7UT613 Transformer Differential Protection


vector group 11
Power Transmission and Distribution

xxx
Energy Automation

80MVA, YNd11
2500/1A side 2: 20kV side 1: 110kV
2L1 500/1A
1L1
2L2
1L2
2L3
Itest 1L3

ISP

PTD EA13 NM 7UT6 Stat.tests 06/2007 No.: 2


Power Transmission and Distribution

Isolated  without I0-treatment


Energy Automation

 I 2A    (1  3 ) 1  (1  3 )   I 2 L1 
  1   
 I 2 B     (1  3 )  (1  3 ) 1    I 2L2 
 I 2  3   1  (1  3 )  (1  3 )
  
 C    I 2L3 

PTD EA13 NM 7UT6 Stat.tests 06/2007 No.: 3


Power Transmission and Distribution

I0-correction
Energy Automation

 I2A    (1  3 ) 1  (1  3 )   I2L1  I 
  1     1  Sp 
 I2B     (1  3 )  (1  3 )  1    I2L2   ISp 
 I2  3     3 I 
 C   1  (1  3 )  (1  3 ) I2
  L3   Sp 

PTD EA13 NM 7UT6 Stat.tests 06/2007 No.: 4


Power Transmission and Distribution

I0-Elimination
Energy Automation

 I2A   1 0  1  I2L1 
  1    
 I2B     1 1 0    I2L2 
 I2  3   
 C  0  1 1   I2L3 

PTD EA13 NM 7UT6 Stat.tests 06/2007 No.: 5