You are on page 1of 34

USER MANUAL

CONTROLLER USER
INTERFACE MANUAL

PART NUMBER:
02250180-094 R01
KEEP FOR
FUTURE
WARRANTY NOTICE REFERENCE
Failure to follow the instructions ©
SULLAIR CORPORATION
and procedures in this manual or, The information in this manual is current
as of its publication date and applies to
misuse of this equipment will controller part number :
VOID its warranty!
88290018-640 R08
and all subsequent serial numbers.
AIR CARE SEMINAR TRAINING
Sullair Air Care Seminars are courses that provide hands-on instruction for the proper operation, maintenance,
and servicing of Sullair products. Individual seminars on Industrial compressors and compressor electrical
systems are offered at regular intervals throughout the year at Sullair’s corporate headquarters training facility
located at Michigan City, Indiana.

Instruction includes training on the function and installation of Sullair service parts, troubleshooting common
faults and malfunctions, and actual equipment operation. These seminars are recommended for maintenance,
contractor maintenance, and service personnel.

For detailed course outlines, schedule, and cost information contact:

SULLAIR CUSTOMER CARE TRAINING DEPARTMENT

1-888-SULLAIR or
219-879-5451 (ext. 5623)
www.sullair.com
- Or Write -
Sullair Corporation
3700 E. Michigan Blvd.
Michigan City, IN 46360
Attn: Service Training Department.
TABLE OF CONTENTS
SECTION 1—SAFETY
5 1.1 GENERAL
5 1.2 PERSONAL PROTECTIVE EQUIPMENT
5 1.3 PRESSURE RELEASE
6 1.4 FIRE AND EXPLOSION
6 1.5 MOVING PARTS
7 1.6 HOT SURFACES, SHARP EDGES AND SHARP CORNERS
7 1.7 TOXIC AND IRRITATING SUBSTANCES
8 1.8 ELECTRICAL SHOCK
8 1.9 LIFTING
9 1.10 ENTRAPMENT

SECTION 2—STARTUP PROCEDURES


11 2.1 INTRODUCTION
11 2.2 CONTROLLER PANEL LAYOUT
12 2.3 START UP PROCEDURES
13 2.4 SHUTDOWN PROCEDURE

SECTION 3—ADJUSTMENTS
15 3.1 INTRODUCTION
15 3.2 COMPRESSOR ADJUSTMENT PROCEDURES
16 3.3 USER ADJUSTABLE CONTROL PARAMETERS
19 3.4 REMOTE UNLOAD
19 3.5 DRAIN CONTROL

SECTION 4—DESCRIPTION
21 4.1 INTRODUCTION
21 4.2 TOUCH PAD BUTTON DESCRIPTION
21 4.3 INDICATOR LED DESCRIPTION
22 4.4 DISPLAY SCREEN
23 4.5 OPERATING MODES
24 4.6 OPERATING STATES
TABLE OF CONTENTS

24 4.7 NORMAL VIEW SERVICE REMINDERS


25 4.8 NORMAL VIEW WARNING MESSAGE
25 4.9 FAULT MESSAGES

SECTION 5—SEQUENCING
27 5.1 INTRODUCTION
27 5.2 NORMAL OPERATION
28 5.3 WIRING AND PIPING
28 5.4 MACHINE PREPARATION PRIOR TO SEQUENCING
29 5.5 SYSTEM OPERATION

SECTION 6—TROUBLESHOOTING
31 6.1 TROUBLESHOOTING INTRODUCTION
31 6.2 TROUBLESHOOTING GUIDE
32 6.3 MACHINE BEHAVIOR AFTER A POWER INTERRUPTION
Section 1

SAFETY
the precautionary statements contained herein are
NOTE applicable to most compressors and the concepts
behind these statements are generally applicable to
all compressors.

1.2 PERSONAL PROTECTIVE


EQUIPMENT
A. Prior to installing or operating the compressor,
OPERATOR IS REQUIRED TO READ
owners, employers and users should become
ENTIRE INSTRUCTION MANUAL.
familiar with, and comply with, all applicable
OSHA regulations and/or any applicable Federal,
State and Local codes, standards, and regula-
1.1 GENERAL tions relative to personal protective equipment,
Sullair Corporation and its subsidiaries design and such as eye and face protective equipment,
manufacture all of their products so they can be respiratory protective equipment, equipment
operated safely. However, the responsibility for safe intended to protect the extremities, protective
operation rests with those who use and maintain clothing, protective shields and barriers and elec-
these products. The following safety precautions are trical protective equipment, as well as noise
offered as a guide which, if conscientiously followed, exposure administrative and/or engineering con-
will minimize the possibility of accidents throughout trols and/or personal hearing protective equip-
the useful life of this equipment. ment.

The compressor should be operated only by those 1.3 PRESSURE RELEASE


who have been trained and delegated to do so, and
who have read and understood this Operator's A. Install an appropriate flow-limiting valve between
Manual. Failure to follow the instructions, procedures the service air outlet and the shut-off (throttle)
and safety precautions in this manual may result in valve, either at the compressor or at any other
accidents and injuries. NEVER start the compressor point along the air line, when an air hose exceed-
unless it is safe to do so. DO NOT attempt to operate ing 1/2" (13mm) inside diameter is to be con-
the compressor with a known unsafe condition. Tag nected to the shut-off (throttle) valve, to reduce
the compressor and render it inoperative by pressure in case of hose failure, per OSHA Stan-
disconnecting and locking out all power at source or dard 29 CFR 1926.302(b)(7) and/or any applica-
otherwise disabling its prime mover so others who ble Federal, State and Local codes, standards
may not know of the unsafe condition cannot attempt and regulations.
to operate it until the condition is corrected.
B. When the hose is to be used to supply a mani-
Install, use and operate the compressor only in full fold, install an additional appropriate flow-limiting
compliance with all pertinent OSHA regulations and/ valve between the manifold and each air hose
or any applicable Federal, State, and Local codes, exceeding 1/2" (13mm) inside diameter that is to
standards and regulations. DO NOT modify the be connected to the manifold to reduce pressure
compressor and/or controls in any way except with in case of hose failure.
written factory approval.
C. Provide an appropriate flow-limiting valve at the
While not specifically applicable to all types of beginning of each additional 75 feet (23m) of
compressors with all types of prime movers, most of hose in runs of air hose exceeding 1/2" (13mm)

5
SECTION 1

inside diameter to reduce pressure in case of accumulate on, under or around acoustical mate-
hose failure. rial, or on any external surfaces of the air com-
pressor. Wipe down using an aqueous industrial
D. Flow-limiting valves are listed by pipe size and
cleaner or steam clean as required. If necessary,
flow-rated. Select appropriate valves accordingly,
remove acoustical material, clean all surfaces
in accordance with their manufacturer's recom-
and then replace acoustical material. Any acous-
mendations.
tical material with a protective covering that has
E. DO NOT use air tools that are rated below the been torn or punctured should be replaced
maximum rating of the compressor. Select air immediately to prevent accumulation of liquids or
tools, air hoses, pipes, valves, filters and other fluid film within the material. DO NOT use flam-
fittings accordingly. DO NOT exceed manufac- mable solvents for cleaning purposes.
turer's rated safe operating pressures for these
D. Disconnect and lock out all power at source prior
items.
to attempting any repairs or cleaning of the com-
F. Secure all hose connections by wire, chain or pressor or of the inside of the enclosure, if any.
other suitable retaining device to prevent tools or
E. Keep electrical wiring, including all terminals and
hose ends from being accidentally disconnected
pressure connectors in good condition. Replace
and expelled.
any wiring that has cracked, cut, abraded or oth-
G. Open fluid filler cap only when compressor is not erwise degraded insulation, or terminals that are
running and is not pressurized. Shut down the worn, discolored or corroded. Keep all terminals
compressor and bleed the receiver tank to zero and pressure connectors clean and tight.
internal pressure before removing the cap.
F. Keep grounded and/or conductive objects such
H. Vent all internal pressure prior to opening any as tools away from exposed live electrical parts
line, fitting, hose, valve, drain plug, connection or such as terminals to avoid arcing which might
other component, such as filters and line oilers, serve as a source of ignition.
and before attempting to refill optional air line
G. Remove any acoustical material or other material
anti-icer systems with antifreeze compound.
that may be damaged by heat or that may sup-
I. Keep personnel out of line with and away from port combustion and is in close proximity, prior to
the discharge opening of hoses or tools or other attempting weld repairs.
points of compressed air discharge.
H. Keep suitable fully charged Class BC or ABC fire
J. DO NOT use air at pressures higher than 2.1 bar extinguisher or extinguishers nearby when ser-
for cleaning purposes, and then only with effec- vicing and operating the compressor.
tive chip guarding and personal protective equip-
I. Keep oily rags, trash, leaves, litter or other com-
ment per OSHA Standard 29 CFR 1910.242 (b)
bustibles out of and away from the compressor.
and/or any applicable Federal, State, and Local
codes, standards and regulations. J. DO NOT operate the compressor without proper
flow of cooling air or water or with inadequate
K. DO NOT engage in horseplay with air hoses as
flow of lubricant or with degraded lubricant.
death or serious injury may result.
K. DO NOT attempt to operate the compressor in
1.4 FIRE AND EXPLOSION any classification of hazardous environment
unless the compressor has been specially
A. Clean up spills of lubricant or other combustible designed and manufactured for that duty.
substances immediately, if such spills occur.
B. Shut off the compressor and allow it to cool. 1.5 MOVING PARTS
Then keep sparks, flames and other sources of
A. Keep hands, arms and other parts of the body
ignition away and DO NOT permit smoking in the
and clothing away from couplings, belts, pulleys,
vicinity when checking or adding lubricant or
fans and other moving parts.
when refilling air line anti-icer systems with anti-
freeze compound. B. DO NOT attempt to operate the compressor with
the fan, coupling or other guards removed.
C. DO NOT permit fluids, including air line anti-icer
system antifreeze compound or fluid film, to

6
SECTION 1

C. Wear snug-fitting clothing and confine long hair


when working around this compressor, especially
when exposed to hot or moving parts. DANGER
D. Keep access doors, if any, closed except when
making repairs or adjustments.
E. Make sure all personnel are out of and/or clear of
the compressor prior to attempting to start or
operate it.
F. Disconnect and lock out all power at source and
verify at the compressor that all circuits are de- Death or serious injury can result from
energized to minimize the possibility of acciden- inhaling compressed air without using
tal start-up, or operation, prior to attempting proper safety equipment. See OSHA stan-
repairs or adjustments. This is especially impor- dards and/or any applicable Federal, State,
tant when compressors are remotely controlled. and Local codes, standards and regulations
on safety equipment.
G. Keep hands, feet, floors, controls and walking
surfaces clean and free of fluid, water or other
liquids to minimize the possibility of slips and B. DO NOT use air line anti-icer systems in air lines
falls. supplying respirators or other breathing air utili-
zation equipment and DO NOT discharge air
from these systems into unventilated or other
1.6 HOT SURFACES, SHARP confined areas.
EDGES AND SHARP
CORNERS C. Operate the compressor only in open or ade-
quately ventilated areas.
A. Avoid bodily contact with hot fluid, hot coolant,
hot surfaces and sharp edges and corners. D. Locate the compressor or provide a remote inlet
so that it is not likely to ingest exhaust fumes or
B. Keep all parts of the body away from all points of other toxic, noxious or corrosive fumes or sub-
air discharge. stances.
C. Wear personal protective equipment including E. Coolants and lubricants used in this compressor
gloves and head covering when working in, on or are typical of the industry. Care should be taken
around the compressor. to avoid accidental ingestion and/or skin contact.
D. Keep a first aid kit handy. Seek medical assis- In the event of ingestion, seek medical treatment
tance promptly in case of injury. DO NOT ignore promptly. Wash with soap and water in the event
small cuts and burns as they may lead to infec- of skin contact. Consult Material Safety Data
tion Sheet for information pertaining to fluid of fill.
F. Wear goggles or a full face shield when adding
1.7 TOXIC AND IRRITATING antifreeze compound to air line anti-icer systems.
SUBSTANCES G. If air line anti-icer system antifreeze compound
A. DO NOT use air from this compressor for respi- enters the eyes or if fumes irritate the eyes, they
ration (breathing) except in full compliance with should be washed with large quantities of clean
OSHA Standards 29 CFR 1910 and/or any appli- water for fifteen minutes. A physician, preferably
cable Federal, State or Local codes or regula- an eye specialist, should be contacted immedi-
tions. ately.
H. DO NOT store air line anti-icer system antifreeze
compound in confined areas.
I. The antifreeze compound used in air line anti-
freeze systems contains methanol and is toxic,
harmful or fatal if swallowed. Avoid contact with
the skin or eyes and avoid breathing the fumes. If

7
SECTION 1

swallowed, induce vomiting by administering a


tablespoon of salt, in each glass of clean, warm
water until vomit is clear, then administer two
teaspoons of baking soda in a glass of clean
water. Have patient lay down and cover eyes to
DANGER
exclude light. Call a physician immediately.
All field equipment must be tested for elec-
trostatic fields prior to servicing or making
1.8 ELECTRICAL SHOCK contact with the machine using the follow-
ing or equivalent test equipment:
A. This compressor should be installed and main-
tained in full compliance with all applicable Fed- • 90-600 VAC: Volt detector such as
eral, State and Local codes, standards and Fluke Model 1AC-A
regulations, including those of the National Elec- • 600-7000 VAC: Voltage detector
trical Code, and also including those relative to such as Fluke Networks Model
equipment grounding conductors, and only by C9970
personnel that are trained, qualified and dele- It is the responsibility of each organization
gated to do so. to provide/arrange training for all their
associates expected to test for electrostatic
B. Keep all parts of the body and any hand-held
fields.
tools or other conductive objects away from
exposed live parts of electrical system. Maintain
dry footing, stand on insulating surfaces and DO 1.9 LIFTING
NOT contact any other portion of the compressor
when making adjustments or repairs to exposed A. If the compressor is provided with a lifting bail,
live parts of the electrical system. Make all such then lift by the bail provided. If no bail is provided,
adjustments or repairs with one hand only, so as then lift by sling. Compressors to be air-lifted by
to minimize the possibility of creating a current helicopter must not be supported by the lifting
path through the heart. bail but by slings instead. In any event, lift and/or
C. Attempt repairs in clean, dry and well lighted and handle only in full compliance with OSHA stan-
ventilated areas only. dards 29 CFR 1910 subpart N and/or any appli-
cable Federal, State, and Local codes, standards
D. DO NOT leave the compressor unattended with and regulations.
open electrical enclosures. If necessary to do so,
then disconnect, lock out and tag all power at B. Inspect points of attachment for cracked welds
source so others will not inadvertently restore and for cracked, bent, corroded or otherwise
power. degraded members and for loose bolts or nuts
prior to lifting.
E. Disconnect, lock out, and tag all power at source
prior to attempting repairs or adjustments to C. Make sure entire lifting, rigging and supporting
rotating machinery and prior to handling any structure has been inspected, is in good condi-
ungrounded conductors. tion and has a rated capacity of at least the
weight of the compressor. If you are unsure of
the weight, then weigh compressor before lifting.
D. Make sure lifting hook has a functional safety
latch or equivalent, and is fully engaged and
latched on the bail or slings.
E. Use guide ropes or equivalent to prevent twisting
or swinging of the compressor once it has been
lifted clear of the ground.
F. DO NOT attempt to lift in high winds.
G. Keep all personnel out from under and away
from the compressor whenever it is suspended.
H. Lift compressor no higher than necessary.

8
SECTION 1

I. Keep lift operator in constant attendance when- N. Make sure pallet-mounted compressors are
ever compressor is suspended. firmly bolted or otherwise secured to the pallet
prior to attempting to forklift or transport them.
J. Set compressor down only on a level surface
NEVER attempt to forklift a compressor that is
capable of safely supporting at least its weight
not secured to its pallet, as uneven floors or sud-
and its loading unit.
den stops may cause the compressor to tumble
K. When moving the compressor by forklift truck, off, possibly causing serious injury or property
utilize fork pockets if provided. Otherwise, utilize damage in the process.
pallet if provided. If neither fork pockets or pallet
are provided, then make sure compressor is 1.10 ENTRAPMENT
secure and well balanced on forks before
attempting to raise or transport it any significant A. If the compressor enclosure, if any, is large
distance. enough to hold a man and if it is necessary to
enter it to perform service adjustments, inform
L. Make sure forklift truck forks are fully engaged
other personnel before doing so, or else secure
and tipped back prior to lifting or transporting the
and tag the access door in the open position to
compressor.
avoid the possibility of others closing and possi-
M. Forklift no higher than necessary to clear obsta- bly latching the door with personnel inside.
cles at floor level and transport and corner at
B. Make sure all personnel are out of compressor
minimum practical speeds.
before closing and latching enclosure doors.

9
NOTES

10
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

Section 2

STARTUP PROCEDURES
2.1 INTRODUCTION the compressor operation.

This compressor is equipped with a Controller for Up Arrow Pad —Used to navigate “up” the list
controlling the compressor system operation, setting of display messages and to increase or change
the machine parameters and performing parameter values for adjustments.
maintenance operations. The Controller is designed
for the safe operation and protection of the Down Arrow Pad —Used to navigate “down”
compressor system. When fault conditions occur, the list of display messages and to decrease or
the controller automatically shuts down the machine change parameter values for adjustments.
before the conditions can cause damage to the
equipment. The Controller also contains features Return/Reset Pad —Angled arrow key pad
that enable sequential interface with other machines. used to return to upper menu when changing
parameters. A long hold is used to clear fault
2.2 CONTROLLER PANEL messages.
LAYOUT
Right Arrow Pad —Used to make selection in
The Controller panel is shown in Figure 2-1. The menu screen and to change digits when making
controller panel consists of : changes to parameters.

Display Screen for displaying machine status. S —Used to save changes to


Set Pad
parameters. The set pad is also used to manually
Start Pad —Large green pad button used to
load or unload the compressor during operation.
start the compressor operation.
Each of the controller components and functions is
Stop Pad —Large red key pad used to stop described in detail in Section 4.

X 1
2
3
S
4

11 10 9 8 7 6 5

Figure 2-1: Controller Panel


1. Run Mode Indicator Light (Green) 7. Return/Reset Button
2. Power On Indicator Light (Red) 8. Cursor/Confirm Button
3. Fault Warning Indicator Light (Red) 9. Up Button
4. Display Panel 10. Down Button
5. Stop Button 11. Set/Load/Unload Button
6. Start Button

02250180-094 R01 11
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 2

2.3 START UP PROCEDURES 4. Exchange any two of the three fan motor
leads at the fan motor starter. Refer to the
COMPRESSOR MOTOR ROTATION compressor User’s Manual.
DIRECTION CHECK (AT 5. Recheck the direction of the fan motor.
INSTALLATION)
INITIAL START-UP AFTER
After the compressor has been installed and the INSTALLATION
electrical wiring is completed, perform following steps
to verify the direction of the compressor motor Perform the following procedure at the initial start-up
rotation. of the compressor following installation.

1. Pull out the EMERGENCY STOP button. 1. Verify that all preparations and checks nec-
essary for proper installation have been
2. Press the START pad and STOP made. Refer to the compressor User’s Man-
ual.
pad in succession to “bump start” the
2. Read the preceding pages of this manual
compressor.
thoroughly.
3. Observe the direction of rotation of the com-
3. Slowly open the shut-off valve to the service
pressor motor shaft. Verify with Operators
line.
Manual for correct rotation.
4. Disconnect and lockout power according to 4. Press the START pad to start the
lockout/tagout procedure. compressor. Compressor will begin operat-
5. If the motor shaft is not turning in the proper ing in the default mode (Automatic) set at the
direction, disconnect the power to the starter factory.
and exchange any two of the three power 5. Check for possible leaks in piping.
input leads. Refer to the Compressor User’s
Manual. 6. Slowly close the service line shut-off valve to
verify nameplate pressure unload setting is
6. Perform above steps 1 - 3 again to confirm correct. The compressor should unload
proper motor/compressor rotation when nameplate pressure is achieved. If
adjustments are necessary, see Compressor
FAN MOTOR ROTATION CHECK (AT
Adjustment Procedures on page 15.
INSTALLATION)
7. Observe the operating temperature. Refer to
Verify the correct fan rotation using the following compressor Operator’s Manual for accept-
steps: able operating range. If temperature
1. With the compressor running, visually check exceeds this range, check the cooling sys-
that the fan rotation is correct. tem and installation environment.

2. If it is incorrect, change the direction of the 8. Open the shut-off valve to the service line.
fan motor by disconnecting power from the 9. After operating the machine for 24 hours,
compressor. inspect the compressor for fluid leaks and
3. Disconnect and lockout power according to proper operating temperature.
lockout/tagout procedure.

12 02250180-094 R01
SECTION 2 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

SUBSEQUENT START-UP PROCEDURE 2.4 SHUTDOWN PROCEDURE


1. On subsequent start-ups, check the fluid Shut down the compressor by pressing the STOP
sight glass for proper fluid level. Service if
necessary. See compressor User’s Manual. pad on the Controller panel.

2. Press the START pad on the display


screen. The machine will prepare to start up
NOTE
in the last operating mode existing at shut-
The system may require a set amount of
down. The current Machine mode will
time to pass prior to restarting.
appear on the display screen.
3. If a different operating mode is desired, use
the arrow pads to navigate to the Load Mode
parameter. Press the pad to change
the mode. Navigate to the desired mode
WARNING
(Automatic or Manual). Press the S pad
to accept and save the mode setting. The compressor may restart automatically
after a power failure or after the E-Stop but-
4. When the compressor is running, observe ton has been reset.
the display panel and maintenance indica-
tors to ensure the values displayed are
within the proper ranges.

02250180-094 R01 13
NOTES

14 02250180-094 R01
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

Section 3

ADJUSTMENTS
3.1 INTRODUCTION 2. Use the UP arrow or DOWN arrow
This section describes steps for using the Controller pad to navigate to the parameter to be
to modify specific parameters that control the changed. Press the RIGHT arrow pad
machine operation to select the parameter.
Typically, the top line of the Controller Display 3. At this point, the controller will prompt for a
Screen will display the operating mode; the bottom password. This is the customer password
line will display the line pressure and compressor and this can be changed within the “CUS-
temperature. As the user presses the down TOMER SET” menu.
navigation arrow, the screen will display various
machine statistics. These values are not adjustable
at the Controller. Navigating past the status screens, NOTE
the screen will display “CUSTOMER SET” and
“FACTORY SET”. The “CUSTOMER SET” menu Default customer password is 0607.
allows adjustment of control parameters. The
“FACTORY SET” menu is set at the factory and not
adjustable without the factory password. 4. To enter the password use the UP arrow
Section 3.2 provides general steps to modifying the
and DOWN arrow to change the digit
compressor control parameters. A description of
each user modifiable parameter is provided in value. Use the RIGHT arrow to move
Section 3.3. to the next digit.
5. After entering the final digit and pressing the
3.2 COMPRESSOR
ADJUSTMENT S pad, the selected parameter will dis-
PROCEDURES
play. To change the parameter value, use
The following steps are to be used to modify a control the UP arrow and DOWN arrow to
parameter:
change the digit value. Use the RIGHT
1. Use UP arrow and DOWN arrow arrow to move to the next digit.
pad on the controller to navigate to select
6. After all desired parameter changes have
“CUSTOMER SET”. This will be indicated by
the text “CUSTOMER SET” appearing in been made, press S pad to save
reverse (negative) characters on the top line
changes.
of the display. Press the RIGHT arrow
pad to enter the menu.

02250180-094 R01 15
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 3

control indication.
7. Press ENTER pad to return to the nor-
STAR-DELTA TIME – Set time (sec) for star (wye) to
mal view. delta starter transition. Disable by setting to zero (0),
standard for full voltage start. Requires
NOTE approximately 4-6 seconds for wye-delta starting.
LOAD DELAY TIME – Load delay time (sec) after
If during the adjustment process, the wye delta transition or completed motor start.
START , STOP , or ENTER UNLOAD RUN TIME – Set time (sec) that machine
will run unloaded in AUTO mode before shutting off.
pad is pressed prior to pressing
STOP DELAY TIME – Set time (sec) that machine
the S pad, the display will return to the will continue to run after pressing the stop
NORMAL view and the parameter value button.
will not be changed. RESTART TIME – Set time (sec) that must pass after
the machine is stopped before it can be restarted.
3.3 USER ADJUSTABLE ON/OFF MODE – Used to specify LOCAL or
CONTROL PARAMETERS REMOTE starting. When REMOTE mode is set,

Listed below are descriptions of the parameter that user must press local button first before the
can be adjusted at the Controller: remote control can start or stop the machine. If the
LOAD PRESS – Loading set point (psi, bar). When machine is stopped by the local button, the
line pressure falls below this value, the machine will remote control will not be able to start the machine.
load. For example, if the load pressure is set to 125
CLEAR OIL FILT – Reset time for oil filter
psi, the machine will load when the line pressure
maintenance. Set to “0000H” to reset.
goes below 125 psi. The minimum differential
between LOAD PRESS and UNLOAD PRESS is 5 CLEAR A-O SEP – Reset time for separator element
psi (0.3bar). Refer to Table 3-1:Default Pressure maintenance. Set to “0000H” to reset.
Settings.
CLEAR AIR FILT – Reset time for air filter
UNLOAD PRESS – Set point (psi, bar) at which the maintenance. Set to “0000H” to reset.
system pressure will begin unloading. For example if
CLEAR FLUID ALM – Reset time for fluid
this parameter is set to 135 psi the machine will
maintenance. Set to “0000H” to reset.
unload when the line pressure exceeds 135 psi. The
minimum differential between LOAD PRESS and CLEAR GREASE AL – Reset time for grease
UNLOAD PRESS is 5 psi (0.3bar). Refer to Table 3- maintenance. Set to “0000H” to reset.
1:Default Pressure Settings.
OIL FILT CHANGE – Set value (hrs) to trigger alarm
MTR START TIME – Determines length of time (sec) for oil filter maintenance. Set value to “0000” to
before start of main compressor motor. Must be disable the alarm.
longer than the STAR-DELTA (wye-delta) TIME plus
A-O SEP CHANGE – Set value (hrs) to trigger alarm
LOAD DELAY TIME.
for separator element maintenance. Set value to
RESTART DELAY – Set to 0 to disable auto-restart. “0000” to disable the alarm.
Otherwise, value is number of seconds that must
AIR FILT CHANGE – Set value (hrs) to trigger alarm
pass upon restoration of power before machine will
for air filter maintenance. Set value to “0000” to
restart following a power interruption.
disable the alarm.
DRAIN/REMOTE – Used to select between drain
FLUID CHANGE – Set value (hrs) to trigger alarm for
control or to allow remote operation. When set as
fluid maintenance. Set value to “0000” to disable the
DRAIN, terminal no. 18 is the connector for drain
alarm.
control. When set as REMOTE and ON/OFF MODE
is set as REMOTE, terminal no. 18 is for remote

16 02250180-094 R01
SECTION 3 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL
GREASE REQ – Set value (hrs) to trigger alarm for time has passed, the master compressor will
grease maintenance. Set value to “0000” to disable command a slave machine to unload or stop.
the alarm.
SEQ DELAY – Set time (sec) that master machine
USER PASSWORD – Customer password setting. allows to pass before sending a command to a slave
machine to load or unload.
COM MODE - Determines communication protocol.
Set to DISABLE for no functionality. Set to SEQ for ROTATE HOURS – During sequencing, this is the
multiple machine sequencing. Set to PC to amount of current run time allowed on a machine
communicate with MODBUS protocol. before it will be stopped and an idle machine started.
SEQUENCE STATE - Set to SLAVE or MASTER LANGUAGE SEL – Select ENGLISH, FRENCH,
when operating in sequence mode with other SPANISH or PORTUGUESE as controller display
machines. language.
COM ADDRESS – Communication address. POWER FREQ – Select incoming power frequency.
SEQUENCE NO. – Number of compressors in DRAIN OPEN – Set time (sec) for drain to remain
sequencing network. energized. Machines are not shipped from the
factory with solenoid drains. DRAIN must be
SEQ LOAD PRESS - Master machine load pressure
selected from DRAIN/REMOTE parameter setting.
set point (psi, bar) at which slave compressor is
started. For example if set at 125 psi, when master DRAIN CLOSE – Set interval (min) between
machine pressure is less than 125 psi and SEQ activation of the drain cycle. Machines are not
DELAY time has passed, the master compressor will shipped from the factory with solenoid drains.
command a slave machine to start and load. DRAIN must be selected from DRAIN/REMOTE
parameter setting.
SEQ UNLOAD PRESS - Master machine unload
pressure set point (psi, bar) at which slave TEMP UNITS – Displayed temperature units (°C/°F).
compressor is commanded to unload or stop. For
PRESSURE UNITS – Displayed pressure units (psi/
example, if set at 135 psi, when master machine
bar).
pressure is greater than 135 psi and SEQ DELAY

Table 3-1: Default Pressure Settings

Factory Setting Pressure Customer Set Values Factory Set Values


Hz Designation
Pressure Load Press Unload Press Max. Unload Shutdown Press
Selection psig bar psig bar psig bar psig bar psig bar
0.8 MPa 50 116 8.0 103 7.1 118 8.1 121 8.3 126 8.7

0.86 MPa 60 125 8.6 112 7.7 127 8.8 130 9.0 135 9.3

1.0 MPa 50 145 10.0 132 9.1 147 10.1 150 10.3 155 10.7

1.03 MPa 60 150 10.3 137 9.4 152 10.5 155 10.7 160 11.0

1.2 MPa 60 175 12.0 161 11.1 176 12.1 179 12.3 184 12.7

1.3 MPa 50 188 13.0 176 12.1 191 13.2 195 13.4 199 13.7

02250180-094 R01 17
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 3

LOAD PRESS: SEQ UNLOAD PRESS: *


NORMAL VIEW XXXX PSI XXXX PSI

TOTAL RUN TIME: UNLOAD PRESS: SEQ DELAY: *


HOURS MIN XXXX PSI XXXXS

LOADED TIME: MTR START TIME: LANGUAGE SEQ: *


HOURS MIN XXXXS ENGLISH

THIS RUN TIME: DRAIN/REMOTE: POWER FREQ.: *


HOURS MIN REMOTE 60 HZ

OIL FILTER: STAR-DELTA TIME: DRAIN OPEN: *


HOURS XXXXS XXXXS

A-O SEPARATOR: LOAD DELAY TIME: DRAIN CLOSE: *


HOURS XXXXS XXXXM

AIR FILTER: UNLOAD RUN TIME: TEMP UNITS: *


HOURS XXXXS °F

FLUID: STOP DELAY TIME: PRESSURE UNITS: *


HOURS XXXXS PSI

GREASE: RESTART TIME: * RESTART DELAY:


HOURS XXXXS XXXXS

ALARM 1: ON/OFF MODE: *


FAULT LOCAL

ALARM 2: LOAD MODE: *


FAULT AUTO

ALARM 3: CLEAR OIL FILT: *


FAULT XXXXH

ALARM 4: CLEAR A-O SEP: *


FAULT XXXXH

ALARM 5: CLEAR AIR FILT:


FAULT XXXXH

PRODUCTION DATE: CLEAR FLUID ALM:


XXXXH

SERIAL NO: CLEAR GREASE AL:


XXXXH

CUSTOMER SET: OIL FILT CHANGE:


FACTORY SET XXXXH

A-O SEP CHANGE: *


XXXXH

AIR FILT CHANGE:


XXXXH

FLUID CHANGE: *
XXXXH

GREASE REQ: *
XXXXH

USER PASSWORD: *
*****

COM MODE: *
PC

COM ADDRESS: *
XXXX

SEQUENCE STATE:
MASTER

SEQUENCE NO.: *
XXXX

SEQ LOAD PRESS:


XXXX PSI

Figure 3-1: Controller Display Flow Diagram

18 02250180-094 R01
SECTION 3 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

3.4 REMOTE UNLOAD 3.5 DRAIN CONTROL


The machine may be configured to allow user- Shoptek compressors are not equipped with
furnished external remote control. This may be wired condensate drain valves however the Controller does
to a remote switch, timer, or other controls to halt have capability to control a solenoid type drain valve.
operation of the compressor as desired. To enable
To enable drain control:
remote control of the compressor:
1. Access “CUSTOMER SET” menu and select
1. Wire the remote contact to terminal 6 and
the DRAIN/REMOTE parameter. Change
terminal 10.
parameter to DRAIN.
2.Change ON/OFF Mode to REMOTE. The local
2. Set the amount of time to energize the drain
button must be pressed to enable solenoid. This is accomplished by the
remote control. DRAIN OPEN parameter in the “CUS-
TOMER SET” menu.
3. Once enabled, the controller will respond to
the wired input. 3. Set the interval between activation of the
drain cycle. This is accomplished by the
• If the contact is open, the compressor unloads and DRAIN CLOSE parameter in the “CUS-
stops delivering air to the system. If the operating TOMER SET” menu.
mode is AUTOMATIC, the compressor will stop
after running unloaded for the period set in the 4. Connect drain solenoid valve to terminals 18
UNLOAD RUN TIME setting. When operating in a and 10.
group of sequenced compressors, this removes
only this compressor for service.
• If the contact is closed, the compressor operates
normally.

02250180-094 R01 19
NOTES

20 02250180-094 R01
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

Section 4

DESCRIPTION
4.1 INTRODUCTION Right Arrow Pad —Used to make selection in
This section describes the components of the menu screen and to change digits when making
Controller, the function of each component, and the changes to parameters.
various types of displays that may appear on the
display screen. Descriptive lists of all messages Set Pad S —Used to save changes to
appearing in the display are also provided. parameters. The set pad is also used to manually
load or unload the compressor during operation.
4.2 TOUCH PAD BUTTON
DESCRIPTION 4.3 INDICATOR LED
The controller panel has seven touch pads that allow
DESCRIPTION
the operator control of the compressor and enable Three LED’s on the controller panel provide
adjustment of the machine operating parameters. indication of the general state of the machine.
Each touch pad and its functions are described
below:
Power On Indicator (RED LED)—Lights
Start Pad —Large green pad button used to whenever power is applied to the controller.
start the compressor operation.
Automatic or Manual Run Mode Indicator
Stop Pad —Large red key pad used to stop (GREEN LED)—Lights when the compressor
the compressor operation. operation is set to start and run automatically. This
LED lights steadily when the motor is running.
Up Arrow Pad —Used to navigate “up” the list
of display messages and to increase or change Fault Warning Indicator (RED LED)—Lights
parameter values for adjustments.
when a compressor fault has occurred. The indicator
will remain lit and the compressor will remain
Down Arrow Pad —Used to navigate “down” inoperative until the fault condition is remedied. The
the list of display messages and to decrease or controller display screen will indicate STOP and a
change parameter values for adjustments. brief description of the cause of the fault. Refer to
Section 6: Troubleshooting on page 31 to resolve
Return/Reset Pad —Angled arrow key pad fault conditions.
used to return to upper menu when changing
parameters. A long hold is used to clear fault
messages.

02250180-094 R01 21
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 4

4.4 DISPLAY SCREEN


Information relevant to the compressor operation is AUTO LOAD
presented in three views on the controller display
screen: Normal View, Main Status Views, Customer
174°F 62PSI
Set Views.
In addition to the standard views, two information
screens are displayed when power is first supplied to Figure 4-3: Display Screen Normal View Example
the compressor. Refer to Figure 4-1. The first
screen shows “SULLAIR” along with the serial The Display Screen will also display fault conditions
number of the compressor. Refer to Figure 4-2. The when they occur.
second screen shows the total operation time of the MAIN STATUS VIEW
compressor along with the controller software
revision level and date of manufacture. Each of The Main Status View shows real-time machine
these screens will display for 3 seconds before the measurement information.
Normal View is displayed.
This information is quickly accessed using the Down
navigational arrow. The top line of the display screen
will indicate the measurement . See Figure 4-4. The
SULLAIR second line will show the current value of the
XXXXXXXXX measurement being viewed.

TOTAL RUN TIME:


Figure 4-1: Information Screen 1 337H 20M

RUN: XXXXXXH
Figure 4-4: Display Screen Main Status View
REV: X.X 2007/01 Example

Listed below are compressor attributes that may be


viewed in the Main Status View.
Figure 4-2: Information Screen 2 TOTAL RUN TIME – Displays the total time the
compressor has been running loaded or unloaded.
LOADED TIME – Displays the total time the
NORMAL VIEW compressor has been running loaded.
The Normal View is the default view for the display THIS RUN TIME – Displays the total time the
screen. When in Normal View, information regarding compressor has been running loaded or unloaded
the compressor current operating conditions appears since the most recent startup.
on the display screen. See Figure 4-3.
THIS LOADING – Displays the total time the
The top line of the display screen in Normal View compressor has been running loaded since the most
shows the current compressor operating mode and recent startup.
state. The lower line of the Display Screen displays
the discharge pressure and the internal temperature OIL FILTER – Displays the total time on the oil filter
of the compressor package. since the last service.
A-O SEPARATOR - Displays the total time on the
separator element since the last service.
AIR FILTER – Displays the total time on the air filter
since the last service.

22 02250180-094 R01
SECTION 4 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL
FLUID – Displays the total time on the fluid since the
last service.
GREASE – Displays the total time on the grease Automatic Mode
(Normal View) AUTO LOAD
since the last service.
174°F 62PSI
ALARM1, ALARM2, ALARM3, ALARM4, ALARM5
– Displays past alarms or faults. Displays the
description along with the number of hours on
Figure 4-6: Compressor Operating Mode Display
machine when the alarm or fault occurred.
PRODUCTION DATE – Displays production date of The compressor operating modes are described
compressor. below:

SERIAL NO. – Displays serial number of machine. Automatic mode - Indicated by the word AUTO
appearing in the upper line of the display window.
CUSTOMER SET VIEW – CONTROL This is a user selected mode that sets the
PARAMETERS compressor motor to automatically start when
The Customer Set View shows current machine conditions necessitate and stop when motor
parameters which are conditions and limits that can operation not required.
be modified by the operator. This view is accessed Manual Mode - Indicated by the word MANUAL
using the navigational arrows and is indicated by the appearing in the upper line of the display window.
text “CUSTOMER SET” appearing on the first line of This is a user selected mode that allows the operator
the display screen. The second line of the display to manually control the compressor motor operation.
screen indicates “FACTORY SET”. These are
factory settings which cannot be changed by the end When the START pad is pressed while in
user without the factory password. Press the Right Manual Mode the compressor motor will run
arrow pad when “CUSTOMER SET” appears continuously until the STOP pad is pressed.
as reverse characters on the display screen. From The compressor and all other machine parameters
here, the parameters are displayed and can be function the same in both Manual and Automatic
changed. Refer to Section 3: Adjustments for modes.
instructions on changing the compressor control
parameters and a list of the control parameters that Stop mode - Indicated by the word STOP
can be modified by the user. appearing in the upper line of the display window.
This mode indicates that the compressor and motor
have been turned off under normal conditions. When
CUSTOMER SET in this mode the machine will not operate until the
START pad is pressed. If the machine is stopped
FACTORY SET due to the E-Stop button being pressed, this is
indicated by the word E-STOP appearing in the
upper line of the display window.

Figure 4-5: Accessing Customer Set View Fault mode - Indicated by the word STOP appearing
in the upper line of the display window along with a
4.5 OPERATING MODES fault code on the lower line. This mode indicates that
a machine problem has occurred causing the
The Operating Mode is the manner in which the controller to shut down the machine until the
machine operation is being controlled. condition is cleared. After a fault condition has been
resolved, the fault indication can be cleared from the
There are four Operating Modes: AUTOMATIC, controller by pressing and holding the Return/Reset
MANUAL, STOP, and FAULT. The active operating
mode of the compressor appears on the upper line of pad. Refer to Section 6: Troubleshooting, for
the display screen’s Normal View. See Figure 4-6.
information on resolving fault conditions.

02250180-094 R01 23
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 4

4.6 OPERATING STATES RUN MODE – Displayed after the motor is started
and before delivering air. A timer is displayed which
Operating States describe the state of the counts down the time between starting of the motor
compressor operation in response to the current and de-energizing of the unload solenoid. This time
mode and current conditions. Essentially, the is set with “LOAD DELAY TIME” in the “CUSTOMER
operating state is what the machine is doing at a SET” menu.
particular moment. Most operating states occur
LOAD - Displayed as the compressor begins
automatically as normal functions of the compressor
delivering air.
and require no direct action from the operator. Text
descriptions of operating states appear on the upper U.L. - Displayed as the compressor is being
line of the display screen while in Normal View. See unloaded automatically.
Figure 4-7.
REMOTE U.L. - Displayed as the compressor is
being unloaded remotely.
Operating State
AUTO LOAD
174°F 62PSI 4.7 NORMAL VIEW SERVICE
REMINDERS
Service reminders may appear in the Normal View
Figure 4-7: Controller Display Normal View: Oper- display. See Figure 4-8.
ating State
When service is due, the display will alternate
The list below provides an explanation of each between the operating state display shown in Figure
Operating State message that may appear in the 4-7 and the alarm display shown in Figure 4-8. The
Normal View display. Some operating states occur upper line will indicate the service to be performed
instantaneously and may not be seen by the and the bottom line will display the time it became
operator. Additionally, upon startup the controller due. When a service reminder appears, the machine
serial number, revision level, and production date are will continue to operate normally, however, the
quickly displayed. appropriate service should be scheduled and
accomplished within a short period of time.
STOPPING - Displayed as the compressor is being
stopped. A timer is also displayed which counts
down the delay from when the (O) button is pressed
and the compressor stops. This delay is set with AIR FILTER ALM
‘STOP DELAY TIME” in the “CUSTOMER SET” XXXXH
menu.
STOP – Displayed after the compressor is stopped.
A timer is also displayed which counts down the time
until the motor can be restarted. This time is set with Figure 4-8: Controller Display Normal View: Ser-
“RESTART TIME” in the “CUSTOMER SET” menu. vice Reminder
REMOTE STOP - Displayed when the compressor The list below provides an explanation of the Service
operation is stopped but is armed to restart. The Reminders that may appear in the Normal View
machine will start when the remote start contact is display. Refer to Section 6: Troubleshooting, for
close. additional instructions on actions to be taken when a
STANDBY - Displayed when the compressor is service reminder appears.
stopped and waiting for proper conditions before OIL FILTER ALM - The compressor fluid filter should
restarting. be changed within the time frame noted in the
STOP: (FAULT) - Displayed as a fault condition is machine operation specifications.
occurring. A-O SEPARATOR - The compressor fluid separator
Y START - Displayed as compressor initiates startup should be changed within the time frame noted in the
processes. A timer is also displayed which counts machine operation specifications.
down the start time. This time is set with “STAR- AIR FILTER ALM - The compressor air filter should
DELTA TIME” in the “CUSTOMER SET” menu. be changed within the time frame noted in the

24 02250180-094 R01
SECTION 4 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL
machine operation specifications.
FLUID CHANGE - The compressor fluid should be STOP:
changed within the time frame noted in the machine
operation specifications. RTD FAULT
GREASE CHANGE - The grease should be changed
within the time frame noted in the machine operation
specifications.
Figure 4-10: Controller Display Normal View:
Fault Message
4.8 NORMAL VIEW WARNING
MESSAGE The list below provides an explanation of the Fault
Messages that may appear when problems occur.
A warning message for high discharge temperature Refer to Section 6: Troubleshooting, for instructions
may appear in the Normal View display. This on actions to be taken when a fault condition occurs.
warning message is displayed if the compressor
discharge temperature exceeds 225°F (107°C). See HIGH DISCH TEMP – The compressor discharge
Figure 4-9. When this warning message appears, temperature has exceeded the set limit.
the display will alternate between the operating state PR XDCR FAULT – The pressure transducer has
shown in Figure 4-7 and the warning message failed or a connection has become loose.
shown in Figure 4-9. While the compressor can
continue to operate at this high temperature, RTD FAULT – The temperature sensor has failed or
measures should be taken to correct this operating a connection has become loose.
condition. This can be an indication of other issues HIGH PRESSURE – The compressor operating
that could lead to machine shut down due to high pressure has exceeded the set limit. Refer to
operating temperatures. Refer to Section 6: Table 3-1: Default Pressure Settings on page 17 for
Troubleshooting for additional instructions and shutdown pressure values.
actions to be taken.
MOTOR OVERLOAD – The motor overload relay
has been tripped due to a power overload in the
motor.
HIGH DISCH TEMP
XXXX°F

Figure 4-9: Controller Display Normal View:


Warning Message

4.9 FAULT MESSAGES


When a Fault condition occurs, the machine will shut
down and the display will indicate STOP on the
upper line of the display window and a fault code on
the lower line of the Normal View display. See Figure
4-10.

02250180-094 R01 25
NOTES

26 02250180-094 R01
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

Section 5

SEQUENCING
5.1 INTRODUCTION pad on the master controller. As long as
Compressor sequencing references the use of slave compressors are powered on and properly
multiple compressors to meet the demands for connected and programmed, the sequencing
compressed air. This may be a simple duplex system network will begin to function.
or may consist of multiple compressors used in
applications with widely varying demands. The main To stop sequencing press the STOP pad on
concept for all configurations is for the compressors the master controller. At this point the sequencing
to operate automatically when compressed air is function will cease operation. However, any slave
needed and to automatically stop if not needed. A compressors which may be running will continue to
properly designed system can offer substantial do so until their STOP pad is pressed.
reductions in operating cost over a single large
compressor. If the master machine is powered off and on,
sequencing is not enabled until the START pad
Many duplex systems are designed with one primary
compressor accompanied by one spare compressor. is pressed. If a slave machine is powered off
This configuration allows the system to remain and on, it will be enabled for sequencing as long as
operational during maintenance of a machine. The the master machine has not been powered off.
controller efficiently runs the compressors to meet
the varying demands during the day and runs the 5.2.1 COMPRESSOR SYSTEMS
backup compressor only when needed. Additionally,
Internal controller sequencing is designed to operate
this configuration will rotate primary and backup
a group of compressors feeding a common header.
compressors to evenly distribute run hours across
As air demands change, the compressors will be
both machines. This can simplify maintenance since
controlled to deliver the required compressed air in
both machines will be on the same schedule.
an efficient manner. If a group of similar compressors
The ST Controller features internal sequencing is used, the controllers can be set up to automatically
functions and can be configured with up to 16 rotate operation to equalize run time. The two
machines in a sequence system. ST Controllers modes of sequencing operation are described below:
cannot sequence with WS or Supervisor controllers. Multiple Machines: This mode is applicable to a
sequence network of 2 or more compressors.
Sequencing order of a compressor is based on the
WARNING machine’s total run hours. In this mode, machines
are started and loaded depending on an individual
Machines should be off-line and not running machine’s total run time. Typically the machine with
when making parameter changes. the next lowest number of total run hours will be the
Unexpected machine operation may occur. next in sequence to start and load. If in the case of a
fault or manual shutdown, a machine taken out of
sequence will be skipped and the machine with the
5.2 NORMAL OPERATION next lowest number of hours in the sequence will be
next to start and load. Additionally, machines will be
The ST Controller operates in a master-slave rotated to ensure that all machines within a network
relationship. To enable a properly configured ST maintain similar total run times. While this sequence
Controller network to sequence, press the START mode is active, digital inputs for Remote control are
disabled.

02250180-094 R01 27
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 5

Rotate Hours: This mode applies only to two 1. Complete all machine startup procedures as
machine applications that supply a demand for only required for stand alone operation. Refer to
one machine. In this mode one compressor will the compressor user’s manual.
operate until the current run time matches the user
2. Confirm that all machines read the same
defined rotate hours parameter. After reaching this
pressure at the common header. If not,
time limit, the primary machine will shut down and
check tubing length and separator condition.
the backup machine will begin supplying air. The
compressors will continue to rotate per this 3. Program ST Controllers as follows. Refer to
parameter. Additionally, in the case of a failure the Section 3 – Adjustments for programming
other machine will automatically start to meet instructions.
demand. During this mode of operation, digital
All Machines:
inputs for remote control are disabled.
a. UNLOAD PRESS: System unload pressure
5.3 WIRING AND PIPING where master machine unloads.
b. LOAD PRESS: System load pressure
Control signals are passed along a shielded where master machine starts and loads.
communication line connected in parallel.
Connections to the ST Controller are to be made at c. COM MODE: Set to SEQ to allow sequenc-
the RS-485 A and B terminals. Refer to Figure 5-1: ing of machines
Sequencing Network Connection.. Care should be Master Machine:
taken to avoid high voltage interference.
Communication and power lines should be routed a. SEQUENCE STATE: Set to MASTER.
separately through different conduit. b. COM ADDRESS: Set to 01 for master
For the most efficient operation in a sequential machine. Only one master machine is
allowed in a network.
system, the line pressure transducers of all machines
should be connected to a common header, down c. SEQUENCE NO.: Set to number of
stream of individual dryers, filters, etc. machines in sequencing network. Set
between 02-16.
5.4 MACHINE PREPARATION d. SEQ LOAD PRESS: Pressure at which
PRIOR TO SEQUENCING master sends command to start slave
machine. Must be set higher than LOAD
For each machine to be connected in the sequence: PRESS.

Figure 5-1: Sequencing Network Connection.

28 02250180-094 R01
SECTION 5 SHOPTEK™ CONTROLLER USER INTERFACE MANUAL
e. SEQ UNLOAD PRESS: Pressure at which Example A
master sends command to unload slave
For this example three machines are in a system with
machine. Must be set lower than UNLOAD
PRESS. the following parameter settings:

f. SEQ DELAY: Set time that master machine a. LOAD PRESS = 112 psig
will allow to pass before sending a command b. UNLOAD PRESS = 127 psig
to a slave machine. The default value is 15
seconds. c. SEQ LOAD PRESS = 116 psig

g. ROTATE HOURS: Set to the desired d. SEQ UNLOAD PRESS = 123 psig
amount of current run time before machine is e. SEQ DELAY = 15 seconds
stopped and replaced by another stopped
machine. f. ROTATE HOURS = 10 hours
Slave Machine(s): 1. When system pressure drops below 112
psig, the master machine starts to operate.
a. SEQUENCE STATE: Set to SLAVE
2. If after the sequence delay time of 15 sec-
b. COM ADDRESS: Set to a unique communi-
onds the system pressure remains below
cation ID number for each machine from 02
116 psig, the master compressor will send a
to 16. Duplicate ID numbers are not allowed.
start command to the compressor with the
c. It is not necessary to set SEQ NO., SEQ lowest number of total run hours. Both the
LOAD PRESS, SEQ UNLOAD PRESS, SEQ master and slave compressors are com-
DELAY, or ROTATE HOURS. These param- pared for total run time.
eters are controlled by the master machine.
3. After an additional 15 seconds, if the system
d. LOAD PRESS must be set lower than SEQ pressure remains below 116 psig, the third
LOAD PRESS and UNLOAD PRESS must compressor will start. In networks with more
be set higher than SEQ UNLOAD PRESS to than three machines, this process will con-
avoid unintended operation of slave com- tinue until the demand is met.
pressors.
4. If the system pressure rises above the
4. After both initial programming and making sequence unload pressure setting of 123
any changes to the program of a controller, a psig, the master machine, after waiting 15
power off reset is necessary. seconds, will send a command for the com-
pressor with the highest number of total run
5. Start machines for sequencing as described
time hours to unload. This continues until
in Normal Operation. Machines will start
only the master machine is operating.
immediately if system pressure is low. On a
fully pressurized system, the machines will 5. When the system pressure is above the
enter standby mode until a demand is recog- unload pressure set point of 127 psig, the
nized. master machine will unload and the unload
timer will begin. If in automatic mode, the
5.5 SYSTEM OPERATION master machine will shut down after the
unload run time has passed.
The following examples describe how machines are
6. If a machine has a current run time equal to
started, fully loaded and unloaded in a multiple
the rotate hours parameter, 10 hours in this
compressor network. The Automatic mode provides
case, and there is a compressor which is
the means for each machine to stop by timing out on
currently stopped, the master machine will
its unload timer when the sequencing order indicates
send a stop command to that compressor
the machine is to be unloaded.
and start the stopped machine.

02250180-094 R01 29
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 5

Example B 2. Once 5 hours of current run time has been


reached on the master machine, it will stop
The following example describes operation of a 2
and send a signal to the slave compressor to
compressor system where only one compressor is
start.
needed for demand and one is a spare. The
parameter settings are as follows: 3. When the slave compressor then reaches 5
hours of current run time, it will stop and the
a. LOAD PRESS = 112 psig
master machine will start. The two machines
b. UNLOAD PRESS = 127 psig will continue to rotate in operation at 5 hour
intervals.
c. SEQ LOAD PRESS = 116 psig
4. Additionally, if either compressor is stopped
d. SEQ UNLOAD PRESS = 123 psig
due to a fault the other compressor will start
e. ROTATE HOURS = 5 hours automatically to meet demand.
1. The master machine will meet demand oper-
ating between the sequence load pressure
and sequence unload pressure.

30 02250180-094 R01
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL

Section 6

TROUBLESHOOTING
6.1 TROUBLESHOOTING c. Check for parts damaged by heat or an elec-
INTRODUCTION trical short circuit, usually apparent by discol-
oration or a burnt odor.
This Troubleshooting section is provided as a guide
Should your problem persist after making the
to aid in diagnosing and resolving compressor
recommended check, consult your nearest Sullair
problems when they occur. The information
Distributor or the Sullair Corporation factory Service
contained in Table 6-1:Troubleshooting Guide, has
been compiled from factory experience and contains Department.
symptoms and usual causes for the described
problems. Each Service Reminder, Warning, or
Fault Message is listed with conditions of when the
NOTE
problem may occur, a probable cause, and a
Section 6.2 and Section 6.3 portray com-
suggested solution to the problem. DO NOT assume
mon systematic problems that can occur
that these are the only problems that may occur.
during controller operation. For a more
This document cannot address every possible thoroughly in-depth coverage of machine
adverse condition that may occur nor does it provide operation troubles, consult the Trouble-
every solution for the potential troubles listed. All shooting Section in the machine’s opera-
available data concerning the trouble should be tor’s manual.
systematically analyzed before undertaking any
repairs or component replacement procedures.
6.2 TROUBLESHOOTING GUIDE
Always perform a detailed visual inspection when a
machine problem occurs prior to attempting any Table 5.1 contains symptoms and usual causes for
repairs. Doing so may avoid unnecessary repair the problems that may occur throughout the
and/or additional damage to the compressor. compressor system. Each warning or fault message
that may appear is listed along with conditions for the
Always remember to:
problem, a probable cause, and a suggested solution
a. Check for loose wiring. to the problem. DO NOT assume that these are the
only troubles that may occur.
b. Check for damaged piping.

02250180-094 R01 31
SHOPTEK™ CONTROLLER USER INTERFACE MANUAL SECTION 6

Table 6-1: Controller Troubleshooting Guide


MESSAGE PROBABLE CAUSE REMEDY
MOTOR OVERLOAD Main motor overload tripped. Reset overload after heater element cools.
Verify correct motor amps.
Fan motor circuit protector tripped Reset circuit protector.
Check that compressor is properly
configured.
Ensure load pressure is set below limit of
compressor.
Check for loose connections.
Check motor starter contact for proper
operation.
Check line voltage, if low consult power
company.
OIL FILTER ALM Service interval has expired. Perform recommended maintenance and
A-O SEPARATOR Maintenance due. reset the reminder in the controller.

AIR FILTER ALM


FLUID CHANGE
GREASE CHANGE
E-STOP E-Stop button active. Release button.
Faulty E-Stop button. Check wiring.
Replace button if necessary.
HIGH PRESSURE Faulty pressure sensor. Check and replace pressure sensor if
defective.
High pressure. Check operation of valves and controls.
Faulty unload solenoid valve. Check solenoid valve operation and wiring.
HIGH DISCH TEMP High ambient temperature, above Improve ventilation.
105°F (40°C).
Fluid level low. Replenish fluid to proper level.
Thermal valve fault. Check thermal valve operation.
Cooler fins dirty. Clean cooler and fan blades.
Temp sensor failure. Check sensor and wiring, replace if
necessary.
PR XDCR FAULT Loose connection Check connections, repair if needed.
Faulty pressure sensor. Check and replace if defective.
RTD FAULT Loose connection Check connections, repair if needed.
Faulty temp sensor. Check and replace if defective.

6.3 MACHINE BEHAVIOR AFTER If the compressor was manually stopped prior to the
A POWER INTERRUPTION power interruption, the controller will return to the
manually stopped mode. Press the start button to
If the compressor was faulted prior to the power manually restart operation.
interruption, the controller will resume the FAULTED
If Auto-Restart is enabled and the compressor was in
condition and display the reason for the fault. Repair
Auto or Manual mode prior to power interruption, the
the cause of the fault and press the ENTER controller will resume that mode after the restart
timer is expired. No key press is necessary to restart
pad to reset the controller. the compressor.

32 02250180-094 R01
NOTES

33
WORLDWIDE SALES AND SERVICE
SULLAIR ASIA, LTD. SULLAIR CORPORATION SULLAIR EUROPE, S.A.
Zuo Pao Tai Road, No. 1 3700 East Michigan Boulevard Zone Des Granges BP 82
Chiwan, Shekou Michigan City, Indiana, 46360 U.S.A. 42602 Montbrison, France
Shenzen, Guangdong PRV. www.sullair.com Telephone: 33-477968470
PRC POST CODE 518068 Telephone: 1-800-SULLAIR (U.S.A. only) Fax: 33-477968499
Telephone: 755-6851686 Fax: 219-874-1273 www.sullaireurope.com
Fax: 755-6853473
www.sullair-asia.com CUSTOMER CARE
for PARTS and Service
1-888-SULLAIR (7855247)
219-874-1835

Champion Compressors, LTD.


324-332 Frankston Dandenong Road
Dandenong VIC
Australia 3175
Ph: +61397039000
Fx: +61397039053
www.championcompressors.com.au

Printed in the U.S.A.


Specifications subject to
change without prior notice.
E10EP

You might also like