10 & 20 Series
TopWorx engineers are happy to provide technical assistance on GOTM Switch products. However, it is the
customer's responsibility to determine the safety and suitability of the product in their application. It is also the
customer's responsibility to install the switch using the current electrical codes in their region.
Figure 14 Figure 15
Figure 3 Figure 4 In Figure 14, the conduit system is filled with water and is leaking inside the
In Figure 3, the ferrous target is too small to In Figure 4, the target has sufficient size switch. Over a period of time, this may cause the switch to fail prematurely.
be detected reliably over the long term. and mass for long term reliable operation. In Figure 15, the termination of the switch may be fitted with a certified
thread-ed cable entry device (user supplied) in accordance with the
■ Switch may be mounted in any position. manufacturer's instructions to prevent water intrusion resulting in premature
Figure10 Figure 11 Figure 12 switch failure. A drip loop with provision for water to escape has also
Side by side on non-ferrous bracket been installed.
(Figure 5 and 6). Sensing Range
Sensing Area Sensing Area Ferrous Target
B A
Attachment of Conduit or Cable
Steel bar target
1/2” (13mm) x 1” (25mm)
x4” (102mm). Factory
standards ferrous
target used to establish
sensing and reset
distance. (Figure 14).
Sensing Area
A-Sensing
B-Reset
Figure 16 Figure 17
■ Position the switch and target in a position that ensures the target comes
within the switches sensing area. If the switch is mounted on a moving part, be sure that the flexible conduit
Figure 5 Figure 6 is long enough to allow for movement, and positioned to eliminate binding
or pulling. (Figure 16). In damp applications, use a certified cable gland or
a similar moisture barrier to prevent water/condensation from entering the
■ Switch mounted on non-magnetic materials conduit hub. (Figure 17).
Figure 13
Sensing Range Sensing Range
Recommended for the best results
a). Keep all ferrous materials at least 1” from switch. Wiring Information
b). Steel placed outside the switches sensing area will not affect functioning. Sensing range including ferrous target and magnets. Ratings
Target Target
It is not recommended that switches are mounted on ferrous metal, due to Volts 120 240 480
Standard & Latching Extended Sensing (available only for 10)
the reduction in sensing distance. AC
Amps 10 5 2.5
Activate/Deactivate the switch
a). Switch with standard contacts - has sensing area on one side of the Volts 24 48 120
switch (A). To activate, the ferrous or magnetic target must fully enter the DC
sensing area of the switch (Figure 7). To deactivate the target must move
fully outside the sensing area, equal or greater than the reset distance in Amps 3 1 0.5
Table.
Table 3
Sensing Range Sensing Range Sensing Range
Figure 1 Figure 2
10 & 20 Series
GO™ Switch Wiring Diagrams 3 Conductor PVC Cable 3DD - 3 Pin DCA DCD DMD 4 Pin M12 Connector
DMD
SUBSEA 3 Pin Mini 4 Pin Mini 4 Pin M12
Connector Connector Connector Connector External ground must be used
Pin 1 - N/C Pin 1 - COM Pin 1 - COM Pin 1 - COM with 120VAC and voltages greater
Pin 2 - COM Pin 2 - N/C Pin 2 - N/O Pin 2 - N/C then 60VDC when using the DMD
connector
Pin 3 - N/O Pin 3 - N/O Pin 3 - N/C Pin 3 - Not Used
Pin 4 - GND Pin 4 - N/O EU Declaration of Conformity
Form “C” The products described herein,
Typ. Dual Load conform to the provisions of the
Hookup
following Union Directives, including
N/ The GO Switch can be wired as PNP or NPN depending on the desired application the latest amendments:
Loa Low Voltage Directive (2014/35/EU)
4 Conductor PVC Cable & RAYCHEM 4DD - 4 Pin 3DE - 3 Pin DMD 4 Pin M12 Connector DMD 4 Pin M12 Connector EMD Directive (2014/30/EU)
COM AC or DC
SUBSEA SUBSEA ATEX Directive (2014/34/EU).
Loa PNP Wiring NPN Wiring
Connector Right Angle
N/C Safety Integrity Level (SIL)
Pin 1 - COM Connector
Pin 2 - N/O Pin 1 - COM Highest SIL Capability: SIL2 (HFT:0)
Pin 3 - N/C Highest SC Capability: SC3 (HFT:0)
Pin 2 - N/O 1 Year Full Proof Test Interval.
Form “Z” Pin 4 - GND Pin 3 - N/C
Normally Closed II 1 GD
Normally Open
Double Make 0518
2813
Double Break