Planing Guide - Sewage Engineering - 2005 - 52
Planing Guide - Sewage Engineering - 2005 - 52
6m
1m
0 1m 14 m
3. Calculating the wastewater Drainage coefficient K for single-family homes: 0.5 l/s • Also refer to
inflow Qw Table 1 of the
Annex, "Values
for characteristic
drainage K"
• DIN EN 12050
• EN 12056
Qben [m3] The requirement of 0.7 m/s < Vmin < 2.5 m/s is thus
= fulfilled. Larger pipe diameters should not be used,
π as more deposits would build up in that case.
x (di[m])2 x 3600 s
4
=5m
Height of transfer Height of
or pipe bottom of water level [m]
backflow level in
reversal point [m]
B. Losses in pipelines According to table for 20 m PE 100 (DN 50) • Also refer to
pipe: Table 8 of the
Annex, "Pipe
H*DP = 0.05 m/100 m pipeline friction losses and
correction factors"
corresponds to 0.0005 m/m
= 0.1 m
Pipeline losses Pipeline
acc. to diagram length [m]
D. Total losses
= 6.9 m
Geodetic height Losses in Losses
difference [m] fittings in pipe- Calculated duty point (minimum value):
[m] lines [m] Qmax = 11.24 m3/h (3.12 l/s)
HTot = 6.9 m
28
• Also refer to
24 Wilo Complete
Catalogue
H
20
16
12
8 A B 6
Hgeo-max 5
4 4
1 2 3
0
0 2 4 6 8 10 12 14 16 18 [m3/h]
Q
1 = MTS 40 E 17.13/11
2 = MTS 40 E 20.14/13
3 = MTS 40 E 23.15/15
4 = MTS 40 E 32.14/21
5 = MTS 40 E 35.15/23
6 = MTS 40 E 35.15/23
= 0.14 m3
Operating cycles [per hour]
VN-Beh 0,14 m3
HZu-Q [m] = + HBeh-min HZu-Q = + 0,245 m
( π x (DBeh)2) ( π x (0,84 m)2)
4 4
= 0.5 m
Tank diameter acc. to manu-
facturer's specifications [m]