GLAZED ELEMENTS

Thermal Shading Light


Glazed Elements - Fenestration Performance Requirements as Transmittance -U
Coefficient - Transmitta
per Green Building Regulations & Specifications
2 SC nce - LT
W/m K

(1) If percentage of total area of external walls that let lights to


the external wall area is:
1-1 Equal or less than 40% 2.10 (max) 0.40 (max) 0.25 (min)
1-2 Between 40% - 60% 1.90 (max) 0.32 (max) 0.10 (min)
1-3 Equal or greater than 60% 1.90 (max) 0.25 (max) 0.10 (min)
(2) For shopfronts and showrooms, other than those at ground
1.90 (max) 0.76 (max)
floor level:

(3) If percentage of glazing portion of a roof to the roof area is:

3-1 Equal or less than 10% 1.90 (max) 0.32 (max) 0.40 (min)
3-2 Greater than 10% 1.90 (max) 0.25 (max) 0.30 (min)

CLIMATE CONDITIONS

Design Parameter Design Criteria

(1) North & South Plaza connecting external corridor summer


24°C
and winter temperature
44.7°C dB
(2) Design Summer Temporature
24.4°C wB
(3) Design Winter Temporature 5.9°C dB
635m Above sea
(4) Altitude
level
50°C dB
(5) External Heat Rejection Plant (Air cooler)
30°C wB
(6) Mean coincident wind speed 3.17 m/s
(7) Latitude 24.71 N / 46.72 E
(8) Extent of variation in Temp on day design (Outdoor daily
14°C
range)

(8) External equipment selection - Max. operating temp. 47°C

U-FACTORS

Design Parameter Design Criteria

(1) External Wall 0.57 W/m²K


(2) Internal Partitioned Wall 2.78 W/m²K
(3) Roof Slab 0.30 W/m²K
(4) Floor 0.568 W/m²K