Checklist #: __________________
NOTE: CHECKED ITEMS ARE THE REQUIREMENTS NOT FOUND IN THE SUBMITTED BUILDING PLANS AND SHALL BE
COMPLIED OR CORRECTED BEFORE THE ISSUANCE OF FIRE SAFETY EVALUATION CLEARANCE (FSEC).
Vertical distance between stairway landings are limited to 3.69 m (12 ft) in assembly
MEANS OF EGRESS 29
occupancies, distance is 2.43 m (8 ft)
8 Provide protected/enclosed horizontal exits with self-closing fire doors. 35 Ramp slopes should not exceed 30.3 cm. (1 ft) in 3.03 m (10 ft.).
Travel distance to an exit shall not be more than me No openings other than the required exits are permitted and exit passageways
9 should be one (1) hr fire resistive construction for a three (3) storey building or less
36 and two (2) hrs for four (4) storey building or more. Any opening therein shall be
10 Exit doors shall swing in the direction of exit travel. protected with an approved self-closing fire doors.
Exit door/s should be openable from the inside without the use of keys, Panic hardware is required on exit doors. In lieu of this, doors shall have no locks or
12 38
special knowledge or effort flush bolts or surface bolts are prohibited. latches.
Provide smoke partition of two (2) hour fire resistance from floor to underside
17 Corridors should have a minimum width of _________ meters. 42
of floor above.
19 Dead-end corridors and exit balconies is limited to 6.08 m (20 ft). 44 Provide fire stopping for all concealed spaces.
Doors between guest’s rooms and corridors shall be self-closing Provide approved emergency alarm bell system on each floor with adequate number
26 49
and shall have a fire protection rating at least twenty (20) minutes. of sending stations.
Provide approved type portable fire extinguisher ABC type, lbs. 70 Provide fire protection/suppression during construction.
2 2
52 capacity for every 278 m . (3000 ft ) of floor area or Provide fire exit plan for each floor of the building showing the routes from each
22.8 m (75 ft) travel distance on every floor level. 71 room to appropriate exits, displayed prominently on the door of each room.
Provide automatic fire extinguishing system where kitchen equipment If high hazard commodities will be stored/handled, automatic fire
55 74
is located (Kitchenhood). suppression system shall be provided
MISCELLANEOUS 77 Provide fire resistive walls between stair & kitchen area.
ADDITIONAL REQUIREMENTS (Subject to compliance with pertinent provisions of the Fire Code of the Philippines of 2008
and Philippine Standard)
_________________________________________________________________________________________________________________________________________________________
ACKNOWLEDGED BY:
PAALALA: “MAHIGPIT NA IPINAGBABAWAL NG PAMUNUAN NG BUREAU OF FIRE PROTECTION SA MGA KAWANI NITO ANG
MAGBENTA O MAGREKOMENDA NG ANUMANG BRAND NG FIRE EXTINGUISHER”