FAN COIL UNITS DRAIN TRAP CALCULATIONS
AIR FLOW ESP
Calculated
S. NO. CODE QTY SUPPLY AIR Proposed H Trap Seal h REMARKS

m3/H Pa mm mm mm
TERMINAL BUILDING
1 FCU‐T2-200-ET1A&B 1 2700 75 37.5 25 12.5

2 FCU‐T2-100-ET1A&B 1 2700 75 37.5 25 12.5

Positive Pressure Negative Pressure


h
H Trap Seal=ESP+ 1/2"
Trap Seal H = ESP + 1"
h = 1/2" (min)
Trap Seal = H/2 (min)