Professional Documents
Culture Documents
Rev E
Rev E
Revision E
June 2011
Instruction Manual
EN Instruction Manual
ES Manual de instrucciones
FR Manuel d’instruction
IT Manuale di istruzioni
DE Bedienungsanleitung
PT Manual de Instruções
CS Návod k použití
PL Instrukcja obsługi
TU Kullanma Kılavuzu
ZH 说明书
Contents
PERSONAL PROTECTIVE EQUIPMENT & ATTIRE. . . . . . . . . . . 4 • PAGE 1 – MAINTENANCE STATUS OF ALL ITEMS. . . . . . . . . . 12
• PAGE 2 – EQUIPMENT REFERENCE DATA. . . . . . . . . . . . . . . . . 12
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
• PAGE 3 - MAINTENANCE STATUS OF ALL ITEMS . . . . . . . . . . 12
SERVICE, MAINTENANCE, AND REPAIR. . . . . . . . . . . . . . . . . . . 4
• PAGES 4 THROUGH 7 – INDIVIDUAL MAINTENANCE ITEMS
COMPRESSOR OPERATING STATES. . . . . . . . . . . . . . . . . . . . . . 5 CONFIGURATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
“STOPPED” STATE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 GENERAL SETTINGS FOLDER. . . . . . . . . . . . . . . . . . . . . . . . . . . 13
• WAITING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 1 – LANGUAGE SELECTION. . . . . . . . . . . . . . . . . . . . . . . . 13
• NOT READY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 2 – TIME & DATE SETTINGS. . . . . . . . . . . . . . . . . . . . . . . . 13
• READY. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 3 – HOME PAGE SELECTION. . . . . . . . . . . . . . . . . . . . . . . 13
“ROTATING” STATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 4 – BACKLIGHT SETTINGS. . . . . . . . . . . . . . . . . . . . . . . . . 13
• STARTING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 5 and 6 – UNITS OF MEASURE SETTINGS. . . . . . . . . . . 14
• UNLOADED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 7 – ADDRESS SETTINGS. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
• LOADING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 • PAGE 8 – DCU PORT CONFIGURATION
• MINLOAD, LOADED, FULL LOAD AND MAXLOAD. . . . . . . . . . 5 (MODBUS SETTINGS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Contents (Contd..)
Only allow Ingersoll Rand trained technicians to perform maintenance on “Original instructions are in English. Other languages are a translation of
these products. For additional information contact Ingersoll Rand or nearest the original instructions.”
Distributor.
Refer all communications to the nearest Ingersoll Rand Office or Distributor.
The use of other than genuine Ingersoll Rand replacement parts may result
in safety hazards, decreased performance, and increased maintenance and
will invalidate all warranties.
SAFETY INFORMATION
EXPLANATION OF SAFETY SIGNAL WORDS OPERATION
Throughout this manual there are steps and procedures which, if not • This product must only be operated by trained (or qualified) personnel.
followed, may result in a hazard. The following signal words are used to • Never remove or tamper with safety devices, guards or insulation
identify the level of potential hazard. materials fitted to the unit.
Indicates an imminently hazardous situation • The product must only be operated at the supply voltage and
DANGER which, if not avoided, will resulting death or frequency for which it is designed.
serious injury. • If the user employs an operating procedure, an item of equipment, or
Indicates a potentially hazardous situation a method of working which is not specifically recommended, the user
WARNING which, if not avoided, could result in death or must ensure the product will not be damaged or made unsafe and
serious injury. that there is no risk to persons or property.
Indicates a potentially hazardous situation • When the main power is switched on, lethal voltages are present in the
CAUTION which, if not avoided, may result in minor or electrical circuits and extreme caution must be exercised whenever it
moderate injury or property damage. is necessary to carry out any work on the unit.
Indicates information or a company policy that • Do not open access panels or touch electrical components while
NOTICE relates directly or indirectly to the safety of voltage is applied unless it is necessary for measurements, tests
personnel or protection of property. or adjustments. This work must only be carried out by a qualified
electrician or technician equipped with the correct tools and
appropriate protection against electrical hazards.
Note: Important Information
SERVICE, MAINTENANCE, AND REPAIR
GENERAL WORKPLACE SAFETY • Repairs should be made only by authorized trained personnel. Consult
your nearest Ingersoll Rand authorized service provider.
• The information presented in this manual should be used in
conjunction with your workplace safety program. • Lethal voltages are used within the product. Use extreme caution
when carrying out electrical checks. Isolate the power supply before
• It is the responsibility of each individual to ensure that they work in a starting any maintenance work.
safe manner and in compliance with any local law or site regulations.
• If replacement parts are required, use only genuine Ingersoll Rand
• Keep the work area clear of hazards. parts.
• Assess hazards, make a list, and discuss with appropriate personnel. • Ensure that all instructions concerning operation and maintenance are
• Know how to quickly contact emergency assistance. strictly followed and that the complete product, with all accessories
and safety devices, is kept in good working order.
DOCUMENTATION, DECALS & TAGS • The accuracy of sensing devices must be checked on a regular basis.
• Read and understand this manual before handling and installing this They must be calibrated or replaced when acceptable tolerances are
product. exceeded. Always ensure any pressure within a compressed air system
• Locate, read and understand all hazard alert symbols, text decals and is safely vented to atmosphere before attempting to remove or install
tags which point out items of extreme importance to personal safety. a sensing device.
• It is your responsibility to make this information available to others. • The product must only be cleaned with a damp cloth, using mild
detergents if necessary. Avoid the use of any substances containing
• Failure to observe these safety guidelines could expose personnel to corrosive acids or alkalis.
potentially hazardous situations which, if not avoided, could result in
death or serious injury. • Do not paint any of the Xe-145F modules or obscure any indicators,
instructions, warnings, or data labels.
• If you have any questions about safety or procedures not included in
this manual, ask your supervisor or contact any Ingersoll Rand office • Battery may explode if mistreated. Do not recharge, disassemble, or
or qualified Ingersoll Rand distributor. subject to fire.
• The battery used in controller model Xe-145F, xe-fmm / xe-fem must
PERSONAL PROTECTIVE EQUIPMENT & ATTIRE be replaced at an Ingersoll Rand service center or by an authorized
• Wear personal protective equipment that is appropriate for the task Ingersoll Rand service technician.
(i.e. safety glasses with side shields, respirator, hearing protection, cut
resistant gloves and safety shoes) at all times.
• Long hair must be tied back or otherwise secured.
• Clothing must be close-fitting.
• Do not wear jewelry.
• LOADING
When a valid load command is issued, the compressor will enter this state.
This state exists until the MinLoad state is satisfied. The duration of this state
depends upon PID settings for the inlet valve at the MinLoad state and the
demand for air.
• UNLOADING
This state occurs when a valid Unload command is issued and will persist
until the compressor reaches the Unloaded state.
• COASTING
When a trip or any stop command is issued and the compressor is running,
the motor will be de-energized and the compressor will begin to coast to a
Stopped state. This state will remain as long as the adjustable Coast Timer is
in effect. At the end of the timer, the compressor will enter either the Ready
or Not Ready state.
Icon Description
Start of the page selection area.
• PASSWORD PROTECTION
There is one level of password protection in the Xe-145F that is entered on
page one of the CONTROL SETTINGS folder. The default password is 2003. The
password can only be changed or reset through the Service Tool software.
• DASHBOARD ICONS (< >) - Indicates adjustable parameters that are not password
The dashboard is intended to be a quick at-a-glance view of system status. protected.
The following table lists standard dashboard icons and their definition. (RO) - Indicates read-only values.
Note that the color of these icons changes based on the state set by the
application while running. (RO/ap) - Indicates read-only parameters that are adjustable from
another page.
Name Icon Description
(RO/st) - Indicates read-only parameters that are only adjustable
Prelube Pump Compressor’s prelube pump is in the through the Service Tool software.
running state.
• PAGE 2 - COUNTERS
Network Control The FMM’s network control is enabled.
HOME FOLDER
• PAGE 1 – SYSTEM OVERVIEW Hour Meters (RO/st) indicate the hours that: the FMM has been powered up,
the compressor has been running, the compressor has run in MinLoad, and
the compressor has run Loaded.
Starts (RO/st) indicates the number of times the FMM’s Starter output (CR1)
has been energized.
Date & Time (RO/ap) is adjustable and configurable in the GENERAL
SETTINGS folder.
• PAGES 4 THROUGH 6 – ANALOG INPUTS Unloaded for the time shown. This saves energy/money by preventing the
compressor from running Unloaded for extended periods. This is usually used
in conjunction with Auto Dual Mode and Auto Hot Start.
Once the cursor is on the enable box, press the LEFT key to access the time.
The units are fixed as minutes.
Auto Hot Start (< >) when purchased, enables the FMM to Start and then
Load the compressor once the System Pressure drops below the shown
setpoint. This is usually used in conjunction with the Unload Shutdown Timer.
Once the cursor is on the enable box, press the LEFT key to access the
setpoint. The units are selectable in the GENERAL SETTINGS folder.
All of the above are analog inputs that can be scaled in the CONTROL • PAGE 2 - AUTODUAL
SETTINGS folder. The Units of Measure can be changed in the
GENERAL SETTINGS folder. The number of pages, stages, and analog
inputs will vary depending on the compressor model.
CT Input (RO) on the last page represents Motor Current and is typically only
present on electric motor driven compressors. This can be scaled through the
CT Ratio parameter in the CONTROL SETTINGS folder.
OPTIONS FOLDER
• PAGE 1 – REMOTE CONTROL AND AUTO HOT START
Auto Dual (< >) enables Auto Dual Mode. A [ x ] appears when the function
is enabled.
Unload Point (< >) & Unload Delay Time (< >): If Auto Dual is enabled, the
FMM will Unload the compressor if the Bypass Valve (BV) position stays at, or
above, the Unload Point position continuously for the amount of time shown;
the Unload Delay Time. The Unload Point position is usually the BV position
where the Check Valve closes.
This saves energy/money by preventing the compressor from running in
MinLoad for extended periods while not contributing to the air system. The
compressor’s driver uses more energy when the compressor is in MinLoad
versus Unloaded.
Reload Pressure (< >): If the compressor in running Unloaded in Auto Dual
Mode, the FMM will Load the compressor if the System Pressure drops below
the Reload Pressure which is set as a percentage of the Pressure Setpoint. It
Remote Control over Web (< >) enables remote control of the FMM through
is set as a percentage of the Pressure Setpoint in order to ensure the Reload
the DCU’s Web Pages. This allows control from computers accessing the Web
Pressure always stays lower than the Pressure Setpoint, especially in cases
Pages via the Ethernet port.
where the Pressure Setpoint is changed regularly.
Remote Control via Comms (< >) enables remote control of the FMM via a
For example, if the Reload Pressure is set to 98% and the Pressure Setpoint is 110
RS485 serial port.
psi, the System Pressure would have to drop below 107.8 psi in order for the FMM
Remote Control over hardwire (< >) when purchased, enables remote to Load the compressor. If the Pressure Set point was changed to 100 psi, the
control of the FMM via digital inputs that are hardwired to remote switches/ System Pressure would have to drop below 98 psi before Loading would occur.
contacts.
Enable ESS anti-Bypass (< >) enables Anti-Bypass Control. A[ x ] appears when
Unload Shutdown Timer (< >) when purchased, enables the FMM to Stop the function is enabled. The number beside the checkbox indicates the Anti-
the compressor if it runs continuously Bypass gain. It provides the setting to encourage the compressor to share the
load.
(< >) - Indicates adjustable parameters that are not password Event Name Description
protected.
FEM Failure Warning: Communication have been lost to
(<pw>) - Indicates adjustable parameters that are password
Fenix Expansion Module (FEM).
protected.
Compressor Started The compressor has started.
DI Warning The Discrete Input “DI” is in a warning condition.
EVENTS FOLDER Discrete Surge A discrete surge switch has detected a surge.
DI Trip The Discrete Input “DI” is in a trip condition.
• PAGES 1 THROUGH 29
Driver Trip Drive controller feedback was not received after a
start command was issued
Fail to Roll Did not achieve minimum slow roll speed in
allotted time
High Failure on AI-n The mA value of the input is greater than 20.5 mA
Load (Location) A Load command has been issued from network
communications.
Loss of Motor Motor current signal was lost while running.
Current
Low Failure on AI-n The mA value of the input is less than
MinLoad Clamped The MinLoad Control or User Setpoint value has
been limited to the MaxLoad Setpoint value.
MinLoad The MinLoad Control Setpoint value has been
Incremented incremented as a result of surge.
MinLoad Reset The MinLoad Control Setpoint value has been reset
to the MinLoad User Setpoint value.
Modulate Mode The Modulate Mode has been enabled.
Enabled
Starter Failure Starter feedback was not received after a Start
command was issued.
Starting Fail Driver feedback was not received after a Start
command was issued.
TTV Switch Fault Trip Limit Switch Stuck
FMM : short circuit AI
FMM : short circuit DI
The pages in the Events folder document up to the last 252 events that the
FMM has experienced, and time stamps each. The events are recorded in
sequence, with number one being the newest and 252 being the oldest. Start key pressed Start command has been issued from the face
When a new event occurs, it becomes number one and all others are shifted plate.
up in number. The page numbers in the Title Bar are used to scroll through
Web Start Start command has been issued from the web
the events, with each page displaying up to seven. Page one displays events
interface.
one through seven, page two displays eight through fourteen, and so on.
COM Start Command Start command has been issued from Modbus
Active Warnings will be highlighted in amber while cleared Warnings will
have amber colored text. The text will begin with an actual description of RMT Start Command Start command has been issue from wired remote
Analog Input and then description of LOW / HIGH Alarm or Trip. Warnings can start contacts
also be timed events, such as air filter due for replacement. Auto Start Command An automatic start occurred (typically from Auto
Active Trips will be highlighted in red while cleared Trips will have red colored Hot or Cold Start).
text. The text will begin with a T for trip, followed by LL (low level) or HL Stop key pressed Stop command has been issued from the face
(high level), and then the analog input number (AI5 is analog input 5, not 15. plate.
Analog input 15 is AI15). Trips can also be triggered by a digital input, such as
Web Stop Stop command has been issued from the web
low seal air or no starter feedback.
interface.
Recordable Events Table
COM Stop Command Stop command has been issued from Modbus
Event Name Description RMT Stop Command Stop command has been issue from wired remote
start contacts
* * End of List * * Displayed for the event name whenever the event
list is not full. Auto Stop Command An automatic stop occurred (typically from
Running Unloaded Shutdown Timer).
A/I Warning The actual value for Analog Input “AI” is greater
than the Warning value. Load key pressed
A/I Trip The actual value for Analog Input “AI” is greater Unload key pressed
than the Trip value. Silence key pressed
Acknowledge An Acknowledge command has been issued from Reset key pressed
(Location) Location.
DCU disconnected Check the two wire connection to the FMM or
Auto Dual Mode The Auto Dual Mode has been enabled FMM power.
Enabled
OverCrank Trip
The selections for page one through five are organized sequentially in rows.
The top row has page one selections and the bottom row has page five
selections.
Variables (< >) include all analog inputs as well as some calculated
variables. The amount of variables will vary depending on the compressor
type and the options it has.
Duration (< >) is selectable from the following five times:
• 10 minutes
• 30 minutes
• 60 minutes
• 12 hours
• 24 hours
Hours left before service (RO/ap) are displayed both digitally and
MAINTENANCE FOLDER graphically. As the hours decrease, the boxes’ fill colors are removed and just
their outline remains. The settings for when the boxes transition are fixed as
• PAGE 1 – MAINTENANCE STATUS OF ALL ITEMS follows:
The total hours for each item’s maintenance interval are adjustable and
resettable from their individual pages (pages 2–5).
The hours decrease as follows:
Air Filter: when compressor is running.
This page displays local service provider contact information. The data for this
page is entered from the web pages. Oil Items: when the oil is circulating (compressor running or prelube pump
is on).
• PAGE 2 – EQUIPMENT REFERENCE DATA
(RO) - Indicates read-only items.
(RO/ap) - Indicates read-only parameters that are adjustable from
another page.
The four maintenance items, and their page order, are fixed. Items cannot be
disabled and additional items cannot be added.
Hours left before service (RO) can be reset with the Reset selection on this
page.
Service schedule hours (< >) indicates the total hours used for the
maintenance interval.
Reset (< >) allows the hours left before service to be rest back to 100% of
the service schedule hours.
NOTICE
Each language appears in its native translation. Delay Time (< >) determines how many seconds of inactivity it will take
before the DCU will return to the Home Page.
(< >) - Indicates adjustable parameters that are not password Select Home Folder (< >) is used to select the Home Folder.
protected.
Select Home Page (< >) is used to select the Home Page within the selected
Home Folder.
• PAGE 2 – TIME & DATE SETTINGS
(< >) - Indicates adjustable parameters that are not password
protected.
Hours (< >) allows the current hour to be set. The hours format is fixed on
24-hour.
Minutes (< >) allows current minutes to be set.
Backlight Brightness (< >) adjusts the brightness of the display.
Seconds (< >) allows current seconds to be set.
Enable Backlight Auto-Off (< >) enables the DCU to shut-off the backlight if
Year (< >) allows current year to be set. there is no user activity for the delay time shown.
Month (< >) allows current month to be set. Backlight Auto-Off Delay Time (< >) determines how many seconds of
inactivity it will take before the DCU will shut-off the backlight.
ASC Address (< >) enter the ASC address for the controller when the
The backlight will be switched on whenever any of the DCU’s
controller is connected to the ASC systems.
keys are pressed.
IMMC Address (< >) enter the IMMC address for the controller when the
(< >) - Indicates adjustable parameters that are not password
controller is connected with the IMMC control. Maximum six controllers can
protected.
be connected with IMMC box. IMMC address should be a number between 1
to 6.
NOTICE (< >) - Indicates adjustable parameters that are not password
protected.
THE START, STOP, LOAD, UNLOAD, RESET, AND ACKNOWLEDGE
KEYS ON THE DCU REMAIN FUNCTIONAL WHILE THE BACKLIGHT IS
SWITCHED OFF. IT IS RECOMMENDED TO PRESS THE ENTER KEY OR ONE • PAGE 8 – DCU PORT CONFIGURATION (MODBUS SETTINGS)
OF THE NAVIGATION KEYS IN ORDER TO SWITCH THE BACKLIGHT ON.
This page configures the Modbus parameters for the DCU port configuration.
Parity (< >) is selectable between None, Even and Odd.
Temperature (< >) is selectable between ⁰F and ⁰C.
Baud Rate (< >) is selectable between 9600, 19200, 38400, 57800 and
Differential Temp. (< >) is selectable between ⁰F and ⁰C. 115200.
Vibration (< >) is selectable between Mils and Micron. Stop Bits (< >) is selectable between 1 and 2.
Pressure (< >) is selectable between psi, kpa, bar, kg/cm². Byte Order (< >) is selectable between big endian and little endian.
Power (< >) is selectable between KW and HP.
Click on “Apply” button to save the changes in Modbus parameters.
Flow (< >) is selectable between ft³/min and m³/min.
Speed (< >) is selectable between ft/s and m/s. (< >) - Indicates adjustable parameters that are not password
protected.
Acceleration (< >) is selectable between ft/s² and m/s².
Precision Length (< >) is selectable between in and cm.
• PAGE 9 – ETHERNET ADDRESS SETTINGS
Some of the units of measure may not be used; it depends on the
compressor type and the purchased options.
(< >) - Indicates adjustable parameters that are not password
protected.
This page configures the DCU IP address, default gateway address, subnet
mask address and Mac address for the Ethernet configuration. This page also
indicates actual IP address, default gateway and subnet mask address for the
controller.
Modbus Address (< >) enter the Modbus address for the controller in to the
network.
This page allows the user to select, how the DCU will be connected to the These pages indicate the list of available options for the compressor. An “x” in
LAN as a web server to get the DCU web pages. The DCU ships with a default the checkbox beside a compressor option indicates that particular option is
IP address of 192.168.2.220. included into the installed configuration file.
Enable DHCP (< >) is selectable between true and false. Operator cannot change the selection of these compressor options through
UI screen.
This page indicates assigned IP address, assigned gateway address and
assigned subnet mask address for the controller. All settings on this page are read only type.
If “Enable DHCP” option is true, then the DCU will obtain an IP address via
DHCP. Once the user changes the “DHCP Enable” option to true, the “Assigned
IP” address (e.g. 10.40.193.73) will appear below this selection in few seconds. The number of pages and digital outputs will vary depending on the
The users connected with the local area network can use this new assigned IP compressor model and options.
to login the DCU web pages.
Click on “Apply” button to save the changes in Ethernet configurations. IMMC SETTINGS FOLDER
Depending on the LAN architecture, not all users will be able to view the web • PAGE 1 – REFERENCE PRESSURE SETTING
pages from their PC.
(RO) - Indicates read-only values. All settings on this page are read only type.
This page indicates the unload/stop pressure, target pressure and load/start
pressure for the common air system.
Selection Ref. Pressure (< >) is a list box value which provides the selection
between remote pressure transducer and average pressure (average type is
automatically determined).
This page indicates the IMMC address ID, operation sequence and IMMC If the IMMC-Box connected pressure transducer fails, the control will fall to
control status for all the controllers connected with the IMMC system. the average automatically.
If any controller in the IMMC network is not online or it is not communicating, The average will be calculated one of three ways.
then also the row for that controller will be shown, including the controller ID, 1. All compressors: This will be used if none are running.
sequence letter and the control status. 2. Running compressors: This will be used if none are loaded.
Control Status includes “Not Connected”, “Load-Sharing”, “Comm Failure”, 3. Running loaded compressors: This will be used when all are running in
“Start Delay Timer”, “Load Delay Timer”, “Stop Delay Timer”, “Unload Delay loaded condition.
Timer”, “Unload Test Timer”, and “Waiting Timer”.
This method used to calculate the average, it will be determined
automatically based on the system current state.
All settings on this page are read only type.
The following settings are numerical settings.
Unload/Stop Press. (RO) is the set point value to unload/stop a compressor.
• PAGE 3 – COMPRESSOR STATUS AND PRESSURE This is a numerical reading with the units of pressure.
When the average pressure is above this setting, IMMC control will unload or
stop a compressor.
Target Press. (< >) is the substitute setting used when IMMC control is
active. This setting overwrites system pressure set point when IMMC control
is enabled. This is a numerical reading with the units of pressure.
IMMC control will do the load sharing for the target pressure of the system.
The user can modify the target pressure from any of the user interface
screen. This will automatically update the value of target pressure in all other
controllers connected with the IMMC system.
Load/Start Pressure (RO) is the set point value to load/start a compressor.
This is a numerical reading with the units of pressure.
When the average pressure is below this setting, IMMC control will load or
start a compressor.
This page shows the full sequence, actual sequence and desired sequence
for all the six controllers in the IMMC system. The service technician can also
change the sequence order on this page.
Enable Machine Control (< >) :
An “x” in the checkbox beside an “Enable Machine Control” option enables
the machine control through IMMC box. To enable the IMMC control this The first row displays the Compressor ID numbers from 1 through 6. The
option must be checked. “Compressor ID” will be the same as the Airbus485 address assigned to
the compressor. The compressor ID which matches the local compressor’s
Minimum Run Timer (< >) is the length of time IMMC control will start
Airbus485 address will be displayed in orange to indicate which compressor’s
compressor after a running trip. It is shown with the unit “Seconds”.
display the user is viewing.
(< >) - Indicates adjustable parameters that are not password Full Sequence (RO) shows the sequence that would be used if all six
protected. compressors were participating in the system. The letters A to F indicate the
compressor’s position in the sequence.
• PAGE 6 – LOCAL SETTINGS Actual Sequence (RO) shows the sequence that is actually being used. Any
compressor which is not participating in the sequence shows a blank rather
than its sequence letter. The letters A to F indicate the compressor’s position
in the sequence.
Desired Sequence (< >) allows the user to enter a new sequence. The
user must enter a unique letter for each active participant in the system.
The remaining letters for non-participants will be assigned automatically in
alphabetical order.
For example, if there are only three participants in the sequence and the
user assigns letters “A”, “B”, and “D” to compressors 1, 2, and 3 respectively,
compressors 3, 4, and 5 will be auto assigned letters “C”, “E” and “F”.
If an invalid sequence is entered (i.e. with insufficient or duplicate letters)
then the sequence will be rejected and the selections will remain same.
Update Sequence allows the user to confirm the sequence. Update
sequence allows the IMMC to validate the new sequence before displaying
the sequence in the “Full Sequence” and “Actual Sequence.” If any invalid
sequence is entered the Desired Sequence will retain the last attempted
Enable Control for Start (< >) : sequence.
An “x” in the checkbox beside an “Enable control for Start” option enables the
machine to start automatically through IMMC box. To enable the machine to (< >) - Indicates adjustable parameters that are not password
start automatically this option must be checked. protected.
Enable Control for Load (< >) : (RO) - Indicates read-only values.
An “x” in the checkbox beside an “Enable control for Load” option enables the
machine to load automatically through IMMC box. To enable the machine to
load automatically this option must be checked.
Enable Control for Unload (< >) :
An “x” in the checkbox beside an “Enable control for Unload” option enables
the machine to unload automatically through IMMC box. To enable the
machine to unload automatically this option must be checked.
Enable Control for Stop (< >) :
An “x” in the checkbox beside an “Enable control for Stop” option enables the
machine to stop automatically through IMMC box. To enable the machine to
stop automatically this option must be checked.
Anti Bypass Gain (RO) provides the setting to encourage the compressors to
Enable Machine Control (< >): share the load. This will be shown to a precision of one decimal with the unit
An “x” in the checkbox beside an “Enable Machine Control” option enables “psi”.
the machine control through IMMC box. To enable the IMMC control this
Inlet Valve Gain (RO) provides the setting encourages compressors in the
option must be checked.
system to distribute the load more evenly. This will be shown to a precision of
Enable Load Sharing (< >): one decimal with the unit “psi”.
An “x” in the checkbox beside an “Enable Load Sharing” option enables the
Wait Timer (RO) is the length of time IMMC control will wait after a start /
IMMC Control to control anti-blow off.
stop / load / unload before doing anything else. Wait Timer is shown with the
Enable immediate start on Trip (< >): unit “Seconds”.
An “x” in the checkbox beside an “Enable immediate start on trip” option
enables IMMC control to bypass the start, load and wait timers in the event of
a member compressor tripping off line while running loaded.
Start Delay Timer (RO) is the delay before starting a compressor after
the pressure goes below the start-load pressure. It is shown with the unit
“Seconds”.
Load Delay Timer (RO) is the delay before loading a compressor after
the pressure goes below the start-load pressure. It is shown with the unit
“Seconds”.
Unload Delay Timer (RO) is the delay before starting an unload test after
the pressure goes above the unload-stop pressure. It is shown with the unit
“Seconds”.
Total Bypass (RO) is the sum of all member compressor bypass valve % open
values. Total Bypass will be shown to a precision of one decimal with the unit Stop Delay Timer (RO) is the delay before stopping a compressor after the
“%”. pressure goes above the unload-stop pressure. It is shown with the unit
“Seconds”.
Allowed Bypass (RO) is the amount of bypass allowed in the system before
unloading a compressor. This will be shown to a precision of one decimal (< >) - Indicates adjustable parameters that are not password
with the unit “%”. protected.
Unload Test Rate (RO) is the rate at which the unload test lowers the (RO) - Indicates read-only values.
compressor’s set point during an unload test. This will be shown to a
precision of one decimal with the unit “psi/mi”.
Unload Test Bypass Valve Max (RO) is the position the bypass valve must
reach before the unload test will pass. This will be shown to a precision of one
decimal with the unit “%”.
All of the above are analog inputs that can be scaled in the CONTROL
SETTINGS folder. The Units of Measure can be changed in the GENERAL (RO) - Indicates read-only values.
SETTINGS folder. The number of stages and analog inputs will vary
depending on the compressor model.
• PAGE 2 – COUNTERS
• PAGE 3 – THROTTLE LIMIT (SURGE CONTROL) CT Ratio (<pw>) this setting comes from the CT nameplate. The nameplate
will read a value similar to 300:5. The CT Ratio for this example is 60.
Power Fail Enable (<pw>) the compressor will trip if amps are not detected
when this parameter is enabled. This is normally enabled. Disable to do a
“dry” (no main motor power) run of the starter.
Starting Timer (<pw>) this is used in two different ways. Compressors that
have integrated wye-detla starters use this to determine when the starter
transitions. Compressors with other starters use this to determine when the
start cycle is complete. Both should have this set to when the driver (motor,
turbine, engine) have accelerated. This can be determined by monitoring
amps while starting and observing when this drops off.
Coasting Timer (<pw>) this is used to prevent restarting while the
compressor is rotating. This should be set by monitoring the coupling and set
when the coupling stops rotating.
Full Load Amps (<pw >) enter directly from the motor nameplate if the
voltage on the nameplate is correct.
Service Factor (<pw>) enter directly from the motor nameplate.
MaxLoad (HLL) (RO) this is calculated from the Full Load Amps. HLL is used
to limit the inlet valve to prevent overloading the motor.
Test Enable (<pw >) enables the test. This can only be enabled while the
compressor is in an Unloaded state.
Test Enable (<pw >) enables the test.
Current State (RO) 1 = Active, 0 = Inactive.
BV Close Rate (<pw>) a higher valve may make the test take less time. This
will have an impact on the repeatability of the test. Inlet Valve (RO) this will allow the user to monitor the valve during the test
without changing pages.
Current State (RO) 1 = Active, 0 = Inactive.
Bypass Valve (RO) this will allow the user to monitor the valve during the test
Inlet Valve (RO) this will allow the user to monitor the valve during the test without changing pages.
without changing pages.
MinLoad value (RO) this is the value of the MinLoad control variable. This is
Bypass Valve (RO) this will allow the user to monitor the valve during the test typically measured in amps, inlet valve %, or head. The purpose of the test to
without changing pages. record the minimum MinLoad value while maintaining the pressure setpoint
on the last stage.
Last Stage Pressure (RO) the purpose of the natural surge test is to record
the maximum pressure on the last stage prior to surging. Pressure Setpoint (RO) displays at what pressure the test will be performed.
Standard Control
This page displays PID settings and parameters relating to the Bypass Valve.
This page will also highlight the PID that is controlling the valve. Page 128 of
this manual shows an example of a highlighted PID.
P (<pw >) proportional band setting
I (<pw>) integral reset (repeat per sec) setting.
D (<pw>) derivative (sec) setting
Target (RO) set point for PID. This parameter is useful for tuning the PIDs.
Fdbck (RO) process feedback for the PID. This parameter is useful for tuning
the PIDs.
CV Settings (<pw>) determines when the controller thinks the check valve
is closed. It detects a pressure differential between the discharge and the
system pressure. The check valve is assumed closed when the differential is
more than this amount.
BV Pos (RO) indicates position of the bypass valve. This parameter is useful
Ambient Control
for tuning the PIDs.
This page displays PID settings and parameters relating to the Inlet Valve. This
page will also highlight the PID that is controlling the valve. TL is highlighted CV Open (RO) indicates the assumed position of the check valve. This
in the example above indicating that this PID is controlling the inlet valve. parameter is determined from CV Settings.
P (<pw >) proportional band setting
(<pw>) - Indicates adjustable parameters that are password
I (<pw>) integral reset (repeat per sec) setting. protected.
D (<pw>) derivative (sec) setting (RO) - Indicates read-only values.
Target (RO) set point for PID. This parameter is useful for tuning the PIDs.
• PAGE 10 – DEADBAND CONTROL
Fdbck (RO) process feedback for the PID. This parameter is useful for tuning
the PIDs.
IV Pos (RO) indicates position of the inlet valve. This parameter is useful for This page appears on ambient control configurations only.
tuning the PIDs.
Ambient Control
Setpoint Ramp Rate (<pw >) this feature is used for loading. The PID will
attempt to control to a pressure set point. However, the difference between
the set point and the feedback may be large if the system is empty (no air
pressure). The set point will be raised at a controlled rate to prevent an over-
reaction to the error.
Inlet Valve Unload Position (<pw>) position where the controller will set
the inlet valve while Unloaded.
Stage 1 Pressure (RO) useful for determining the Inlet Valve Unload Position
BV Unload Rate (<pw>) rate (% per scan) that the Bypass Valve opens during
the Unloading state.
IV Unload Rate (<pw>) rate (% per scan) that the Inlet Valve opens during
the Unloading state.
These pages configure the range of the analog instruments. The factory • PAGES 23 THRU 25 – APPLICABLE CCNS, VERSIONS, &
default numbers are found on the schematics. SERIAL NUMBERS
Actual (RO) level at which the analog signal will cause a warning.
Min (<pw>) value of the analog instrument at 4 mA.
Max (<pw>) value of the analog instrument at 20 mA.
The cooling water solenoid valve controls water flow through the cooler. The
valve is used to stop water flow when it is not needed by the compressor. The
normal operation of the valve is to open when the compressor is running and
for a designated time after a stop. The valve may also open, while stopped,
if the oil or any air temperatures are above the normal alarm level. This is
helpful, for example, to cool an air end if the compressor trips due to short
interruption of power.
DO Cooling Water (RO) indicates output for the cooling water solenoid valve.
The parameter is checked when the controller output to solenoid is on to
open.
Post run water valve timer (<pw>) timer to control how long the valve stays
open after a stop.
WEB ACCESS
Ingersoll Rand DCU web pages are a visualization application which offers a window using a web browser on your PC. DCU web pages allows the user to
monitor air system at a glance or take a more detailed look into system operation, equipment status and setup through an intuitive web-page based user
interface. To access this application running on the DCU, simply connect DCU via a Web Browser from any PC using an Ethernet connection. The PC can be local
stand alone or part of a LAN.
The system administrator can assign a user one of three levels of access (view only, user, and administrator) which will determine which functions will be
available to that user. For example, only users with administrator access will be able to make new accounts and to view or modify the configuration overview
parameters. See section Account Management.
The DCU functions as a web server for the compressor. The web server offers the following through the interface:
• Display of current operating state of the compressor
• Compressor Information – model number, serial number, rated capacity and other details
• Start, Stop, Reset Alarm, Load and Unload buttons
• Adjust target pressure
• Display of analog signals
• Display of hour meters.
• Display of Event log
• Graphing
• Display of maintenance timers
• Edit and display of maintenance log
• Notification of hour meters via email
• Notification of alarm/trip events via email
• Automatic and periodic notification of the performance report and inspection log via email
COMMISSIONING PROCEDURES
There are certain parameters that must be configured in order for the DCU to properly communicate to the LAN and to the network. Outlined below is a list of
steps that must be completed before the visualization software can be fully utilized. Please be sure that you have ADMIN rights before attempting to configure
the DCU.
If you will only be connecting to the DCU to a single PC, go to step 1. If you will be using a static IP or DHCP assigned IP address on your company’s LAN please
go to step 2.
1. Connect the DCU to a PC – Follow the procedure outlined in section “CONNECTING DCU TO A PC”. Please go to step 3.
2. Configure the DCU Ethernet settings – Obtain a static IP address from your IT department or have an assigned domain name for DHCP access. Follow the
procedures in “ETHERNET CONFIGURATION”.
3. Login to the web pages – Follow the procedure in section “LOGIN PROCESS”.
4. Configure compressor information – Follow the procedures in section “COMPRESSOR INFORMATION”. Make sure you have the compressor nameplate
data available.
5. Set up user accounts – Follow the procedures in section “ACCOUNT MANAGEMENT”.
CONNECTING DCU TO A PC
In order to configure your computer to communicate point-to-point with the DCU module of Xe-145-F controller, you must first set the IP address range of
your computer to the default IP address range of the DCU. To do this, please follow the instructions listed below to configure the computer IP address. These
settings are accessible using Windows XP by selecting:
Using Classic View:
Select Start
Select Settings
Select Network Connections
3) Scroll down the connection list to find the “Internet Protocol (TCP/IP)”. Selecty the “Internet Protocol (TCP/IP)” and click on “Properties”.
6) Enter IP address for the computer (192.168.2.221), Enter the Subnet mask for the computer (255.255.255.0) and leave all other field boxes blank.
8) Connect an Ethernet cable to your computer and to the DCU. Within a minute, the computer will make a connection to the Visualization Box. Once
connected, you will be able to log into and configure the DCU.
ETHERNET WIRES
Wiring the network is accomplished by connecting the user computer to the DCU using Category 5 (or better) cables. The connection point on the user
computer is a RJ-45 port located on the Network Interface card.
The Ethernet cables are terminated with CAT 5 RJ-45 (RJ means “Registered Jack”) modular plugs. RJ-45 plugs are similar to
those seen on the end of a telephone cable except they have eight versus four or six contacts on the end of the plug and they
are about twice as big.
ETHERNET CONFIGURATION
The Ethernet configuration allows the user to select how the DCU will be connected to the LAN.
The DCU ships with a default IP address of 192.168.2.220. If “Enable DHCP” option is true in the “General Settings” *screen# 10] of the DCU, then it will obtain an
IP address via DHCP. Refer Xe-145F Instruction manual for more information.
Once the user changes the “DHCP Enable” option to true, the “Assigned IP” address (e.g. 10.40.193.73) will appear below this selection in few seconds. The users
connected with the local area network can use this new assigned IP to login the DCU web pages. Please note that depending on the LAN architecture, not all
users will be able to view the web pages from their PC.
Caution! Changing the Ethernet configuration of the DCU may cause the web pages to become unresponsive and require IT or other support to return the DCU to an
operational condition. Be certain all Ethernet settings are correct before saving changes.
LOGIN PROCESS
The server is accessed either by host name or by IP. Accessing by name requires that a router be in the network. During the installation and commissioning
process a network address was assigned to the DCU by your IT department.
This address may be a static IP (e.g. http://192.168.2.220, recommended) or a DHCP assigned domain name address (e.g. http://fenixsim.com). A domain name
address is a web page address chosen by the user to represent the DCU. The domain name must be approved by your IT department but can generally be any
text label you wish. You must have this address before you can log in to the DCU web pages. See section – Ethernet Configuration.
Please note that DCU Web Pages requires Internet Explorer 7 ( or newer) or Mozilla Firefox 2 (or newer). Certain functions may not behave correctly when using
older browser software.
To log in to the web pages you must first type the address into your browser and then press the enter button. For example, with a DHCP enabled DCU box you
might type this:
If the DCU is configured correctly you will then see the DCU web pages in your browser. This may take a few seconds depending on our network connection
speed.
The login screen requires the user to enter their username, password and select the language for the web pages. This login screen will authenticate the user
against the type of account. After log in the user can view/modify the data as per the available access to the user account.
Enter the username & password for log into system and access the web pages.
If the user name or password are incorrect the login page will show a message “Unknown combination of username and password”.
Click on the dropdown control and select the “Language” from language dropdown control. The full list of languages for the Xe-145F controller is supported by
the web interface. The user may select one language from this list. This selection will be the language for the web interface after the login is successful.
Click on “Login” button to continue. Upon successfully logging in you will see the system HOME screen as shown below.
Only 5 users can concurrently login to the controller at a time. If another user attempts to login, an error message will be displayed. “The limit on
the number of concurrent users has been reached. Please wait for a user to logoff before trying again.
Please see below section for default account information, and section “ACCOUNT MANAGEMENT” for more detailed information about the account
management process.
DEFAULT ACCOUNTS
The DCU web pages come with default administator account. The system administrator can assign users one of three levels of access (view only, user and
administrator) which will determine which functions will be available. For example, only users with administrator access will be able to create a new user
account and view or modify the configuration overview parameters.
It is highly advised that the administrator change these accounts as soon as feasible to prevent unauthorized access to the Visualization software. The three
level of access rights are as follows:
1) VIEW : The user is able to view information on all the screens. The user is unable to change any set points or access to the configuration over
view screens.
2) USER : The user has all rights available to the VIEW access level as well as being able to change pressure setpoint on the HOME screen and
working duarion of the maintanance counter. The user is able to manually start, stop, load and unload the compressors, as well as
reset the alarm.
3) ADMIN : The user has all rights of the VIEW and USER access levels as well as full access to the configuration overview screens and the account
management utility.
Please note that there can be as many as five (5) maximum users logged into the system at one time, and only one administrator logged in at one time. Only a
user with ADMIN rights will be able to modify these default accounts.
The default account is:
Login : admin
Password : pwadmin
Rights : ADMIN
NAVIGATION
Each of the main segments is represented by a tab on the top of web pages. Clicking on the tab will bring you to the screen for that particular segment.
TAB NAVIGATION
Clicking this tab will bring the user to the HOME page.
Home
See section HOME PAGE
Clicking this tab will bring the user to the DCU EVENT LOG.
Event Log
See section EVENT LOG UTILITY
Clicking this tab will bring the user to the PERFORMANCE LOG.
Performance Log
See section PERFORMANCE LOG UTILITY
Clicking this tab will bring the user to the GRAPHING page.
Graphing
See section GRAPHING UTILITY
Clicking this tab will bring the user to the MAINTENANCE page.
Maintenance
See section MAINTENANCE UTILITY
Clicking this tab will bring the user to the INSPECTION LOG.
Inspection Log
See section INSPECTION LOG UTILITY
Compressor Clicking this tab will bring the user to the COMPRESSOR INFORMATION page.
Information See section COMPRESSOR INFORMATION
Clicking this tab will bring the user to the ACCOUNT page.
Account
See section ACCOUNT MANAGEMENT
COMMAND BUTTONS
All pages show five command buttons (Start, Stop, Reset Alarm, Load and Unload), five dash board icons and current status of the compressor.
Note: If the current user’s account type does not have the necessary access rights to control the compressor via the web interface, remote control from the web interface
will be disabled at the controller.
“Command Keys” on the DCU web pages command the compressor to perform actions as specified in the following table.
Stops the compressor. This button should be pressed instead of the E-Stop for normal stopping
Stop
operation.
Reset Alarm Clears Warnings and Trips once the condition is corrected.
Remote starting and stopping can be accomplished through the Ethernet Port. Panel power must be on, all utilities must be running and
permissive functions satisfied in order for the start-up from the web page.
DASHBOARD ICONS
“Dashboard Icons” are intended to be a quick at-a-glance view of system status. These icons are always visible regardless of the folder/page selected.
The following table lists standard dashboard icons and their definition. Note that the color of these icons changes based on the state set by the application
while running.
Service Required A Service reminder is nearing or has expired (i.e. an air or oil filter needs to be changed)
Compressor Name, User Name, Print Button and Log Out button are always visible on the right side top of the page, regardless of the tab selected.
The user can set the “Compressor Name” from the “Compressor
Information” tab. The user can use this host name as a browser address
Compressor Name
for the web pages. A “Compressor Name” is a domain address to log in
the DCU web pages.
Currently logged in user is shown on the right side top in each web
Logged in User
page.
Print Button Click on “Print” button, to print the content on existing web page.
HOME PAGE
The “HOME” tab shows information about the compressor operating parameters, total power consumption, running hours, loaded hours, number of starts, etc.
Click on the pressure set point value in the white box, to change the “Pressure Set Point” value. Enter the new pressure set point value and click on “Confirm”
button. “Pressure Set Point” is only editable parameter for the “Admin” and “User” type accounts. The user with “View” type account can’t change these system
parameters.
Click on the dropdown control and select the number of events per page. If the events per page are 20, then previous events will be available in the next page.
Click on the “Next” button will display the previous twenty events.
The “Event Type” dropdown allows the user to filter the list of events by event type. The user can select the type of event from the list by clicking the dropdown
control. The events recorded and placed into one of three categories: Warnings, Trips/Shutdowns, and System Events. “EVENT LOG” page highlights all the trips
in red text, warnings in yellow text and system events in the blue text.
The “History” dropdown allows the user to select the option to see the event log history for a selected time period. Click on the dropdown command and select
option “Last 7 Days” to see the event log of last 7 days.
The EVENT LOG will record the last 500 events. Once this 500 event limit has been reached the oldest events will be cleared and the newest events will appear
at the top of the event log.
The “PERFORMANCE LOG” page is divided into two major sections. The top section displays the parameter values. The bottom section contains the controls for
the Performance log.
The “Running Hours” are the amount of time that the compressor has been operating between all start and stop sequence. The “Loaded Hours” is the amount
of time that the compressor has been running and not running unloaded. The “Unloaded Hours” is the amount of time that the compressor has been running
unloaded. The “Minloaded Hours” is the time the compressor has been running in the MinLoad state.
The “PERFORMANCE LOG” provides two dropdown controls that allow the user to select sampling of reporting and reporting settings. The user can change the
frequency of reporting and monitoring interval by clicking on the dropdown controls.
The time period of the performance report is selected based on the “Frequency of Reporting”. Click on the dropdown control and select the “Frequency
of Reporting” at which performance log will be emailed to the users that request it via the email notification section of the “ACCOUNT” page. The default
frequency of reporting is “Every 8 hours”. In this case after every 8 hours, the web page application will send the performance log to the user at a specified
email account.
The sampling rate of the data capture can be set by the user selection of the “Monitoring Interval”. The “Monitoring Interval” dropdown control determines the
time interval after which parameters will be updated in to the “PERFORMANCE LOG”. All parameters are stored in a rolling FIFO manner.
User names will be displayed as “E-mail recipients” in the “PERFORMANCE LOG”, if the check box for the same is checked in the Email notification section of the
“ACCOUNT” page.
Refer E-mail notification section of the “ACCOUNT” page to change the E-mail address
Whenever the user changes the “Frequency of reporting” and/or “Monitoring Interval”, a “Submit” button will appear on the screen. Click on “Submit” button to
save the changes.
For example, if you are currently viewing the 4 week graph, clicking the performance report utility will produce a performance report for that 4 week period of
time.
GRAPHING UTILITY
Click on “GRAPHING” tab to view the data in a graphical format for the selected analog input variable and time duration. The GRAPHING UTILITY allows the user
to plot a graph on hour, day or week basis. The default option is Hours. Activation of a button will deselect any other button previously selected. When “Hours”
has been selected, the X axis will be scaled such that the span on graph represents duration of 1 hour.
When “Days” has been selected, the X axis will be scaled such that the span on graph represents duration of 1 day.
When “Weeks” has been selected, the X axis will be scaled such that the span on graph represents duration of 1 week.
The drop down menu allows the user to choose a variable to view data on the graph. Click on the dropdown menu and select the variable to monitor on the
graph. Variables include all analog inputs as well as some calculated variables. The amount of variables will vary depending on the compressor type and the
available options.
By moving the mouse over graph will display the determined value at the position of cursor with the date and time. Due to performance requirements the
data on the real time chart cannot be interacted with directly so this allows the user to determine the approximate value of any data point.
MAINTENANCE UTILITY
“MAINTENANCE” tab contains the contact address & contact number to call for parts or service and a list of consumable parts with maintenance counters and
service schedule hours same as shown on the “MAINTENANCE” folder of DCU.
This tab provides a service scheduler so that periodic maintenance reminders may be scheduled for consumable parts. A page includes the Inlet Air Filter, Oil in
the Compressor, Oil Filter and Oil Mist Arrester as consumable parts. The slide bar on the page indicates current location within the time range.
The user can change the working hours of maintenance counter after maintenance. Double click on values in the white box to reset the timer and slide bar.
Click on the service scheduled hours in the white box, to change the maintenance counter for the consumable parts. Enter the new value of working duration
and click on “Confirm” button.
Maintenance counter for the consumable parts is only editable for the “Admin” and “User” type accounts. The user with “View” type account can’t change these
system parameters.
After changing the working hours of maintenance counter, click on the “Reset Button” of the selected variable to reset the slide bar position.
The user can also change the contact address & contact number to call for parts or service. This is the number of the local Ingersoll-Rand representative. Click
on “Confirm” button to save the changes.
“Admin” and “User” type accounts can only have an access to change the working duration of the maintenance counter and Contact details. The
“View” type account can’t have an access to change these parameters.
Click on the dropdown control and select the “Interval”. The default time interval is “Daily”. If the time interval is “Weekly”, then the web page application will
send the inspection log to the user at a specified email address on weekly basis.
Click on the dropdown control and select the “Time of day”. It is shown in a 24 hours clock format.
Click on the “Submit” button to save the changes into the report settings. The user will receive the INSPECTION LOG as per the selected time interval and time
of the day. If the interval is “Daily” and time of day is “09:00” then the web page application will send inspection logs via email, everyday at 9:00 AM.
The user name will be displayed as “E-mail recipients” in the “INSPECTION LOG”, if the check box for the same is checked in the Email notification section of the
“ACCOUNT” page.
Refer E-mail notification section of the “ACCOUNT” page to change the E-mail address
COMPRESSOR INFORMATION
The “COMPRESSOR INFORMATION” tab contains the compressor name, compressor model number, compressor serial number, rated capacity, rated pressure,
rated voltage, running current, starting current, power requirement, motor service factor, measuring units and Email (SMTP) settings.
COMPRESSOR IDENTIFICATION
The “Host Name” is shown as a “Compressor Name” on the right side top of each web page. The user can use this domain name as a web page browser address
to access the DCU web pages. To change the existing host name, enter the new hostname in the white box and click on “Submit” button.
Once the user will submit the new host name, the compressor name will be changed automatically on the next login.
Enter the “Serial Number” and “Model Number” as per the compressor nameplate, and click on “Submit” button to save these compressor details.
User account with access level “Admin” can only have an access to change the parameters in “Compressor Identification” and “Email (SMTP)
Settings” blocks. User account with access level “User” and “VIEW” cannot have an access to change these parameters
COMPRESSOR DETAILS
Enter the rated capacity, rated pressure, rated voltage, running current, starting current, nominal power in kW and main motor service factor as per the data
available in the compressor datasheet.
Click on the “Submit” button to save the compressor details.
UNIT TYPE
Click on the dropdown control and select the measurement unit type for the compressor parameters. Default unit type is “English”.
Note: User account with access level “Admin” and “User” can only have an access to change these compressor parameters. User account with access level “VIEW” can
only monitor the data and the user can not have an access to change these parameters.
ACCOUNT MANAGEMENT
The administrator can create any number of users desired and assign each user one of three levels of access, as well as assigning email notifications to various
events that may occur.
ADD ACCOUNT
The “ACCOUNT” tab shows the list of accounts that currently exist which are listed by user name and access rights. Clicking on an account will highlight that
account in blue color. Click on “ADD ACCOUNT” button to add an account with a specified access level for the web page application. Enter the ADMIN password
to proceed.
To generate a new user account; enter the unique username, password and select the user access rights. Click on “Add Account” button will add the new user
account into the list of user accounts. Only a user with “ADMIN” rights will be able to make a new account or remove the existing accounts.
Select the user account from the list and click on “Remove Account” button to delete the selected user account.
Click on the dropdown control and choose the new access level for selected user account. Click on “Submit” button to save the changes in access level for
selected user account.
Click on “Edit Password” button to change the login password. All the type of users has an access to change their login password through this page.
Set the email filter settings for the user. The filter will set which, if any, events will dispatch an email to the user. Checking an event will cause that event to send
an email. Multiple users may receive emails for any or all events.
To get the email notifications for the warnings, trips, performance log and inspection log; check mark the boxes, enter the valid email address and click on
“Submit” button.
User account with access level “Admin” can only have an access to make a new account or modify the access level of these accounts. User account
with access level “User” and “VIEW” can’t have an access to make a new account or modify the user accounts