Professional Documents
Culture Documents
2354235 11/2008
User manual
07/2023
www.schneider-electric.com
Contents
EAV94277 07/2023 3
Important information
NOTICE
Read these instructions carefully, and become familiar with the device before trying to install, operate, or maintain it. The following special
messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential injury hazards that exist at this point. Obey all safety messages
that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation which, if not avoided, can result in death, serious injury or
equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, can result in injury or equipment
damage.
NOTICE
Notice, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can
result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller of the adjustable speed drive as defined by NEC.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this product.
4 EAV94277 07/2023
Before you begin
Read and understand these instructions before performing any procedure with this drive.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
• Only appropriately trained persons who are familiar with and fully understand the contents of the present manual and all other
pertinent product documentation and who have received all necessary training to recognize and avoid hazards involved are
authorized to work on and with this drive system.
• Installation, adjustment, repair and maintenance must be performed by qualified personnel.
• Verify compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to
grounding of all equipment.
• Only use properly rated, electrically insulated tools and measuring equipment.
• Do not touch unshielded components or terminals with voltage present.
• Prior to performing any type of work on the drive system, block the motor shaft to prevent rotation.
• Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus
voltage that can exceed 800 Vdc.
- Verify that no other voltage is present in the drive system.
• Before applying voltage to the drive system:
- Verify that the work has been completed and that the entire installation cannot cause hazards.
- If the mains input terminals and the motor output terminals have been grounded and short-circuited, remove the ground and
the short circuits on the mains input terminals and the motor output terminals.
- Verify proper grounding of all equipment.
• Verify that all protective equipment such as covers, doors, grids is installed and/or closed.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNEXPECTED MOVEMENT
Drive systems may perform unexpected movements because of incorrect wiring, incorrect settings, incorrect data or other errors.
• Carefully install the wiring in accordance with the EMC requirements.
• Do not operate the product with unknown or unsuitable settings or data.
• Perform a comprehensive commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Damaged products or accessories may cause electric shock or unanticipated equipment operation.
DANGER
ELECTRIC SHOCK OR UNANTICIPATED EQUIPMENT OPERATION
Do not use damaged products or accessories.
Failure to follow these instructions will result in death or serious injury.
Contact your local Schneider Electric sales office if you detect any damage whatsoever.
NOTICE
RISK OF DAMAGE TO THE DRIVE
The drive should be cleaned and maintained on a regular basis when operating in high temperature, humid, greasy, chemical, dusty
or vibrating environments to prevent reduced driver lifespan and equipment damage.
Failure to follow these instructions can result in equipment damage.
EAV94277 07/2023 5
Before you begin
WARNING
LOSS OF CONTROL
• The designer of any control scheme must consider the potential failure modes of control paths and, for critical control functions,
provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop,
overtravel stop, power outage, and restart.
• Separate or redundant control paths must be provided for critical control functions.
• System control paths may include communication links. Consideration must be given to the implications of unanticipated
transmission delays or failures of the link.
• Observe all accident prevention regulations and local safety guidelines. (a)
• Each implementation of the product must be individually and thoroughly tested for proper operation before being placed into service.
Failure to follow these instructions can result in death, serious injury or equipment damage.
a. For USA: Additional information, refer to NEMA ICS 1.1 (latest edition), “Safety Guidelines for the Application, Installation, and
Maintenance of Solid State Control” and to NEMA ICS 7.1 (latest edition), “Safety Standards for Construction and Guide for Selection,
Installation and Operation of Adjustable Speed Drive Systems.”
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the mains voltage.
Failure to follow these instructions can result in equipment damage.
This equipment has been designed to operate outside of any hazardous location. Only install this equipment in zones known to be free of
a hazardous atmosphere.
DANGER
POTENTIAL FOR EXPLOSION
Install and use this equipment in non-hazardous locations only.
Failure to follow these instructions will result in death or serious injury.
6 EAV94277 07/2023
Before you begin
Your application consists of a whole range of different interrelated mechanical, electrical, and electronic components, the drive being just
one part of the application. The drive by itself is neither intended to nor capable of providing the entire functionality to meet all safety-related
requirements that apply to your application. Depending on the application and the corresponding risk assessment to be conducted by you,
a whole variety of additional equipment is required such as, but not limited to, external encoders, external brakes, external monitoring
devices, guards, etc.
As a designer/manufacturer of machines, you must be familiar with and observe all standards that apply to your machine. You must conduct
a risk assessment and determine the appropriate Performance Level (PL) and/or Safety Integrity Level (SIL) and design and build your
machine in compliance with all applicable standards. In doing so, you must consider the interrelation of all components of the machine. In
addition, you must provide instructions for use that enable the user of your machine to perform any type of work on and with the machine
such as operation and maintenance in a safe manner.
The present document assumes that you are fully aware of all normative standards and requirements that apply to your application. Since
the drive cannot provide all safety-related functionality for your entire application, you must ensure that the required Performance Level and/
or Safety Integrity Level is reached by installing all necessary additional equipment.
WARNING
INSUFFICIENT PERFORMANCE LEVEL/SAFETY INTEGRITY LEVEL AND/OR UNINTENDED EQUIPMENT OPERATION
• The designer of any control scheme must consider the potential failure modes of control paths and, for critical control functions,
provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop,
overtravel stop, power outage, and restart.
• Conduct a risk assessment according to EN ISO 12100 and all other standards that apply to your application.
• Use redundant components and/or control paths for all critical control functions identified in your risk assessment.
• If moving loads can result in hazards, for example, slipping or falling loads, operate the drive in closed loop mode.
• Verify that the service life of all individual components used in your application is sufficient for the intended service life of your overall
application.
• Perform extensive commissioning tests for all potential error situations to verify the effectiveness of the safety-related functions and
monitoring functions implemented, for example, but not limited to, speed monitoring by means of encoders, short circuit monitoring
for all connected equipment, correct operation of brakes and guards.
• Perform extensive commissioning tests for all potential error situations to verify that the load can be brought to a safe stop under all
conditions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
EAV94277 07/2023 7
Before you begin
Machines, controllers, and related equipment are usually integrated into networks. Unauthorized persons and malware may gain access to
the machine as well as to other devices on the network/fieldbus of the machine and connected networks via insufficiently secure access to
software and networks.
WARNING
UNAUTHORIZED ACCESS TO THE MACHINE VIA SOFTWARE AND NETWORKS
• In your hazard and risk analysis, consider all hazards that result from access to and operation on the network/fieldbus and develop
an appropriate cybersecurity concept.
• Verify that the hardware infrastructure and the software infrastructure into which the machine is integrated as well as all
organizational measures and rules covering access to this infrastructure consider the results of the hazard and risk analysis and are
implemented according to best practices and standards covering IT security and cybersecurity, such as:
• ISO/IEC 27000 series, ISO/ IEC 15408, IEC 62351, ISA/IEC 62443,
• NIST Cybersecurity Framework,
• Information Security Forum - Standard of Good Practice for Information Security,
• Schneider Electric Recommended Cybersecurity Best Practices.
• Verify the effectiveness of your IT security and cybersecurity systems using appropriate, proven methods.
Failure to follow these instructions can result in death, serious injury or equipment damage.
WARNING
LOSS OF CONTROL
Perform a comprehensive commissioning test to verify that communication monitoring properly detects communication interruptions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
NOTICE
MOTOR OVERHEATING
Install external thermal monitoring equipment under the following conditions:
If several motor are connected to the same drive, Install external thermal monitoring equipment for each motor
Failure to follow these instructions can result in equipment damage.
8 EAV94277 07/2023
Documentation structure
The following Altivar 310 technical documents are available on the Schneider Electric website (www.schneider-electric.cn).
EAV94277 07/2023 9
Steps for setting up (also refer to Quick Start)
6. Start
10 EAV94277 07/2023
Setup - Preliminary recommendations
Line contactor
NOTICE
RISK OF DAMAGE TO THE DRIVE
Do not switch on the drive at intervals of less than 60 s.
Failure to follow these instructions can result in equipment damage.
NOTICE
MOTOR OVERHEATING
Install external thermal monitoring equipment if a motor with a nominal current of less than 20% of the nominal current of the drive is
connected.
Failure to follow these instructions can result in equipment damage.
EAV94277 07/2023 11
Drive& ratings
(1) These power ratings are for a Switching frequency range of 4 kHz, in continuous operation. The Switching frequency range is
adjustable from 2 to 12 kHz.
Above 4 kHz, the drive will reduce the Switching frequency range if an excessive temperature rise occurs. Derating should be
applied to the nominal drive current if continuous operation above 4 kHz is required:
• 10% derating for 8 kHz
• 20% derating for 12 kHz
(2) Values given for applications requiring significant overload (up to 150% for 60 s).
(3) Values given for applications requiring slight overload (up to 110% for 60 s).
(4) Line current network requirements:
• ≤ 4 kW, network short circuit current Isc ≤ 5 kA
• > 4 kW, network short circuit current Isc : ≤ 22 kA for Heavy duty, ≤ 5 kA for Normal duty
(5) • Easy Altivar ATV310•••N4•F drives with integrated EMC filter fulfill IEC/EN61800-3 with 25 m/82 ft shielded motor cable for
CE, and with 5m/16.4ft shielded motor cable for RE.
• Easy Altivar ATV310•••N4• drives without integrated EMC filter, need to add external EMC filter to fulfill the IEC/EN 61800-3
standard. Refer to External EMC filter selection table page 13.
NOTICE
RISK OF DAMAGE TO THE DRIVE
The drive will be damaged if it operates above the nominal current (In) for an extended period of time.
Operating time should not exceed 60 s at 1.5 x In.
Failure to follow these instructions can result in equipment damage.
12 EAV94277 07/2023
Drive& ratings
EAV94277 07/2023 13
Dimensions and weights
ATV310H037N4p, ATV310H075N4p
a b c G H H1 Ø For Weight
ATV310H mm mm mm mm mm mm mm screw kg
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
037N4p 72 130 130 60 118 143 5 0.8
M4
(2.83) (5.12) (5.12) (2.36) (4.65) (5.63) (0.20) (1.8)
72 130 140 60 118 143 5 0.8
075N4p M4
(2.83) (5.12) (5.51) (2.36) (4.65) (5.63) (0.20) (1.8)
ATV310HU15N4p, ATV310HU22N4p
a b c G H H1 Ø For Weight
ATV310H mm mm mm mm mm mm mm screw kg
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
105 130 151 93 118 143 5 1.1
U15N4p M4
(4.13) (5.12) (5.94) (3.66) (4.65) (5.63) (0.20) (2.43)
105 130 151 93 118 143 5 1.1
U22N4p M4
(4.13) (5.12) (5.94) (3.66) (4.65) (5.63) (0.20) (2.43)
a b c G H H1 Ø For Weight
ATV310H mm mm mm mm mm mm mm screw kg
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
140 171 151 126 157 184 5 1.8
U30N4p M4
(5.51) (6.73) (5.94) (4.96) (6.18) (7.24) (0.20) (3.97)
140 171 151 126 157 184 5 1.8
U40N4p M4
(5.51) (6.73) (5.94) (4.96) (6.18) (7.24) (0.20) (3.97)
140 171 151 126 157 184 5 1.8
U55N4p M4
(5.51) (6.73) (5.94) (4.96) (6.18) (7.24) (0.20) (3.97)
ATV310HU75N4p, ATV310HD11N4p
a b c G H H1 Ø For Weight
ATV310H mm mm mm mm mm mm mm screw kg
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
150 220 171 130 210 232 5 3.7
U75N4p M4
(5.91) (8.66) (6.73) (5.12) (8.27) (9.13) (0.20) (8.16)
150 220 171 130 210 232 5 3.7
D11N4p M4
(5.91) (8.66) (6.73) (5.12) (8.27) (9.13) (0.20) (8.16)
14 EAV94277 07/2023
Dimensions and weights
ATV310HD15N4p, ATV310HD18N4p
a b c G H H1 Ø For Weight
ATV310
mm mm mm mm mm mm mm screw kg
H
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
D15N4p 180 311 191 160 295 330 6 6.3
M5
(7.09) (12.24) (7.52) (6.29) (11.61) (12.99) (0.23) (13.9)
D18N4p 180 311 191 160 295 330 6 6.3
M5
(7.09) (12.24) (7.52) (6.29) (11.61) (12.99) (0.23) (13.9)
NOTE: for ATV310HD15N4pF and ATV310HD18N4pF, the weight is 6.7 kg (14.8 Ib).
ATV310HD22N4p
4X 6
a b c G H H1 Ø For Weight
ATV310
mm mm mm mm mm mm mm screw kg
H
(in.) (in.) (in.) (in.) (in.) (in.) (in.) s (lb)
D22N4p 180 384.5 212 156 371.5 390 6 8.5
M5
(7.09) (15.14) (8.35) (6.14) (14.63) (15.35) (0.23) (18.7)
NOTE: for ATV310HD22N4pF, the weight is 9.7kg (21.4Ib).
12 12
EAV94277 07/2023 15
Environmental Conditions
Temperature Conditions
Mounting types:
Type A: IP20, IP4X for top with vent cover
Type B: IP20 side by side
Type C: IP20
16 EAV94277 07/2023
Environmental Conditions
Relative Humidity
Without dripping water and without condensation: 5...95% according to IEC 60068-2-3
Operating Altitude
Operating altitude Supply voltage Electrical supply network Derating
TT/TN IT Corner-Grounded
m Up to 1000 380 - 460 V three-phase Without derating
ft Up to 3280
m 1000 ... 2000 380 - 460 V three-phase With derating current by 1% (maxi)
ft 3280 ... 6560
per additional 100 m (328 ft)
m 2000 ... 3000 380 - 460 V three-phase With derating current by 1% (maxi)
ft 6560 ... 9840
- per additional 100 m (328 ft)
EAV94277 07/2023 17
Mounting
Mounting
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• The drive panel must be properly grounded before power is applied.
• Use the provided ground connecting point as shown in the figure below.
Failure to follow these instructions will result in death or serious injury.
DANGER
ATV310HpppN4p - GROUND CONTINUITY HAZARD
An anodized heatsink can create an insulation barrier to the mounting surface. Ensure that you follow the recommended grounding
connections.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK CAUSED BY FOREIGN OBJECTS OR DAMAGE
Conductive foreign objects in the product or damage may cause parasitic voltage.
• Do not use damaged products.
• Keep foreign objects such as chips, screws or wire clippings from getting into the product.
Failure to follow these instructions will result in death or serious injury.
Leave sufficient free space to ensure that the air required for cooling
purposes can circulate from the bottom to the top of the drive.
10 mm
(2 in.)
(0.4 in.) Drive installation should employ fastening washers and screws in
combination.
18 EAV94277 07/2023
Mounting
Mounting types
Type A mounting
Type B mounting
Type C mounting
With these types of mounting, drives with a Switching frequency range of 4 kHz can be used up to an ambient temperature which was listed
below:
For ATV310N4 @ Heavy duty
1. At ambient temperatures, Type B and Type C mounting between +55°C and +60°C:
Derate current by 2.4% for every 1°C of temperature rise
Switching frequency range will adjust according to the internal temperature of the drive
EAV94277 07/2023 19
Mounting
20 EAV94277 07/2023
Wiring
General instructions
DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK
• Wire cross sections and tightening torques must comply with the specifications provided in this document
• Do not use multi-conductor cables without cable lugs for any connection with a voltage higher than 25 Vac.
Failure to follow these instructions will result in death or serious injury.
Keep power cables separate from devices containing circuits with low-level signals (detectors, PLCs, measuring apparatus, video,
telephone). Always cross control and power cables at 90° if possible.
DANGER
INSUFFICIENT PROTECTION AGAINST OVERCURRENTS CAN CAUSE FIRE OR EXPLOSION
• Use properly rated overcurrent protection devices.
• Use the fuses/circuit breakers specified.
• Do not connect the product to a supply mains whose short circuit current rating (current that flows during a short circuit) exceeds
the specified permissible value.
• When rating the upstream mains fuses and the cross sections as well as the lengths of the mains cables, take into account the
minimum required prospective short-circuit current (Isc). Refer to the Upstream Protection Device section.
• If the minimum required prospective short-circuit current (Isc) is not available, increase the power of the transformer or decrease
the length of the cables.
Failure to follow these instructions will result in death or serious injury.
Control
For control and speed reference circuits, we recommend using shielded twisted cables with a pitch of between 25 and 50 mm (1 and 2 in.).
Connect the shielding to ground.
WARNING
UNINTENDED BEHAVIOR OF INPUTS AND OUTPUTS
The functions of the inputs and outputs depend on the selected operating mode and the settings of the corresponding parameters.
• Verify that the wiring is appropriate for the settings.
• Only start the system if there are no persons or obstructions in the zone of operation.
• When commissioning, carefully run tests for all operating states and potential error situations.
Failure to follow these instructions can result in death, serious injury or equipment damage.
EAV94277 07/2023 21
Wiring
Equipment Grounding
Ground the drive according to local and national code requirements. A minimum wire size of 10 mm² may be required to meet standards
limiting leakage current.
DANGER
ELECTRIC SHOCK CAUSED BY INSUFFICIENT GROUNDING
Insufficient grounding causes the hazard of electric shocks.
• Ground the drive system before applying voltage.
• Do not use conduits as protective ground conductors; use a protective ground conductor inside the conduit.
• The cross section of the protective ground conductor must comply with the applicable standards.
• Do not consider cable shields to be protective ground conductors.
Failure to follow these instructions will result in death or serious injury.
DANGER
ATV310HpppN4p - GROUND CONTINUITY HAZARD
An anodized heatsink can create an insulation barrier to the mounting surface. Ensure that you follow the recommended grounding
connections.
Failure to follow these instructions will result in death or serious injury.
DANGER
ELECTRIC SHOCK CAUSED BY INSUFFICIENT GROUNDING
This product has an increased leakage current > 3.5 mA.
• Use a protective ground conductor with at least 10 mm2 (AWG 6) or two protective ground conductors with the cross section of the
conductors supplying the power terminals.
• Verify compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to
grounding of all equipment.
Failure to follow these instructions will result in death or serious injury.
NOTICE
DESTRUCTION DUE TO INCORRECT MAINS VOLTAGE
Before switching on and configuring the product, verify that it is approved for the mains voltage.
Failure to follow these instructions can result in equipment damage.
22 EAV94277 07/2023
Wiring
DANGER
HAZARD OF FIRE OR ELECTRIC SHOCK
For drives y 4kW, the length of stripped part of wires connecting motors and drives and connecting to brake resistor should not exceed
10 mm (0.4 in.).
Failure to follow these instructions will result in death or serious injury.
WARNING
INSUFFICIENT PROTECTION AGAINST OVERCURRENTS
• Properly rated overcurrent protective devices must be used.
• Do not connect the product to a supply mains whose short-circuit current rating (Isc) exceeds the permissible value (1).
Failure to follow these instructions can result in death, serious injury or equipment damage.
(1) the permissible value of the drive short-circuit current rating is 5 kA for product up to 4kW and 22 kA above 4 kW.
EAV94277 07/2023 23
Wiring
R1C
R1A
R1B
b
R/L1
S/L2
T/L3
AO1
COM
AI1
+5V
+24 V
PA / +
W/T3
COM
U/T1
V/T2
LO+
LO-
LI1
LI2
LI3
LI4
PB
W1
U1
V1
M
3a
Power
3-phase
motor
Wiring label
Input 380 V
Output 380 V
24 EAV94277 07/2023
Wiring
Operation on an IT System
Definition
IT system: Isolated or impedance grounded neutral. Use a permanent insulation monitoring device compatible with nonlinear loads, such
as an XM200 type or equivalent.
Corner grounded system: System with one phase grounded.
Operation
NOTICE
OVERVOLTAGE OR OVERHEATING
If the drive is operated via an IT or corner grounded system, the integrated EMC filter must be disconnected as described in the present
manual.
Failure to follow these instructions can result in equipment damage.
EAV94277 07/2023 25
Wiring
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the instructions in "Before your begin" chapter before performing any procedure in this chapter.
Failure to follow these instructions will result in death or serious injury.
The drives have a built-in EMC filter (*). As a result, they exhibit leakage current to ground. If the leakage current creates compatibility
problems with your installation (residual current device or other), then you can reduce the leakage current by deactivating the Y capacitors
as shown below. In this configuration the product does not meet the EMC requirements according to the standard IEC 61800-3.
(*): Except ATV310HDN4A/ ATV310HDN4E drives (for 3-phase 380...460 V supply mains)
Step Action
1 Remove the power terminal cover
2 The switch is factory set to the position shown on detail
3 To disconnect the built-in EMC filter, remove the screw from its location and set it to the position as shown on detail
4 Refit the front cover
NOTE:
• Use only the screw supplied.
• Do not operate the drive with setting screw removed.
Grounding No
26 EAV94277 07/2023
Power terminals
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the instructions in "Before your begin" chapter before performing any procedure in this chapter.
Failure to follow these instructions will result in death or serious injury.
The incoming line power terminals and output terminals to the motor are located at the bottom of the drive. The power terminals can be
accessed without opening the wiring trap if you use stripped wire cables.
EAV94277 07/2023 27
Power terminals
28 EAV94277 07/2023
Power terminals
037N4p 0.8~1
1.5~2.5 (16~14) 2.5 (14)
075N4p (7.1 to 8.9)
U15N4p 0.8~1
1.5~2.5 (16~14) 2.5 (14)
U22N4p (7.1 to 8.9)
EAV94277 07/2023 29
Power terminals
(1) The value in bold corresponds to the minimum wire gauge to permit secureness.
(2) 70°C copper cable (minimum wire size for rated use).
(3) Recommended to maximum value.
Screwdriver(s)
For ≤18.5 kW terminal wiring, use Phillips-head screwdriver PH2 (Ø6).
For 22 kW terminal wiring, use Phillips-head screwdriver PH2 (Ø6) or PH3 (Ø8).
30 EAV94277 07/2023
Power terminals
d2 1.5~1.8mm
Ring Plug
F
B
C
E
d1 Figure 1 Figure 2 Wire
EAV94277 07/2023 31
Control terminals
Keep the control circuits away from the power cables. For control and speed reference circuits, we recommend using shielded twisted
cables with a pitch of between 25 and 50 mm (1 and 2 in.). Connect the shield to ground as outlined on page 36.
COM
AI1
5V
AO1
(1) The value in bold corresponds to the minimum wire gauge to permit secureness.
(2) Recommended to maximum value.
Recommended screwdriver(s)
Control terminal wiring requires a Phillips-head screwdriver PH0 (Ø3).
32 EAV94277 07/2023
Control terminals
(1)
(1) LO logic output maximum current could be 100 mA when external power supply or internal +24 V supply alone to LO. If the internal
+24 V supply logic inputs also, the maximum current will be 80 mA
EAV94277 07/2023 33
Control terminals
Pin Signal
1 Reserved
2
3
4 D1 (1)
5 D0 (1)
8........................1 6 Reserved
7 VP
NOTE: Supply for RS232 / RS485 converter or a remote terminal.
8 Common (1)
NOTICE
RISK OF SERIAL PORT DAMAGE
Do not connect shield layer of the cable to Common (pin8).
Failure to follow these instructions can result in equipment damage.
34 EAV94277 07/2023
Control terminals
NOTE: The modification will be taken into account only at the next control power-on.
Source - using external supply Sink - using external supply
COM
AO1
R1C
R1C
R1A
R1B
R1A
R1B
COM
AO1
AI1
5V
AI1
5V
G
G
LO+
LO+
COM
COM
LO-
LO-
+24V
+24V
LI1
LI1
LI2
LI2
LI3
LI4
LI3
LI4
0V 0V
+24 V +24 V
AO1
R1C
R1C
R1A
R1B
R1A
R1B
COM
AO1
AI1
5V
AI1
5V
G
G
LO+
LO+
COM
COM
LO-
LO-
+24V
+24V
LI1
LI1
LI2
LI2
LI3
LI4
LI3
LI4
WARNING
UNANTICIPATED EQUIPMENT OPERATION
• If the function Logic input type 203 is set to "01" or "02", do not connect the "0 V" terminal to ground or to protective ground.
• Verify that accidental grounding of digital inputs configured for sink logic, caused, for example, by damage to the signal cables,
cannot occur.
• Follow all applicable standards and directives such as NFPA 79 and EN 60204 for proper control circuit grounding practices.
• If you connect a PLC with sink output to the drive:
- Make sure to set the parameter 203 to "02" before you connect the PLC to the drive.
- Disconnect the hardware wiring between PLC and drive when you try to restore the factory setting 102 to "64" of the drive.
Failure to follow these instructions can result in death, serious injury or equipment damage.
EAV94277 07/2023 35
Electromagnetic Compatibility
Shielded cables
EMC measures Objective
Connect large surface areas of cable shields, use cable clamps and ground straps. Reduces emissions.
Use cable clamps to connect a large surface area of the shields of all shielded cables to the mounting plate at
the control cabinet entry.
Ground shields of digital signal wires at both ends by connecting them to a large surface area or via conductive Reduces interference affecting
connector housings the signal wires, reduces
emissions
Ground the shields of analog signal wires directly at the device (signal input); insulate the shield at the other Reduces ground loops due to
cable end or ground it via a capacitor (for example, 10 nF, 100 V or higher. low-frequency interference.
Use only shielded motor cables with copper braid and a coverage of at least 85%, ground a large surface area Diverts interference currents in a
of the shield at both ends. controlled way, reduces
emissions.
Cable Installation
EMC measures Objective
Do not route fieldbus cables and signal wires in a single cable duct together with lines with DC and AC voltages Reduces mutual interference.
of more than 60 V (fieldbus cables, signal lines and analog lines may be in the same cable duct).
Recommendation: Use separate cable ducts at least 20 cm apart.
Keep cables as short as possible. Do not install unnecessary cable loops, use short cables from the central Reduces capacitive and
grounding point in the control cabinet to the external ground connection. inductive interference.
Use equipotential bonding conductors in the following cases: wide-area installations, different voltage supplies Reduces current in the cable
and installation across several buildings. shield, reduces emissions.
Use fine stranded equipotential bonding conductors. Diverts high-frequency
interference currents
If motor and machine are not conductively connected, for example by an insulated flange or a connection without Reduces emissions, increases
surface contact, you must ground the motor with a ground strap or a ground wire. The conductor cross section immunity.
must be at least 10 mm2 (AWG 6).
Use twisted pair for the DC supply. Reduces interference affecting
For digital and analog inputs use shielded twisted cables with a pitch of between 25...50 mm (1...2 in). the signal cables, reduces
emissions.
Power Supply
EMC measures Objective
Operate product on mains with grounded neutral point. Enables effectiveness of mains
filter.
Surge arrester if there is a risk of overvoltage. Reduces the risk of damage
caused by overvoltage.
36 EAV94277 07/2023
Check list Before Switching On
Mechanical Installation
Verify the mechanical installation of the entire drive system:
Step Action
Electrical installation
Verify the electrical connections and the cabling:
Step Action
EAV94277 07/2023 37
Factory configuration
If the above values are compatible with the application, the drive can be used without changing the settings.
R1B
b
R/L1
S/L2
T/L3
AO1
COM
AI1
+5V
(2)
(4)
+24 V
PA / +
W/T3
COM
U/T1
V/T2
LO+
LO-
LI1
LI2
LI3
LI4
PB
W1
U1
V1
M
3a
3-phase Source
motor
38 EAV94277 07/2023
Basic functions
Drive ventilation
Ratings up to 0.75 kW (1 HP) do not include a fan. Other ratings do contain a built-in cooling fan. There are two cooling fan run modes: in
the first, the fan runs when drive is running; in the second, the fan runs when the drive thermal state requires ventilation. The fan runs only
runs when the drive thermal state requires ventilation.
NOTE: The motor thermal state memo returns to zero when the drive power is cycled if Motor thermal state memo 604.3
parameter (page 106) is not set to 01.
NOTICE
MOTOR OVERHEATING
The motor thermal state is not saved when drive is switched off.
When the drive is switched on, it is not aware of the thermal state of the connected motor or motors.
To enable correct temperature monitoring of the motors, install an external temperature sensor for each motor.
Failure to follow these instructions can result in equipment damage.
NOTICE
MOTOR OVERHEATING
Install external thermal monitoring equipment under the following conditions:
• If a motor with a nominal current of less than 20% of the nominal current of the drive is connected.
• If you use the function Motor Switching.
• If several motors are connected to the same drive
Failure to follow these instructions can result in equipment damage.
EAV94277 07/2023 39
Programming
HMI description
Functions of the display and keys
WARNING
LOSS OF CONTROL
The function Stop key priority 405 parameter disables the Stop keys of the drive and of the Remote Display Terminal if the setting
of the parameter is 00.
Only set this parameter to 00 if you have implemented appropriate alternative stop functions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
40 EAV94277 07/2023
Programming
Remote control
Remote operation and programming by HMI is possible using the optional display terminal part VW3A1006. The dimensions of the display
terminal part are 70 mm (2.76 in) x 50 mm (2.76 in).
EAV94277 07/2023 41
Programming
First power-up
At first power-up you are prompted to set Standard motor frequency 301 (page 66). Next time power is applied --00 appears.
Operating mode selection is then possible using the MODE or JOG key as detailed below.
Menus structure
Access to menus and parameters is possible through the Reference (rEF) mode (page 47), Monitoring (800-) mode (page 47) and
Configuration (COnF) mode (page 53). Switching between these modes is possible at any time using the MODE key or Jog Dial on the
keyboard. The first MODE key depression moves from current position to the top of the branch. A second depression switches to next mode.
3s Actual Frequency
ESC ESC
ESC
42 EAV94277 07/2023
Structure of parameter tables
The mode, sectional, menu, sub-menu and parameter table structure is laid out below.
NOTE: Parameters containing the sign in the code column can be modified with the drive running or stopped.
Example:
5
400-
Control menu 9
00
408 M Forced local assignment
6 10
00 v No
LIH v L1H
L2H v L2H
L3H v L3H
L4H v L4H
EAV94277 07/2023 43
Function compatibility table
A p
Fast stop (page 77)
(1)
X p A
DC injection (page 78)
(1)
(1) Priority is given to the first of these two stop modes to be activated.
44 EAV94277 07/2023
Reference Mode rEF
Use the reference mode to monitor and if local control is enabled (Reference channel 1 401 page 73 = 183), adjust the actual reference
value by rotating the jog dial.
When local control is enabled, the jog dial of the HMI acts as a potentiometer to change the reference value up and down within the limits
preset by other parameters (512.0 and 512.2). There is no need to press the ENT key to confirm the change of the reference.
If local command mode is disabled, using Command channel 1 407 page 74, only reference values and units are displayed. The value
will be "read only" and cannot be modified by the jog dial (the reference is no longer given by the jog dial but from an AI or other source).
The actual reference displayed determined by the choice made in Reference channel 1 401 page 73.
Organization tree
(1) Determined by active reference channel.
Possible values: rEF
402
403
801 ESC
59.11
806
(1) ENT
(2) 2 s or ESC
ESC
0 to 100% -
59.11
M Internal PID reference value
This parameter allows modification of the PID internal reference with the jog dial.
(1) Visibility determined by drive settings.
0 to 100% -
806
M PID reference value value
This parameter is the PID reference value expressed as a %.
(1) It is not necessary to press ENT key to confirm modification of the reference.
EAV94277 07/2023 45
Monitoring mode MOn
When the drive is running, the value displayed is that of one of the monitoring parameters. The default value displayed is the motor Output
frequency 802 (page 47).
While the value of the desired new monitoring parameter is being displayed, press the jog dial button a second time to display the unit.
Organization tree
ENT ENT
900- 901 ESC
ESC
ENT
902
ESC
ENT ENT
903 HErt
ESC
(2)
ENT
904
ESC
values ENT
800 905 ESC
units
--00 ENT
906
ENT ESC
ENT
907 ESC
ENT
ENT ENT
(1) HErt 908 ESC
ESC
(2)
ENT ENT
ENT
801 HErt 909
ESC ESC
(2)
ENT ENT
ENT ENT
802 HErt 910 ESC
ESC
(2) (2)
ENT ENT
ENT ENT
911
803 ESC
ESC
(2) (2)
ENT
ENT ENT
912 100
804 ESC
ESC
(2)
ENT
805
ENT ENT
913 ESC
r0t1
ESC
(2)
ENT
ENT ENT
806 914 ESC
ESC
(2)
ENT
ENT ENT
807 915 ESC
ESC
(2)
ENT ENT ENT
808 916 ESC
ESC
(2)
ENT ENT ENT
809 917
ESC ESC
(2)
ENT ENT ENT
810 ESC
918 ESC
(2)
ENT ENT
811 01 919
ESC ESC
ENT
920 ESC
ENT
921 ESC
ENT
999
ESC
(1) Determined by active reference channel. Displayed parameter values and units of the diagram are given as
Possible values: examples.
402
403
(2) 2 s or ESC
46 EAV94277 07/2023
Monitoring mode MOn
External display terminal or local force mode configured. Forced local reference 409 (page 74) set to
163 and Forced local assignment 408 (page 74) is not 00.
Displays the Actual speed reference coming from the remote display terminal. This value is not visible in
factory setting.
%
403 M Integrated display jog dial reference
Embedded display terminal active or local force mode configured. Forced local reference 409 (page 74)
set to 183 and Forced local assignment 408 (page 74) is not 00.
Displays the Actual speed reference coming from the jog dial. This value is not visible in factory setting.
Hz
801 M Speed reference
Actual frequency reference
Hz
802 M Output frequency
This parameter provides the estimated motor speed. It corresponds to the estimated motor frequency (on
the motor shaft). In Standard Motor control type 03 (page 67), Output frequency 802 is equal to motor
stator frequency.
In Motor control type 309 selection of high performance motor control type 00 (page 67), Output
frequency 802 is equal to the frequency corresponding to estimated motor speed.
Range: -400 to 400 Hz
A
803 M Motor current
Estimation of the effective motor current (output of the drive) from phase current measurements with an
accuracy of 5%.
During DC injection, the current displayed is the maximum value of current injected in the motor.
%
804 M PID error
Visible only if the PID function is configured [PID feedback assignment 59.00 (page 86) set to
01]. See PID diagram on page 85.
%
805 M PID feedback
Visible only if the PID function is configured [PID feedback assignment 59.00 (page 86) set to
01]. See PID diagram on page 85.
%
806 M PID reference
Visible only if the PID function is configured [PID feedback assignment 59.00 (page 86) set to
01]. See PID diagram on page 85.
V
807 M Main voltage
Line voltage from the point of view of the DC bus, motor running or stopped.
%
808 M Motor thermal state
Display of the motor thermal state. Above 118%, drive displays (page 114) Motor overload F013 fault.
%
809 M Drive thermal state
Display of the drive thermal state. Above 118%, drive displays (page 114) Drive overheat F011 fault.
%
810 M Output power
The parameter displays the ratio between "estimated motor power (on the shaft) versus drive
rating."
EAV94277 07/2023 47
Monitoring mode MOn
Code Name/Description
48 EAV94277 07/2023
Monitoring mode MOn
State 0
LI1 LI2 LI3 LI4
Example above: LI1 and LI3 are at 1; LI2 and LI4 are at 0.
-
902 M State of the logic output LO1 and relay R1
Can be used to visualize the state of the logic output.
State 1
State 0
r1 LO1
Hz
903 M Display of high speed value
Displays frequency corresponding to the high speed value. Range from Low speed 512.0 (page 101) to
Maximum frequency 308 (page 67) is not set to 06.. Visible only if 2 High speed assignment 512.3
or 4 High speed assignment 512.4 (page 102) is configured.
-
904 M Drive Power rating
Indicates the drive power rating. This is part the of the drive reference. Refer to page 12. Possible values:
037 = 0.37 kW
075 = 0.75 kW
U15 = 1.5 kW
U22 = 2.2 kW
U30 = 3 kW
U40 = 4 kW
U55 = 5.5kW
U75 = 7.5kW
D11 = 11kW
D15 = 15 kW
D18 = 18.5 kW
D22 = 22 kW
-
905 M Drive voltage rating
Indicates the Drive rate voltage. This is part of the drive reference, see page 12. Possible values:
N4= 360 V~460 V 3-phase in, 360 V~460 V 3-phase out
-
906 M Specific Product Number
This parameter is used to identify the specific version of the product.
When the product is in standard version, this parameter value will be 0 and invisible. When the product is
in specific or customized version, the value will be non-zero and visible in the menu.
-
907 M Card 1 Software Version
Application software version
Example: 1105 for 1.1 ie 05
1 (version, major), 1 (version, minor), 05 (ie, evolution number)
EAV94277 07/2023 49
Monitoring mode MOn
Total time the motor has been powered up. Range: 0 to 65535 hours. Value displayed is as described in the
table below. Parameter resettable by services.
Hours Display
1 0.01
10 0.10
100 1.00
1000 10.0
10000 100
Total time the drive has been powered on. Range: 0 to 65535 hours. Value displayed is as described in
the table above. Parameter resettable by services.
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
Range: 0 to 65535 hours. Value displayed is as described in the table above. Parameter resettable by
customer.
50 EAV94277 07/2023
Monitoring mode MOn
This parameter describes the drive state at the moment of the first detected fault.
bit 0 bit 1 bit 2 bit 3 bit 4
ETA.1: Switched ETA.5: ETA.6: Forced local ETA.15 :
on Fast stop Switch on enabled Motor rotation in forward direction
disabled (or stopped)
This parameter describes the drive state at the moment of the second detected fault. See 915.
This parameter describes the drive state at the moment of the third detected fault. See 915.
This parameter describes the drive state at the moment of the fourth detected fault. See 915.
EAV94277 07/2023 51
Monitoring mode MOn
Range: 2 - 9999
52 EAV94277 07/2023
Configuration mode, ConF
1. Store/recall parameter set: these 2 functions are used to store and recall customer settings.
2. FULL: This menu permits to access to all other parameters. It includes 6 sub-menus:
- Macro-configuration 100- (page 55)
- Input Output menu 200- (page 56)
- Motor Control menu 300- (page 66)
- Control menu 400- (page 73)
- Function menu 500- (page 75)
- Fault detection management menu 600- (page 103)
- Communication menu 700- (page 110)
Organization tree
ENT
ESC
100
200++-
ENT 300-
ConF
ENT 400-
101
ENT
nO 500-
ESC
1. ENT
102 nO 600-
ESC
ENT
2. ESC
700-
EAV94277 07/2023 53
Configuration Mode
2s
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that restoring the factory settings is compatible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
2s To change the assignment of this parameter, press ENT key for 2 s.
LI assignment information
It is possible with ATV310 to use multi assignment function (ie: 501.4 and 503 on the same LI).
It is also possible on some functions to assign LIH (high) or LIL (low), which means that the assigned function will be activated to high (LIH)
or low level (LIL) of LI.
54 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
100 M Macro-configuration 00
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that the selected macro configuration is compatible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Macro configuration provides a shortcut to configure a set of parameters suited to a specific field of
application.
3 macro configurations are available:
00 v Start/stop. Only forward is assigned.
04 v PID regulation. Activate PID function, dedicate AI1 for feedback and AIV1 for reference.
09 v Speed. Allocate LI to a preset speed which provides a means of configuring speed functions for a
specific field of application.
2s To change the assignment of this parameter, press the ENT key for 2 s.
EAV94277 07/2023 55
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment Factory
500- range setting
WARNING
UNANTICIPATED EQUIPMENT OPERATION
If this parameter is changed, the parameters 2-wire type control 202 (page 60) and the assignments of the
digital inputs are reset to the factory setting.
Verify that this change is compatible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury or equipment damage.
2s To change the assignment of this parameter, press the ENT key for 2 s.
56 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
2 wire type control diagrams (see page 60)
400-
Level detection diagram with no priority
500-
600-
700-
EAV94277 07/2023 57
Configuration Mode - Complete menu (FULL)
58 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
3-wire control diagrams (see page 60)
400-
F: motor frequency 500-
Reference
600-
700-
LI Run Enable
LI Forward
t
LI Reverse
EAV94277 07/2023 59
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment Factory
500- range setting
WARNING
UNANTICIPATED EQUIPMENT OPERATION
Verify that the parameter setting is compatible with the type of wiring used.
Failure to follow these instructions can result in death, serious injury or equipment damage.
2-wire type control parameter can only be accessed if Type of control 201 (page 56) is set to 2C.
00 v Positive: the inputs are active (state 1) at a voltage equal to or higher than 11 V (for example +24 V
terminal). They are inactive (state 0) when the drive is disconnected or at a voltage lower than 5 V.
01 v Negative using internal supply: the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V or when the drive
is disconnected.
02 v Negative using external supply: the inputs are active (state 1) at a voltage lower than 10 V (for example
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V.
NOTE: The modification will be taken into account only at the next control power-on.
60 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
200- I/O MENU (continued)
600-
204-
AI1 CONFIGURATION MENU 700-
This function establishes an interface between the analog input signal and drive internal value.
5U v Voltage: 0-5 Vdc
10U v Voltage: 0-10 Vdc
0A v Current: x-y mA. Range determined by the AI1 current scaling parameter of 0% 204.1 and AI1 current
scaling parameter of 100% 204.2 settings below. See page 61.
LIU v Logic input. AI1 must be wired the same way as a logic input LIx in source mode.
00 v Not assigned
01 v No fault
02 v Drive run
04 v Frequency threshold reached
05 v Motor frequency when max. reference value reached 512.2
06 v I threshold reached
07 v Frequency reference reached
08 v Motor thermal threshold reached
21 v Process underload fault
22 v Process overload fault
123 v 4-20 mA signal loss visible only if 204.0 is set to 0A (see above).
NOTE: Relay R1 can be assigned to upstream protection to avoid overvoltage in the drive:
• Connect fault relay R1 to the contactor, see schematic page 24.
• Use Relay R1 (R1 assignment 205 ) with protection.
NOTE: When R1 is assigned to Process overload or Process underload fault, the relay will active and last
time duration setting by 209 or 212.
EAV94277 07/2023 61
Configuration Mode - Complete menu (FULL)
200-
300-
Code Name/Description Adjustment Factory
400- range setting
500-
200- I/O MENU (continued)
600-
700- 206-
LO1 CONFIGURATION MENU
206.0 M LO1 assignment 00
This parameter is used for a remote indication of the drive status.
00 v Not assigned
01 v No fault
02 v Drive run
04 v Frequency threshold reached
05 v Motor frequency when max. reference value reached 512.2
06 v I threshold reached
07 v Frequency reference reached
08 v Motor thermal threshold reached
21 v Process underload fault
22 v Process overload fault
123 v 4-20 mA signal loss visible only if 204.0 is set to 0 A (see above).
126 v Auxiliary pump
NOTE: When LO1 is assigned to Process overload or Process underload fault, the logic output will
active and last the time duration setting by 209 or 212.
206.1 M LO1 status (output active level) 00
00 v Positive logic: active high
01 v Negative logic: active low
WARNING
LOSS OF CONTROL
Depending on the assignments and settings of the logic outputs, signal output functions may not be effective if the
wiring is incorrect or inoperative.
• Do not set this parameter to 01 unless you can ensure that the signal will be available under all circumstances.
• Verify correct settings for all parameters used to set signal output functions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
(hysteresis)
208
208 -10%
t
70% - 150% of
208 M Process overload threshold 305 parameter
90% of 305
value 70% - 150%
parameter value
62 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
Code Name/Description Adjustment range Factory setting
400-
200- I/O MENU (continued) 500-
If 602.0=01, the drive will automatically restart after this time delay following the overload fault F012.
700-
Minimum time permitted between an overload being detected and any automatic restart.
In order for an automatic restart to be possible, the maximum restart time 602.1 (page 103) must exceed
that of this parameter by at least one minute.
Visible only if the "Overload time delay 207" above is not set to 0.
Underload detection is only active when the system is in steady state (Actual speed reference reached).
A value of 0 will disable application underload detection.
20% to 100% of 305
211 M Process underload threshold parameter
60%
Visible only if Process underload time delay 210 is not set to 0. This parameter is used to detect an
application underload condition on the motor. Process underload threshold 211 can be adjusted between
20 and 100% of the rated drive current.
Visible only if the "Process underload time delay 210" above is not set to 0.
0 to 400 Hz 50 or 60 Hz,
213 M Motor frequency threshold Determined by
drive rating
Visible only if R1 assignment 205 (page 61) or LO1 assignment 206.0 (page 62) is set to 04.
Visible only if R1 assignment 205 (page 61) or LO1 assignment 206.0 (page 62) is set to 06.
0 to 118% of 808
215 M Motor thermal state threshold parameter
100%
EAV94277 07/2023 63
Configuration Mode - Complete menu (FULL)
200-
300-
700- 216-
AO1 configuration menu
216.0 M AO1 assignment 00
This parameter provides type selection for the drive analog output signal.
10U v Voltage: 0-10 Vdc
0A v Current: 0-20 mA
4A v Current: 4-20 mA
64 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
500-
217 M Reference Template bsd 600-
700-
This parameter defines how the speed reference is taken into account for analog inputs only.
In the case of the PID controller, BNS and BNS0 are not applied. The limits are set by the Low Speed
512.0 and High Speed 512.2 parameters.
BSD v Standard
Frequency At zero reference the frequency = 512.0
512.2
512.0
-100%
reference
0% +100%
512.0
512.2
BNS v Deadband
Frequency At reference = 0 to 512.0 the frequency = 0
512.2
-100% 512.0
reference
0
512.0 +100%
512.2
BLS v Pedestral
Frequency At zero reference to 512.0, the frequency = 512.0
512.2
-100% 512.0
reference
512.0 +100%
512.2
BNS0 v Deadband at 0%
Frequency This operation is the same as BSD Standard,
except that in the following cases at zero
512.2 reference, the frequency = 0: the signal is less
than the minimum value, which is greater than 0
(example: 2 mA on a 4–20 mA input). The signal
512.0 is greater than minimum value, which is greater
-100% 0% than the maximum value (example: 21 mA on a
reference
+100% 20–4 mA input)
512.0
512.2
EAV94277 07/2023 65
Configuration Mode - Complete menu (FULL)
200-
300-
400-
WARNING
LOSS OF CONTROL
500-
• Fully read and understand the manual of the connected motor.
600- • Verify that all motor parameters are correctly set by referring to the nameplate and the manual of the connected motor.
• If you modify the value of one or more motor parameters after having performed auto-tuning, the value of Auto-tuning is reset to 00
700-
and you must re-perform auto-tuning.
Failure to follow these instructions can result in death, serious injury or equipment damage.
This parameter modifies the presets of the following parameters: Rated motor voltage 304 below, High
speed 512.2 (page 102), Motor frequency threshold 213 (page 63) and Rated motor frequency 306 .
00 v 50 Hz
01 60 Hz
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
Drive power -5 to Determined by drive rating
302 M Rated motor power drive power +2 and dual rating
according to dual
rating
Rated motor power given on the nameplate, in kW if Standard motor frequency 301 is set to 50 Hz,
in HP if Standard motor frequency 301 is set to 60 Hz.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
Determined by drive rating
303 M Rated motor cos phi 0.5 to 1
and dual rating
This parameter is visible only if Motor parameter choice 319 (page 70) is set to [00].
If Rated motor cos phi 303 is available, Rated Motor Power 302 disappears.
Power factor (pf) is given on the motor rating plate.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
NOTE: Do not confuse this with motor "Service Factor". Setting 303 to 1 or very near to 1 may
result in unsatisfactory motor operation. If the motor power factor is not indicated on the nameplate,
leave this parameter at the factory default (approximately 0.80).
Nominal motor voltage is given on the nameplate. If the line voltage is less than the nominal motor voltage,
Rated motor voltage 304 should be set to the value of the line voltage applied to the drive terminals.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
66 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
300- Motor control menu (continued)
600-
0.25 In to 1.5 In (1) Determined by drive rating
305 M Rated motor current and dual rating
700-
Nominal motor current is given on the nameplate. Motor thermal current 604.0 (page 106) varies
according to the nominal motor current 305.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
Maximum frequency 308 gives the upper value possible for High speed 512.2 (page 102). The factory
setting is 60 Hz, or preset to 72 Hz [if Standard motor frequency 301 (page 66) is set to 60 Hz].
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
Permits selection of motor control types suitable for application and performance requirements.
00 v Performance: Sensorless vector control with internal speed loop based on a voltage feedback calculation.
For applications requiring high performance during starting or operation.
03 v Standard: 2 point V/F control without internal speed loop.
For simple applications that do not require high performance. Simple motor control law maintaining a
constant Voltage Frequency ratio, permits adjustment of curve start point.
This law is generally used for motors connected in parallel. Some applications using motors in parallel or
with high performance requirements may require use of the "high performance" (00) control type.
06 v Pump: U2/F; for dedicated use with variable torque fan and pump applications not requiring high starting
torque.
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed again.
EAV94277 07/2023 67
Configuration Mode - Complete menu (FULL)
200-
300-
600-
300- Motor control menu (continued)
Low 312 parameter value Correct 312 parameter value High 312 parameter value
In this case, increase 312In this case, reduce 312
Visible only ifMotor control type 309 (page 67) is set to 00.
Low 313 parameter value Correct 313 parameter value High 313 parameter value
In this case, increase 313In this case, reduce 313
Visible only if Motor control type 309 (page 67) is set to 00.
68 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
300- Motor control menu (continued) 600-
This function defines the magnetizing current at zero frequency as a % of the rated magnetizing current.
Adjustment curve for PUMP law
100%
314
Parameter
value
Frequency
Visible only if Motor control type 309 (page 67) is set to 06.
Noise refers to audible noise. Means of adjusting motor noise must be provided to satisfy environmental
requirements.
Random frequency modulation avoids possible noise resonance that can occur at fixed frequency.
00 v No
01 v Yes
EAV94277 07/2023 69
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600-
300- Motor control menu (continued)
700- 318 M Auto-tuning 00
WARNING
UNEXPECTED MOVEMENT
Autotuning moves the motor in order to tune the control loops.
• Only start the system if there are no persons or obstructions in the zone of operation.
Failure to follow these instructions can result in death, serious injury or equipment damage.
During autotuning, noise development and oscillations of the system are normal.
WARNING
LOSS OF CONTROL
If you modify the value of one or more motor parameters after having performed auto-tuning, the value of Auto-
tuning is reset to 00 and you must re-perform auto-tuning.
Failure to follow these instructions can result in death, serious injury or equipment damage.
Attention:
• Auto-tuning must be performed with the motor connected and cold.
• The parameters Rated motor power 302 (page 66) and Rated motor current 305 (page 67) must
be consistent.
• Auto-tuning is performed only if no stop command has been activated. If a freewheel stop or fast stop
function has been assigned to a logic input, this input must be set to 1 (active at 0).
• Auto-tuning takes priority over any run or prefluxing commands, which will take effect after the auto-
tuning sequence.
• Auto-tuning may last for 1 to 10 seconds. Do not interrupt. Wait for the display to change to 02 or
00.
• Re-perform auto-tuning after motor cables are replaced to ensure effectiveness of motor control.
This parameter allows to choose which motor parameter will be configured (power or power factor).
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed
again.
70 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
320 M Vector control 2 points 00
600-
00 v [00] No
01 v [01] Yes 700-
For use in the following application contexts: when the rated speed and rated frequency of the motor must
be exceeded for optimization of operation performance at constant power, or when the maximum voltage
of the motor must be limited to a certain value below the main voltage.
The U/F diagram must therefore be modified according to the motor's work ability at maximum voltage
and Top frequency.
Motor voltage
Maximum Voltage 321
Motor Rated Voltage 304
Frequency
Standard Motor Frequency 301 Maximum Frequency 322
314 parameter
321 M Max voltage of constant power value ~ 460 V
380 V
306 parameter
322 M Max frequency of constant power value ~ 400Hz
50Hz
This parameter is used to select the default value of rated drive current and motor nameplate.
This parameter cannot be modified on drive with power equal to or lower than 2.2 kW.
A modification of its setting resets several parameters of the drive:
- motor nameplate parameters (302, 303, 304, 305, 306, 307)
- status of tune results
- current parameters: In (drive rating current), motor thermal current (604.0), current limitation (511.1
and 511.2), motor current threshold (214) and current injections (502.5, 502.7, 504.1).
00 v Normal duty: Normal rating, dedicated mode for applications requiring slight overload (up to 1. In for
60 s).
01 v Heavy duty: High rating, dedicated mode for applications requiring significant overload
(up to 1.5In for 60s).
NOTE:
1. This parameter must be set before performing an autotuning.
2. Modifying this parameter resets the motor tune parameters. Auto-tuning will need to be performed
again.
NOTE: Both modes use the same hardware, the overload in normal duty is lower than the one in normal
duty, consequently, the rated drive current (In) in normal duty mode is adapted to be slightly higher than
the one in heavy duty mode. The default motor nameplate and other current limitation are adapted
accordingly.
EAV94277 07/2023 71
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Control menu
500- Control channel diagram
600-
Forced local assignment
700- Stop key priority
407 Command channel 1 408
405
nO
Terminals nO
Local Forced local reference
409 LI
Remote display
Modbus
Not assigned
Analog input terminal
Channel 406
configuration Remote display
Integrated display with Jog dial
Combined mode
Separate mode
Low speed
72 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
400- Control menu 600-
01 v Anolog terminal
163 v Remote display
164 v Modbus
183 v Integrated display with Jog dial
-400 Hz to 400 Hz
402 M External reference value -
0% to 100% of
403 M Integrated display jog dial reference 512.2 parameter
value
Embedded display terminal active or local force mode configured. Forced local reference 409 set to
183 and Forced local assignment 408 is not set to 00. Displays the Actual speed reference
coming from the jog dial. This value is not visible in the factory settings.
This parameter can enable or disable the stop button located on the drive and remote display.
2s Disabling the stop button is effective if the active command channel is not the drive display terminal or the
remote display.
WARNING
LOSS OF CONTROL
The function Stop key priority 405 parameter disables the Stop keys of the drive and of the Remote Display Terminal
if the setting of the parameter is 00.
Only set this parameter to 00 if you have implemented appropriate alternative stop functions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
01 v Combined mode
02 v Separate mode
2s To change the assignment of this parameter, press the ENT key for 2 s.
EAV94277 07/2023 73
Configuration Mode - Complete menu (FULL)
200-
300-
00 v Not assigned
L1H v L1H: LI1 active high
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: LIU active high
409 M Forced local reference 00
74 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
500- Function menu 600-
501-
Ramp menu 700-
0.0 s to 999.9 s
501.0 M Acceleration 3.0 s
Acceleration time between 0 Hz and the Rated motor frequency 306 (page 67).
Make sure this value is compatible with the inertia being driven.
0.0 s to 999.9 s
501.1 M Deceleration 3.0 s
Time to decelerate from the Rated motor frequency 306 (page 67) to 0 Hz.
Make sure this value is compatible with the inertia being driven.
00 v Linear
01 v S Shape
02 v U Shape
The rounding coefficient is fixed, wherein
t1 = 0.6 x set ramp time (linear)
S Shape t2 = 0.4 x set ramp time (round)
t3 = 1.4 x ramp time
00 v Not assigned
LIH v L1H: LI1 active high
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: LIU active high
L1L v L1L: LI1 active low
L2L v L2L: LI2 active low
L3L v L3H: LI3 active low
L4L v L4H: LI4 active low
LUL v LUL: LIU active low
See LI assignment information on page 54.
EAV94277 07/2023 75
Configuration Mode - Complete menu (FULL)
200-
300-
600-
500- Function menu (continued)
700- 501-
Ramp menu (continued)
501.4 M Acceleration 2 0.0 to 999.9 s 5.0 s
Visible only if Ramp switching commutation 501.3 (page 75) is not set to 00.
Second acceleration ramp time, adjustable from 0.0 to 999.9 s
This ramp becomes the active ramp only when PID is used to perform start and wake-up phases.
See PID: wake up level (page 89).
00 v Function inactive. The drive will decelerate based on normal deceleration time settings. This setting is
compatible with optional dynamic braking (if used).
01 v This function automatically increases deceleration time when stopping or reducing the speed of high inertia
loads to help prevent DC bus overvoltage or overbraking.
02 v Motor Braking: This mode allows the drive to attempt the most rapid stop possible without the use of a
dynamic brake resistor. It uses motor losses to dissipate energy generated by braking.
This function may be incompatible with positioning. This function should not be used when an optional
braking resistor and module are being used.
76 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
500- Function menu (continued)
600-
502-
Stop configuration menu 700-
This stop type is activated when the input or corresponding register bit changes to 0. If the input returns to
state 1 and the run command is still active, the motor will only restart if Type of control 201 (page 56) =
2C and 2-wire type control 202 (page 60) = 00 or 02. If not, a new run command must be sent.
00 v Not assigned
L1L v L1L: LI1 active Low to stop
L2L v L2L: LI2 active Low to stop
L3L v L3L: LI3 active Low to stop
L4L v L4L: LI4 active Low to stop
LUL v LUL: LIU active Low to stop
00 v Not assigned
L1L v L1L: LI1 active Low to stop
L2L v L2L: LI2 active Low to stop
L3L v L3L: LI3 active Low to stop
L4L v L4L: LI4 active Low to stop
LUL v LUL: LIU active Low to stop
502.3 M Fast stop Ramp divider 1 to 10 4
Visible only if Fast stop assignment 502.2 (page 77) is not set to 00 or 502.0 is set to 08 Fast stop
(page 77).
When stop requests are sent the active ramp time [Deceleration 501.1 (page 75) or Deceleration 2
501.5 (page 76)] is divided by this coefficient.
EAV94277 07/2023 77
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600-
500- Function menu (continued)
700- 502-
Stop configuration menu
502.4 M DC injection assignment 00
WARNING
UNINTENDED MOVEMENT
• Do not use DC injection to generate holding torque when the motor is at a standstill.
• Use a holding brake to keep the motor in the standstill position.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
DC injection is activated when the input switches to 0. If the input returns to state 1 and the run
command is still active, the motor will only restart if Type of control 201 (page 56) = 2C and 2-wire
type control 202 (page 60) = 00 or 02. If not, a new run command must be sent.
This parameter is forced to 00 if Type of stop 502.0 is set to 08 (page 77)
00 v Not assigned.
L1H v L1H: L1 active high
L2H v L2H: L2 active high
L3H v L3H: L3 active high
L4H v L4H: L4 active high
LUH v LUH: LIU active high (AI1 used as logic input: AI1 type 204.0 sets to LIU)
NOTICE
OVERHEATING
Verify that the connected motor is properly rated for the DC injection current to be applied in terms of amount
and time.
Failure to follow these instructions can result in equipment damage.
Level of DC injection braking current activated via digital input or selected as stop mode.
This parameter can be accessed if DC injection assignment 502.4 is set to a value different from 00
or if Type of stop 502.0 is set to DC injection stop 03.
NOTE: this setting is independent from the AUTO DC INJECTION MENU 504- function.
NOTICE
OVERHEATING
Verify that the connected motor is properly rated for the DC injection current to be applied in terms of amount
and time.
Failure to follow these instructions can result in equipment damage.
Maximum current injection time DC injection level 502.5 . After this time, the injection current
becomes DC injection level 2 502.7 .
This parameter can be accessed if DC injection assignment 502.4 is set to a value different from 00
or if Type of stop 502.0 is set to DC injection stop 03.
NOTE: this setting is independent from the AUTO DC INJECTION MENU 504- function.
78 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
500- Function menu (continued) 600-
502-
Stop configuration menu 700-
0.1*In to DC
502.7 M DC injection level 2 injection level 0.5*In (in A)
502.5 (1)
NOTICE
OVERHEATING
Verify that the connected motor is properly rated for the DC injection current to be applied in terms of amount
and time.
Failure to follow these instructions can result in equipment damage.
Injection current activated by digital input or selected as stop mode once period IDC injection time for
DCLI 502.6 has elapsed.
This parameter can be accessed if DC injection assignment 502.4 is set to a value different from 00
or if Type of stop 502.0 is set to DC injection stop 03.
NOTE: this setting is independent from the AUTO DC INJECTION MENU 504- function.
NOTICE
OVERHEATING
Verify that the connected motor is properly rated for the DC injection current to be applied in terms of amount
and time.
Failure to follow these instructions can result in equipment damage.
Maximum injection time for DC injection level 2 502.7, selected as stop mode only.
This parameter can be accessed if Type of stop 502.0 is set to DC injection stop 03.
NOTE: this setting is independent from the AUTO DC INJECTION MENU 504- function.
EAV94277 07/2023 79
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600-
500- Function menu (continued)
700- 504-
AUTO DC INJECTION MENU
504.0 M Automatic DC injection 01
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If the parameter 504.0 Automatic DC injection is set to 02, DC injection is always active, even if the motor
does not run.
Verify that using this setting does not result in unsafe conditions.
Failure to follow these instructions will result in death or serious injury.
WARNING
UNINTENDED MOVEMENT
• Do not use DC injection to generate holding torque when the motor is at a standstill.
• Use a holding brake to keep the motor in the standstill position.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
00 v No DC injected current
01 v Time limited DC injection
02 v Continuous DC injection
0 to 120% of Rated 70% of Rated
504.1 M Automatic DC injection current motor current motor current
305 305 (in A)
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Verify that the connected motor is properly rated for the DC injection current to be applied in terms of amount
and time in order to avoid overheating and damage to the motor.
Failure to follow this instruction can result in equipment damage.
Visible only if Automatic DC injection 504.0 is not set to 00.
Injection current on stopping and continuous DC injection.
80 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
500- Function menu (continued)
600-
505.0 M Jog assignment 00 700-
This parameter employs a 2 or 3-wire control related logic input, providing step by step control of motor
running. Acceleration and deceleration ramps taken into account in the Jog function are 0.1 s.
00 v Function inactive
L1H v L1H: L1 active high
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: LIU active high
Forward
Reverse
Motor
frequency
505.1
Acceleration
505.1 Acceleration command 0.5 s
L1H....L4H, LUH
3-wire control
Jog
Forward
Reverse
LI1 Run
Normal
Motor ramp
frequency
505.1
505.1 Jog
ramp
EAV94277 07/2023 81
Configuration Mode - Complete menu (FULL)
200-
300-
Code Name/Description Adjustment range Factory setting
400-
Variable saved
to RAM or ROM Variable saved
Variable not saved
to ROM
Variable not saved or saved to RAM
00
506.2 M Store
Up speed/down speed command will change the initial speed reference. Eventually it produces an overall
"speed increment". This speed increment accumulates over time depending on the actions of Lix and Liy.
It is therefore necessary to keep a record of speed incrementation when changing speed reference.
Visible only if parameter 506.0 and 506.1 are configured.
00 v Do not save. Variables not saved after the RUN command has disappeared.
01 v Save to RAM. Variables saved to RAM after STOP command ends and disappear when power off.
02 v Save to ROM. Variables saved to ROM when power off.
82 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
500-
0 - 100% 00
506.3 M Clear the function 600-
When the CLEAR command is activated, acceleration and deceleration commands are deactivated. All 700-
speed increments are reset when the CLEAR command is activated, regardless of the save method used.
Visible only if parameter 506.0 and 506.1 are configured.
Preset speeds
2, 4, or 8 speeds can be preset, requiring 1, 2 or 3 logic inputs respectively.
EAV94277 07/2023 83
Configuration Mode - Complete menu (FULL)
200-
300-
600-
500- Function menu (continued)
700- 507-
Preset speed menu
507.0 M 2 preset speeds 00
00 v Function inactive
L1H v L1H: L1 high activation level
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: active high
507.1 M 4 preset speeds 00
As 507.0
As 507.0
84 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
400-
PID reference PID error
Reference 500-
channel 1 806 804
401 600-
Activation internal
PID reference value 700-
59-
59.05 Preset PID PID reference
PID correction reverse
PID:
Modbus PID gain
assignment 59.16
value ramp wake up level
Remote display
59.13 59.06 59.01
+ No +
Integrated display 59.12 59.19 59.02 (1)
with Jog dial 59.14 59.07 Yes
+ 59.03 +
2, 3, 4 preset PID
Internal PID reference value PID min/max
reference value 59.08 value reference
59.09 PID feedback
59.10 59.00
scale factor
59.11
No
59.04 59.20 59.15
Analog terminal
805
Acceleration
High speed deceleration ramp
Speed
Automatic reference 512.2
(1)
Manual 801
512.0
Low speed
PID manual reference
59.18
No
Anolog terminal
Integrated display
with Jog dial
Preset
speed
EAV94277 07/2023 85
Configuration Mode - Complete menu (FULL)
200-
300-
Code Name/Description Adjustment range Factory setting
400-
500-
500- Function menu (continued)
600-
59-
PID menu
700-
59.00 M PID feedback assignment 00
00 v Not assigned.
01 v Analog terminal. Choice not possible if 401 is set to 01.
86 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
500- Function menu (continued) 600-
59-
PID menu (continued) 700-
Visible only if [PID feedback assignment 59.00 (page 86) is not set to 00.
00 v None
L1H v L1H
L2H v L2H
L3H v L3H
L4H v L4H
LUH v LUH
Before assigning 4 preset PID assignment 59.07, 2 preset PID assignment 59.06 (page 86) must be
assigned.
EAV94277 07/2023 87
Configuration Mode - Complete menu (FULL)
200-
300-
600-
500- Function menu (continued)
700- 59-
PID menu (continued)
501.4 M Acceleration 2 0.0 to 999.9 s 5.0 s
This parameter only can be activated when the system is starting.
Second acceleration ramp time, adjustable from 0.1 to 999.9 s.
The time required to accelerate from 0 to Rated motor frequency 306 (page 67). Make sure that this value
is compatible with the inertia being driven.
Visible only if PID feedback assignment 59.00 (page 86) and PID predictive speed 59.15
(page 87) are not set to 00.
This parameter will reverse the internal error value of PID system.
00 v No , no negative speed
01 v Yes, no negative speed
02 v No, allow negative speed
03 v Yes, allow negative speed
Visible only if PID feedback assignment 59.00 (page 86) is not set to 00.
This parameter can disable the PID and enable the standard manual reference.
00 v No
01 v Anolog terminal
02 v Integrated display with Jog dial
Visible only if PID feedback assignment 59.00 (page 86) and PID auto/manual assignment 59.17
(page 88) are not set to 00.
88 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
500-
500- Function menu (continued)
600-
59-
PID menu (continued) 700-
Visible only if PID feedback assignment 59.00 (page 86) is not set to 00.
If PID functions and Low speed operating time512.1 are set at the same time, the PID regulator may try
to set a speed lower than Low speed 512.0. This will result in unwanted operations consisting of starting,
running at Low speed 512.0, stopping and so on. Parameter PID: wake up level 59.19 can be used
to set a minimum PID error threshold to restart after a prolonged stop below Low speed 512.0.
Visible only if PID feedback assignment 59.00 (page 86) and Low speed operating time 512.1
(page 101) are not set to 00.
Visible only if PID feedback assignment 59.00 (page 86) and Low speed operating time 512.1
(page 101) is not set to 00.
EAV94277 07/2023 89
Configuration Mode - Complete menu (FULL)
200-
300-
0 - 100% (*0)
0 - 600s
59.23 M PID supervision function time delay 0s
0 - 600s (*0)
510-
PUMP SUB-MENU
207 M Process overload time delay 0-100 s 5s
The overload detection threshold is expressed as a percentage of [Nominal motor current] (nCr). To
activate the function, this value must be smaller than the limit current.
If [Overload fault management] (604.2) = [alarm ignore], then this parameter will be unaccessable.
Minimum time allowed between overload detection and any automatic restart.
To perform an automatic restart, the value of the [Automatic restart] (602.1) must exceed this parameter
by at least one minute.
Value of zero will inactivate the function and make other parameters unaccessable.
20%-100% 60%
211 M Process Underload threshold
The underload threshold at zero frequency is expressed as a percentage of rated motor torque.
90 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
212 M Process underload fault duration 0-6 min. -
600-
Minimum time allowed between underload detection and any automatic restart. 700-
To perform an automatic restart, the value of the [Automatic restart] (602.1) must exceed this parameter
by at least one minute.
This time avoids the effects of transient pressure fluctuations and so avoids vibrations generated during
pump starting and stopping.
0-308 parameter
510.4 M Auxiliary pump stop frequency value
0Hz
The auxiliary pump will stop below this frequency after the auxiliary pump stop delay (value of 510.5).
This time avoids the effects of transient pressure fluctuations and so avoids vibrations generated during
pump starting and stopping.
Below this threshold function activated if 510.7 value >0 and the auxiliary pump is stopped.
0-400Hz 0Hz
510.9 M Zero flow detection offset
EAV94277 07/2023 91
Configuration Mode - Complete menu (FULL)
Variable pump
ATV310
Pressure sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
Enter the values given on the motor rating plate in the Motor control menu 300-
First level adjustment parameters
501.0 Acceleration: 0.7 s
501.1 Deceleration: 0.7 s
512.0 Low speed: 30 Hz
512.2 High speed: 60 Hz
Analog input menu AIt
204.0 Scale of analog input AI1: 0-20 mA
Motor control menu drC
311 Nominal motor slip: 0 Hz
313 Frequency loop gain: 70%
310 IR compensation: 0%
Application functions menu FUn
202 2-wire type control: LEL
PI sub-menu
59.00 Assignment of the PI function feedback: AI1
59.01 PI regulator proportional gain: 5.00
59.02 PI regulator integral gain: 8.00
59.11 Internal PI regulator reference: 39%
59.19 Restart error threshold: 40%
59.25 Supervision of the PI regulator function: LFF
59.22 PI feedback supervision threshold: 17%
59.23 PI feedback supervision function time delay: 1 s
59.26 Fallback speed: 50 Hz
Pump sub-menu PMP
510.7 Zero flow detection: 1 min
510.8 Zero flow detection activation threshold: 50 Hz
510.9 Zero flow detection offset: 5 Hz
512.1 Sleep threshold operating time: 3 s
59.15 Quick start threshold: 25 Hz
59.21 Sleep threshold offset: 10 Hz
Automatic DC injection sub-menu AdC
504.0 Automatic DC injection assignment: nO
Automatic restart function Atr
602.0 Automatic restart: YES
Fault menu 600-
208 Process Overload threshold: 11%
209 Process overload fault duration: 1
59.24 Frequency hysteresis reached: 2 Hz
92 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
Single variable with auxiliary pump mode - 1 variable speed pump (variable pump) and one fixed speed
pump (auxiliary pump)
Pressure
sensor
0-20 mA
4-20 mA
0+5 V
0+10 V
The auxiliary pump is controlled by the ATV310 via logic output LO.
Enter the values given on the motor rating plate in the Motor control menu 300-
First level adjustment parameters
501.0 Acceleration: 0.1 s
501.1 Deceleration: 0.1 s
512.0 Low speed: 35 Hz
Analog input menu 204-
204.0 Scale of analog input AI1: 0-20 mA
Motor control menu 300-
311 Nominal motor slip: 0 Hz
313 Frequency loop gain: 70%
310 IR compensation: 0%
Application functions menu FUn
202 2-wire type control: 00
PI sub-menu
59.00 Assignment of the PI function feedback: 01
59.01 PI regulator proportional gain: 5.00
59.02 PI regulator integral gain: 8.00
59.11 Internal PI regulator reference: 51%
59.19 Restart error threshold: 42%
Pump sub-menu PMP
510.0 Selecting the operating mode: 01 (Yes)
510.1 Starting frequency of the auxiliary pump: 49 Hz
510.2 Time delay before starting the auxiliary pump: 1 s
510.3 Ramp for reaching the nominal speed of the auxiliary pump: 1 s
510.4 Stopping frequency of the auxiliary pump: 39.6 Hz
510.5 Time delay before the auxiliary pump stop command: 1 s
510.6 Ramp for stopping the auxiliary pump: 1 s
510.7 Zero flow detection: 1 min
510.8 Zero flow detection activation threshold: 42 Hz
510.9 Zero flow detection offset: 2 Hz
512.1 Sleep threshold operating time: 5 s
59.21 Sleep threshold offset: 3 Hz
206.1 Assignment as logic/analog output PMP
Automatic DC injection sub-menu 504-
504.0 Automatic DC injection assignment: 00
Automatic restart function 602-
602.0 Automatic restart: 01 (active)
Fault menu 600-
210 Process underload function time delay 5 s
211 Process underload threshold: 59%
212 Time delay before automatic restart for the underload fault: 1
EAV94277 07/2023 93
Configuration Mode - Complete menu (FULL)
Connection diagram
3-phase supply
380 V...460 V
(1)
S/L2
T/L3
R/LI
R1C
R1A
ATV310
+24 V
W/T3
U/T1
COM
V/T2
+5 V
LO+
LO-
AI1
LI1
LI2
LI3
LI4
KM1
KM1
Auxiliary pump
Pressure
M1 sensor M2
3 3
0-20 mA
Variable 4-20 mA
pump 0+5 V 3-phase supply
380 V...460 V
(1) Fault relay contacts, for remote indication of the drive status.
NOTE: Fit interference suppressors to all inductive circuits near the drive or connected to the same circuit (relays, contactors, solenoid
valves, etc.).
94 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
PI feedback
LPI*(1+3%)
LPI
LPI*(1-2%)
Motor speed Fallback mode
defined by 59.25
HSP
HSP - AP0
MPI = LFF
LFF
MPI = YES
< tPI tPI
End-of-time delay
Once the variable pump is running at maximum speed (higher than 512.2 – 59.24) and at the same time the PI feedback is lower than
the supervision threshold 59.22*(1-2%), a time delay tPI is launched. If at the end of this time delay the value of the PI feedback is still
lower than the supervision threshold 59.22*(1+3%), the drive switches to fallback mode as defined by parameter 59.25.
- 59.25 = 01:
The drive will perform a freewheel stop.
- 59.25 = 04:
The drive will run at a fixed frequency 59.26 and will display fault code --12.
In both cases the drive reverts to PI regulation mode as soon as the PI feedback is higher than the supervision threshold 59.22*(1+3%).
In single variable with auxiliary pump mode (510.0 = 01), the PI feedback supervision function is only active when both pumps are
operating.
EAV94277 07/2023 95
Configuration Mode - Complete menu (FULL)
Frequency of the
variable pump Auxiliary pump starting
512.2
Starting frequency
510.1 Frequency
Auxiliary pump corresponding to the
stopping auxiliary pump flow
rate
Stopping frequency
510.4
Flow rate of the installation
When the frequency exceeds the starting threshold (510.1), a time delay (510.2) is launched to avoid the effects of transient flow
fluctuations. If after this time delay, the frequency remains higher than the starting threshold, the auxiliary pump is started. When the start
command is sent, the variable pump will go from its current speed reference to the auxiliary pump stopping frequency (510.4) following
a ramp (510.3) that equals the time taken for the auxiliary pump to reach its nominal speed. Parameter rOn is used to minimize the
booster effect on starting the auxiliary pump.
Frequency of the
variable pump
2 1 2 .2
512.2
Auxiliary pump starting
510.1
5 1 0 .1
510.4
5 1 0 .4
512.0
5 1 2 .0
0 t
510.2
5 1 0 .2 510.3
5 1 0 .3
96 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
When the frequency is lower than the stopping threshold (510.4), a time delay is launched (510.5) to avoid the effects of transient flow
fluctuations. If after this time delay, the frequency remains lower than the stopping threshold, the auxiliary pump is stopped. When the stop
command is sent, the variable pump will go from its current speed reference to the auxiliary pump starting frequency (510.1) following a
ramp (510.6) that equals the auxiliary pump stopping time. Parameter 510.6 is used to minimize the booster effect on stopping the
auxiliary pump.
Frequency of the
variable pump
1 2 .2
5512.2
1 0 .1
5510.1
Auxiliary pump
stopping
510.4
5 1 0 .4
512.0
5 1 2 .0
t
510.6
5510.5
1 0 .2 5 1 0 .6
EAV94277 07/2023 97
Configuration Mode - Complete menu (FULL)
PI feedback
5 9 .2 0
59.20
t
Motor frequency
512.0+59.21
512 .0 + 5 9 .2 1
512.0
512 .0
512.1
512 .1 t
Frequency of the
variable pump
512.2
5 1 2 .2
59.15
5 9 .1 5
t
0 1 .0
5510.4
98 EAV94277 07/2023
Configuration Mode - Complete menu (FULL)
PI feedback
PI error
Frequency reference
5510.8
1 0 .8
5 512.0
1 2 .0 ++510.9
5 1 0 .9
5512.0
1 2 .0
t
5510.7
1 0 .7 510.7
5 1 0 .7
• If the request is no longer present (zero flow), the PI error will not increase.
PI feedback
Frequency reference
5512.2
1 2 .2
5510.8
1 0 .8
Sleep threshold 512.0 + 59.21
2 .0 + +5510.9
5 1512.0 1 0 .9
5 1512
2 .0
t
5510.7
1 0 .7 5512.1
1 2 .1
• Set the sleep function so that the drive switches to sleep mode when zero flow is detected (510.9 y 59.21).
EAV94277 07/2023 99
Configuration Mode - Complete menu (FULL)
200-
300-
400-
Code Name/Description Adjustment Factory setting
500- range
600-
500- Function menu (continued)
700-
511-
CURRENT LIMITATION MENU
511.0 M 2nd current limitation commutation 00
Assignment
00 v Function inactive
L1H v L1H: LI1 active high
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: LIU active high
L1L v L1L: LI1 active low
L2L v L2L: LI2 active low
L3L v L3L: LI3 active low
L4L v L4L: LI4 active low
LUL v LUL: LIU active low
If the assigned input is at 0, the first current limitation is active.
If the assigned input is at 1, the second current limitation is active.
See LI assignment information (page 54).
Determined by
511.1 M Current limitation 0.25 to 1.5 In (1) drive rating
and dual rating
First current limitation.
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Depending on the settings of this parameter, the error response to detected errors is disabled or the transition
to the operating state Fault is suppressed if an error is detected.
• Verify that the settings of this parameter do not result in equipment damage.
• Implement alternative monitoring functions for disabled monitoring functions.
Failure to follow these instructions can result in equipment damage.
Determined by
511.2 M Current limitation 2 0.25 to 1.5 In (1) drive rating
and dual rating
Second current limitation.
This function allows reduction of the drive current limit.
Visible only if 2nd current limitation commutation 511.0 (page 100) is not set to 00.
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
Depending on the settings of this parameter, the error response to detected errors is disabled or the transition
to the operating state Fault is suppressed if an error is detected.
• Verify that the settings of this parameter do not result in equipment damage.
• Implement alternative monitoring functions for disabled monitoring functions.
Failure to follow these instructions can result in equipment damage.
300-
500-
500- Function menu (continued) 600-
512-
Speed limit menu 700-
0 Hz to 512.2 0 Hz
512.0 M Low speed parameter value
Motor frequency at minimum reference.
0.1 to 999.9 s 00
512.1 M Low speed operating time
Following operation at Low speed 512.0 for a defined period, a motor stop is requested automatically.
The motor restarts if the reference value is greater than Low speed 512.0 and if a run command is still
present.
NOTE: 00 corresponds to an unlimited period.
300-
High speed configuration
400-
The logic inputs enable selection of the desired high speed.
500-
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600- FAULT DETECTION MANAGEMENT MENU 600-
602-
Automatic restart menu
602.0 M Automatic restart 00
This function can be used to automatically perform individual or multiple Fault Resets. If the cause of the error
that has triggered the transition to the operating state Fault disappears within while this function is active, the
drive resumes normal operation. While the Fault Reset attempts are performed automatically, the output
signal "Operating state Fault" is not available. If the attempts to perform the Fault Reset are not successful,
the drive remains in the operating state Fault and the output signal "Operating state Fault" becomes active.
WARNING
UNANTICIPATED EQUIPMENT OPERATION
• Verify that activating this function does not result in unsafe conditions.
• Verify that the fact that the output signal "Operating state Fault" is not available while this function is active
does not result in unsafe conditions.
Failure to follow these instructions can result in death, serious injury or equipment damage.
00 v Function inactive.
01 v Automatic restart after locking on a detected fault, if the cause has disappeared and the other
operating conditions permit the restart.
The restart is performed by a series of automatic attempts separated by increasingly longer waiting
periods: 1 s, 5 s, 10 s, then 1 minute for subsequent attempts. The drive status relay remains
activated if this function is active. The speed reference and the operating direction must be
maintained.
Use 2 wire type control (Type of control 201 (page 56) = 00 and 2-wire type control 202 (page
60) = 00). If the restart has not taken place once the Max. automatic restart 602.1 has elapsed,
the procedure is aborted and the drive remains locked until it is turned off and then on again.
The detected faults which permit use of this function are listed on page 116.
5 min.
602.1 M Max. automatic restart
00 v 5 min.
01 v 10 min.
02 v 30 min.
03 v 1 hr
04 v 2 hr
05 v 3 hr
06 v Infinite
Visible only if Automatic restart 602.0 is not set to 00. This parameter can be used to limit the
number of consecutive restarts on a recurrent fault.
300-
700-
603 M Catch on the fly 00
This function is used to enable a smooth restart if the run command is maintained after the following events:
• Loss of line supply or disconnection
• Reset of current fault or automatic restart
• Freewheel stop
The speed given by the drive resumes from the estimated speed of the motor at the time of the restart, then
follows the ramp to the reference speed.
This function requires 2-wire level control.
00 v Function inactive
01 v Function active
300-
Motor thermal protection
400-
Function:
500-
Thermal protection by calculating the I2t.
600-
• Naturally-cooled motors: 700-
The tripping curves depend on the motor frequency.
• Force-cooled motors:
Only the 50 Hz tripping curve need be considered, regardless of the motor frequency.
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600-
600- FAULT DETECTION MANAGEMENT MENU (continued)
700- 604-
Motor Thermal Protection menu
0.2 to 1.5 In (1) Determined by drive
604.0 M Motor thermal current rating
Current used for motor thermal detection. Set ItH to the nominal current on the motor rating plate.
01 v Self-ventilated
02 v Motor-ventilated
604.2 M Overload fault management 01
NOTICE
OVERHEATING AND DAMAGE TO THE MOTOR
If this parameter is set to 00, the error response to detected errors is disabled and the transition to the
operating state Fault is suppressed.
• Verify that the settings of this parameter do not result in equipment damage.
• Implement alternative monitoring functions for disabled monitoring functions.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
If output phase monitoring is disabled, phase loss and, by implication, accidental disconnection of cables, are
not detected.
Verify that the setting of this parameter does not result in unsafe conditions.
Failure to follow these instructions will result in death or serious injury.
00 v Function inactive
01 v Tripping on F014 (1 phase loss) or F015 (3 phase loss) fault with freewheel stop.
01
606 M Input Phase loss
This parameter is only accessible in this menu on 3-phases drives.
00 v Fault ignored
01 v Fault with freewheel stop
If one phase disappears, the drive switches to fault mode, but if 2 or 3 phases disappear, the drive
continues to operate until it trips on an undervoltage fault.
08 v DC Injection
300-
500-
600- FAULT DETECTION MANAGEMENT MENU (continued) 600-
607-
Undervoltage menu 700-
Behaviour in the event of the undervoltage fault prevention level being reached
00 v No action (freewheel)
02 v Stop following an adjustable ramp Undervoltage ramp deceleration time 607.2.
00 v No test
01 v The IGBTs are tested on power up and every time a run command is sent. These tests cause a slight
delay (a few ms).
In the event of a fault, the drive will lock. The following faults can be detected:
- Drive output short-circuit (terminals U-V-W): F018, F019, F021 display
- IGBT faulty: F020 display, where x indicates the number of the IGBT concerned
IGBT short-circuited: x2F, where x indicates the number of the IGBT concerned
00 v Fault ignored. This configuration is only possible if AI1 current scaling parameter of 0% 204.1
(page 61) is not greater than 3 mA or AI1 type 204.0 = 0 A.
01 v Freewheel stop
08 v DC injection
2s To change the assignment of this parameter, press the ENT key for 2 s.
300-
400-
Code Name/Description Adjustment range Factory setting
500-
600-
600- FAULT DETECTION MANAGEMENT MENU (continued)
700- 610 M Detected fault inhibition assignment 00
In rare cases, the monitoring functions of the drive may be unwanted because they impede the purpose of the
application. A typical example is a smoke extractor fan operating as a part of a fire protection system. If a fire
occurs, the smoke extractor fan should operate as long as possible, even if, for example, the permissible
ambient temperature of the drive is exceeded. In such applications, damage to or destruction of the device
may be acceptable as collateral damage, for example, to keep other damage from occurring whose hazard
potential is assessed to be more severe.
A parameter is provided to disable certain monitoring functions in such applications so that automatic error
detection and automatic error responses of the device are no longer active. You must implement alternative
monitoring functions for disabled monitoring functions that allow operators and/or master control systems to
adequately respond to conditions which correspond to detected errors. For example, if overtemperature
monitoring of the drive is disabled, the drive of a smoke extractor fan may itself cause a fire if errors go
undetected. An overtemperature condition can be, for example, signaled in a control room without the drive
being stopped immediately and automatically by its internal monitoring functions.
DANGER
MONITORING FUNCTIONS DISABLED, NO ERROR DETECTION
• Only use this parameter after a thorough risk assessment in compliance with all regulations and standards
that apply to the device and to the application.
• Implement alternative monitoring functions for disabled monitoring functions that do not trigger automatic
error responses of the drive, but allow for adequate, equivalent responses by other means in compliance
with all applicable regulations and standards as well as the risk assessment.
• Commission and test the system with the monitoring functions enabled.
• During commissioning, verify that the drive and the system operate as intended by performing tests and
simulations in a controlled environment under controlled conditions.
Failure to follow these instructions will result in death or serious injury.
To assign fault inhibit, press and hold down the ENT key for 2 s.
00 v Function inactive
L1H v L1H: LI1 active high
L2H v L2H: LI2 active high
L3H v L3H: LI3 active high
L4H v L4H: LI4 active high
LUH v LUH: LIU active high
Following detected faults can be inhibited:
F008, F025, F028,F011, F013, F014, F015, F016, F022, F024,
2s F027, and F030.
2s To change the assignment of this parameter, press the ENT key for 2 s.
700-
611 M Modbus detected fault management 01
Behaviour of the drive in the event of a communication fault with integrated Modbus.
00 v Fault ignored
01 v Freewheel stop
08 v DC injection
WARNING
LOSS OF CONTROL
If this parameter is set to 00, Modbus communication monitoring is disabled.
• Only use this setting after a thorough risk assessment in compliance with all regulations and standards that
apply to the device and to the application.
• Only use this setting for tests during commissioning.
• Verify that communication monitoring has been re-enabled before completing the commissioning procedure
and performing the final commissioning test.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Lowers the tripping threshold of the F030 fault to operate on a line supply down to 50% of nominal
line voltage. In this case, a line choke must be used and the performance of the drive controller
cannot be guaranteed.
00 v No
01 v Yes
NOTICE
RISK OF DAMAGE TO THE DRIVE
A line choke must be used when the parameter 612 is set to 01.
Failure to follow these instructions can result in equipment damage.
This function will initialize the settings in the Monitor (800-) section, menu 900- (page 49).
00 v No
07 v Reset fan time display
614 M Reset all previous detected faults via Run key of HMI 00
If this function is active and the RUN key on the equipment panel is pressed for at least 2 s, some
detected faults (1) can be reset.
This function is only effective for 2-wire or 3-wire control.
If type of control 201 (page 56) = 00 and 2 wire type control 202 (page 60) = 00 and the RUN
command is still valid, the drive will run the motor after the fault is reset.
To change the assignment of this parameter, press the ENT key for 2 s.
(1) These errors include: F001, F002, F006, F008, F010, F014, F015, F017, F018, F019, F020,
F021, F025, F027 and F028.
00 v Inactive
01 v Active
WARNING
UNANTICIPATED EQUIPMENT OPERATION
2s If parameter 614 is set to 1, pressing the RUN key for 2 s with clear and some detected errors (1).
• Verify that activating this function does not result in unsafe conditions.
• Only use this parameter after a thorough risk assessment in compliance with all regulations and
standards that apply to the device and to the application.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
300-
600-
700- Communication menu
NOTE: For following parameters, the modifications will be taken into account only at the next control power on.
700-
701 M Modbus address OFF to 247 OFF
Modbus address is adjustable in the range OFF to 247. When OFF, communication is not active.
24 v 4.8 kbps
28 v 9.6 kbps
32 v 19.2 kbps
36 v 38.4 kbps
703 M Modbus format 8E1
02 v 8o1
03 v 8E1
04 v 8N1
05 v 8N2
704 M Modbus time out 0.1 to 30 s 10 s
The drive detects a Modbus fault if the drive does not receive a Modbus request within a predefined time
period (time out).
705-
Input scanner menu (values are expressed in hexadecimal)
705.0 M Com scanner read address parameter 1 0C81
706-
Output scanner menu (values are expressed in hexadecimal)
706.0 M Com scanner write address parameter 1 2135
0000
706.2 M Com scanner write address parameter 3
Address of the 3rd input word.
0000
706.3 M Com scanner write address parameter 4
Address of the 4th input word.
300-
500-
700- Communication menu (continued)
600-
707-
Input scanner access menu (values are expressed in hexadecimal) 700-
ETA value
707.0 M Com scanner read address value 1
Value of the 1st input word.
RFRD value
707.1 M Com scanner read address value 2
Value of the 2nd input word.
8000
707.2 M Com scanner read address value 3
Value of the 3rd input word.
8000
707.3 M Com scanner read address value 4
Value of the 4th input word.
708-
Output scanner access menu (values are expressed in hexadecimal)
CMD value
708.0 M Com scanner write address value 1
Value of the 1st output word.
LFRD value
708.1 M Com scanner write address value 2
Value of the 2nd output word.
8000
708.2 M Com scanner write address value 3
Value of the 3rd output word.
8000
708.3 M Com scanner write address value 4
Value of the 4th output word.
Servicing
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Read and understand the instructions in "Before your begin" chapter before performing any procedure in this chapter.
Failure to follow these instructions will result in death or serious injury.
The ATV310 does not require any preventive maintenance. However, it is advisable to perform the following checks regularly:
• Check environment and tightness of connections
• Remove any dust from the drive
• Ensure proper fan operation
Physical damage to covers
Services
NOTICE
RISK OF DAMAGE TO DRIVE
Perform the following activities.
Failure to follow these instructions can result in equipment damage.
Product impact Enclosure - Control panel (LED Check drive display part Once per month
display)
Corrosion Terminals - connectors - screws Check and clean
Prolonged storage
For products that have been stored for more than 2 years, voltage should be gradually increased in product capacitors.
NOTICE
RISK OF DERATED PERFORMANCE DUE TO CAPACITOR AGING
The product capacitor performances after a long time storage above 2 years can be degraded. In that case, before using the product,
apply the following procedure:
• Use a variable AC voltage supply, connected between L1 and L2 (even for ATVpppppN4 catalog numbers).
• Increase AC supply voltage to have:
- 80% of rated voltage for 30 min
- 100% of rated voltage for 30 min
Failure to follow these instructions can result in equipment damage.
Display menu
Use the status of the drive and its current values shown on the display menu as an aid for finding the causes of detected faults.
Fan replacement
Fan spares can be ordered for the ATV310. Contact the Schneider Electric Customer Care Center for details.
Remove screw of fan support and pull out the fan support
Uncoupled the connected parts and remove the fan
1
2
ATV310HD22N4pF
• The assignment of the "Fast stop" or "Freewheel" functions will prevent the drive starting if the corresponding logic inputs are not powered
up. The ATV310 then displays 502.1 in freewheel stop mode and --01 in fast stop mode. --00 is displayed at freewheel stop
end. This is normal, since these functions are active at zero so drive can safely stop in case of wire break. Assignment of LI to be checked
in the COnF/FULL/500-/502- menu.
• Make sure that the run command input(s) is activated in accordance with the selected control mode (parameters in COnF/FULL/
200- menu Type of control 201 (page 56) and 2-wire type control 202 (page 60).
• If the reference channel or command channel is assigned to Modbus, the drive displays "502.1" freewheel stop when the power supply
is connected and remains in stop mode until the communication bus sends a command.
• "RUN" key is inactive in factory setting. Adjust parameters Reference channel 1 401 (page 73) and Command channel 1 407
(page 74) to control the drive locally (COnF/FULL/400- menu). See "How to control the drive locally" (page 45).
F025 and F028 faults can also be reset remotely by means of a logic input (in COnF/FULL/600- menu, parameter Detected
fault reset assignment 601 (page 103).
F007, F025 and F028 faults can be inhibited and cleared remotely by means of a logic input (parameter Detected fault inhibition
assignment 610 (page 108).
---- Problem with application firmware • Invalid application firmware • Re-download application firmware.
update using the Multi-Loader tool
F001 Precharge • Charging relay control fault or • Turn the drive off and then back on again.
charging resistor damaged • Check the connections.
• Check the stability of the main supply.
• Contact local Schneider Electric
representative.
F002 Unknown drive rating • Power card and stored card • Contact local Schneider Electric
versions different representative.
F003 Unknown or incompatible power • The power card is incompatible • Contact local Schneider Electric
board with the control card representative.
F004 Internal serial link fault • Communication interruption • Contact local Schneider Electric
between the internal cards representative.
F005 Invalid industrialization zone • Internal data inconsistent • Contact local Schneider Electric
representative.
F006 Current measurement circuit • Current measurement is not • Contact local Schneider Electric
correct due to hardware circuit representative.
fault
F007 Internal thermal sensor detected • The drive temperature sensor is • Contact local Schneider Electric
fault not operating correctly representative.
• The drive is in short circuit or open
F008 Internal CPU • Internal microprocessor fault • Turn the drive off and then back on again.
• Contact local Schneider Electric
representative.
Fault detection codes that can be cleared with the automatic restart function, after
the cause has disappeared
These faults can also be cleared by turning on and off or by means of a logic input (parameter Detected fault reset assignment 601 (page
103).
F011, F013, F014, F015, F016, F022, F024 and F027 faults can be inhibited and cleared by means of a logic input [Detected fault inhibition
assignment 610 (page 108)].
F009 Overbraking • Sudden braking or load inertia too • Increase the deceleration time.
high • Install a module unit with a braking resistor if necessary.
• Check the main supply voltage to ensure it is under the
maximum acceptable (20% over maximum main supply
during run status).
F011 Drive overheat • Drive temperature too high • Check the motor load, the drive ventilation and the
ambient temperature. Wait for the drive
to cool down before restarting. See Mounting and
temperature conditions on page 18.
F012 Process overload • Process overload • Check that drive parameters and application processes
fault are compatible.
F013 Motor overload • Triggered by excessive motor • Check configuration of motor thermal protection and
current motor load.
F014 1 Output phase loss • Loss of one phase on drive output • Check the connections from the drive to the motor.
• If using a downstream contactor, make sure the
connection, cable and contactor are right.
F015 3 Output phases loss • Motor not connected • Check the connections from the drive to the motor.
• Motor power too low, below 6% of • Test on a low power motor or without a motor. In factory
the rated drive current settings mode, motor phase loss detection is active
• Output contactor open Output Phase loss detection 605 page 106 = 01. To
• Transient instability in the motor check the drive in a test or maintenance environment,
current without having to use a motor with the same rating as the
drive, deactivate motor phase loss detection Output
Phase loss detection 605 = 00.
• Check and optimize IR compensation 310 page 68,
Rated motor voltage 304 page 66 and Rated motor
current 305 page 67 and then perform Auto-tuning
318 page 70.
F016 Main overvoltage • Line voltage too high: • Turn Off the Drive. Check and adjust the line voltage.
- At drive power on, supply is 10% After line come back to nominal voltage (within tolerance)
over the maximum acceptable do power On.
voltage level If intermittent F016 code appear, set R1 assignment
- At power with no run command, 205 to 01 and it can be connected to upstream
20% over maximal line supply protection to avoid overvoltage in the drive. In this case
• Disturbed mains supply LO1 can be used for others drive status see page 61
F017 Input phase loss • Drive incorrectly supplied or a fuse • Check the power connection and the fuses.
blown • Use a 3-phase line supply.
• Failure of one phase • Disable reporting of this fault type by setting Input Phase
• 3-phase ATV310 used on a single- loss detection detection 606 (page 106) to 00.
phase line supply
• Unbalanced load
• This protection only operates with
the drive on load
Fault detection codes that can be cleared with the automatic restart function, after
the cause has disappeared (continued)
F021 Load short circuit • Short-circuit at drive output • Check the cables connecting the drive to the motor and
• Short circuit detection at the run the condition of motor insulation.
command or DC injection
command if parameter IGBT Test
608 (page 107) is set to 01
F022 Modbus interruption • Interrupted communication on the • Check the connections of communication bus.
Modbus network • Check the time-out (parameter Modbus time out 704
page 110).
• Refer to the Modbus user manual.
F024 HMI communication • Communication interruption with • Check the terminal connection.
the external display terminal
F026 PI feedback fault • PID feedback below lower limit • Verify the PID function feedback.
• Verify the PID feedback supervision (parameter PID
feedback supervision 59.25 page 90) and time delay
setting (parameter PID supervision function time delay
59.23 page 90).
F027 IGBT overheat • Drive overheated • Check the size of the load/motor/drive.
• IGBT internal temperature is too • Reduce the Switching frequency 315 page 69.
high for the ambient temperature • Wait for the drive to cool down before restarting.
and load .
F029 Process underload • Process underload • Check that drive parameters and application processes
fault • Time that motor current is below are compatible.
the Process underload threshold
211 (page 63) exceeds the
Process underload time delay
210
(page 63) to protect the application
F033 AI1 current loss Detected if: • Check the terminal connection.
• Analog input AI1 is configured as
current
• AI1 current scaling parameter of
0% 204.1 (page 61) is greater
than 3 mA
• Analog input current is lower than
2 mA
Fault detection codes that will be cleared as soon as their causes disappear
USF faults can be inhibited and cleared remotely by means of a logic input parameter Detected fault inhibition assignment 610 (page 108).
F030 Undervoltage • Line supply too low • Check the voltage and parameters on the Undervoltage
• Transient voltage dip phase loss menu 607- (page 107).
F031 Incorrect • HMI block replaced by an HMI • Return to factory settings or retrieve the backup
configuration block configured on a drive with a configuration, if it is valid.
different rating • If the fault remains after reverting to the factory settings,
• The current configuration of contact your local Schneider Electric representative.
customer parameters is
inconsistent
F032 Invalid configuration • Invalid configuration • Check the configuration loaded previously.
(1) The configuration loaded in the • Load a compatible configuration.
drive via the bus or communication
network is inconsistent.
The configuration upload has been
interrupted or is not fully finished
F034 Download invaild When save parameter setting or • Power cycle drive.
configuration restore to factory setting, the drive • Restore to factory setting.
detect invalid configuration. • If the fault remains after reverting to the factory settings,
contact your local Schneider Electric representative.
(1) When the CFI is present in the previous fault menu, it means the configuration has been interrupted or is not fully finished.
Some detected faults that are reset by pressing the RUN key
See Reset all previous detected faults via Run key of HMI 614 parameter (page 109).
A-17 Key alarm • Key pressed down for longer than 10 seconds
(1) • Membrane switch disconnected
• Display terminal woken up while a key is being pressed
cLr Confirm fault reset • This message appears if the STOP key is pressed while the display terminal is displaying a fault
(1)
dEU.E Drive mismatch • Drive type (brand) does not match display terminal type (brand)
(1)
(1) Flashing
1. Connect the ground terminal to the grounding screws located below the output
terminals.
2. Connect the power terminals.
R S 3. Connect the logic inputs.
4. Turn on the drive without giving a run command.
5. Assign factory settings to the drive, i.e. Factory / recall customer parameter set
R1A LO+ 102 (page 54) = 64.
R1B LO- 6. Set the motor parameters (in COnF mode) only if the factory configuration of the
R1C COM drive is not suitable.
(a
MODE ESC
LI1 7. Perform an auto-tuning.
COM LI2 (b 8. Set parameter Reverse direction 503 (page 79) to LI2H.
AI1 LI3
5V STOP/ LI4
AO1
RESET
+24V
ConF
RUN
MODBUS
500
503
PA+ PB U V W
L2H
1. Connect the ground terminal to the grounding screws located below the output
terminals.
2. Connect the power terminals.
3. Connect the logic inputs.
R S T 4. Turn on the drive without giving a run command.
5. Assign factory settings to the drive, i.e. Factory / recall customer parameter set
102 (page 54) = 64.
R1A LO+ 6. Set 201 to 00 (see page 56).
R1B LO-
7. Set the motor parameters (in COnF mode) only if the factory configuration of the
R1C COM
drive is not suitable.
LI1
COM
MODE ESC
LI2
(a) 8. Perform an auto-tuning.
AI1 LI3 9. Set parameter Logic inputs type 203 (page 60) to 01.
5V STOP/
RESET
LI4
AO1 +24V
ConF
RUN
MODBUS
200-
203
PA+ PB U V W
01
MODBUS
200-
203
PO PA+ PC- U V W
02
1. Connect the ground terminal to the grounding screws located below the output
terminals.
2. Connect the power terminals.
R S T
3. Connect the logic input LI1 and analog input AI1.
4. Turn on the drive without giving a run command.
5. Assign factory settings to the drive, i.e. Factory / recall customer parameter set 102
R1A LO+ (page 54) = 64.
R1B LO-
R1C COM
6. Set the motor parameters (in COnF mode) only if the factory configuration of the
(a)
MODE ESC
LI1 drive is not suitable.
0-20 mA
COM LI2
7. Perform an auto-tuning.
AI1 LI3
5V STOP/ LI4 8. Set AI1 type 204.0 (page 61) to 0A, AI1 current scaling parameter of 0% 204.1
(page 61) to 0 A.
RESET
AO1 +24V
RUN
Check that AI1 current scaling parameter of 100% 204.2 (page 61) is set to
20 mA.
MODBUS
2
204- 0
ConF
204.1
PA+ PB U V W
200-
1
(a) Run Forward
204- 204.2
0A
9. Start
ሏႜ
ConF
MODBUS
500
507- 507.0
PA+ PB U V W
L2H
ConF
500
500-
507.3
20
ConF
500
507- 5 0 7 .1
L3H
ConF
500
507-
507.4
30
ConF
500
507-
507.5
40
Preset speed 3 - 30 Hz
Preset speed 2 - 20 Hz
Forward (LI1)
507.0 (LI2)
507.1 (LI3)
RUN
ConF
MODBUS
400-
PA+ PB U V W
406
02
(a): Run Forward
Set Reference channel 1 401 (page 73) to 164.
ConF
400- 401
164
Check that Command channel 1 407 (page 74) is set to 01.
ConF
400-
407
01
9. Start
Introduction
Overview
DANGER
INSUFFICIENT PROTECTION AGAINST OVERCURRENTS CAN CAUSE FIRE OR EXPLOSION
• Use properly rated overcurrent protection devices.
• Use the fuses/circuit breakers specified.
• Do not connect the product to a supply mains whose prospective short circuit current rating (current that flows during a short circuit)
exceeds the specified maximum permissible value.
• When rating the upstream mains fuses and the cross sections as well as the lengths of the mains cables, take into account the
minimum required prospective short-circuit current (Isc). Refer to the Upstream Protection Device section.
• If the minimum required prospective short-circuit current (Isc) is not available, apply the instructions given in the section below.
Failure to follow these instructions will result in death or serious injury.
The specified maximum permissible values and products for IEC compliance are specified in the present document (user manual).
General
• The Short Circuit Protective Device (SCPD) rated to the drive will help protect the upstream installation in case of a short-circuit
internal to the drive and mitigate the damage to the drive and its surrounding area.
• The SCPD rated to the drive is mandatory to help ensuring the safety of the Power Drive System.
It comes in addition to the upstream branch circuit protection which is in compliance with the local regulation for electrical installation.
• The SCPD shall mitigate the damage in case of detected error condition such as an internal short-circuit of the drive.
• The SCPD must take into account both following characteristics...
- a maximum prospective short-circuit current
- a minimum required prospective short-circuit current (Isc).
If the minimum required prospective short-circuit current (Isc) is not available, increase the power of the transformer or decrease the length
of the cables
In other cases, contact your Schneider Electric Customer Care Center (CCC) for specific selection of Short Circuit Protective Device
(SCPD).
NOTE: The electronic power output short-circuit protection circuitry meets the requirements of IEC 60364-4-41:2005/AMD1 - Clause 411.
Wiring Diagram
This diagram shows an example of installation with both SCPD types, Circuit-breaker and Fuse link rated to the drive.
(1) Drive
The following equations allow to estimate the value of the symmetrical three-phase prospective short-circuit current (Isc) at the drive
connection points.
Then, the SCPD type shall be selected according to the drive. If no selection is available, Schneider Electric Customer Care Center (CCC)
should be contacted.
EMC filter series have no significant effect on the minimum prospective shortcircuit current capability of the main source.
Through the line option, the Isc will be limited to a maximum value independent of the transformer and cable. Therefore the below
equations can be used to estimate the minimum prospective short-circuit current capability.
IEC Fuses
Introduction
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR FIRE
The opening of the branch-circuit protective device is able to be an indication that a fault current has been interrupted.
• Current-carrying parts and other components of the controller should be examined and replaced if damaged.
• If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced.
Failure to follow these instructions will result in death or serious injury.
NOTE: Only gR and gS fuses are mandatory in case of using braking ports, to comply with IEC 61800-5-1 Ed 2.1.
NOTE:
• Integral solid state short circuit protection in the drive does not provide branch circuit protection. Branch circuit protection must be
provided in accordance with any local codes.
• The drive has a 100 kA interrupt rating on the output of the drive. In addition to providing a rating based on shorting the output of the drive,
these short circuit current ratings have been obtained by shorting components internal to the drive. These ratings allow proper
coordination of short circuit protection.
NOTE: Verify that the minimum required prospective short-circuit current (Isc) value from the table above is lower than the value estimated
in the Calculation section, page 128.
Current limiting fuses can be chosen as SCPD according to the following table for both Normal duty (ND) and Heavy duty (HD):
User
Code Page Name Unit Possible value / Function Factory setting
setting
00 None
59.00 86 PID feedback assignment 00
01 Terminal
59.01 86 PID proportional gain 0.01 to 100 - 1
59.02 86 PID integral gain 0.01 to 100 - 1
0.00 to
59.03 86 PID derivative gain - 0.00
100.00
0.00 to
59.04 86 PID feedback scale factor - 0.00
100.00
Activation internal PID 00 No
59.05 86 00
reference value 01 Yes
00 None
L1H L1H
59.06 86 2 preset PID assignment - L2H L2H 00
L3H L3H
L4H L4H
59.07 87 4 preset PID assignment 59.06 As 59.06 00
59.08 87 2 preset PID reference value % 0 to 100 - 25%
59.09 87 3 preset PID reference value % 0 to 100 - 50%
59.10 87 4 preset PID reference value % 0 to 100 - 75%
59.11 87 Internal PID reference value % PID 0 to 100 - 0%
59.12 87 PID reference value ramp s 0 to 99.9 - 0s
59.13 87 PID min value reference % PID 0 to 100 - 0%
59.14 87 PID max value reference % PID 0 to 100 - 100%
59.15 87 PID predictive speed - 01 to 400 - nO
00 No
59.16 88 PID correction reverse - 00
01 Yes
00 No
L1H L1H: LI1 active high
59.17 88 PID auto/manual assignment L2H L2H: LI2 active high 00
L3H L3H: LI3 active high
L4H L4H: LI4 active high
00 No
59.18 88 PID manual reference 01 Terminal 00
02 AIV
59.19 89 PID: wake up level % 0 to 100 - 0%
59.20 89 PID: Wake up threshold % 0 to 100 - 0%
59.21 90 Sleep offset threshold Hz 0 to 512.2 - 0 Hz
PID feedback supervision 0 to 100
59.22 90 % - 0 (No)
threshold
PID supervision function time 0 to 600
59.23 90 s - 0s
delay
Maximum frequency detection 0 to 512.2
59.24 90 Hz - 0 Hz
Hysteresis
01 Fault and freewheel stop
59.25 90 PID feedback supervision - 01
04 Fall back speed
59.26 90 Fall back speed Hz 0 to 512.2 - 0 Hz
00 Start/stop
100 55 Macro-configuration - 04 PID regulation 00 -
09 Speed
User
Code Page Name Unit Possible value / Function Factory setting
setting
00 No
101 54 Store customer parameter set - 00
01 Yes
00 No
Factory / recall customer
102 54 - 02 REC 00
parameter set
64 INI
00 2 wire type control
201 56 Type of control - 00
01 3-wire control
00 0/1 level
202 60 2-wire type control - 01 Transition 00
02 Priority FW
00 Positive
203 60 Logic inputs type - 01 Negative internal supply 00
02 Negative external supply
5u Voltage: 0-5 Vdc
10u Voltage: 0-10 Vdc
204.0 61 AI1 type - 5U
0A Current: x-y mA
LIu Logic input
AI1 current scaling parameter
204.1 61 mA 0 to 20 - 4 mA
of 0%
AI1 current scaling parameter
204.2 61 mA 0 to 20 - 20 mA
of 100%
204.3 61 AI1 filter time s 0 to 10 - 0s
00 Not assigned
01 No error detected
02 Drive run
04 Freq. threshold reached
05 512.2 reached
205 61 R1 assignment - 06 I threshold reached 01
07 Freq. reference reached
08 Mot. therm. state reach.
21 Process underload fault
22 Process overload fault
123 AI1 Al. 4-20
00 Not assigned
01 No error detected
02 Drive run
04 Freq. threshold reached
05 512.2 reached
06 I threshold reached
206.0 62 LO1 assignment - 00
07 Freq. reference reached
08 Mot. therm. state reach.
21 Process underload fault
22 Process overload fault
123 4-20 mA signal loss
126 Auxiliary pump
00 Positive logic: active
206.1 62 LO1 status (output active level) - 00
01 Negative logic: active
62
207 Process overload time delay s 0 to 100 - 5s
90
62
208 Process overload threshold % of In 70 to 150 - 90%
90
63
209 Process overload fault duration min 0 to 6 - 0 min
90
63
210 Process underload time delay s 0 to 100 - 0s
90
63 % of
211 Process underload threshold 20 to 100 - 60%
90 305
User
Code Page Name Unit Possible value / Function Factory setting
setting
63 Process underload fault
212 min 0 to 6 - 0 min
91 duration
213 63 Motor frequency threshold Hz 0 to 400 - 50 or 60 Hz
0 to
214 63 Motor current threshold A - InV
1.5 of In
% of
215 63 Motor thermal state threshold 0 to 118 100%
tHr
00 None
129 Estimated Motor current
130 Estimated motor freq.
131 Ramp output
135 PID reference value
216.0 64 AO1 assignment 00
136 PID feedback
137 PID error
139 Output power
140 Motor thermal state
141 Drive thermal state
10U Voltage
216.1 64 AO1 type OA Current 0A
4A Current
BSD Standard
BLS Pedestal
217 65 Reference Template 00
BNS Deadband
BNS0 Deadband at 0 %
00 50 Hz
301 66 Standard motor frequency Hz 00
01 60 Hz
Determined by
kW or
302 66 Rated Motor Power - - drive rating and
HP
dual rating
Determined by
303 66 Rated motor cos phi - 0.5 to 1 - drive rating and
dual rating
304 66 Rated motor voltage V 360 to 460 - 380 V
Determined by
305 67 Rated motor current A (1) 0.25 to 1.5 - drive rating and
dual rating
50 or 60 Hz
306 67 Rated motor frequency Hz 10 to 400 -
(301)
Determined by
0 to
307 67 Rated motor speed rpm - drive rating and
32767
dual rating
60 or 72 Hz
308 67 Maximum frequency Hz 10 to 400
(to 301)
00 SVC performance
309 67 Motor control type - 03 Standard U/F 03
06 Pump
310 68 IR compensation % 25 to 200 - 100%
% of
311 68 Slip compensation 0 to 150 - 100%
nSL
312 68 Frequency loop stability % 0 to 100 - 20%
313 68 Frequency loop gain % 0 to 100 - 20%
314 69 Flux Profile % 0 to 100 20%
315 69 Switching frequency kHz 2 to 16 - 12
00 No
317 69 Motor noise reduction 00
01 Yes
User
Code Page Name Unit Possible value / Function Factory setting
setting
00 No
318 70 Auto-tuning - 01 Yes 00
02 Complete
00 00
319 70 Motor parameter choice - 01
01 01
00 No
320 71 Vector control 2 points - 00
01 Yes
321 71 Max voltage of constant power V Value of parameter 314 to 460 V 380 V
Max frequency of constant
322 71 V Value of parameter 306 to 460 Hz 50 Hz
power
00 Normal duty
323 71 Dual Rating - 01
01 Heavy duty
01 Terminal
163 HMI
401 73 Reference channel 1 01
164 Modbus
183 Jog Dial
-400 to
402 73 External reference value Hz - -
400
Integrated display jog dial
403 73 % 0 to 100 - -
reference
00 No
404 73 Reverse inhibition 00
01 Yes
00 No
405 73 Stop key priority Yes
01 Yes
01 Combined mode
406 73 Channel configuration 01
02 Separate mode
01 Terminals
02 Local
407 74 Command channel 1
03 Remote display
10 Modbus
00 No
L1H L1H
408 74 Forced local assignment L2H L2H 00
L3H L3H
L4H L4H
00 None
01 Terminal
409 74 Forced local reference 00
163 HMI
183 Jog Dial
0.0 to
501.0 75 Acceleration s - 3.0 s
999.9
0.0 to
501.1 75 Deceleration s - 3.0 s
999.9
00 Linear
501.2 75 Ramp shape assignment 01 S-shape 00
02 U-shape
00 None
L1H L1H: LI1 active high
L2H L2H: LI2 active high
L3H L3H: LI3 active high
501.3 75 Ramp switching commutation L4H L4H: LI4 active high 00
L1L L1L: LI1 active low
L2L L2L: LI2 active low
L3L L3L: LI3 active low
L4L L4L: LI4 active low
User
Code Page Name Unit Possible value / Function Factory setting
setting
0.0 to
501.4 76 Acceleration 2 s - 5s
999.9
0.0 to
501.5 76 Deceleration 2 s - 5s
999.9
00 No
Decel Ramp Adaptation
501.6 76 01 Yes Yes
assignment
02 Motor braking
00 Ramp stop
03 DC injection
502.0 77 Type of stop 00
08 Fast stop
13 Freewheel stop
00 No
L1L L1L: LI1 active low
502.1 77 Freewheel stop assignment L2L L2L: LI2 active low 00
L3L L3L: LI3 active low
L4L L4L: LI4 active low
00 NONE
L1L L1L: LI1 active low
502.2 77 Fast stop assignment L2L L2L: LI2 active low 00
L3L L3L: LI3 active low
L4L L4L: LI4 active low
502.3 77 Fast stop Ramp divider 1 to 10 - 4
00 None / Not assigned
L1H L1H: LI1 active high
L2H L2H: LI2 active high
502.4 78 DC injection assignment 00
L3H L3H: LI3 active high
L4H L4H: LI4 active high
LuH LUH: LIU active high
502.5 78 DC injection level 0.1 to 1.41 - 0.64*In
502.6 78 IDC injection time for DCLI 0.1 to 30 - 0.5 s
0.1 to DC
502.7 79 DC injection level 2 injection level - 0.5*In
value
502.8 79 Injection standstill braking time 0.1 to 30 - 0.5 s
00 Function inactive
L1H L1H active high
503 79 Reverse direction - L2H L2H active high 00
L3H L3H active high
L4H L4H active high
00 No
504.0 80 Automatic DC injection 01 Yes Yes
02 Continuous
70% of Rated
504.1 80 Automatic DC injection current A 0 to Rated motor current 305 motor current
305
504.2 80 Automatic DC injection time s 0.1 to 30 0.5 s
00 Function inactive
L1H LI1 active high
505.0 81 Jog assignment - L2H LI2 active high 00
L3H LI2 active high
L4H LI4 active high
505.1 81 Jog Frequency Hz 0 to 10 - 5 Hz
User
Code Page Name Unit Possible value / Function Factory setting
setting
00 Function inactive
L1H LI1 active high
L2H LI2 active high
506.0 82 Up speed command - 00
L3H LI2 active high
L4H LI4 active high
LUH LIU active high
00 Function inactive
L1H LI1 active high
L2H LI2 active high
506.1 82 Down speed command - 00
L3H LI2 active high
L4H LI4 active high
LUH LIU active high
00 Do not save
506.2 82 Store - 01 Save to RAM 00
02 Save to ROM
00 Function inactive
L1H LI1 active high
L2H LI2 active high
506.3 83 Clear the function - L3H LI2 active high 00
L4H LI4 active high
LUH LIU active high
159 Function is cleared
Reactivity of +/- speed around
506.4 83 % 0 to 100 - 0%
ref.
00 Function inactive
L1H L1 high activation level
507.0 84 2 preset speeds - L2H LI2 active high 00
L3H LI2 active high
L4H LI4 active high
507.1 84 4 preset speeds As 507.0 00
507.2 84 8 preset speeds As 507.0 00
507.3 84 Preset speed 2 Hz 0 to 400 - 10 Hz
507.4 84 Preset speed 3 Hz 0 to 400 - 15 Hz
507.5 84 Preset speed 4 - 0 to 400 - 20 Hz
507.6 84 Preset speed 5 Hz 0 to 400 - 25 Hz
507.7 84 Preset speed 6 Hz 0 to 400 - 30 Hz
507.8 84 Preset speed 7 Hz 0 to 400 - 35 Hz
507.9 84 Preset speed 8 Hz 0 to 400 - 40 Hz
00 Function inactive
L1H L1 high activation level
507.0 84 2 preset speeds - L2H LI2 active high 00
L3H LI2 active high
L4H LI4 active high
508 84 Skip frequency Hz 0 to 400 - 0 Hz
00 No
510.0 91 Selecting operating mode - -
01 Yes
Starting frequency of the parameter
510.1 91 Hz 0 to parameter 308 value
auxiliary pump 512.2 value
Time delay before starting 0.0 to
510.2 91 s - 2s
auxiliary pump 999.9
0.0 to
510.3 91 Auxiliary pump ramp reaching s - 2s
999.9
510.4 91 Auxiliary pump stop frequency Hz 0 to parameter 308 value 0 Hz
User
Code Page Name Unit Possible value / Function Factory setting
setting
0.0 to
510.5 91 Auxiliary pump stop time delay s - 2s
999.9
0.0 to
510.6 91 Auxiliary pump stop ramp s - 2s
999.9
510.7 91 Zero flow detection period min 0.0 to 20 - 0 min
Zero flow detection activation
510.8 91 Hz 0.0 to 400 - 0 Hz
threshold
510.9 91 Zero flow detection offset Hz 0.0 to 400 - 0 Hz
00 NONE
L1H L1H: LI1 active high
L2H L2H: LI2 active high
L3H L3H: LI3 active high
2nd current limitation
511.0 100 L4H L4H: LI4 active high 00
commutation
L1L L1L: LI1 active low
L2L L2L: LI2 active low
L3L L3L: LI3 active low
L4L L4L: LI4 active low
Determined by
0.25 to
511.1 100 Current limitation A - drive rating and
1.5 of In
dual rating
Determined by
2nd current limitation 0.25 to
511.2 100 A - drive rating and
commutation 1.5 of In
dual rating
512.0 101 Low speed Hz 0 to 512.2 - 0 Hz
89
512.1 Low speed operating time s 0.1 to 999.9 - nO
101
50 or 60Hz
512.0 to determined by
512.2 102 High speed Hz -
308 301 parameter
value
00 None
L1H L1H: LI1 active high
512.3 102 2 High speed assignment - L2H L2H: LI2 active high 00
L3H L3H: LI3 active high
L4H L4H: LI4 active high
512.4 102 4 High speed assignment - As 512.3 As 512.3 00
50 or 60 Hz
512.0 to determined by
512.5 102 High speed 2 Hz -
308 301 and max.
308
512.6 102 High speed 3 Hz As 512.5 As HS2 As 512.5
512.7 102 High speed 4 Hz As 512.5 As HS2 As 512.5
00 Fan runs while drive is running
513 102 Cooling fan control
01 Temperature control mode
00 None
L1H L1H: LI1 active high
Detected fault reset
601 103 - L2H L2H: LI2 active high 00
assignment
L3H L3H: LI3 active high
L4H L4H: LI4 active high
00 No
602.0 103 Automatic restart 00
01 Yes
User
Code Page Name Unit Possible value / Function Factory setting
setting
0 5 min.
1 10 min.
2 30 min.
602.1 103 Max. automatic restart 3 1 hr 5 min.
4 2 hr
5 3 hr
6 Infinite
00 Function inactive
603 104 Catch on the fly 00
01 Function active
Determined by
604 106 Motor thermal current A 0.2 to 1.5 In -
drive rating
01 Self-ventilated
604.1 106 Motor protection type - 01
02 Motor-ventilated
00 Fault ignored
604.2 106 Overload fault management - 01 Freewheel stop 01
08 DC injection
00 Not stored at power off
604.3 106 Motor thermal state memo - 00
01 Stored at power off
00 Function inactive
605 106 Output Phase loss - 01
01 Function active
00 Fault ignored
606 106 Input Phase loss - 01 Freewheel stop 01
08 DC injection
00 Detected fault and R1
Undervoltage detected fault relay set to 0
607.0 107 - 0
management 01 Detected fault and R1
relay set to 1
00 Freewheel stop
607.1 107 Undervoltage prevention - 00
02 Ramp stop
Undervoltage ramp
607.2 107 s 0.0 to 10.0 - 1.0 s
deceleration time
00 No test
608 107 IGBT Test 00
01 Yes
00 00
609 107 4-20mA loss Behaviour 01 01 00
08 DC injection
00 NONE
L1H L1H: LI1 active high
Detected fault inhibition
610 108 L2H L2H: LI2 active high 00
assignment
L3H L3H: LI3 active high
L4H L4H: LI4 active high
00 No
Modbus detected fault
611 109 01 Yes Yes
management
08 DC injection
00 No
612 109 Degraded line supply operation 00
01 Yes
00 Function inactive 00
613 109 Reset power run
01 Reset fan time display
Reset all previous detected 00 Inactive -
614 109 - 00
faults via Run key of HMI 01 Active
701 110 Modbus address OFF to 247 - Off
24 4.8 kbps
28 9.6 kbps
702 110 Modbus baud rate 19.2 kbps
32 19.2 kbps
36 38.4 kbps
User
Code Page Name Unit Possible value / Function Factory setting
setting
00 8o1
01 8E1
703 110 Modbus format - 8E1
02 8n1
03 8n2
704 110 Modbus time out - 0.1 to 30 - 10
Com scanner read address
705.0 110 - 0C81
parameter 1
Com scanner read address
705.1 110 - 219C
parameter 2
Com scanner read address
705.2 110 - 0
parameter 3
Com scanner read address
705.3 110 - 0
parameter 4
Com scanner write address
706.0 110 2135
parameter 1
Com scanner write address
706.1 110 219C
parameter 1
Com scanner write address
706.2 110 0
parameter 3
Com scanner read address
706.3 110 0
parameter 4
Com scanner read address
707.0 111 CMD value
value 1
Com scanner read address
707.1 111 LFRD value
value 2
Com scanner read address
707.2 111 8000
value 3
Com scanner read address
707.3 111 8000
value 4
Com scanner write address
708.0 111 ETA value
value 1
Com scanner write address
708.1 111 LFRD value
value 2
Com scanner write address
708.2 111 8000
value 3
Com scanner write address
708.3 111 8000
value 4
01 Terminal
63 HMI
801 47 Speed reference
164 Modbus
183 Jog Dial
802 47 Output frequency Hz - - -
803 47 Motor current A - - - -
804 47 PID error - - - - -
805 47 PID feedback - - - - -
806 47 PID reference - - - - -
807 47 Main voltage V - - - -
808 47 Motor thermal state % - - - -
809 47 Drive thermal state - - - - -
810 47 Output power % - - - -
811 48 Product status - - - - -
User
Code Page Name Unit Possible value / Function Factory setting
setting
901 49 State of logic inputs LI1 to LI4 - - - - -
State of the logic output LO1
902 49 - - - - -
and relay R1
903 49 Display of high speed value Hz - - - -
904 49 Drive Power rating -
905 49 Drive voltage rating - - - - -
906 49 Specific Product Number - - - - -
907 49 Card 1 Software Version - - - - -
908 50 Card 2 Software Version - - - - -
909 50 Run elapsed time display 0.01h 0.01 to 999 - - -
910 50 Power On time display 0.01 to 999 - - -
911 50 Fan time display 0.01 to 999 - - -
912 50 Process elapsed time 0.01 - - - -
r0t0
rOt1
913 50 Modbus communication status - - -
r1t0
r1t1
914 50 Last fault 1 - See page 114 - -
915 51 State of drive at fault 1 - - - - -
916 51 Last fault 2 - See page 114 - -
917 51 State of drive at fault 2 - - - - -
918 51 Last fault 3 - See page 114 - -
919 51 State of drive at fault 3 - - - - -
920 51 Last fault 4 - See page 114 - -
921 51 State of drive at fault 4 - - - - -
OFF Password disabled
999 52 HMI Password - OFF
On Password activated
EAV94277 07/2023