User’s Manual
ACS150 Drives (0.37…4 kW, 0.5…5 HP)
15
Type code
The type code contains information on the specifications and configuration of the
drive. You find the type code on the type designation label attached to the drive. The
first digits from the left express the basic configuration, for example ACS150-03E-
08A8-4. The explanations of the type code selections are described below.
ACS150-03E-08A8-4
ACS150 product series
1-phase/3-phase
01 = 1-phase input
03 = 3-phase input
Configuration
E = EMC filter connected, 50 Hz frequency
U = EMC filter disconnected, 60 Hz frequency
Output current rating
In format xxAy, where xx indicates the integer part and y the fractional part,
e.g. 08A8 means 8.8 A.
For more information, see section Ratings on page 109.
Input voltage range
2 = 200…240 VAC
4 = 380…480 VAC
Hardware description
109
Technical data
Ratings
x = E/U A A A A kW HP
1-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
01x-02A4-2 6.1 2.4 3.6 4.2 0.37 0.5 R0
01x-04A7-2 11.4 4.7 7.1 8.2 0.75 1 R1
01x-06A7-2 16.1 6.7 10.1 11.7 1.1 1.5 R1
01x-07A5-2 16.8 7.5 11.3 13.1 1.5 2 R2
01x-09A8-2 21.0 9.8 14.7 17.2 2.2 3 R2
3-phase UN = 200…240 V (200, 208, 220, 230, 240 V)
03x-02A4-2 3.6 2.4 3.6 4.2 0.37 0.5 R0
03x-03A5-2 5.0 3.5 5.3 6.1 0.55 0.75 R0
03x-04A7-2 6.7 4.7 7.1 8.2 0.75 1 R1
03x-06A7-2 9.4 6.7 10.1 11.7 1.1 1.5 R1
03x-07A5-2 9.8 7.5 11.3 13.1 1.5 2 R1
03x-09A8-2 11.8 9.8 14.7 17.2 2.2 3 R2
3-phase UN = 380…480 V (380, 400, 415, 440, 460, 480 V)
03x-01A2-4 2.2 1.2 1.8 2.1 0.37 0.5 R0
03x-01A9-4 3.6 1.9 2.9 3.3 0.55 0.75 R0
03x-02A4-4 4.1 2.4 3.6 4.2 0.75 1 R1
03x-03A3-4 6.0 3.3 5.0 5.8 1.1 1.5 R1
03x-04A1-4 6.9 4.1 6.2 7.2 1.5 2 R1
03x-05A6-4 9.6 5.6 8.4 9.8 2.2 3 R1
03x-07A3-4 11.6 7.3 11.0 12.8 3 3 R1
03x-08A8-4 13.6 8.8 13.2 15.4 4 5 R1
00353783.xls E
Technical data
110
Symbols
Input
I1N continuous rms input current
Output
I2N continuous rms current. 50% overload is allowed for one minute every ten minutes.
I2,1min/10min maximum (50% overload) current allowed for one minute every ten minutes
I2max maximum output current. Available for two seconds at start, otherwise as long as
allowed by the drive temperature.
PN typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
Sizing
The current ratings are the same regardless of the supply voltage within one voltage range. To achieve
the rated motor power given in the table, the rated current of the drive must be higher than or equal to
the rated motor current.
Note 1: The maximum allowed motor shaft power is limited to 1.5 · PN. If the limit is exceeded, motor
torque and current are automatically restricted. The function protects the input bridge of the drive
against overload.
Note 2: The ratings apply at ambient temperature of 40°C (104°F).
Derating
The load capacity decreases if the installation site ambient temperature exceeds 40°C (104°F) or if the
altitude exceeds 1000 metres (3300 ft).
Temperature derating
In the temperature range +40°C…+50°C (+104°F…+122°F), the rated output current is decreased by
1% for every additional 1°C (1.8°F). The output current is calculated by multiplying the current given in
the rating table by the derating factor.
Example If the ambient temperature is 50°C (+122°F), the derating factor is 100% - 1 % · 10°C =
90% or 0.90. The output current is then 0.90 · I . °C
2N
Altitude derating
In altitudes 1000…2000 m (3300…6600 ft) above sea level, the derating is 1% for every 100 m (330 ft).
Switching frequency derating
If the 8 kHz switching frequency (see parameter 2606) is used:
• Derate I2N to 75% for R0 or to 80% for R1…R2, and
• Ensure that parameter 2607 SWITCH FREQ CTRL = 1 (ON), which reduces the switching
frequency if/when the drive’s internal temperature exceeds 110°C. See parameter 2607 for details.
If the 12 kHz switching frequency (see parameter 2606) is used:
• Derate I2N to 50% for R0 or to 65% for R1…R2 and derate ambient temperature to 30°C (86°F), and
• Ensure that parameter 2607 SWITCH FREQ CTRL = 1 (ON), which reduces the switching
frequency if/when the drive’s internal temperature exceeds 100°C. See parameter 2607 for details.
Technical data
111
Technical data
112
Technical data
113
Symbols
IP20 (cabinet) / UL open
H1 height without fastenings and clamping plate
H2 height with fastenings, without clamping plate
H3 height with fastenings and clamping plate
IP20 / NEMA 1
H4 height with fastenings and connection box
H5 height with fastenings, connection box and hood
Technical data
114
Motor connection
Voltage (U2) 0 to U1, 3-phase symmetrical, Umax at the field weakening point
Short-circuit protection The motor output is short-circuit proof by IEC 61800-5-1 and UL 508C.
(IEC 61800-5-1, UL 508C)
Frequency Scalar control: 0…500 Hz
Frequency resolution 0.01 Hz
Current See section Ratings on page 109.
Power limit 1.5 · PN
Field weakening point 10…500 Hz
Switching frequency 4, 8 or 12 kHz
Maximum recommended R0: 30 m (100 ft), R1…R2: 50 m (165 ft)
motor cable length With output chokes the motor cable length may be extended to 60 m (195 ft) for R0 and
100 m (330 ft) for R1…R2.
To comply with the European EMC Directive, use the cable lengths specified in the table
below for 4 kHz switching frequency. The lengths are given for using the drive with the
internal EMC filter or an optional external EMC filter.
4 kHz switching frequency Internal EMC filter Optional external EMC filter
Second environment 30 m (100 ft) To be added
(category C3 1))
First environment - To be added
(category C2 1))
1)
See the new terms in section Compliance with the IEC/EN 61800-3 (2004) on page 119.
Technical data
115
Control connections
Analog input X1A: 2 Voltage signal, unipolar 0 (2)…10 V, Rin > 312 kohm
Current signal, unipolar 0 (4)…20 mA, Rin = 100 ohm
Resolution 0.1%
Accuracy ±1%
Auxiliary voltage X1A: 4 24 VDC ± 10%, max. 200 mA
Digital inputs X1A: 7…11 Voltage 12…24 VDC with internal or external supply
(frequency input X1A: 11) Type PNP and NPN
Frequency input Pulse train 0…16 kHz (X1A: 11 only)
Input impedance 2.4 kohm
Relay output X1B: 12…14 Type NO + NC
Max. switching voltage 250 VAC / 30 VDC
Max. switching current 0.5 A / 30 VDC; 5 A / 230 VAC
Max. continuous current 2 A rms
Efficiency
Approximately 95 to 98% at nominal power level, depending on the drive size and options
Cooling
Method R0: Natural convection cooling. R1…R2: Internal fan, flow direction from bottom to top.
Free space around the drive See chapter Mechanical installation, page 19.
Degrees of protection
IP20 (cabinet installation) / UL open: Standard enclosure. The drive must be installed in a
cabinet to fulfil the requirements for shielding from contact.
IP20 / NEMA 1: Achieved with an option kit including a hood and a connection box.
Technical data