlascopco.com/smartlink, log in with the user
credentials.
• Enjoy SMARTLINK!
• In case more SMARTLINK-ready machines are available, you can add these via My Profile.

APF221384 17
Instruction book

3 Elektronikon® Graphic controller

3.1 Elektronikon control system

Electronic controller

Controller panel

Parts and functions

Reference Name Function


1 Alarm Flashes if a shut-down warning condition exists.
2 Service Lights up if service is needed
3 Automatic operation Indicates that the regulator is automatically
controlling the compressor.
4 Voltage on Indicates that the voltage is switched on.
5 Enter Key to select the parameter indicated by the
horizontal arrow. Only the parameters followed by
an arrow pointing to the right can be modified.
6 Escape To go to previous screen or to end the current
action
7 Scroll keys Keys to scroll through the menu.
8 Stop Button to stop the compressor. LED (3) goes out.
9 Start Button to start the compressor. LED (3) lights up
indicating that the electronic regulator is operative.

The Voltage on LED should not be used as a voltage indicator during maintenance.

18 APF221384
Instruction book

Main functions
In general, the regulator has the following functions:
• Controlling the motor speed (Variable Speed Drive), reducing the power consumption and
pressure band.
• Controlling the speed of the fans of the coolers, reducing the power consumption and noise
level.
• Protecting the compressor.
• Monitoring components - service warning.
• Automatic restart after voltage failure.

Controlling the compressor speed - reducing power consumption and pressure band
VSD compressors optimize the power consumption and reduce the operating pressure band by
matching the motor speed to the air net pressure.
The regulator will continuously vary the motor speed maintaining the net pressure as close as
possible to the programmed pressure set-point. The pressure fluctuations will be very low.

Indirect stopping

Example of a pressure/time diagram

Ref. Designation
(1) Pressure
(2) Direct stop offset
(3) Set-point
(4) Motor speed
(5) Minimum
(6) Time
(7) Load
(8) Indirect stop
(9) Start

APF221384 19
Instruction book

Ref. Designation
(10) Indirect stop offset

If the motor is running at minimum speed and the net pressure rises to a value equal to the sum
of the programmed pressure set-point and the programmed indirect stop offset, the compressor
will stop.
When the net pressure drops, the regulator will calculate the optimum moment to restart the
compressor to avoid the net pressure decreasing below the pressure set-point (anticipated
starting).

Direct stopping
If the net pressure should rise to a value equal to the sum of the programmed pressure set-point
and the programmed direct stop offset, the compressor will be stopped immediately.
The regulator will calculate the optimum moment to restart the compressor.

3.2 Digital output contacts

Warning

Voltage-free outputs may only be used to control or monitor functional systems.


They should NOT be used to control, switch or interrupt safety related circuits.

Stop the compressor and switch off the supply before connecting external equipment.
Check the Safety precautions.

Connections for external equipment


The Elektronikon (Mk5) always comes with expansion module IO2 that has a number of digital
output contacts which can be used to connect external equipment.
Depending on the optional equipment, extra expansion modules are added to the machine
configuration (IO2, IO34).

20 APF221384
Instruction book

Expansion Module IO2 for Elektronikon (Mk5)

The digital output contacts have following specifications:

Relay Connector Maximum load


K01 3 X 31 15 A / 250 V AC
15 A / 30 V DC
RC* protected
K02 3 X 31 15 A / 250 V AC
15 A / 30 V DC
RC* protected
K03 3 X 31 15 A / 250 V AC
15 A / 30 V DC
RC* protected
K04 3 X 31 10 A / 250 V AC
10 A / 30 V DC
resistive load
K05 3 X 30 10 A / 250 V AC
10 A / 30 V DC
resistive load
K06 3 X 30 10 A / 250 V AC
10 A / 30 V DC
resistive load
K07 3 X 30 10 A / 250 V AC
10 A / 30 V DC
resistive load
K08 3 X 30 10 A / 250 V AC
10 A / 30 V DC
resistive load

APF221384 21
Instruction book

Relay Connector Maximum load


K09 3 X 30 10 A / 250 V AC
10 A / 30 V DC
resistive load
K10 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
K11 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
K12 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
K13 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
K14 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
K15 3 X 32 10 A / 250 V AC
10 A / 30 V DC
resistive load
* = Resistor Capacitor

3.3 Icons used

Status icons

Name Icon Description

When the compressor is stopped, the icon is motionless.


Stopped / Running
When the compressor is running, the icon rotates.

Compressor status Motor stopped

Running unloaded

Running loaded

22 APF221384
Instruction book

Local start / stop

Machine control mode


Remote start / stop

Network control

Automatic restart after voltage


Automatic restart after voltage failure is enabled
failure

Week timer Week timer is active

Emergency stop

Active protection functions Shutdown

Warning

Service required

Service

Error

Main screen Displayed when 2 or 4 line layout is picked.

Main chart Displayed when chart layout is picked.

APF221384 23
Instruction book

Menu icons

Icon Description
Converter(s)

Service

Alarms (warnings, shutdowns)

Week timer

Info

Test

Counters

Regulation setpoints

Inputs

Outputs

Event history (saved data)

Settings

24 APF221384
Instruction book

Input icons

Icon Description
Pressure

Temperature

Digital input

Special protection

System icons

Icon Description
Fan (overload)

Automatic restart (ARAVF)

Main chart

Compressor element (LP, HP, ...)

Filter(s)

Frequency converter

Motor

Expansion module

Network settings/problem

General alarm

APF221384 25
Instruction book

Oil circuit

Regulation

General settings

Access key

Remote start/stop (Password protected)

Navigation arrows

Icon Description
Up

Down

3.4 Main screen

Control panel

Control panel

26 APF221384
Instruction book

Function
The main screen shows the status of the compressor and is the gateway to all functionality
implemented in the controller.
The main screen is shown automatically when the power is switched on. The display switches to
sleep mode when no keys are pushed for a programmable time.
Five different main screens can be chosen:
1. Two value lines
2. Four value lines
3. Chart (High Resolution)
4. Chart (Medium Resolution)
5. Chart (Low resolution)

Two and four value views

Typical Main screen (Four value lines)

Text on figures

(1), (2) Compressor Outlet


(3) Inlet Guide Vanes % Open
(4) Blow-Off Valve % Closed
(5) Starting
(6) Menu
(7) Unload

• Section A displays information regarding the compressor operation (e.g. outlet pressure,
temperature at compressor outlet ).
• Section B displays Status icons. Following icon types are shown in this field:
• Fixed icons
These icons are always shown in the main screen and cannot be selected by the cursor
(e.g. Compressor stopped or running)
• Shortcut icons
These icons are always shown in the main screen. If the icon is selected and the Enter
key is pushed, the screen will jump to the corresponding menu (e.g. if the icon for Motor

APF221384 27
Instruction book

stopped or Running Loaded is selected, the screen will jump directly to the regulation
menu after pressing the Enter key).
• Control mode icons
These icons are always shown in the main screen. If the icon is selected and the Enter
key is pushed, the screen jumps to the control mode menu. Following control modes
are available:

Local control

Remote control

Network control

• Optional icons
These icons are only shown if their corresponding function is activated (e.g. week timer,
automatic restart after voltage failure, etc.)
• Pop up icons
These icons pop up if an abnormal condition occurs (warnings, shutdowns, service,...)
To show more information about displayed icons, select the icon using the scroll keys and
push the Enter key.
• Section C is called the Status bar
This bar shows the text that corresponds to the selected icon.
• Section D shows the Action buttons. These buttons are used:
• to call-up or program settings
• to reset a shutdown, service message or emergency stop
• to have access to all data collected by the controller
The function of the buttons depends on the displayed menu. The most common functions
are:

Designation Function
Menu To go to the menu
Modify To modify programmable settings
Reset To reset a timer or message

To enable an action button, highlight this button by using the Scroll keys and push the Enter
key.
To go back to the previous menu, push the Cancel / Escape key.

28 APF221384
Instruction book

Chart views

When the Chart (High Resolution) display is selected, a chart with an X-axis covering 4 minutes
is displayed. The value displayed on the Y-axis depends on the selection made in the input
screen. Each chart dot represents 1 second.

When the Chart (Medium Resolution) display is selected, a chart with an X-axis covering 4 hours
is displayed. The value displayed on the Y-axis depends on the selection made in the input
screen. Each chart dot represents a 1 minute average value.

When the Chart (Low resolution) display is selected, a chart with an X-axis covering 10 days is
displayed. The value displayed on the Y-axis depends on the selection made in the input screen.
Each chart dot represents a 1 hour average value.

APF221384 29
Instruction book

3.5 Controller menu structure

Main menu
Press the Enter key to go to the main menu screen that is shown below.

Menu structure
Please find the tree structure on the 2 top levels below. The items are mentioned as they appear
on the screen from top to bottom and left to right. If questions regarding lower levels appear,
please consult your local Atlas Copco Customer Centre.
SERVICE PLAN

Topic Description
Overview Displays an overview of the running service plans
Service Plan Displays configuration of the service plans
Next Service Displays the next service task
History Displays a log of all automatic shutdowns that have appeared in the past

PROTECTIONS

Topic Description
General Displays a list of main protections
Fan Displays a list of overload fan motor protections
Filter(s) Displays a list of filter(s) protections
Expansion module Displays a list of expansion module communication protections
Element(s) Displays a list of protections related to the compressor stages
Convertor(s) Displays errors concerning actuators
Main Motor Displays motor related protections to avoid motor damage
Oil Circuit Displays a number of protections in the oil circuit

WEEK TIMER

30 APF221384
Instruction book

Topic Description
Displays 4 programmable week action schemes
Week Action Schemes Each week action scheme contains 7 programmable days and these days can
contain a number of successive events on selected time slots.
Contains 10 weeks and each week can be selected as 1 of the 4 week action
Week Cycle
schemes
Status Displays the status (On/Off) of the week timer functionality
Remaining Running Allows to set a timer to keep the compressor running for 1-240 minutes
Time

INFORMATION

Topic Description
Refers to the company website where more detailed info on the product can be
www.atlascopco.com found
More The More button displays the software versions, addresses, licenses, ...

TEST

Topic Description
Regreasing Test Allows to run the motor regreasing program
Allows a functionality check of the safety valve. (This feature can only be
Safety Valve Test
enabled by a service technician.)

COUNTERS

Topic Description
Displays the number of hours the compressor has been running in unloaded &
Running hours loaded mode
Loaded Hours Displays the number of hours the compressor has been running in loaded mode
Motor Starts Displays the number of motor starts
Load Relay Displays the number of load relay toggles (thus unload/load transitions)
Displays the number of manual motor starts that exceed the automatic motor
Fast Starts
starts
Displays the number of hours the compressor has been running between 1 %
VSD 1 — 20 % RPM
and 20 %
Displays the number of hours the compressor has been running between 20 %
VSD 20 — 40 % RPM
and 40 %
Displays the number of hours the compressor has been running between 40 %
VSD 40 — 60 % RPM
and 60 %
Displays the number of hours the compressor has been running between 60 %
VSD 60 — 80 % RPM
and 80 %
Displays the number of hours the compressor has been running between 80 %
VSD 80 — 100 % RPM
and 100 %
Accumulated air volume Displays the accumulated air volume
Module Hours Displays the number of hours the module has been powered
Direct stops Displays the number of compressor stops

APF221384 31
Instruction book

Topic Description
Emergency stops Displays the number of compressor stops by use of the emergency stop

REGULATION

Topic Description
The pressure setpoint that is higher than setpoint 1, where the loaded
Unloading pressure 1
compressor switches to unload
The pressure setpoint that is lower than setpoint 1, where the unloaded
Loading pressure 1
compressor switches to load
The pressure setpoint that is higher than setpoint 2, where the loaded
Unloading pressure 2
compressor switches to unload
The pressure setpoint that is lower than setpoint 2, where the unloaded
Loading pressure 2
compressor switches to load
Selection of 1st or 2nd pressure band. A pressure band is a combination of a
Pressure band used
loading pressure, a setpoint and an unloading pressure
Digital pressure band Allows a remote signal to control the pressure band selection.
selection
Reduced unload
pressure The unload pressure is reduced
Reduced load pressure The load pressure is reduced
Reduced setpoint The setpoint is reduced
Setpoint 1 Value of setpoint 1
Indirect stop level 1 Value of indirect stop level 1
Direct stop level 1 Value of direct stop level 1
Setpoint 2 Value of setpoint 2
Indirect stop level 2 Value of indirect stop level 2
Direct stop level 2 Value of direct stop level 2
Setpoint used Which setpoint is used
Regulation mode In which regulation mode is the compressor
Digital pressure band
selection Which pressure band is selected
Maximum speed factor Value of the maximum speed factor

INPUTS

Topic Description
General Displays a number of general readouts and bipolar states
Element(s) Displays a list of readouts related to the compressor stages
Fan Displays the status of the fan
Filter Displays the status of the filter
Converter(s) Displays the status of the converter(s)
Main Motor Displays a number of readouts and bipolar states concerning the main motor
Network Displays a number of bipolar states of remote signals
Oil Circuit Displays a number of readouts and bipolar states concerning the oil circuit

32 APF221384
Instruction book

OUTPUTS

Topic Description
General Displays a number of analogue and digital outputs
Fan Displays the activation of the fan
Element(s) Displays the activation of the element(s)
Converter(s) Displays the activation of the converter(s)
Oil circuit(s) Displays the activation of the oil circuit(s)
Main Motor Displays a number of digital outputs concerning the main motor status

SPM (Shock Pulse Method)

Topic Description
Motor, drive end Displays the vibration level at the drive end of the motor
Motor, non-drive end Displays the vibration level at the non-drive end of the motor
Low pressure stage, Displays the vibration level at the drive end of the low pressure compressor
drive end stage (when option is chosen)
Low pressure stage, non- Displays the vibration level at the non-drive end of the low pressure compressor
drive end stage (when option is chosen)
Gearbox Displays the vibration level at the gearbox

EVENT HISTORY

Topic Description
Displays a log file of all shutdowns and shows the status of the type, counters,
-
inputs and outputs at the moment a shutdown appeared

SETTINGS

Topic Description
Network Displays the CAN and ethernet configuration
Regulation Displays settings concerning the compressed air flow regulation
General Displays settings concerning time, date, unit and display time-out
Only displayed when compressor motor voltage < 690V and when ARAVF is
Automatic Restart available. Automatic Restart After Voltage Failure can only be enabled by a
service technician.
Access Key Displays the controller access level that can be modified with password input
Displays the availability to use a password to protect the controller from
User Password
unwanted manipulation
Main Chart Displays the input and the range of the main chart
Remote control Displays the remote control mode (Password protected)
Main Motor Displays the settings of the main motor

APF221384 33
Instruction book

3.6 Web server


All controllers have a built-in web server that allows direct connection to the company network or
to a dedicated PC via a local area network (LAN). This allows to consult certain data and settings
via a PC instead of the display of the controller.

Getting started

If the unit is equipped with a SMARTBOX, the network connection of the controller is
already in use. To allow the web server functionality, the network cable that is
connected to the SMARTBOX should be unplugged and replaced by the cable of the
company network.
If both the web server functionality and SMARTBOX are required, please contact your
local Customer Center for support.

Make sure you are logged in as administrator.


• Use the internal network card from your computer or a USB to LAN adapter.
• Use a UTP cable (CAT 5e) to connect to the controller (see picture below).

Configuration of the network card


• Go to Network and Sharing Center (1).

• Click on Change adapter settings (1).

34 APF221384
Instruction book

• Select the Local Area Connection, which is connected to the controller.

• Click with the right button and select Properties (1).

• Use the check box Internet Protocol version +4 (TCP/IPv4) (1) (see picture). To avoid
conflicts, uncheck other properties if they are checked. After selecting TCP/IPv4, click on the
Properties button (2) to change the settings.

• Use the following settings:


• IP Address 192.168.100.200 (1)
• Subnetmask 255.255.255.0 (2)
Click OK (3) and close network connections.

APF221384 35
Instruction book

Configure a company network (LAN) connection


• Ask your IT department to generate a fixed IP address in your company’s network.
• That IP address will be excluded from the DNS server, so it will be reserved for the
controller.
• Also get the correct Gateway and Subnet mask settings. For example:
• IP = 10.25.43.200
• Gateway = 10.25.42.250
• Subnet mask = 255.255.254.0
• Connect the controller to the company's network (LAN) by using a UTP cable (min. CAT 5e).

• Adapt the network settings in the controller:


• Go to Main Menu

36 APF221384
Instruction book

• Go to Settings (1)

• Go to Network (1)

• Go to Ethernet (1)

• Switch Off (1) the Ethernet communication to allow editing the settings

APF221384 37
Instruction book

• Adapt IP Address (1)


• Adapt Gateway IP (2)
• Adapt Subnet Mask (3)
• Switch On (4) the Ethernet communication

• Wait a few minutes so the LAN network can connect to the controller

Configuration of the web server


The internal web server is designed and tested for Microsoft® Internet Explorer.
Also "Opera", "Mozilla Firefox", "Safari"and "Chrome" should work.
Viewing the controller data

All screen shots are indicative. The number of displayed fields depends on the selected
options.

• Open your browser and type the IP address of the controller you want to view in your
browser (in this example http://192.168.100.100). The interface opens:

38 APF221384
Instruction book

Screen shot (example!)

Navigation and options


• The banner shows the unit type and the language selector. In this example, three languages
are available on the controller.

• On the left side of the interface, you can find the navigation menu.
If a license for ESi is foreseen, the menu contains 3 buttons.
• Machine: shows all generator settings.
• ES: shows the ESi status (if a license is provided).
• Preferences: allows to change temperature and pressure unit.

APF221384 39
Instruction book

Unit settings
All unit settings can be displayed or hidden. Put a check mark in front of each point of interest
and it will be displayed. Only the machine status is fixed and can not be removed from the main
screen.
Analog inputs
Lists all current analog input values. The measurement units can be changed in the preference
button from the navigation menu.

Counters
Lists all current counter values from controller and unit.

Info status
Machine status is always shown on the web interface.

Digital inputs
Lists all digital inputs and their status.

Digital outputs
Lists all digital outputs and their status.

40 APF221384
Instruction book

Special protections
Lists all special protections of the unit.

Service plan
Displays all levels of the service plan and their status. This screen shot underneath only shows
the running hours. It is also possible to show the current status of the service interval.

3.7 Programmable settings


A number of controller parameters are programmable. Check the generic screen shot on
programmable parameter Y in menu X below:

• (1) = the minimum value

APF221384 41
Instruction book

• (2) = the maximum value


• (3) = the selected value
• (4) = the factory setting icon (it only appears when the selected value equals the factory
setting value)

42 APF221384
Instruction book

4 Installation

4.1 Installation remarks

General

• The compressor is intended for indoor use only.


• Working with machinery controlled by a frequency converter requires special
safety precautions, which depend on the type of network (TN, TT or IT). Consult
Atlas Copco.
• When good EMC practices for installation are followed, the compressor qualifies
for installation in EMC category C3, according to EN61800-3, for use in a 2nd
environment (a 2nd environment includes all establishments other than those
directly connected to a low voltage power supply network which supplies buildings
used for domestic purposes).
• Cooling air for starter cabinet:
Contamination levels (ambient) according to IEC 60721-3-3
• Chemical gases: Class 3C2
• Solid particles: Class 3S2
• No conductive dust allowed
• No condensation allowed
• Maximum allowed relative humidity is 60 % in the presence of corrosive
gases

The compressor is not intended to be used on a low-voltage public network which supplies
domestic premises. Radio frequency interference can be expected if used on such a
network.

APF221384 43
Instruction book

4.2 Dimension drawing

Compressor dimensions

Dimension drawing of air-cooled G 160 VSD Pack, metric units

44 APF221384
Instruction book

Dimension drawing of air-cooled G 160 VSD Pack, imperial units

Text on figures

Reference Description
(1) View from right side
(2) Ventilation air inlet of the canopy
(3) Front view
(4) Compressor air inlet
(5) Ventilation air outlet of the canopy
(6) Ventilation for cubicle
(7) Electric cable entry
(8) Cooling air inlet of the motor
(9) View from left side

APF221384 45
Instruction book

Reference Description
(10) View A
(11) Compressor air outlet
(12) Data plate
(13) Cooling air outlet
(14) Top view
(15) Detail B
(16) Water outlet of the energy recovery (not present)
(17) Cooling water inlet (not present)
(18) Water inlet of the energy recovery (not present)
(19) Cooling water outlet (not present)
(20) Holes for the remote control of the pressure sensing and communication
(21) Manual drain
(22) Automatic drain
(23) 4 slotted holes only for horizontally pulling unit out of container

46 APF221384
Instruction book

4.3 Installation proposal

Compressor room example

Compressor room example of air-cooled G 160 VSD Pack

APF221384 47
Instruction book

Text on figures

Reference Description
(1) Install the compressor on a level floor suitable for taking its weight.
(2) Compressed air outlet valve (not in scope of supply).
(3) Delivery pipe:
The maximum pipe length can be calculated as follows:
L = (dp x d5 x p) / (450 x Qc1.85)
L = Length of pipe in m
dp = Pressure drop (recommended maximum = 0.1 bar)
d = Inner diameter of the outlet pipe in mm
p = Absolute pressure at the compressor outlet in bar(a)
Qc = Free air delivery of the compressor in l/s
The connection of the air delivery pipe is made on top of the main air net pipe in order
to minimize carry-over of possible condensate residue.
(4) Ventilation:
The inlet grid(s) and ventilation fan must be installed in such a way that any re-
circulation of cooling air to the compressor is avoided. The air velocity to the grid(s) has
to be limited to 5 m/s
The maximum allowable pressure drop over all cooling ducts together is 30 Pa
The maximum air temperature at the compressor intake opening is 46 °C (55 °C for
HAT version), minimum 0 °C
The required ventilation to limit the compressor room temperature can be calculated as
follows:
Qv = 0.1N / dT
Qv= Required ventilation capacity in m3/s
N = Shaft input of the compressor in kW
dT = Compressor room temperature over the outdoor temperature in °C
(5) Drain pipes to condensate collector. The drain pipes may not enter in the collector.
Individual drain pipes may not be interconnected to avoid interference
Compressor condensate contains oil. Depending on local legislation, it is recommended
to install an oil/water separator (consult Atlas Copco)
(6) Control cubicle with monitoring panel
(7) Main cable entry
(10) Minimum free area to be reserved for the compressor installation
(11) Distance to take out the motor from the right side
(12) Ventilation proposals
(A) Compressor air inlet and canopy ventilation air inlet
(B) Cooling air and motor ventilation outlet
(C) Motor cooling air inlet

48 APF221384
Instruction book

4.4 Main fuses and supply cables (section & maximum length)

Electrical connections

APF221384 49
Instruction book

Text on figures

Reference Description
(1) Customer's installation
(2) Compressor motor
(3) Optical

Warnings
• Obey local regulations if they are stricter than the regulations mentioned in this
document.
• Obey the applicable electrical directives when installing and connecting the
compressor to the power circuit:
• CSA/UL
• UL: UL508A
• CSA: C22.2
• Do not allow voltage drops that exceed 10% of the nominal supply voltage to allow
safe shutdown of the installation within 0.4 s
• Apply the listed cable sections on main supply cables AND earth cable.
• Do not exceed the ambient temperature listed in the Limits section to avoid cable
damage.
• Mount all cables on a horizontally ventilated cable tray.
• Do not stack or group cables as this avoids heat dissipation.
• Connect the power cable with the correct (CSA certified) cable lugs on the
terminals in the electrical cabinet.
• Respect a minimum distance of 10 mm (0.4") between stripped cable ends.
• Use only the prescribed cable types:
• CSA-UL: (R, RW, T) multicore 110 °C (230 °F)
• Display the fuse type information next to the fuse holder of the mains branch.

Cable size and main fuses


Overview of fuse types

Electrical approval Fuse type


CSA/UL class RK5 1

1 Class RK5 according UL248-9

Cables, fuses and maximum cable length for Pack compressors (CSA-UL)

FLA* FLA*
Maximum
(nominal (under-
Model Cables Fuses (A) cable
voltage) voltage)
length (m)
(A) (A)
G 160 VSD 2 x (3x MCM 600 + AWG 000) 1X (3X 500) 148 378 420

FLA*: Full-Load Ampacity

50 APF221384
Instruction book

4.5 Quality of safety components


When installing a remote emergency button, the following B10d values are advised:
• Emergency stop button: 500 000

4.6 Installation instructions for cubicle fan

Description
The fan must be installed on the cubicle roof with 8 bolts 0147 1963 08 as follows:
• Take off the top of the fan assembly (fan stays).
• Mount the fan with 8 bolts to the roof as shown in figure A (the fan is made invisible to show
the bolt positions).
• Reinstall the top.
Connect the fan cable as shown in figure B once the dummy connector is removed. The
dummy connector is required to allow a qualification run at the end of the assembly line.

Figure A

APF221384 51
Instruction book

Figure B

Completed assembly of the cubicle fan

4.7 Pictographs

Control panel of Elektronikon controller


Refer to the chapter Controller panel for pictographs of the Elektronikon controller.

52 APF221384
Instruction book

Other locations

Reference Description
13 Automatic condensate drain
14 Automatic condensate drain for optional oil/water separator (type OSD)
15 Manual condensate drain
16 Stop the compressor before maintenance or repair
17 Warning: under tension
18 Read Instruction book before starting the compressor
19 Switch off the voltage and depressurize the compressor before maintenance or repair
20 Before connecting the compressor electrically, consult the Instruction book for the motor
rotation direction
21 Torques for steel (Fe) or brass (CuZn) bolts
22 Consult the Instruction book before greasing
23 Switch off the voltage before removing the protecting cover inside the electric cabinet
24 Oil the gaskets, screw on the filters and tighten by hand (approx. one half turn)
25 Consult the Instruction book before maintenance or repair
26 Cooling water inlet
27 Cooling water outlet
28 Oil outlet

APF221384 53
Instruction book

5 Operating instructions

5.1 Initial start-up

Warning

The operator must apply all relevant Safety precautions.

Switch off the voltage before making any adjustment.

Outdoor/altitude operation
If the compressor is installed outdoors or if the air inlet temperature can be below freezing point,
precautions must be taken. In this case, and also if operating at high altitude, consult Atlas
Copco.

Moving/lifting
The compressor can be moved by a lift truck using the slots in the frame. Make sure that the
forks protrude from the other side of the frame. The compressor can also be lifted after inserting
beams in the slots. Make sure that the beams cannot slide and that they protrude from the frame
equally. The chains must be held parallel to the bodywork by chain spreaders in order not to
damage the compressor. The lifting equipment must be placed in such a way that the
compressor is lifted perpendicularly. Lift gently and avoid twisting.

General preparations

Step Action
1 Install the compressor, see the sections Dimension drawing, Installation proposal and
Main fuses and supply cables.
2 Stick labels near the control panel to warn the operator that:
• the compressor may start automatically after a voltage failure
• the compressor is automatically started and stopped
• the compressor may be remotely controlled
3 A number of VCI (Volatile Corrosion Inhibitor) plates are provided inside the bodywork to
protect the compressor against corrosion. Remove the plates.
4 If the compressor has not run for the past 6 months, it is required to improve the
lubrication of the compressor element before starting. Fill up the compressor element as
described in section Oil change (paragraph: Filling the compressor element with oil).
5 Check that the compressor is filled with oil; the pointer of the oil level indicator should be
in the green range (see the section Oil change).

54 APF221384
Instruction book

Protection during transport

Transport fixtures

Step Action
1 The coupling housing supports, motor support and air receiver supports are secured to
the frame, immobilizing the vibration dampers during transport.
2 Remove the bushes (1) from the gear casing supports and the motor support.
3 Remove the brackets fitted next to the air receiver supports.

Electric cabinet

Step Action
1 Check that the electrical connections correspond to the local codes. The installation
must be earthed and protected by fuses in all phases. An isolating switch must be fitted.
2 Check the wires on the transformers for correct connection.
3 Check the setting of the circuit breakers (see the section Settings of circuit breakers).

APF221384 55
Instruction book

Start up

Step Action
1 Close the drain valves (see the section Cooling and condensate system).
2 Switch on the voltage.
3 Start the compressor and stop it immediately. Check the rotation direction of the drive
motor while the motor is coasting to a stop. To determine the rotation direction of the
motor, look at the fan through the grating at the non-drive end of the motor. The correct
rotation direction is indicated by an arrow on the gear casing and on the fan cowl.
On air-cooled compressors, check the rotation direction of the fan motor. The fan is
visible through the grating in the air inlet panel (see section Dimension drawing). The
correct rotation direction is indicated by arrows on the fan inlet plate.
4 If the rotation direction is wrong, press the emergency stop button, switch off the voltage
and reverse two incoming electric lines.
If the rotation direction of the fan motor is wrong, consult your Atlas Copco customer
centre.
5 Run the compressor for a few minutes and check that it is operating normally.

5.2 Before starting

Warning

The operator must apply all relevant safety precautions. See the section Safety precautions.
Switch off your mobile phone when in the vicinity of a VSD compressor which is under
tension.

Control panel

Elektronikon Graphic controller

Reference Name
1 Alarm

56 APF221384
Instruction book

Reference Name
2 Service
3 Automatic operation
4 Voltage on
5 Enter
6 Escape
7 Scroll keys
8 Stop
9 Start

Procedure

Step Action
1 Switch on the voltage. Voltage on LED lights up.
2 Close the condensate drain valves (see the section Cooling and condensate system).
3 Open the air outlet valve.
4 Check the oil level indicator (see the section Oil change). The pointer should be in the
green range or orange range.

5.3 Starting

Warning

The operator must apply all relevant Safety precautions.

Control panel

Elektronikon Graphic controller

APF221384 57
Instruction book

Reference Name
1 Alarm
2 Service
3 Automatic operation
4 Voltage on
5 Enter
6 Escape
7 Scroll keys
8 Stop
9 Start

Procedure

Step Action
1 Press the start button. The compressor starts running in unloaded condition. The
automatic operation LED lights up.
2 Approx. 10 seconds later (programmable), the compressor starts running loaded.

5.4 During operation

Warning

The operator must apply all relevant Safety precautions.

The operator should immediately stop the machine in case of oil leaks internally in the
machine as well as externally and consult a competent technician to resolve the cause.
The machine should not be restarted before the problem has been remedied.
The load cycle of the compressor must be limited to maximum two cycles per minute.

58 APF221384
Instruction book

Compressors with Elektronikon Graphic controller

Elektronikon Graphic controller

1. Check the readings on the display.


2. When reaching the preset unloading pressure, shown on the display, the compressor will
start running unloaded. From now on, the electronic control module will calculate the
optimum moment to stop and restart the compressor motor automatically, depending on the
maximum permissible number of motor starts and on the air consumption.
3. To unload the compressor manually, select Unload on the display using the cursor keys and
press the Enter key. To put the compressor back into automatic operation, select Load on
the display using the cursor keys and press the Enter key.

If the compressor is stopped, it may start automatically.

5.5 Checking the display

Warning

Before carrying out any maintenance, repair work or adjustment, stop the compressor,
press the emergency stop button and switch off the voltage. Close the air outlet valve
and open the manual condensate drain valve.

APF221384 59
Instruction book

Elektronikon Graphic controller

Control panel of Elektronikon Graphic controller

1. Regularly check the display for readings and messages. Normally, the main display is
shown.
2. Always check the display and remedy the trouble if alarm LED (4) is alight or blinks.
The display will show a service message if a service plan interval has been exceeded or if a
service level for a monitored component has been exceeded. Carry out the service actions
of the indicated plans or replace the component and reset the relevant timer.
Regularly check the Inputs and Outputs menus for a quick look at the compressor status.

5.6 Stopping

Important

After pressing the stop button, the compressor will run unloaded for 30 seconds. The
compressor stops after this period. A start command during this period is ignored.
After stopping, the compressor is prevented from restarting within a programmable time
(20 seconds). A start command given during this minimum stop time will be memorized;
the automatic operation LED lights up. The compressor will start when the minimum
stop time has elapsed.

60 APF221384
Instruction book

On compressors equipped with an Elektronikon Graphic controller

Control panel

Procedure

Frequently stopping the compressor using the emergency stop button may damage the
compressor. Only use the emergency stop button in case of emergency.

Step Action
1 Press stop button (13). The compressor will run unloaded for 30 seconds and then stop.
2 To stop the compressor in case of emergency, press the emergency stop button. Alarm
LED (4) starts flashing. After remedying the trouble, unlock the emergency stop button
by pulling it back.
3 Close the air outlet valve.
4 Open the condensate drain valves.
5 Switch off the voltage.

5.7 Taking out of operation

Disconnecting the compressor


At the end of the service life of the compressor, proceed as follows:

Step Action
1 Stop the compressor and close the air outlet valve.
2 Switch off the voltage and disconnect the compressor from the mains.
On VSD compressors, wait at least 6 minutes as hazardous high voltage remains on the
condensers of the start and speed regulation unit.
3 Depressurize the compressor by opening the drain valve and loosening the oil filler plug
one turn.

APF221384 61
Instruction book

Step Action
4 Shut off and depressurize the part of the air net which is connected to the outlet valve.
Disconnect the compressor air outlet pipe from the air net.
5 Drain the oil and condensate circuits.
6 Disconnect the compressor condensate piping from the condensate drain net.

5.8 Use of air receiver

Instructions

Step Action
1 This equipment can contain pressurised air and oil; be aware of its potential danger if
used improperly.
2 This equipment must only be used as compressed air/oil separator and must be
operated within the specified limits.
3 No alterations must be made to this equipment by welding, drilling, grinding or other
methods of mechanical working without written permission of the manufacturer. If there
is damage to a part under pressure from any cause, the complete part must be
replaced.
4 For the oil separator vessel: original bolts have to be used after opening for inside
inspection. The bolts must be removed and fitted with the correct tool. The bolts must be
tightened with a torque of 355 Nm (+/- 85 Nm). Damaged bolts must not be re-used. O-
rings must be replaced.
5 The safety valve is designed in such a way that the pressure will not permanently
exceed the maximum allowable operating pressure of the vessel, except for short
pressure surges up to 1.1 times the design pressure.
6 Only use oil specified by the manufacturer.
7 Make sure the vessel is fully depressurised before opening the drain plug or fill plug.
8 This vessel and other parts under pressure have been designed and built to guarantee
an operational lifetime in excess of 20 years and an infinite number of pressure load
cycles. A visual inspection (for damage, non-authorised alterations,...) of the vessel (at
the outside and inside) is recommended every 5 years. Make sure the vessel is fully
depressurised and isolated before carrying out an internal inspection.
9 At every inspection, also check the oil drain flexible. Replace if there is any wear or
damage.

62 APF221384
Instruction book

6 Maintenance

6.1 Preventive maintenance schedule

Warning

Before carrying out any maintenance, repair work or adjustment, proceed


as follows:
• Stop the compressor.
• Press the emergency stop button.
• Close the air outlet valve and open the manual condensate drain valves.
• For compressors equipped with electronic water drains, press the test
buttons on top of the electronic drains until the air system between the air
receiver and the outlet valve is fully depressurized.
• Switch off the voltage.
• Open and lock the isolating switch.
The operator must apply all relevant Safety precautions.

Warranty - Product Liability


Use only authorized parts. Any damage or malfunction caused by the use of unauthorized parts
is not covered by Warranty or Product Liability.

General
When servicing, replace all removed gaskets, O-rings and washers.

Preventive maintenance schedule

The maintenance schedule is prior to the maintenance warnings displayed on the


controller. It is the responsibility of the owner to carry out the required maintenance at
the appropriate moment.

Period Running hours Operation


Daily 8 Check readings on display.
Daily 8 Check that condensate is discharged during loading.
Daily 8 Check oil level. Before starting, the level should be in the middle of
the sight-glass.
3-Monthly -- Clean compressor.
3-Monthly -- Check for possible leaks.
3-Monthly 500 Check the coolers; clean them if necessary. See the section Coolers.
3-Monthly -- Remove air filter elements and inspect
Yearly -- Have safety valve tested
Yearly -- Have all flexibles inspected
Yearly 8000 Replace oil filters
Yearly 8000 If Roto-Xtend Duty Fluid is used, change oil
2-Yearly 8000 Have oil separator element replaced

APF221384 63
Instruction book

Period Running hours Operation


When displayed -- Carry out service action according to the displayed service plans.

When operating in a dusty atmosphere, inspect the air filters more frequently.
Use always Atlas Copco filters.
The separator element must also be replaced when the pressure difference over the
element exceeds 0.8 bar (12 psi). Check the pressure drop when the compressor is
running loaded and preferably with a stable working pressure.
Damaged flexibles must be replaced immediately.

Service agreements
Atlas Copco Customer Centres have a range of service agreements to suit your needs:
• An Inspection Plan
• A Preventive Maintenance Plan
• A Total Responsibility Plan
Contact your Customer Centre to set up a tailor-made service agreement. It will ensure optimum
operational efficiency, minimize downtime and reduce the total life cycle costs.

Service plan
A number of service operations are grouped (called Level A, Level B, Level C...). Each level
stands for a number of service actions to be carried out at the time intervals programmed in the
Elektronikon regulator.
When a level is reached, a message will appear on the screen. After carrying out all service
actions, the interval timers must be reset using the “Reset” key in the “Service” menu. Consult
your Atlas Copco Service Centre.

6.2 Motors

Warning

• Stop the compressor and switch off the voltage. The operator must apply all
relevant Safety precautions.
• Never mix greases of different brands or types.
• Motor bearing maintenance is crucial to avoid motor damage.

Maintenance is limited to applying the motor grease mass at the interval that is stated on the
motor bearing data plate attached to the motor.
Contact your local Atlas Copco customer center in following cases:
• If not all the necessary data are present on the bearing plate.
• If the correct lubrication method is not clearly stated in the general instruction book.
• If the maximum ambient/bearing temperature differs from the one mentioned on the motor
data plate.

64 APF221384
Instruction book

Fan motors
The bearings of the fan motors are greased for life. The fan motor must be replaced after 40000
operating hours.

ABB drive motor

Compressor type Power Interval Amount Interval Amount


D end D end ND end ND end
G 160 VSD 160 kW 4000 h 20 gr (0.71 oz) 4000 h 20 gr (0.71 oz)

6.3 Oil specifications

Atlas Copco Roto-Xtend Duty Fluid


Atlas Copco Roto-Xtend Duty Fluid is a high-quality synthetic lubricant for oil-injected scroll and
screw compressors which keeps the compressor in excellent condition. Roto-Xtend Duty Fluid
can be used for compressors operating at ambient temperatures between 0 ˚C (32 ˚F) and 46 ˚C
(115 ˚F) (see section Service kits).

Important

Never mix oils of different brands or types.

6.4 Oil change

Warning

The operator must apply all relevant Safety precautions.

APF221384 65
Instruction book

Vent, filler and drain plugs

Oil drain plugs on compressor elements

Vent, filler and drain plugs on air-cooled compressors

66 APF221384
Instruction book

Procedure

Step Action
1 Run the compressor until warm.
Stop the compressor.
Close the air outlet valve.
Switch off the voltage.
Wait a few minutes.
Depressurize by unscrewing plug only one turn to permit any pressure in the system to
escape.
2 Loosen vent plugs on top of the oil coolers.
3 Drain the oil by removing the drain plugs.
Plugs are fitted on the:
• Air receiver / Oil separator with drain point
• Oil stop valve
• Check valve
• Gearbox
• Oil coolers of air-cooled compressors
• Oil filter housing
Tighten the plugs after draining.
4 Remove filler plug.
Fill the air receiver / oil separator with oil until the level reaches the filler opening.
Refit and tighten plug.
Tighten the vent plug of the oil cooler.
5 Disconnect the air inlet hose from the inlet bend.
Pour 10 liter of oil into the compressor stage.
Reinstall the air inlet hose.
6 Run the compressor loaded for a few minutes to allow the oil cooler by-pass valve to
open.
Stop the compressor.
Wait a few minutes.
7 Depressurize the system by unscrewing plug only one turn to permit any pressure in the
system to escape.
Remove the plug.
Fill the air receiver / oil separator with oil until the level reaches the filler opening.
Tighten the filler plug.

APF221384 67
Instruction book

Step Action
8 After carrying out all service actions in the relevant “Service Plan”, reset the service
warning.
Refer to the Service menu section.

6.5 Oil filter change

Warning

Stop the compressor and switch off the voltage. The operator must apply all relevant
Safety precautions.

Position of oil filters

Procedure

68 APF221384
Instruction book

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage. Wait a few
minutes and depressurize the air receiver by unscrewing the oil filler plug (of the air
receiver) only one turn to permit any pressure in the system to escape.
2 Use an oil pan to avoid possible oil spillage. Unscrew the oil filters only one turn and
wait a few minutes to let the oil of the filter flow back into the oil separator. Remove the
oil filters.
3 Clean the filter seats on the manifold. Oil the gaskets of the new filters and screw the
filters into place until the gaskets contact their seats. Then tighten with a maximum
torque of 10 Nm.
4 Tighten the oil filler plug (of the air receiver).
5 Reset the service warning after carrying out all service actions in the relevant Service
Plan. Refer to the Service menu section.

6.6 Storage after installation

Procedure
Run the compressor, e.g. twice a week, until warm.

If the compressor is going to be stored without running from time to time, protective
measures must be taken. Consult the Atlas Copco Customer Centre.

6.7 Service kits

General
Service kits comprise all parts needed for servicing components and offer the benefits of genuine
Atlas Copco parts while keeping the maintenance budget low. All service kits are indicated in the
relevant Parts Lists.

Atlas Copco Roto-Xtend Duty Fluid


Roto-Xtend Duty Fluid can be ordered in the following quantities:
• 5-litre can: 2901 1700 00
• 20-litre can: 2901 1701 00
• 209-litre drum: 2901 1702 00
See Oil specifications.

APF221384 69
Instruction book

7 Adjustments and servicing procedures

7.1 Air filters

Warning

Stop the compressor, close the air outlet valve, press the emergency stop button and
switch off the voltage. The operator must apply all relevant Safety precautions.

Position of air filters

Air filters (1)

Procedure

Step Action
1 Remove the filter elements (1).
2 Fit the new filter elements (1).
3 Reset the service warning after carrying out all service actions in all applicable service
plans. Refer to the service menu section of the regulator.

70 APF221384
Instruction book

7.2 Coolers

Warning

Stop the compressor, press the emergency stop button and switch off the voltage. The
operator must apply all relevant Safety precautions.

Procedure

Cooler block (1) of air-cooled G 160 VSD

Keep the cooler block clean to maintain the cooling efficiency.


On air-cooled compressors proceed as follows:

APF221384 71
Instruction book

Service panel of the cooler (1), air-cooled cooler

Step Action
1 Open the service door at the cooler side.
2 Remove the service panel (1) at the cooler side.
3 Remove any dirt form the coolers with a fibre brush, brush in the direction of the fins.
Also remove any dirt from the fans.
4 Clean the coolers with an air jet in the reverse direction to normal flow. Use low
pressure air; if necessary, the pressure may be increased up to 6 bar (e) (87 psig).
5 If it is necessary to clean the coolers with a cleaning agent, consult Atlas Copco.
6 Mount the service panel.
7 Close the door.

7.3 Safety valve

Warning

Stop the compressor and switch off the voltage. The operator must apply all relevant
Safety precautions.

Never run the compressor without safety valves.


No adjustments are allowed.

72 APF221384
Instruction book

Testing

Location of safety valve on air-cooled compressor

The valve can be tested on a separate compressed air line.


Consult the Atlas Copco Customer Centre if the valve does not open at the correct pressure (see
the section Settings of safety valve).

APF221384 73
Instruction book

8 Problem solving

8.1 Problem solving

Warning

Before carrying out any maintenance, repair work or adjustment, stop the compressor,
press the emergency stop button and switch off the voltage. Close the air outlet valve
and open the manual condensate drain valves.
Open and lock the isolating switch.
The operator must apply all relevant Safety precautions.

Control panel

Elektronikon Graphic controller

Faults and remedies

A service message appears on the display


Stop the compressor and carry out the indicated service actions.
Reset the message. Refer to the Service menu section.

A shut-down warning message appears on the display


The alarm LED (4) will light up indicating that the temperature at the outlet of the compressor elements is
too high. The message disappears as soon as the cause of the problem is remedied.

74 APF221384
Instruction book

Unit is shut down


The alarm LED (4) will flash indicating either that the outlet temperature is too high or that the motor
overload relay has tripped. Remedy the problem.
Move the cursor to the action button Menu and push the Enter key (10). Using the Scroll keys (12), move
the cursor to the protections icon. Push the Enter key (10). Move the cursor to the blinking icon and press
the Enter key (10). Move the cursor to the Reset button and press the enter key again.

Multiple shut-down
If there are multiple sequential failures with short time intervals on a specific shut-down functionality,
consult your Atlas Copco Customer Centre.

Excessive oil consumption


Have the compressor inspected by your Atlas Copco Customer Centre.

Condition Fault Remedy


Condensate is not discharged from Discharge pipe of condensate Check and correct as necessary.
condensate traps during loading. trap clogged.
WSD (electronic water drain) Consult Atlas Copco.
malfunctioning.

Condition Fault Remedy


Compressor air delivery or pressure Air consumption exceeds air Check equipment connected.
below normal. delivery of compressor.
Choked air filters. Replace filters.
Air leakage. Check and correct.

Condition Fault Remedy


Compressor element outlet Oil level too low. Check and correct.
temperature or delivery air Oil coolers clogged. Refer to the Coolers section.
temperature above normal.
Air cooler clogged. Refer to the Coolers section.
On air-cooled compressors, Check and correct as necessary.
insufficient cooling air or cooling
air temperature too high.

APF221384 75
Instruction book

9 Technical data

9.1 Readings on display

Important

The readings are valid when operating under reference conditions. See the
section Reference conditions.

Normally the main display is shown (see the section Function keys), indicating
the actual air outlet pressure and the actual compressor status. The arrow down
key allows the operator to call up other information such as actually measured
pressures and temperatures.

Important readings

Compressor outlet pressure bar(e) (psig) Depends on programmed


unloading and loading
pressures
Pressure drop over air filters bar Below 0.05
Pressure difference over oil separator bar Below 0.8
Oil injection pressure at the compressor elements bar(e) (psig) Depends on programmed
unloading and loading
pressures
Compressor outlet temperature, air-cooled Pack compressors ˚C Approx. 28
Cooling air inlet temperature of Pack compressor ˚C Below 46

9.2 Reference conditions

Reference conditions

Absolute inlet pressure bar(a) 1


Relative air humidity % 0
Air inlet temperature ˚C 20
Nominal working pressure See Compressor data
Cooling medium inlet temperature ˚C 20

76 APF221384
Instruction book

9.3 Limits

Limits

The compressor will automatically adapt its minimum working speed when necessary to
protect the compressor element bearings.
This will improve the lubrication of the bearings and thus will result in a longer lifetime of
the compressor element.

Minimum air inlet/ambient temperature ˚C 0


Maximum air inlet/ambient temperature ˚C 40
Minimum cooling air temperature ˚C 0
Maximum cooling air temperature ˚C 40
Maximum working pressure See section Compressor
data

9.4 Settings of safety valve

Compressor type Setting


For VSD Pack compressors 15 bar

9.5 Settings of overload relays, fuses and circuit breakers

Setting of fan protection for air-cooled compressors

Supply voltage (V) Q25/Q26 (A)


460 5.0

9.6 Compressor data

Data for 125 psi (8.6 bar) 60 Hz compressors

Units G 160 VSD


Maximum working pressure, Pack bar(e) 9.1
Nominal working pressure bar(e) 6.9
Motor shaft speed for:
Pack compressors r/min 3095
Power input, Pack kW 209
Oil capacity l 92

APF221384 77
Instruction book

Units G 160 VSD


Sound pressure level dB(A) 80

78 APF221384
Instruction book

10 Pressure equipment directives

General
This machine is a pressure assembly of category IV according to 2014/68/EU.
Parts of article 4.3 of 2014/68/EU are subject to Sound Engineering Practice (SEP).
Parts of category I according to 2014/68/EU are integrated into the machine and fall under the
exclusion of article 1.2, (f)(i).
Parts subject to the Simple Pressure Vessel Directive 2014/29/EU are excluded from 2014/68/EU
according to article 1.2 (c).
The following pressure bearing parts are subject to 2014/68/EU Pressure Equipment Directive
greater than or equal to category II:
• Oil separator vessel : Cat IV
Design standard : ASME section VIII div. 1.
Material: SA-395, according ASME BPVC section II-A
The design pressure of the vessel is 15 bar(e) (218 psi)
Fatigue is calculated for an infinite lifetime taking into account the dP as mentioned in the
table below
• Safety valve : Cat IV
Design code : AD-Merkblätter, A2

Re-inspection data

APF221384 79
Instruction book

Reference Description
(1) Cast identification
(2) Data plate
H Height of the vessel (without support and cover)
D Diameter of the vessel

Part V dP MWAC H TH D CF (cover) E


number (vess
el)
1635 1489 210 l 14 bar Vessel shell: 1076 mm 1284 mm 550 mm 0.8 0.85
08 5.9 mm
Vessel
bottom bowl:
5.8 mm
Cover: 8.5
mm

Used abbreviations:
• V: Volume
• dP: Pressure difference
• MWAC: Minimum wall thickness after corrosion
• H: Height of the vessel
• TH: Total height including the supports
• D: Diameter of the vessel
• CF: Casting factor (according ASME BPVC section VIII div 1)
• E: Welding coefficient/factor

80 APF221384
Instruction book

11 Documentation

APF221384 81
We stand by our responsibilities towards our customers, towards the environment and
the people around us.
We make performance stand the test of time.
This is what we call - Sustainable Productivity.

Atlas Copco Airpower


Oil-free Air Division, Boomsesteenweg 957, 2610 Wilrijk, Belgium
Phone: +32 (0)3 870 21 11

Atlas Copco Airpower NV. All rights reserved. Designs and specifications are subject to change without notice or obligation.

You might also like