Technical Information
Deltapilot M FMB50, FMB51,
FMB52, FMB53
Hydrostatic level measurement
Application
The device is used for the following measuring tasks:
• Hydrostatic pressure measurement in liquids and paste-like media in all areas of
process engineering, process measuring technology, pharmaceuticals and the food
industry
• Level, volume or mass measurement in liquids
Your benefits
• Very good reproducibility and long-term stability
• Maximum plant safety provided by one-of-a-kind, condensate-resistant CONTITE
measuring cell
• High reference accuracy: ±0.2 %
optionally ±0.1 %
• Turn down up to 100:1
• Uniform platform for differential pressure, hydrostatics and pressure (Deltabar M
– Deltapilot M – Cerabar M)
• Simple, fast commissioning through a user interface designed for real-world
applications
• Used for process pressure monitoring up to SIL 2, certified to IEC 61508 Edition
2.0 and IEC 61511 by TÜV NORD
• Usage in drinking water: KTW, NSF
Deltapilot M FMB50, FMB51, FMB52, FMB53
Table of contents
2 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Operability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Operating concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Local operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Operating languages . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
System integration . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Ordering information . . . . . . . . . . . . . . . . . . . . . . . 74
Special device versions . . . . . . . . . . . . . . . . . . . . . . . . . 74
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Measuring point (TAG) . . . . . . . . . . . . . . . . . . . . . . . . . 74
Configuration data sheet . . . . . . . . . . . . . . . . . . . . . . . . 74
Supplementary documentation . . . . . . . . . . . . . . . 77
Standard documentation . . . . . . . . . . . . . . . . . . . . . . . . 77
Supplementary device-dependent documentation . . . . . . . 77
Field of Activities . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Special Documentation . . . . . . . . . . . . . . . . . . . . . . . . . 77
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Weld-in adapter, Process adapter and Flanges . . . . . . . . . 78
Mounting bracket for wall and pipe mounting . . . . . . . . . 78
Suspension clamp (FMB53 only) . . . . . . . . . . . . . . . . . . 78
Extension cable shortening kit (FMB53 only) . . . . . . . . . . 78
M12 connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Adapter Uni for FMB50 . . . . . . . . . . . . . . . . . . . . . . . . 78
Service-specific accessories . . . . . . . . . . . . . . . . . . . . . . 79
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . 79
Endress+Hauser 3
Deltapilot M FMB50, FMB51, FMB52, FMB53
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
seriousor fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
seriousor fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minoror medium injury.
NOTICE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personalinjury.
Electrical symbols
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Visual inspection
Symbols in graphics
Symbol Meaning
1. , 2. , 3. … Series of steps
A, B, C, ... Views
4 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
List of abbreviations
1
p
0
LRL LRV URV URL MWP OPL
A0029505
1 OPL: The OPL (overpressure limit = measuring cell overload limit) for the device depends on the lowest-rated
element, with regard to pressure, of the selected components, i.e. the process connection has to be taken into
consideration in addition to the measuring cell. Observe pressure-temperature dependency.
2 MWP: The MWP (maximum working pressure) for the measuring cells depends on the lowest-rated element,
with regard to pressure, of the selected components, i.e. the process connection has to be taken into
consideration in addition to the measuring cell. Observe pressure-temperature dependency. The MWP may be
applied at the device for an unlimited period of time. The MWP can be found on the nameplate.
3 The maximum measuring range corresponds to the span between the LRL and URL. This measuring range is
equivalent to the maximum calibratable/adjustable span.
4 The calibrated/adjusted span corresponds to the span between the LRV and URV. Factory setting: 0 to URL.
Other calibrated spans can be ordered as customized spans.
p Pressure
LRL Lower range limit
URL Upper range limit
LRV Lower range value
URV Upper range value
TD Turn down. Example - see the following section.
A0029545
1 Calibrated/adjusted span
2 Zero point-based span
3 Upper range limit
Example:
• Measuring cell: 10 bar (150 psi)
• Upper range limit (URL) = 10 bar (150 psi)
• Calibrated/adjusted span: 0 to 5 bar (0 to 75 psi)
• Lower range value (LRV) = 0 bar (0 psi)
• Upper range value (URV) = 5 bar (75 psi)
URL
TD =
|URV - LRV|
In this example, the TD is 2:1. This span is based on the zero point.
Endress+Hauser 5
Deltapilot M FMB50, FMB51, FMB52, FMB53
A0023537
A0023538
A0023539
A0023540
Field of application
• Level measurement
• Pressure measurement
Industries
• FMB50: Food, pharmaceuticals, chemicals, power plants, automotive, etc.
• FMB51: Food, pharmaceuticals, chemicals, power plants, automotive, etc.
• FMB52: Food, pharmaceuticals, chemicals, power plants, automotive, etc.
• FMB53: Environment (freshwater and wastewater)
6 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Process connections
FMB50
• Thread
• Flanges
• Flush hygienic connections
FMB51
• Thread
• Flanges
FMB52
• Thread
• Flanges
FMB53
Suspension clamp
Measuring ranges
From –0.1 to +0.1 bar (-1.5 to +1.5 psi) to –1 to +10 bar (-15 to 150 psi)
OPL
Max. 40 bar (600 psi)
Reference accuracy
0.2 % (optionally 0.1 %) depending on measuring range
Supply voltage
• 11.5 to 45 VDC (versions with plug-in connector 35 VDC)
• For intrinsically safe device versions: 11.5 to 30 VDC
• IO-Link communication: 18 VDC required at least (11.5 to 30 VDC if IO-Link is not used but rather
the current output)
Output
4 to 20 mA with superimposed HART protocol, IO-Link (only for FMB50), PROFIBUS PA or
FOUNDATION Fieldbus
Endress+Hauser 7
Deltapilot M FMB50, FMB51, FMB52, FMB53
Options
• Gold/rhodium-coated membrane
• 3.1 inspection certificate
• 3A approval and EHEDG approval for FMB50
• Specific firmware versions
• Initial device settings can be ordered
• Separate housing
Specialties
• Absolute resistance to condensate due to hermetically sealed CONTITETM cell
• Maximum flexibility thanks to modular design
• Special cleaning of the transmitter to remove paint-wetting impairment substances, for use in
paint shops
74 -
A0020029
TYPE EL
February 2010
A0024005
8 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
patm
pmess = pges - patm
pmess = (patm + phydr.) - patm
phydr.
h~p
h
p
h=
r·g
A0023541
1 Membrane
2 Measuring element
3 Rear membrane of the CONTITE™ measuring cell
g Gravitational acceleration
h Level height
Ptot Total pressure = hydrostatic pressure + atmospheric pressure
Patm Atmospheric pressure
Phydr. Hydrostatic pressure
Pmeas Measured pressure in the measuring cell = hydrostatic pressure
ρ Density of the medium
Due to its weight, a liquid column creates hydrostatic pressure. If the density is constant, the
hydrostatic pressure depends solely on the height h of the liquid column.
The CONTITE™ measuring cell, which works according to the principle of the gauge pressure
measuring cell, constitutes the core of the Deltapilot M. In contrast to conventional gauge pressure
measuring cells, the precision measuring element (2) in the CONTITE™ measuring cell is absolutely
protected, situated between the membrane (1) and the rear membrane (3). Thanks to this hermetic
sealing of the measuring element, the CONTITE™ measuring cell is absolutely insensitive to
condensate/condensation and aggressive gases. The pressure applied is transferred from the
membrane to the measuring element by means of an oil without any loss in pressure.
Any measured errors due to fluctuations in temperature are compensated for in the electronics unit
by means of the measuring cell temperature.
A linearization function with max. 32 points, which is based on a table entered manually or semi-
automatically, can be activated on site or via remote operation. This function facilitates
measurement in engineering units, and provides a linear output signal for spherical and horizontal
cylindrical vessels, and vessels with a conical outlet.
Level measurement in closed You can determine the differential pressure in tanks with pressure overlay using two Deltapilot M.
tanks with pressure overlay The pressure measured values of the two probes are sent to a signal processing unit such as Endress
Endress+Hauser 9
Deltapilot M FMB50, FMB51, FMB52, FMB53
+Hauser RMA or a PLC. The signal processing unit or PLC determines the difference in pressure and
uses this to calculate the level and the density where necessary.
2 3
1
A0023542
1 Deltapilot 1 measures the total pressure (hydrostatic pressure and top pressure)
2 Deltapilot 2 measures the top pressure
3 Signal processing unit determines the difference in pressure and uses this to calculate the level
NOTICE
Measured errors can occur.
Large measured errors can occur if the ratio of the level to the top pressure is >1:6. This does not
affect reproducibility.
‣ When selecting the measuring cell, make sure you select measuring ranges that are sufficiently
wide (see example).
Example:
• Max. hydrostatic pressure = 600 mbar (9 psi)
• Max. top pressure (Deltapilot 2):
300 mbar (4.5 psi)
• Max. total pressure, measured with Deltapilot 1:
300 mbar (4.5 psi) + 600 mbar (9 psi) = 900 mbar (13.5 psi) measuring cell to be selected:
0 to 1 200 mbar (0 to 18 psi)
• Max. pressure, measured with Deltapilot 2:
300 mbar (4.5 psi) → measuring cell to be selected: 0 to 400 mbar (0 to 6 psi)
NOTICE
Possibility of probe 2 flooding during differential pressure measurement.
Measured errors can occur.
‣ When installing, make sure that probe 2 cannot be flooded.
Density measurement You can measure the density in tanks with pressure overlay using two Deltapilot M and a signal
processing unit or a PLC. The signal processing unit or the PLC calculates the density from the known
distance between the two Deltapilot M devices Δh and the two measured values p1 and p2.
10 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
2
3
p2
∆h
p1
1
A0023544
Level measurement with Level measurement with automatic density correction is possible in conjunction with a limit switch
automatic density correction such as Liquiphant and a PLC. The limit switch always switches at the same level. In the switch point,
(with media changing in the the signal processing unit determines the corrected density from the pressure of the Deltapilot M
tank) currently measured and the known distance between Deltapilot M and the limit switch. The signal
processing unit then calculates the level from the new density and the measured pressure of the
Deltapilot M.
3
2
∆h
1
A0023546
1 Deltapilot M
2 Liquiphant
3 PLC
Electrical differential
pressure measurement with
gauge pressure measuring
cells
Deltapilot M
FXN 520
1 1
Fieldgate Multidrop-Connector Á
FXA520 FXN520
2
A0023549
1 Shutoff valves
2 e.g. filter
In the example given, two Deltapilot M devices (each with a gauge pressure measuring cell) are
interconnected. The differential pressure can thus be measured using two independent Deltapilot M
devices.
Endress+Hauser 11
Deltapilot M FMB50, FMB51, FMB52, FMB53
LWARNING
Explosion Hazard!
‣ If using intrinsically safe devices, strict compliance with the rules for interconnecting intrinsically
safe circuits as stipulated in IEC60079-14 (proof of intrinsic safety) is mandatory.
12 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Input
Measured variable Measured process variables
Hydrostatic pressure
Measuring range
Measuring cell Maximum measuring range Smallest MWP OPL Vacuum resistance Option 3)
2)
calibratable
4) span (preset at factory) 1)
lower (LRL) Upper (URL) Synthetic oil/
Inert oil
[bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [bar (psi)] [barabs (psiabs)]
0.1 (1.5) –0.1 (-1.5) +0.1 (+1.5) 0.01 (0.15) 2.7 (40.5) 4 (60) 1C
0.4 (6) –0.4 (-6) +0.4 (+6) 0.02 (0.3) 5.3 (79.5) 8 (120) 1F
1.2 (18) –1 (-15) +1.2 (+18) 0.06 (1) 16 (240) 24 (360) 0.01/0.04 (0.145/0.6) 1H
Endress+Hauser 13
Deltapilot M FMB50, FMB51, FMB52, FMB53
Output
Output signal • 4 to 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
• Digital communication IO-Link, 3-wire (only for FMB50)
• Digital communication signal PROFIBUS PA (Profile 3.02)
• Digital communication signal FOUNDATION Fieldbus
Output Option 1)
4 to 20mA HART 2
PROFIBUS PA 3
FOUNDATION Fieldbus 4
Load - 4 to 20 mA HART
R Lmax
[W]
1456
1239
804
369
11.5 20 30 40 45 U
[V]
1
2
3 R Lmax £ U – 11.5 V
23 mA
A0023090
1 Supply voltage 11.5 to 30 V DC for intrinsically safe device versions (not for analog)
2 Supply voltage 11.5 to 45 V DC (versions with plug-in connector 35 V DC) for other types of protection and
for uncertified device versions
3 RLmax maximum load resistance
U Supply voltage
When operating via a handheld terminal or via a PC with an operating program, a minimum
communication resistance of 250 Ω must be taken into account.
14 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Load for current output in In order to guarantee sufficient terminal voltage, a maximum load resistance RL (including line
the case of an IO-Link device resistance) must not be exceeded depending on the supply voltage UB of the supply unit.
R L max
[W ]
1022
587
2 R L max £ U B - 6.5V
23mA
217
0 11,5 20 30 U B
1 [V]
A0045615
If the load is too high, the device performs the following points:
• Output of failure current and display of "M803" (Output: MIN alarm current)
• Periodic checking to establish if it is possible to quit fault state
Dead time, time constant Presentation of the dead time and the time constant:
I
100 %
90 %
63 %
t1 t2 t
t3
A0019786
Dynamic behavior, current Device Dead time (t1) [ms] Time constant T63 (= t2) [ms] Time constant T90 (= t3) [ms]
output (HART electronics)
Max. FMB50 60 90 210
Dynamic behavior, digital Device Dead time (t1) [ms] Dead time (t1) [ms] + Dead time (t1) [ms] +
output (HART electronics) Time constant T63 (= t2) [ms] Time constant T90 (= t3) [ms]
Reading cycle
• Acyclic: max. 3/s, typically 1/s (depending on command # and number of preambles)
• Cyclic (burst): max. 3/s, typically 2/s
Endress+Hauser 15
Deltapilot M FMB50, FMB51, FMB52, FMB53
The device offers the BURST MODE function for cyclic value transmission via the HART
communication protocol.
Response time
When recording step responses, it is important to bear in mind that the response times of the
measuring cell might be added to the specified times.
• Acyclic: min. 330 ms, typically 590 ms (depending on command # and number of preambles)
• Cyclic (burst): min. 160 ms, typically 350 ms (depending on command # and number of
preambles)
Dynamic behavior, PROFIBUS Device Dead time (t1) [ms] Dead time (t1) [ms] + Dead time (t1) [ms] +
PA Time constant T63 (= t2) [ms] Time constant T90 (= t3) [ms]
Response time
• Acyclic: approx. 23 ms to 35 ms (depending on Min. Slave Interval)
• Cyclic: approx. 8 ms to 13 ms (depending on Min. Slave Interval)
Dynamic behavior, Device Dead time (t1) [ms] Dead time (t1) [ms] + Dead time (t1) [ms] +
FOUNDATION Fieldbus Time constant T63 (= t2) [ms] Time constant T90 (= t3) [ms]
Reading cycle
• Acyclic: typically 5/s
• Cyclic: max. 10/s (dependent on the number and type of function blocks used in a closed-control
loop)
Response time
• Acyclic: typically 70 ms (for standard bus parameter settings)
• Cyclic: max. 20 ms (for standard bus parameter settings)
16 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
IO-Link Dead time (t1) [ms] Time constant (T63), t2 [ms] Time constant (T90), t3 [ms]
Reading cycle
• Acyclic: cyclic/n where n is dependent on the size of the acyclic data
• Cyclic: min. 100/s
Response time
Cyclic: <10 ms at 38.4 kbps
When recording step responses, it is important to bear in mind that the response times of the
measuring cell might be added to the specified times.
Galvanic isolation The following devices have a galvanic isolation between electronic and probe:
• FMB51, FMB52, FMB53
• FMB50 with separate housing
HART specification 6
DD revision • 01 (Dutch))
• 02 (Russian))
Endress+Hauser 17
Deltapilot M FMB50, FMB51, FMB52, FMB53
HART device variables The following measured values are assigned to the device variables:
Measured values for PV (primary variable)
• Pressure
• Level
• Tank content
Measured values for SV, TV (second and third variable)
• Pressure
• Level
Measured values for QV (fourth device variable)
Temperature
Multidrop current 4 mA
1) Or higher if operating near ambient temperature limits (–40 to +85 °C (–40 to +185))
Protocol-specific data IO- IO-Link is a point-to-point connection for communication between the device and an IO-Link master.
Link (only for FMB50) The IO-Link communication interface enables direct access to the process and diagnostic data. It also
provides the option of configuring the device while in operation.
Device operational 5 s after the supply voltage is applied, the device is operational (first valid
measured value after 2 s)
Device description
In order to integrate field devices into a digital communication system, the IO-Link system needs a
description of the device parameters, such as output data, input data, data format, data volume and
supported transfer rate.
18 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
This data is available in the device description (IODD 1)), which is provided to the IO-Link master via
generic modules when the communication system is commissioned.
The IODD can be downloaded as follows:
• Endress+Hauser: www.endress.com
• IODDfinder: https://ioddfinder.io-link.com/#/
GSD Revision 5
DD Revision 1
DD Files • www.endress.com
• www.profibus.org
Output values Measured values for PV (via Analog Input Function Block)
• Pressure
• Level
• Tank content
Measured values for SV
• Pressure
• Temperature
Input values Input value sent from PLC, can be shown on display
DD revision 0x01021
Number of VCRs 44
1) IO Device Description
Endress+Hauser 19
Deltapilot M FMB50, FMB51, FMB52, FMB53
Permanent entries 44
Client VCRs 0
Server VCRs 5
Source VCRs 8
Sink VCRs 0
Subscriber VCRs 12
Publisher VCRs 19
Link settings
Slot time 4
Transducer Blocks
TRD1 Block Contains all parameters related to the • Pressure or level (channel 1)
measurement • Process temperature (channel 2)
• Measured pressure value (channel 3)
• Max. pressure (channel 4)
• Level before linearization (channel 5)
Diagnostic Block Contains diagnostic information Error code via DI channels (channel 10 to 15)
Function blocks
Resource Block The Resource Block contains all the data that uniquely identify the device. It is an 1 Enhanced
electronic version of a nameplate of the device.
Analog Input The AI Block receives the measuring data from the Sensor Block, (selectable via a 2 25 ms Enhanced
Block 1 channel number) and makes the data available to other function blocks at its output.
Analog Input Enhancement: digital outputs for process alarms, fail safe mode.
Block 2
Digital Input This block contains the discrete data of the Diagnostic Block (selectable via a channel 1 20 ms Standard
Block number 10 to 15) and provides them for other blocks at the output.
Digital Output This block converts the discrete input and thus initiates an action (selectable via a 1 20 ms Standard
Block channel number) in the DP Flow Block or in the TRD1 Block. Channel 20 resets the
counter for max. pressure transgressions value.
PID Block The PID Block serves as a proportional-integral-derivative controller and is used almost 1 40 ms Standard
universally for closed-loop-control in the field including cascade and feedforward. Input
IN can be indicated on the display. The selection is performed in the Display Block
(DISPLAY_MAIN_LINE_CONTENT).
Arithmetic Block This block is designed to permit simple use of popular measurement math functions. 1 35 ms Standard
The user does not have to know how to write equations. The math algorithm is selected
by name, chosen by the user for the function to be performed.
20 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Input Selector The Input Selector Block facilitates the selection of up to four inputs and generates an 1 30 ms Standard
Block output based on the configured action. This block normally receives its inputs from AI
Blocks. The block performs maximum, minimum, average and ‘first good’ signal
selection. Inputs IN1 to IN4 can be indicated on the display. The selection is performed
in the Display Block (DISPLAY_MAIN_LINE_1_CONTENT).
Signal The Signal Characterizer Block has two sections, each with an output that is a non-linear 1 40 ms Standard
Characterizer function of the respective input. The non-linear function is generated by a single look-up
Block table with 21 arbitrary x-y pairs.
Integrator Block The Integrator Block integrates a variable as a function of the time or accumulates the 1 35 ms Standard
counts from a Pulse Input Block. The block may be used as a totalizer that counts up
until reset or as a batch totalizer that has a setpoint, where the integrated value or
accumulated value is compared to pre-trip and trip settings, generating a binary signal
when the setpoint is reached.
Endress+Hauser 21
Deltapilot M FMB50, FMB51, FMB52, FMB53
Power supply
LWARNING
Limitation of electrical safety due to incorrect connection!
‣ When using the measuring device in hazardous areas, installation must comply with the
corresponding national standards and regulations and the Safety Instructions or Installation or
Control Drawings .
‣ All explosion protection data are given in separate Ex documentation, which is available upon
request. The Ex documentation is supplied as standard with all Ex devices .
‣ In accordance with IEC/EN61010 a suitable circuit breaker must be provided for the device.
‣ HART: Overvoltage protection HAW569-DA2B for the non-hazardous area, ATEX II 2 (1) Ex ia
IIC and IEC Ex ia can be ordered as an option (see "Ordering information" section).
‣ Protective circuits against reverse polarity, HF influences and overvoltage peaks are integrated.
6
- +
2
5
4
3
A0023505
1 External ground terminal (only for devices with certain approvals or if "Measuring point" (TAG) is ordered)
2 Internal ground terminal
3 Supply voltage → 23
4 4 to 20 mA for HART devices
5 For HART and FOUNDATION Fieldbus devices: With a handheld terminal, all the parameters can be
configured anywhere along the bus line via menu operation.
6 Terminals
7 For HART devices: test terminals, see section "Taking 4 to 20 mA test signal" → 23
IO-Link
L+
2 1
C/Q IO-Link
3 4
L–
A0045628
1 Supply voltage +
2 4-20 mA
3 Supply voltage -
4 C/Q (IO-Link communication)
22 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
IO-Link
• 11.5 to 30 V DC if only the analog output is used
• 18 to 30 V DC if IO-Link is used
PROFIBUS PA
Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
Version for non-hazardous areas: 9 to 32 V DC
PROFIBUS PA
The digital communication signal is transmitted to the bus via a twin-core connecting cable. The bus
line also provides the power supply. For further information on the network structure and
grounding, and for further bus system components such as bus cables, see the relevant
documentation, e.g., Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning
and commissioning" and the PNO Guideline.
FOUNDATION Fieldbus
The digital communication signal is transmitted to the bus via a twin-core connecting cable. The bus
line also provides the power supply. For further information on the network structure and grounding
and for further bus system components such as bus cables, see the relevant documentation, e.g.,
Operating Instructions BA00013S "FOUNDATION Fieldbus Overview" and the FOUNDATION Fieldbus
Guideline.
Terminals • Supply voltage and internal ground terminal: 0.5 to 2.5 mm2 (20 to 14 AWG)
• External ground terminal: 0.5 to 4 mm2 (20 to 12 AWG)
Endress+Hauser 23
Deltapilot M FMB50, FMB51, FMB52, FMB53
ATEX II1/2D Ex t, II1/2GD Ex ia, Metal M20x1.5 (Ex e) 7 to 10.5 mm (0.28 to 0.41 in)
II3G Ex nA,
IEC Ex t Da/Db
A B – +
2 1
– 1 2 +
BU BN GNYE 3
– +
A0023097
Material: PA 6.6
A B – +
+ –
Han7D
+ –
A0019990
24 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
+
+
–
–
PE
1 2 3 4
A0019991
1 RD = red
2 BK = black
3 GNYE = green
4 4 to 20 mA
4 3
1 2
A0011175
1 Signal +
2 Not assigned
3 Signal –
4 Earth
Endress+Hauser offers the following accessories for devices with an M12 plug:
Plug-in jack M 12x1, straight
• Material: body PA; coupling nut CuZn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 52006263
Plug-in jack M 12x1, elbowed
• Material: body PBT/PA; coupling nut GD-Zn, nickel-plated
• Degree of protection (fully locked): IP66/67
• Order number: 71114212
Cable 4 x 0.34 mm2 (20 AWG) with M12 socket, elbowed, screw plug, length 5 m (16 ft)
• Material: body PUR; coupling nut CuSn/Ni; cable PVC
• Degree of protection (fully locked): IP66/67
• Order number: 52010285
L+
2 1
C/Q IO-Link
3 4
L–
A0045628
1 Supply voltage +
2 4-20 mA
3 Supply voltage -
4 C/Q (IO-Link communication)
Endress+Hauser 25
Deltapilot M FMB50, FMB51, FMB52, FMB53
1 3
2 4
A0011176
1 Signal -
2 Signal +
3 Shield
4 Not assigned
IO-Link
Endress+Hauser recommends using twisted, four-core cable.
PROFIBUS PA
Endress+Hauser recommends using twisted, shielded twin-core cable, preferably cable type A.
For further information regarding cable specifications, see Operating Instructions BA00034S
"PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO guideline 2.092
"PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP).
FOUNDATION Fieldbus
Use a twisted, shielded twin-core cable, preferably cable type A.
For further information on the cable specifications, see Operating Instructions BA00013S
"FOUNDATION Fieldbus Overview", FOUNDATION Fieldbus Guideline and IEC 61158-2 (MBP).
Residual ripple No influence on 4 to 20 mA signal up to ±5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)].
Overvoltage protection The device can be fitted with overvoltage protection. The overvoltage protection is mounted at the
(optional) factory on the housing thread (M20x1.5) for the cable gland and is approx. 70 mm (2.76 in) in
length (take additional length into account when installing). The device is connected as illustrated in
the following graphic.
For details refer to TI01013KDE, XA01003KA3 and BA00304KA2.
Ordering information:
Product Configurator, order code for "Mounted accessories", option NA
26 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Wiring
+
A -
1 3
+ 2
rt +
B - sw -
4
A0023111
Endress+Hauser 27
Deltapilot M FMB50, FMB51, FMB52, FMB53
Influence of the installation • <2.3 mbar (0.0345 psi) when using synthetic oil (FDA).
position • <5 mbar (0.075 psi) when using inert oil.
A position-dependent zero shift can be corrected → 31.
Calibration position
1 2
A0023545
1 FMB50
2 FMB51, FMB52, FMB53
To minimize the effect of the orientation (e.g. in the case of vertical device installation), position
offset is preset at the factory.
Reference accuracy The reference accuracy comprises the non-linearity according to the limit point method, pressure
hysteresis and non-repeatability in accordance with [IEC62828-1/IEC 61298-2].
28 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Thermal change of the zero Version Measuring –10 to +60 °C +60 to +85 °C Only FMB50:
output and the output span cell (+14 to +140 °F) (+140 to +185 °F) +85 to +100 °C
(+185 to +212 °F)
FMB50 100 mbar < (0.32 + 0.30 x TD) < (0.34 + 0.40 x TD) < (0.34 + 0.55 x TD)
FMB51/52/53 (1.5 psi)
snap-on
FMB51/52/53 100 mbar < (0.32 + 0.50 x TD) < (0.34 + 0.60 x TD) -
welded (1.5 psi)
FMB50/51/52/53 400 mbar < (0.31 + 0.25 x TD) < (0.32 + 0.30 x TD) -
(6 psi)
1.2 bar < (0.31 + 0.10 x TD) < (0.32 + 0.15 x TD) < (0.33 + 0.20 x TD)
(18 psi),
4 bar (60 psi),
10 bar
(150 psi)
Total performance The "Total performance" specification comprises the non-linearity including hysteresis, non-
reproducibility as well as the thermal change of the zero point.
100 mbar (1.5 psi) • < 0.18 of the upper range limit (URL) / year
• < 0.45 of the upper range limit (URL) / 5 years
400 mbar (6 psi), • < 0.1 of the upper range limit (URL) / year
1.2 bar (18 psi) • < 0.25 of the upper range limit (URL) / 5 years
4 bar (60 psi), • < 0.05 of the upper range limit (URL) / year
10 bar (150 psi) • < 0.125 of the upper range limit (URL) / 5 years
Total error The total error comprises the long-term stability and the total performance:
Endress+Hauser 29
Deltapilot M FMB50, FMB51, FMB52, FMB53
30 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Mounting
General installation The position-dependent zero point shift can be corrected:
instructions • directly at the device via operating keys on the electronic insert
• directly at the device via operating keys on the display
• via digital communication if the cover is not open .
Endress+Hauser offers a mounting bracket for installing the device on pipes or walls.
FMB51/FMB52/FMB53 • When mounting rod and cable versions, make sure that the probe head is located at a point as free
as possible from flow. To protect the probe from impact resulting from lateral movement, mount
the probe in a guide tube (preferably made of plastic) or secure it with a clamping fixture.
• In the case of devices for hazardous areas, comply strictly with the safety instructions when the
housing cover is open.
• The length of the extension cable or the probe rod is based on the planned level zero point.
The height of the protective cap must be taken into consideration when designing the layout of the
measuring point. The level zero point (E) corresponds to the position of the membrane.
Level zero point = E; top of the probe = L.
17 (0.67)
E
L
A0023559
Endress+Hauser 31
Deltapilot M FMB50, FMB51, FMB52, FMB53
61 (2.4)
238 (9.37)
A0023566
Wall and pipe mounting, Endress+Hauser offers the following mounting bracket for installing the device on pipes or walls:
transmitter (optional)
A0032492
Ordering information:
• included in the delivery for the FMB50/51/52 with a separate housing (available for order via
feature "Separate housing") and for the FMB53
• available for order as a separate accessory (Part No.: 71102216).
Further details→ 54.
32 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
"Separate housing" version With the "separate housing" version, you are able to mount the housing with the electronics insert at
a distance from the measuring point. This allows for trouble-free measurement:
• Under particularly difficult measuring conditions (at installation locations that are cramped or
difficult to access)
• If rapid cleaning of the measuring point is required and
• If the measuring point is exposed to vibrations.
You can choose between different cable versions:
• PE: 2 m (6.6 ft), 5 m (16 ft) and 10 m (33 ft)
• FEP: 5 m (16 ft).
Ordering information:
• Product Configurator, order code for "Separate housing" or
• Product Configurator, order code for "Accessory enclosed" ordering feature, option PA
Dimensions → 54
In the case of the "separate housing" version, the measuring cell is delivered with the process
connection and cable ready mounted. The housing and a mounting bracket are enclosed as separate
units. The cable is provided with a socket at both ends. These sockets are simply connected to the
housing and the measuring cell.
5
4
r ³ 120 (4.72)
1 2 3
A0023567
1 Process connection with measuring cell - see the following section for the degrees of protection
2 Process connection adapter (weight: 0.93 kg (2.05 lb))
3 Cable (weight: 0.05 kg/meter (0.11 lb)), both ends are fitted with a socket
4 Mounting bracket provided, suitable for pipe and wall mounting (for pipes from 1 1/4" up to 2" diameter)
5 Housing with electronic insert - degrees of protection → 35
Degree of protection for the process connection and measuring cell with the use of
• FEP cable:
• IP 69 2)
• IP 66 NEMA 4/6P
• IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
• PE cable:
• IP 66 NEMA 4/6P
• IP 68 (1.83 mH2O for 24 h) NEMA 4/6P
Technical data of the PE and FEP cable:
• Minimum bending radius: 120 mm (4.72 in)
• Cable extraction force: max. 450 N (101.16 lbf)
• Resistance to UV light
2) Designation of the IP protection class according to DIN EN 60529. Previous designation "IP69K" according to DIN 40050 Part 9 is no longer valid
(standard withdrawn on November 1, 2012). The tests required by both standards are identical.
Endress+Hauser 33
Deltapilot M FMB50, FMB51, FMB52, FMB53
Oxygen applications Oxygen and other gases can react explosively to oils, grease and plastics, such that, among other
things, the following precautions must be taken:
• All components of the system, such as measuring devices, must be cleaned in accordance with the
BAM (DIN 19247) requirements.
• Depending on the materials used, a certain maximum temperature and a maximum pressure must
not be exceeded for oxygen applications.
The maximum temperature Tmax for oxygen applications is 60 °C (140 °F).
The devices that are suitable for gaseous oxygen applications are indicated by pmax in the following
table.
FMB50 2) • Depends on the lowest-rated element, with regard to pressure, of the selected
components: overpressure limit (OPL) of the measuring cell or process connection
(1.5 x PN) 3)
• Depends on fill fluid 4)
FMB51 2) • Depends on the lowest-rated element, with regard to pressure, of the selected
components: overpressure limit (OPL) of the measuring cell or process connection
(1.5 x PN) 3)
• Depends on fill fluid 4)
• Depends on seal material
PWIS cleaning Special cleaning of the transmitter to remove paint-wetting substances, for use in paint shops, for
instance.
Ordering information:
Ordering information: Product Configurator, "Service" ordering feature, option HC
The stability of the materials used must be checked before using them in the medium.
The protective cap of the process isolating diaphragm must be removed if necessary (FMB51/
FMB52/ FMB53).
Applications with hydrogen A gold-coated metallic membrane offers universal protection against hydrogen diffusion, both in
gas applications and in applications with water-based solutions.
Special measuring cells for For acids, alkalis or sea water, Endress+Hauser offers a membrane with a gold/platinum coating.
acids, alkalis or sea water
With temperature exposure (up to 85 °C (185 °F)) there is an additional zero point deviation of
(not FMB50)
1.1 mbar (0.0165 psi).
Ordering information:
Product Configurator, order code for "Membrane material", option N
34 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Environment
Ambient temperature range Device
• Without LCD display: –40 to +85 °C (–40 to +185 °F) (–25 to +85 °C (–13 to +185 °F) under static
conditions with IO-Link)
• Without LCD with IO-Link with current output: +70 °C (+158 °F)
• Without LCD with IO-Link without current output: +80 °C (+176 °F)
• With LCD display: –20 to +70 °C (–4 to +158 °F)
Extended temperature operation range (–40 to +85 °C (–40 to +185 °F)) with limitations in optical
properties, such as display speed and contrast, for example
• With separate housing (not for diaphragm seals): –20 to +60 °C (–4 to +140 °F)
(Installation without insulation)
Without LCD display –40 to +85 °C (–40 to +185 °F) With PE cable: –40 to +70 °C (–40 to +158 °F)
With FEP cable: –40 to +80 °C (–40 to +176 °F)
With M12 plug , elbowed –25 to +85 °C (–13 to +185 °F) With PE cable: –25 to +70 °C (–13 to +158 °F)
With FEP cable: –25 to +80 °C (–13 to +176 °F)
1) Extended temperature application range (–40 to +85 °C (–40 to +185 °F)) with restrictions in optical
properties such as display speed and contrast
Without LCD display –40 to +90 °C (–40 to +194 °F) With PE cable: –40 to +70 °C (–40 to +158 °F)
1) With FEP cable: –40 to +80 °C (–40 to +176 °F)
With LCD display –40 to +85 °C (–40 to +185 °F)
With M12 plug, elbowed –25 to +70 °C (–13 to +158 °F) With PE cable: –25 to +70 °C (–13 to +158 °F)
With FEP cable: –25 to +70 °C (–13 to +158 °F)
1) Extended temperature application range (–40 to +85 °C (–40 to +185 °F)) with restrictions in optical
properties such as display speed and contrast
Climate class Class 4K4H (air temperature: –20 to +55 °C (–4 to +131 °F), relative humidity: 4 to 100%) satisfied
as per DIN EN 60721-3-4 (condensation possible)
Endress+Hauser 35
Deltapilot M FMB50, FMB51, FMB52, FMB53
Electromagnetic • Electromagnetic compatibility as per all the relevant requirements of the EN 61326 series and
compatibility NAMUR Recommendation EMC (NE21).
• Max. deviation during EMC-tests : < 0.5 % of the span
• All tests were performed with full measurement range (TD 1:1).
Further details can be found in the manufacturer declaration.
36 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Process
Process temperature range FMB50 FMB51 FMB52 FMB53
–10 to +100 °C (+14 to +212 °F) –10 to +85 °C With PE cable: –10 to +70 °C (+14 to +158 °F)
135 °C (275 °F) for 30 min. (+14 to +185 °F) With FEP cable: –10 to +80 °C (+14 to +176 °F)
maximum
Min. process temperature when using the KALREZ
seal: –3 °C (+27 °F)
Endress+Hauser 37
Deltapilot M FMB50, FMB51, FMB52, FMB53
Mechanical construction
For the dimensions, see the Product Configurator: www.endress.com
Search for product → click "Configuration" to the right of the product image → after
configuration click "CAD"
The following dimensions are rounded values. For this reason, they may deviate slightly from
the dimensions given on www.endress.com.
Housing height → 38
Process connections → 40
Installation clearance -
Device height
1
2
103 (4.06)
112 (4.41)
127 (5)
A0023569
Engineering unit mm (in). Front view, left-hand side view, top view
38 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
112 (4.41)
2
93 (3.66)
76 (3)
A0023570
Engineering unit mm (in). Front view, left-hand side view, top view
Thread depth of cable gland 10 mm (0.39 in) max.
Endress+Hauser 39
Deltapilot M FMB50, FMB51, FMB52, FMB53
A 50 B 50
25 (0.98)
25 (0.98)
1
59 (2.32)
59 (2.32)
G 1½" A G 1½" A
ø55 (2.17) ø55 (2.17)
A0023581 A0023582
C 50
25 (0.98)
54 (2.13)
NPT 1½"
ø55 (2.17)
A0023584
kg (lb)
A Thread ISO 228 G 1 ½" A AISI 316L (1.4435) 0,8 (1.76) - GGJ
Thread ISO 228 G 1 ½" A • 1: top section AISI 316L (1.4435) 0,8 (1.76) - GGC
B
• 2: bottom section Alloy C276 (2.4819)
C Thread ANSI 1 ½" MNPT AISI 316L (1.4435) 0,8 (1.76) CRN RGJ
40 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
g2
b
f
41
dM = ø35.8
g
k
D
A0020004
D Diameter of flange
b Thickness
g Raised face
f Height of raised face
k Hole circle
g2 Diameter of hole
Engineering unit mm
1) 2)
Flange Boltholes Weight Option 3)
1) The roughness of the surface in contact with the medium including the raised face of the flange (all standards) is
Ra10 to 12.5 µm (394 to 492 µin). Lower surface roughness available on request.
2) Material AISI 316L: Endress+Hauser supplies DIN/EN stainless steel flanges as per AISI 316L (DIN/EN material number 1.4404 or 14435). With
regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1: 2001 Tab. 18.
The chemical composition of the two materials can be identical.
3) Product Configurator, "Process connection" ordering feature
Endress+Hauser 41
Deltapilot M FMB50, FMB51, FMB52, FMB53
g2
b
f
1.61
dM = ø1.41
g
k
D
A0022644
D Diameter of flange
b Thickness
g Raised face
f Height of raised face
k Hole circle
g2 Diameter of hole
Engineering unit mm
1) 2)
Flange Boltholes Weight Approval Option 3)
[in] [lb./sq in] [in] [in] [in] [in] [in] [in] [kg (lb)]
1½ 150 5 0.69 2.88 0.06 4 0.62 3.88 2.55 (5.62) CRN AEJ
(not FMB51/52)
2 150 6 0.75 3.62 0.06 4 0.75 4.75 3.45 (7.61) CRN AFJ
4 150 9 0.94 6.19 0.06 8 0.75 7.5 8.25 (18.19) CRN AHJ
1) The roughness of the surface in contact with the medium including the raised face of the flange (all standards) is
Ra3.2 to 6.3 µm (125 to 250 µin). Lower surface roughness available on request.
2) Material AISI 316/316L: Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated).
3) Product Configurator, "Process connection" ordering feature
42 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
JIS flanges, connection dimensions as per JIS B 2220 BL, raised face RF
g2
b
f
41
dM = ø35.8
g
k
D
A0020004
D Diameter of flange
b Thickness
g Raised face
f Height of raised face
k Hole circle
g2 Diameter of hole
Engineering unit mm
1) 2)
Flange Boltholes Weight Option 3)
1) The roughness of the surface in contact with the medium including the raised face of the flange (all standards) is
Ra3.2 to 6.3 µm (125 to 250 µin). Lower surface roughness available on request.
2) Material AISI 316L (1.4435)
3) Product Configurator, "Process connection" ordering feature
Endress+Hauser 43
Deltapilot M FMB50, FMB51, FMB52, FMB53
A B C
59.5 (2.34)
59.5 (2.34)
59.5 (2.34)
20.5 (0.81)
11.2 (0.44)
10.2 (0.4)
D E
59.5 (2.34)
59.5 (2.34)
23.5 (0.93)
20.5 (0.81)
4x
ø11.5 (0.45)
kg (lb)
3)
A DIN 11851 DN 40 PN 25 AISI 316L 0.7 (1.54) EHEDG, 3A, CRN MZJ
(1.4435) 3)
B DIN 11851 DN 50 PN 25 0.9 (1.98) EHEDG, 3A, CRN MRJ
3)
C DIN 11864-1 A DN 50 PN 16 1 (2.21) EHEDG, 3A NDJ
DIN 11866-A pipe, slotted nut, 316L
D Tri-Clamp ISO 2852 DN 40 – DN 51 (2"), - 0.7 (1.54) EHEDG, 3A, CRN TDJ
DIN 32676 DN 50
E DRD DN 50 (65 mm), slip-on flange AISI 304 (1.4301) PN 25 1.1 (1.98) - TIJ
1) Roughness of the surface in contact with the medium is Ra < 0.76 µm (30 µin) as standard. Lower surface roughness available on request.
2) Product Configurator, "Process connection" ordering feature
3) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material
number 1.4307).
44 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
F G H
59.5 (2.34)
59.5 (2.34)
59.5 (2.34)
20.5 (0.81)
27 (1.06)
ø9 (0.35)
ø68 (2.68)
ø49.9 (1.96)
ø84 (3.31) ø65 (2.56)
ø70 (2.76)
A0020010
Rd 70 x 1/6
ø90 (3.54)
ø84 (3.31)
A0020012
A0020011
kg (lb)
F Varivent type N for pipes 40 – 162 PN 40 AISI 316L EHEDG, 3A, CRN TRJ
(1.4435) 3)
G SMS 2" PN 25 1 (2.21) 3A TXJ
1) Roughness of the surface in contact with the medium is Ra < 0.76 µm (30 µin) as standard. Lower surface roughness available on request.
2) Product Configurator, "Process connection" ordering feature
3) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material
number 1.4307).
Endress+Hauser 45
Deltapilot M FMB50, FMB51, FMB52, FMB53
A 1 B 1
4
2 2 4
69.3 (2.73)
179.83 (7.08)
3 3
5
5
ø43.5 (1.71)
A0026355
ø43.5 (1.71)
1 Top section: AISI 316L (1.4404) A0020014
• Roughness of the surface in contact with the medium is Ra < 0.76 µm (30 µin) as standard.
Surface finish Ra < 0.38 µm (15 µin) electropolished (wetted), ordering information: Product
Configurator, "Service" ordering feature, option "HK"
• Silicone molded seal:
FDA 21CFR177.2600/USP Class VI, order number: 52023572
• EPDM molded seal:
FDA (177.2600), USP Class VI; 5 pcs, order number: 71100719
• EPDM O-ring with AISI 316L (1.4404) support ring:
FDA (177.2600), USP Class VI; 1 pc, order number: 71431380
1) 2)
Item Designation Nominal pressure Weight Approval . Option 3)
46 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
A 1 B 1
2 2
78 (3.07)
188 (7.4)
23.6 (0.93)
23.6 (0.93)
28.7 (1.13)
28.7 (1.13)
ø2"
2 9/16-16 UNS-2B ø2"
ø3" 2 9/16-16 UNS-2B
A0020015 ø3"
A0020016
A Anderson short process adapter 2-3/16", 3.5 (50) • 1: Top section AISI 316L (1.4404) 1.5 (3.31) 3A USJ
316L, incl. silicone molded seal FDA • 2: Bottom section AISI 316L (1.4435)
21CFR177.2600 • Slotted nut AISI 316L (1.4404)
1) Roughness of the surface in contact with the medium is Ra < 0.76 µm (30 µin) as standard. Lower surface roughness available on request.
2) Product Configurator, "Process connection" ordering feature
Endress+Hauser 47
Deltapilot M FMB50, FMB51, FMB52, FMB53
H
ø21,3 (0.84)
L
ø42,4 (1.67)
208 (8.19)
ø43,5 (1.71)
A0023592
Housing weight → 38
Threaded connection incl. measuring cell tube and measuring cell 1.65 kg (3.64 lb)
Flange connection incl. measuring cell tube and measuring cell, without a flange -
48 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
H
ø21,3 (0.84)
L
ø42,4 (1.67)
208 (8.19)
ø43,5 (1.71)
A0023593
Housing weight → 38
Flange connection incl. measuring cell tube and measuring cell, without a flange 1.30 kg (2.87 lb)
Endress+Hauser 49
Deltapilot M FMB50, FMB51, FMB52, FMB53
H
ø10,4 (0.41)
L
ø42,4 (1.67)
236 (9.29)
ø43,5 (1.71)
A0023594
Housing weight → 38
Threaded connection incl. measuring cell tube and measuring cell 1.65 kg (3.64 lb)
Flange connection incl. measuring cell tube and measuring cell, without a flange -
50 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
H
ø10,4 (0.41)
L
ø42,4 (1.67)
236 (9.29)
ø43,5 (1.71)
A0023597
Housing weight → 38
Flange connection incl. measuring cell tube and measuring cell, without a flange 1.30 kg (2.87 lb)
Endress+Hauser 51
Deltapilot M FMB50, FMB51, FMB52, FMB53
137 (5.39)
1 1
2 2
3 3
7)
.8
(7
00
222 (8.74)
³2
R
235 (9.25)
ø61 (2.4)
238 (9.37)
4
L
ø10,4 (0.41)
ø42,4 (1.67)
236 (9.29)
ø43,5 (1.71)
A0023598
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
Engineering unit mm (in)
Housing weight → 38
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel) 0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel) 0.18 kg/m (0.40 lbs/3.3 ft)
52 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
1 1
127 (5)
2 2
3 3
7)
.8
(7
0 0
211 (8.31)
³2
R
224 (8.82)
ø61 (2.4)
238 (9.37)
4
L
ø10,4 (0.41)
ø42,4 (1.67)
236 (9.29)
ø43,5 (1.71)
A0023600
FMB53 with suspension clamp and mounting bracket (mounting bracket without marine approval)
Engineering unit mm (in)
Housing weight → 39
PE cable (cable length > 120 m (394 ft) = Delivery on cable reel) 0.13 kg/m (0.28 lbs/3.3 ft)
FEP cable (cable length > 120 m (394 ft) = Delivery on cable reel) 0.18 kg/m (0.40 lbs/3.3 ft)
Endress+Hauser 53
Deltapilot M FMB50, FMB51, FMB52, FMB53
86 (3.39)
70 (2.76)
ø42...60 (1.65...2.36)
69 (2.72)
ø6 (0.24)
1
2
112 (4.4)
52 (2.05)
127 (5)
50 (1.97)
L
122 (4.8) 140 (5.51)
158 (6.22) 175 (6.89)
B 63 (2.48)
1
114 (4.49)
2
95 (3.74)
81 (3.19)
6 (0.24)
1)
Item Designation Weight (kg (lb) Option
54 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
FMB50: Reduction in If the separate housing is used, the mounting height of the process connection is reduced compared
installation height to the dimensions of the standard version.
34 (1.34)
26 (1.02)
7 (0.28)
19 (0.75)
r ³ 120 (4.72) r ³ 120 (4.72)
91 (3.58)
F31 F15
1
2 1
2
ø54.1 (2.13)
1 1
A0025833
FMB51, FMB52: Reduction in If the separate housing is used, the mounting height of the process connection is reduced compared
installation height to the dimensions of the standard version.
44 (1.73)
36 (1.42)
17 (0.67)
29 (1.14)
81 (3.19)
F31 F15
1
2 1
2
ø54.1 (2.13)
1 1
A0025827
Endress+Hauser 55
Deltapilot M FMB50, FMB51, FMB52, FMB53
L1
121,7 (4.79)
2)
.7
(4
20
³1
R
ø54.1 (2.13) 2
L
3
A0023603
1 Mounting bracket for pipe and wall mounting (for pipes from 1 ¼" up to 2" diameter)
2 Process connection adapter
3 Measuring cell tube
L1 PE: 2 m (6.6 ft), 5 m (16 ft) and 10 m (33 ft); FEP: 5 m (16 ft)
L Probe length = 500 to 300 000 mm (20 to 11 810 in)
Connecting cable with process connection adapter and mounting bracket, depicted here with a FMB52
Engineering unit mm (in)
Separate housing for FMB51 and FMB52 Weight of housing → 38 + 0.65 kg (1.43 lb)
Ordering information for FMB50, FMB51, FMB52: Product Configurator, order code for
"Separate housing".
56 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
13
2
6 3
8
9
5 4
12 11 10 7
A0023615
8 Fastening for wired-on tag plate AISI 304 (1.4301)/ AISI 316 (1.4401)
15 Plug PBT-GF30 FR
Endress+Hauser 57
Deltapilot M FMB50, FMB51, FMB52, FMB53
F15 housing
14 1
8 7
6
11 2
3
13 12 10 9 5 4
A0023616
2 Cover
4 Sight glass for non-hazardous area, ATEX Ex ia, NEPSI Polycarbonate (PC)
Zone 0/1 Ex ia, IECEx Zone 0/1 Ex ia, FM NI, FM IS,
CSA IS
4 Sight glass for ATEX 1/2 D, ATEX 1/3 D, ATEX 1 GD, Mineral glass
ATEX 1/2 GD, ATEX 3 G, FM DIP, CSA dust ignition-
proof
7 Fastening for wired-on tag plate AISI 304 (1.4301)/ AISI 316 (1.4401)
10 Nameplates Lasered on
14 Screw A4-50
58 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Connecting parts
4 4
1 5
2 3 6 10 11
7
8
1 9
5 6
A0023617
8 FEP cable for separate housing Abrasion-proof cable; shielded using galvanized steel
wire netting; insulated with fluorinated ethylene
propylene (FEP), black; copper wires, twisted, UV-
resistant
Endress+Hauser 59
Deltapilot M FMB50, FMB51, FMB52, FMB53
Fill fluid
Designation Option 1)
Inert oil 2
FMB51 FMB53
ISO228 Version „GGC“
1 9
2 10
3 11
4 12
5 13
6 14 16
7 15
8 8
17
FMB52 ISO228 Version „GGC“
1 9
10
2
3 11 3
4 12 4
5 13 5
6 14 6
7 15 7
8 8 8
A0023619
1 Process connection → 40
60 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
3 FEP cable Abrasion-proof cable; shielded using galvanized steel wire netting
and aluminum-coated film; insulated with fluorinated ethylene
propylene (FEP), black; copper wires, twisted, UV-resistant
7 Seals → 62
15 Seals → 62
DIN/EN flanges
Endress+Hauser supplies DIN/EN flanges made of stainless steel AISI 316L as per material numbers
1.4435 or 1.4404. With regard to their stability-temperature property, the materials 1.4435 and
1.4404 are grouped together under 13E0 in EN 1092-1 Tab. 18. The chemical composition of the
two materials can be identical.
Membrane
Endress+Hauser 61
Deltapilot M FMB50, FMB51, FMB52, FMB53
Seals
Designation Option 1)
FKM Viton A 2)
EPDM J 2)
Kalrez 6375 L 2)
62 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Operability
Operating concept Operator-oriented menu structure for user-specific tasks
• Commissioning
• Operation
• Diagnosis
• Expert level
Reliable operation
• Local operation possible in several languages
• Standardized operation at the device and in the operating tools
• Parameters can be locked/unlocked using the device's write protection switch (not IO-Link), using
the device software or via remote control
Overview
4 5
3
2
– + E
1
A0016498
1 Operating keys
2 Bar graph
3 Symbol
4 Header
5 Parameter identification number
Endress+Hauser 63
Deltapilot M FMB50, FMB51, FMB52, FMB53
Setting lower range value and upper range value - reference pressure present at the
device
Device reset
Function Operation with operating keys and elements on the electronic insert
Setting lower range value and upper range value - reference pressure ― ―
present at the device
Device reset
Ordering information:
Product Configurator, "Output, Operation" ordering feature
HART
on
Display
2 Zero
3 1 2 3 4 5 off
1 Span on
SW / Alarm min
SW / P2=High
off
SW / Alarm min
SW / P2=High
delta p only
damping
damping
SW /
SW /
HART
8 7 6 5 4
A0032658
1 Operating keys for lower range value (zero) and upper range value (span)
2 Green LED to indicate successful operation
3 Slot for optional local display
4 DIP switch only for Deltabar M
5 DIP switch only for Deltabar M
6 DIP switch for alarm current SW / Alarm Min (3.6 mA)
7 DIP switch for switching damping on/off
8 DIP switch for locking/unlocking parameters relevant to the measured value
64 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
IO-Link
Display
2 Zero
3
1 Span 4
not used
A0045576
1 Operating keys for lower range value (zero) and upper range value (span)
2 Green LED to indicate successful operation
3 Slot for optional local display
4 Slot for M12 plug
PROFIBUS PA
2 on
Display
1 Zero
3 1 2 3 4 5 off
1
damp 2 on
SW / P2=High
not used 3
delta p on:Ö off:SW 4
only on:P2= High off:SW 5 off
damping
on SW
off HW
SW /
Address
10 9 8 7 6
5 4
A0032659
Endress+Hauser 65
Deltapilot M FMB50, FMB51, FMB52, FMB53
FOUNDATION Fieldbus
on
Display
2 Zero
1 3 1 2 3 4 5 off
on
SW / P2=High
TM
FOUNDATION off
Simulation
SW / P2=High
delta p only
damping
simulation
damping
SW /
SW /
8 7 6 5 4
A0032660
Operating languages You can also choose another language in addition to the standard language "English":
Designation Option 1)
English AA
German AB
French AC
Spanish AD
Italian AE
Dutch AF
Chinese AK
Japanese AL
Remote operation Depending on the position of the write protection switch on the device, all software parameters are
accessible.
Hardware and software for remote operation HART IO-Link PROFIBUS PA FOUNDATION Fieldbus
1) 2) 3)
FieldCare → 66
FieldXpert SFX100 → 67 — —
NI-FBUS Configurator → 67 — — —
FieldCare
FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare,
you can configure all Endress+Hauser devices as well as devices from other manufacturers that
support the FDT standard.
66 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
FieldPort SFP20
The FieldPort SFP20 is a USB interface for the configuration of Endress+Hauser IO-Link devices, and
also of devices from other vendors. Combined with the IO-Link CommDTM and the IODD Interpreter,
the FieldPort SFP20 complies with the FDT/DTM standards.
Commubox FXA195
For intrinsically safe HART communication with FieldCare via the USB port. For details refer to
TI00404F/00/EN.
Profiboard
For connecting a PC to PROFIBUS.
Proficard
For connecting a laptop to PROFIBUS.
FF configuration program
FF configuration program, such as NI-FBUS Configurator, to
• connect devices with "FOUNDATION Fieldbus signal" into an FF-network
• set FF-specific parameters
Endress+Hauser 67
Deltapilot M FMB50, FMB51, FMB52, FMB53
System integration The device can be given a tag name (max. 8 alphanumeric characters).
1)
Designation Option
IO-Link (optional)
IO-Link information
IO-Link is a point-to-point connection for communication between the measuring device and an IO-
Link master. The measuring device features an IO-Link communication interface type 2 (pin 4) with
a second IO function on pin 2. This requires an IO-Link-compatible assembly (IO-Link master) for
operation. The IO-Link communication interface enables direct access to the process and diagnostic
data. It also provides the option of configuring the measuring device while in operation.
Characteristics of the IO-Link interface:
• IO-Link specification: Version 1.1
• IO-Link Smart Sensor Profile 2nd Edition
• Speed: COM2; 38.4 kBaud
• Minimum cycle time: 10 ms
• Process data width: 14 Byte
• IO-Link data storage: Yes
• Block configuration: Yes
• Device operational: The measuring device is operational 5 seconds after the supply voltage is
applied
IO-Link download
http://www.endress.com/download
• Select "Device Driver" from the search options shown
• For "Type", select "IO Device Description (IODD)"
Select IO-Link (IODD)
IODD for Deltapilot FMB50
• Under the product root, select the desired device and follow any further instructions.
68 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
https://ioddfinder.io-link.com/
Search by
• Manufacturer
• Article number
• Product type
Endress+Hauser 69
Deltapilot M FMB50, FMB51, FMB52, FMB53
CE mark The device meets the legal requirements of the relevant EC directives. Endress+Hauser confirms that
the device has been successfully tested by applying the CE mark.
RoHS The measuring system complies with the substance restrictions of the Restriction on Hazardous
Substances Directive 2011/65/EU (RoHS 2).
RCM marking The supplied product or measuring system meets the ACMA (Australian Communications and Media
Authority) requirements for network integrity, interoperability, performance characteristics as well
as health and safety regulations. Here, especially the regulatory arrangements for electromagnetic
compatibility are met. The products bear the RCM marking on the nameplate.
A0029561
Ex approvals • ATEX
• IECEx
• FM
• CSA
• NEPSI
• Combinations of different approvals also
All explosion protection data are given in separate documentation which is available upon request.
The Ex documentation is supplied as standard with all Ex devices .
EAC conformity The measuring system meets the legal requirements of the applicable EAC guidelines. These are
listed in the corresponding EAC Declaration of Conformity along with the standards applied.
The manufacturer confirms successful testing of the device by affixing to it the EAC mark.
Suitable for hygiene For information on installation and approvals, see documentation SD02503F "Hygiene approvals".
applications
For information on 3-A and EHEDG-tested adapters, see documentation TI00426F "Weld-in adapter,
process adapter and flanges".
Certificate of current Good Product Configurator, order code for "Test, Certificate" option "JG"
Manufacturing Practices
• The certificate is only available in English
(cGMP)
• Materials of construction of product wetted parts
• TSE compliance
• Polishing and surface finish
• Material/ compound compliance table (USP Class VI, FDA conformity)
Functional safety SIL The Deltapilot M with 4 to 20 mA output signal has been developed to assessed and certified by TÜV
NORD CERT as per IEC 61508 Edition 2.0 and IEC 61511. These devices can be used to monitor the
process level and pressure up to SIL 2. For a detailed description of the safety functions with
Deltapilot M, settings and functional safety data, see the "Functional safety manual - Deltapilot M"
SD00347P.
Ordering information:
70 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
CRN approval Some device versions have CRN approval. A CRN-approved process connection with a CSA approval
must be ordered for a CRN-approved device. These devices are fitted with a separate plate bearing
the registration number 0F14101.5.
Ordering information:
Product Configurator, “Process connection” ordering feature and
Product Configurator, "Approval" ordering feature
Other standards and The applicable European guidelines and standards can be found in the relevant EU Declarations of
guidelines Conformity. The following standards were also applied:
DIN 16086:
Electrical pressure measuring instruments - Pressure transmitters, pressure measuring instruments -
Concepts, specifications on data sheets
EN 61326 series:
EMC product family standard for electrical equipment for measurement, control and laboratory use.
EN 60529:
Degrees of protection provided by enclosures (IP code)
AD2000 The pressure retaining material 316L (1.4435/1.4404) corresponds to AD2000 - W2/W10.
Pressure Equipment Pressure equipment with permitted pressure ≤ 200 bar (2 900 psi)
Directive 2014/68/EU (PED)
Pressure equipment (maximum working pressure PS ≤ 200 bar (2 900 psi)) can be classified as
pressure accessories according to the Pressure Equipment Directive 2014/68/EU. If the maximum
working pressure is ≤ 200 bar (2 900 psi) and the pressurized volume of the pressure equipment is ≤
0.1 l, the pressure equipment is subject to the Pressure Equipment Directive (see Pressure Equipment
Directive 2014/68/EU, Article 4, point 3). The Pressure Equipment Directive only requires that the
pressure equipment shall be designed and manufactured in accordance with the "sound engineering
practice of a Member State".
Reasons:
• Pressure Equipment Directive (PED) 2014/68/EU Article 4, point 3
• Pressure equipment directive 2014/68/EU, Commission's Working Group "Pressure", Guideline
A-05 + A-06
Note:
A partial examination shall be performed for pressure instruments that are part of a safety
instrumented system for the protection of a pipe or vessel from exceeding allowable limits (safety
accessory in accordance with Pressure Equipment Directive 2014/68/EU Article 2, point 4).
Manufacturer declaration Depending on the desired configuration, the following documents can be ordered additionally with
the device:
• TSE-free, materials free from animal origin
• Regulation (EC) No. 2023/2006 (GMP)
• Regulation (EC) No. 1935/2004 on materials and articles intended to come into contact with food
Endress+Hauser 71
Deltapilot M FMB50, FMB51, FMB52, FMB53
GL ― LE
ABS ― LF
LR ― LG
BV ― LH
DNV ― LI
1) Product Configurator, "Additional options 1" and "Additional options 2" ordering feature
KTW LQ
NSF61 LR
1) Product Configurator, "Additional options 1" and "Additional options 2" ordering feature
Classification of process Endress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or
sealing between electrical dual seal devices with annunciation, allowing the user to waive the use and save the cost of installing
systems and (flammable or external secondary process seals in the conduit as required by the process sealing sections of ANSI/
combustible) process fluids NFPA 70 (NEC) and CSA 22.1 (CEC). These instruments comply with the North-American
in accordance with ANSI/ ISA installation practice and provide a very safe and cost-saving installation for pressurized applications
12.27.01 with hazardous fluids.
Further information can be found in the control drawings of the relevant devices.
Sensor range; % A
72 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Designation Option 1)
Endress+Hauser 73
Deltapilot M FMB50, FMB51, FMB52, FMB53
Ordering information
Detailed ordering information is available as follows:
• In the Product Configurator on the Endress+Hauser website:www.endress.com → Click "Corporate"
→ Select your country → Click "Products" → Select the product using the filters and search field →
Open product page → The "Configure" button to the right of the product image opens the Product
Configurator.
• From your Endress+Hauser Sales Center:www.addresses.endress.com
Product Configurator - the tool for individual product configuration
• Up-to-the-minute configuration data
• Depending on the device: direct input of information specific to the measuring point, such as
measuring range or operating language
• Automatic verification of exclusion criteria
• Automatic generation of the order code with its breakdown in PDF or Excel output format
• Ability to order directly in the Endress+Hauser Online Shop
Special device versions Endress+Hauser offers special device versions as Technical Special Products (TSP).
For further information please contact your local Endress+Hauser Sales Center.
Configuration data sheet IO-Link: The following data can only be selected for cyclic data and not for acyclic data.
74 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Pressure
If the option "J" was selected for the order code for "Calibration; Unit" in the Product Configurator, the
following configuration data sheet must be completed and included with the order.
Pressure unit
Display
Damping
Endress+Hauser 75
Deltapilot M FMB50, FMB51, FMB52, FMB53
Level
If the option "K" was selected for the order code for "Calibration; Unit" in the Product Configurator, the
following configuration data sheet must be completed and included with the order.
Example
Empty pressure [a]: ___________ Empty calibration ___________
Low pressure value (empty) [Pressure [a]: [Scaled unit]
engineering unit] Low level value B
(empty)
A0023621
A 0 mbar / 0m
B 300 mbar (4.5 psi) /
3 m (9.8 ft)
Display
Damping
76 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
Supplementary documentation
For an overview of the scope of the associated Technical Documentation, refer to the following:
• Device Viewer (www.endress.com/deviceviewer): Enter the serial number from the
nameplate
• Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the
2D matrix code (QR code) on the nameplate
Supplementary device- Additional documents are supplied depending on the device version ordered: Always comply strictly
dependent documentation with the instructions in the supplementary documentation. The supplementary documentation is an
integral part of the device documentation.
Field of Activities Pressure measurement, powerful instruments for process pressure, differential pressure, level and
flow:
FA00004P/00/EN
Endress+Hauser 77
Deltapilot M FMB50, FMB51, FMB52, FMB53
Accessories
Weld-in adapter, Process See technical information TI00426F/00.
adapter and Flanges
Extension cable shortening See Product Configurator, "Accessory enclosed" ordering feature, option "PW" or can be ordered as a
kit (FMB53 only) separate accessory (part no. 71125862).
For details refer to SD00553P/00/A2.
M12 connector → 24
Adapter Uni for FMB50 For dimensions and technical data, see Technical Information TI00426F.
78 Endress+Hauser
Deltapilot M FMB50, FMB51, FMB52, FMB53
DeviceCare SFE100 Configuration tool for HART, PROFIBUS and FOUNDATION Fieldbus field devices
Field Xpert SMT70, The Field Xpert SMT70 tablet PC for device configuration enables mobile plant
SMT77 asset management in hazardous (Ex Zone 2) and non-hazardous areas. It is
suitable for commissioning and maintenance staff. It manages Endress+Hauser
and third-party field instruments with a digital communication interface and
documents the progress of the work. The SMT70 is designed as a complete
solution. It comes with a pre-installed driver library and is an easy-to-use, touch-
enabled tool for managing field devices throughout their entire life cycle.
The Field Xpert SMT77 for device configuration enables mobile plant asset
management in areas categorized as Ex Zone 1. It is suitable for commissioning
and maintenance staff for easy management of field instruments with a digital
communication interface. The touch-enabled tablet PC is designed as a complete
solution. It comes with comprehensive pre-installed driver libraries and offers users
a modern software user interface to manage field instruments throughout the
entire life cycle.
Registered trademarks
• KALREZ®
Registered label of E.I. Du Pont de Nemours & Co., Wilmington, USA
• TRI-CLAMP®
Registered label of Ladish & Co., Inc., Kenosha, USA
• HART®
Registered trademark of the FieldComm Group, Austin, USA
•
Registered trademark of the IO-Link Community.
• PROFIBUS PA®
Trademark of the PROFIBUS User Organization, Karlsruhe, Germany
• FOUNDATIONTM Fieldbus
Registered trademark of the FieldComm Group, Austin, USA
• GORE-TEX® trademark of W.L. Gore & Associates, Inc., USA
Endress+Hauser 79
*71581317*