Sprinklers in schools

Copyright Department for Children, Schools and Families


Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Acknowledgments
We are grateful to the following individuals We are also grateful to the following members
and organisations that have contributed to of the Standard Specifications, Layouts and
the production of this guidance: Dimensions (SSLD) Forum who have helped
shape the broad approach to standardisation in
Dr Corinne Williams, co-author,
this and other guidance documents in this series:
BRE Fire and Security
Louise Jackman, co-author, Mukund Patel, DCSF (SSLD Chair)
BRE Fire and Security Alan Jones, DCSF (SSLD Policy Lead)
Richard Daniels, DCSF Beech Williamson, Partnerships for Schools
Chris Bissell, DCSF Paul Foster, EC Harris
Gareth Beal, EC Harris Michal Cohen, Walters and Cohen Architects
Alan Brinson, European Fire Karen Rogers, Walters and Cohen Architects
Sprinkler Network Christian Held, Penoyre and Prasad Architects
Bernard Cain, British Automatic Fire Sunand Prasad, Penoyre and Prasad Architects
Sprinkler Association Linton Ross, Feilden Bradley Clegg Architects
Stewart Kidd, British Automatic Fire Peter Clegg, Feilden Bradley Clegg Architects
Sprinkler Association Paul Hetherington, Alumasc
Jack Fairbrother, Essex County Council Richard Parker, AMEC
Leslie Heaviside, Chairman British Standards Andrew Williams, BRE
Committee FSH/18/2 Sprinklers Bill Healy, Build Offsite
Ian Morris, Atkins Richard Ogden, Build Offsite
Matthew Smith, Zurich Municipal Mike Entwisle, Buro Happold
John Stephens, Fire Protection Association John Tebbit,
Construction Products Association
Michael Ankers,
We are also grateful to Armstrong Priestley Ltd
Construction Products Association
for providing drawings for the design examples
Bea Etayo, Fulcrum Consulting
and to Dave Griffin and Allan Cooper of EC
Peter Blunt, Mtech Group
Harris for their comments on the Costs
Martin Goss, Mtech Group
comment section.
David Mackness, SCAPE System Build Ltd
Martin Lipson, 4Ps
Mairi Johnson, CABE
Richard Saxon CBE
Peter Woolliscroft, OGC
Richard Brindley, RIBA
Vic Ebdon, Devon County Council
Don Bryson, D B Consultancy
Kevin Kendall, Nottinghamshire County Council
--`,`````,,,,`,`,,

Copyright Department for Children, Schools and Families


Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Contents
1 Introduction 2 Special considerations 22
Policy on sprinklers in schools 2
Who is this guidance for? 3
How the guidance should be used 3
Background to Standard Specifications, 4
Layouts and Dimensions (SSLD)
Aims and scope of this guidance 4
Definitions 5

2 Key performance requirements 6


Background 6
School fire hazard scenarios 8
Description of sprinkler systems 8
Cost comment 26

Approvals and certification 10 3 Design examples 28


Example 1 Sprinklers to protect classroom 28
and corridor for property protection
Design, installation and maintenance 11
Example 2 Sprinklers to protect roof space 30
of sprinklers in schools
for property protection
Example 3 Sprinklers to protect sports hall 31
Key elements 12 and storage room for property protection
Consultation and planning 12 Example 4 Single town main water supply 33
Extent of sprinkler protection 13 for property protection
Classification of occupancies and 14 Example 5 Pump and tank water supply 35
fire hazards for property protection
Example 6 Pump and tank water supply 36
for life safety
Water supplies 18
4 References 38

Annex A: Table relating key elements of 42


Sprinkler design characteristics 20 sprinkler system design and installation
and applications to BS EN 12845 Clauses and LPC
Maintenance 21 Technical Bulletins
Special requirements for life safety systems 21

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 1
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Introduction

This guidance is one of a series of Policy on sprinklers in schools


Standard Specifications, Layouts and Following the introduction of a new policy
Dimensions (SSLD) notes produced to on sprinkler systems in March 2007, the
Department for Children, Schools and Families
inform the Building Schools for the (DCSF) now expects the majority of new
Future (BSF) programme. The guidance state-funded schools to be fitted with sprinkler
in this document will also have direct systems. However, the decision should be
application to other state-funded based on a risk analysis of the particular school
concerned. To help clients, local authorities and
school buildings. design teams assess the level of risk and make
the right decisions, DCSF has developed two
new practical aids: a simple fire risk assessment
tool to assess the need for sprinklers in the
proposed school building; and a spreadsheet-
based cost benefit analysis tool to help users
decide whether sprinklers represent good value
for money1,2.

This document should be read in conjunction


with DCSF's Building Bulletin 100 Design for fire
safety in schools (BB 100)3. BB 100 shows how
the requirements for life safety contained in
the Building Regulations can be met in the
design of a new or refurbished school. As well
as covering life safety, BB 100 emphasises the
importance of protecting school buildings from

1 DCSF, Risk assessment tool for fire precautions in schools, available on www.teachernet.gov.uk/fire
2 DCSF, Cost-benefit analysis for fire precautions in schools, available on www.teachernet.gov.uk/fire
3 DCSF, BB 100 Building Bulletin 100 Design for fire safety in schools, available on www.teachernet.gov.uk/fire

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
2
Copyright
Standard specifications, layouts and dimensions
Department for Children, Schools and Families
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
fire damage. It includes guidance on sprinklers, School building clients, their professional
stressing their importance as a measure that advisers, contractors and their supply chains
can limit fire damage. should use this guidance to inform their
decisions on sprinkler systems.
Who is this guidance for? To help encourage the take up of these
• Teachers and governors acting as clients for performance specifications, this guidance will
school capital projects. become the standard in BSF programme
• Local authority officers responsible for documentation and the Government will
procuring school capital projects. expect it to be adopted in the majority of
situations where it is reasonable and
• Diocesan building officers.
appropriate to do so.
• Local authority and private sector school
designers and specifiers. While we would expect projects to comply with
the standards, other solutions – possibly based
• Building control officers (or equivalent) and
on new products or technologies, or reflecting
fire safety officers.
local factors – may equally comply with the
• Manufacturers and suppliers. performance specification and could be used.
• Contractors. We do not want to stifle innovation by being
too prescriptive.
How the guidance should be used It will be for users to exercise their own skill and
This guidance sets out the standards of expertise in deciding whether a standard or
performance for sprinkler systems for schools example shown in this document is reasonable
and shows through some examples how they and appropriate for their own circumstances.
might be delivered. It is one of a number of This guidance does not affect obligations and
publications on various building elements liabilities under the law relating to construction
within the SSLD series. The aim is to and building.
disseminate best practice and avoid
Though principally aimed at secondary school
‘reinventing the wheel’ every time a school
building projects delivered through the BSF
building is designed, so that consistently high
programme, the specifications and examples
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

quality environments can be delivered, offering


also apply to other educational buildings, for
best whole-life value for money.
example, primary schools.

Copyright Department for Children, Schools and Families


Sprinklers in schools 3
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Background to Standard Aims and scope of this guidance
Specifications, Layouts and This document provides standard performance
Dimensions (SSLD) specifications for sprinkler systems in schools
The BSF programme offers a unique opportunity and some design examples.
over the next 10-15 years to transform our
It is structured as follows:
secondary schools, providing innovative learning
environments that will inspire pupils to achieve Section 2: The performance requirements for
more. High quality, modern school buildings sprinkler systems in schools.
will help to raise standards and play a crucial
part in the Government’s programme of Section 3: Design examples for school sprinkler
educational reform. systems.

With the huge increases in funding associated Section 4: References to relevant DCSF,
with this programme, there is considerable sprinkler standards and other design guidance.
scope for using standardised specifications, This specification is concerned with sprinklers
layouts and dimensions to speed up design for property protection and/or life safety
and construction, reduce whole-life costs and purposes to meet any recommendations in
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

deliver consistently high quality and better BB 100 intended to satisfy the requirements
value school buildings. Standardisation will of the Building Regulations.
support the use of more off-site fabrication
and modern methods of construction, which Sprinkler systems can be property protection
should help to improve health and safety systems or life safety systems or both. The
performance, reduce waste and deliver more designer should decide which purpose they
sustainable solutions. For the supply industry, serve and specify this at an early stage in the
being involved in standardisation will help to project development. The purpose should be
demonstrate market leadership – and help clarified at the earliest stage with the relevant
firms reduce risk and increase sales, profitability, authorities having jurisdiction.
and market size.
At present, most schools require property
The examples in this document and the others protection sprinkler systems, which are used
in the SSLD series have been developed based to meet insurers’ requirements. More than
on extensive consultation under the auspices of 100 years of experience with property
the SSLD Forum. Set up by the Department for protection sprinkler systems have shown that
Children, Schools and Families (DCSF), this they protect life as well as property. However,
forum represents key stakeholders in the in recent years it has been felt beneficial to
building design, research, contracting, and require an increased provision of assurance
supply industry communities, as well as local for life safety in achieving continuity of
authority construction client bodies. In addition, performance, largely in connection with water
a specialist Steering Group has been involved supplies, valves and the extent of available
with this sprinkler specification. protection in certain circumstances.

4
Copyright
Standard specifications, layouts and dimensions
Department for Children, Schools and Families
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Life safety systems have additional features, Distribution pipe: a pipe feeding either a range
intended to increase the reliability of the system pipe directly or a single sprinkler on a non
and its ongoing availability, and are used to terminal range pipe more than 0.3 m long.
meet Building Regulations’ requirements or to
k factor: the sprinkler orifice coefficient.
meet requirements of the Regulatory Reform
(Fire Safety) Order 2005. Range pipe: a pipe feeding sprinklers directly or
via arm pipes.
Where sprinkler systems are selected as a
compensatory feature to other fire protection School: a place of education for children older
systems in BB 100, life safety sprinkler systems than 2 and younger than 19 years. Includes
should be used. nursery schools, primary schools and secondary
schools as defined in the Education Act 1996.
Definitions
For the purposes of this guidance, the
following applies:

Area of operation: the maximum area over


which it is assumed for design purposes that
sprinklers will operate in a fire.

Arm pipe: a pipe less than 0.3 m long, other

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
than a last section of a range pipe, feeding a
single sprinkler.

Authorities having jurisdiction: the


organisations responsible for approving
sprinkler systems, equipment and procedures,
e.g. the fire and building control bodies,
the fire insurers, the local water authority
or other appropriate public authorities.

Cavity barrier: for property protection purposes,


a separating element which resists the passage
of flame, smoke and/or heat for a period of
30 minutes.

Design density: the minimum density of


discharge, in mm per minute of water, for which
a sprinkler installation is designed, determined
from the discharge of a specified group of
sprinklers, in litres per minute, divided by the
area covered, in m2.

Copyright Department for Children, Schools and Families


Sprinklers in schools 5
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
Key performance requirements

UK fire statistics4 show that fire deaths Background


in schools are rare. From 1994 to 2002, Currently, the main problem with fires in
only one person died in approximately schools is property losses, which are large and
rising. An analysis of large fires (involving a
14,700 reported fires in schools. These fatality and/or a loss greater than £100,000)5
statistics also show that the number of found that the total estimated fire damage
injuries in school fires is small. Note reported by insurers was £46.9 million for 24
that ‘injuries’ in these fire statistics school fires in 2004. This is the direct loss of
insurance claims; the true cost is higher than
includes precautionary checks. From this as there will be associated losses that are
1994 to 2002, 461 people were injured, hard to quantify, such as loss of education,
an average of 51 per year. In 2002, loss of facilities, loss for the community.
there were 46 injuries, of which 19 See Cost comment, page 26.

were people referred to hospital for To put the above into a context, schools have
precautionary checks. These statistics the greatest financial fire losses compared with
other building occupancies5. In 2003 and 2004,
indicate that the risk of injury or death
educational fire losses were twice those of the
from fires in schools is very low but the next highest occupancy type, which is retail.
risk can never be eliminated. In 2004, educational fire losses were 60 times
those of office fires, the occupancy often
referred to for benchmarking.

4 UK Fire Statistics, 1994-2002.


5 A Lewis, FPA Large Loss Analysis 2004, Fire Engineers Journal and Fire Prevention, February 2007.

6
Copyright
Standard specifications, layouts and dimensions
Department for Children, Schools and Families
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Automatic fire sprinkler systems are a well Consideration of the costs of a sprinkler system
established technology and have demonstrated in a cost benefit analysis does not simply include
their effectiveness in protecting life and the costs of installation and provision of water
property in industrial and commercial supplies, but also includes the costs of inspection,
applications over many years. In the UK testing and ongoing system maintenance.
currently, sprinklers are increasingly being
The benefits of sprinklers in a cost benefit
considered and installed in school buildings.
analysis include:
Sprinklers can be installed in schools for a
• reduced insurance premium;
number of reasons, including:
and in the event of a fire:
• property/asset protection to follow DCSF
• reduced risk of deaths and injuries;
policy guidelines;
• reduced property damage;
• property/asset protection to meet
insurers’ requirements; • reduced environmental impact;
• property/asset protection to preserve the • preservation of education and other facilities
continuity of education and facilities for to the community; and
the community; • reduced fire brigade costs.
• life safety recommendations intended to
If a sprinkler system is being proposed as an
meet the Building Regulations;
alternative solution, there may also be indirect
• life safety, as an alternative solution to satisfy cost reductions due to building design changes.
recommendations intended to meet the See Sprinklers as a compensatory feature, page
Building Regulations; and 25 and Cost comment, page 26.
• life safety, additional to the Building Regulations.

Automatic sprinkler systems are part of the


overall package of fire safety measures in a
school and should not be considered in
isolation. For example, there would generally
be a fire detection and alarm system installed
and passive fire protection measures in place.
A complex school building may also have a
smoke and heat exhaust ventilation system.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 7
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
School fire hazard scenarios Description of sprinkler systems
Examples of school fire hazard scenarios are: A typical school sprinkler system consists of a
water supply, valves, an alarm and an array of
• Accidental electrical fire due to faulty electrical
pipework (distribution and range pipes) fitted
equipment placed close to furniture, fabrics or
with individual sprinkler heads. The sprinkler
papers in a classroom, causing a fire which
heads are fitted at specific locations, normally
then spreads.
at ceiling level and in concealed spaces.
• Deliberate ignition of school bags or notice The pipework is normally permanently filled
boards and papers in a corridor, causing a fire with water and if the sprinkler system is for life
which then spreads. safety purposes, it should be permanently
• External deliberate fire close to the exterior of charged with water.
a school building, spreading into the school. The main purpose of an automatic fire sprinkler
Examples of fire sources are wheelie bin system is to provide water to suppress and
rubbish, pallets, a vehicle, or vegetation. control and, in some cases, extinguish a fire.
Note: fires external to the school are not a
design scenario for a sprinkler system, see There are three stages to consider with sprinkler
External fires, page 22. system performance in a fire:
• Accidental ignition of waste paper by an illicit • Detection of the fire.
smoker’s smoking materials in
• Operation of the system and raising the alarm.
washroom/toilet areas, causing a fire which
then spreads. • Fire suppression and control.

• Accidental electrical overload causing ignition


of combustibles in ceiling void or roof space,
resulting in a fire which then spreads.
• Accidental fire involving a naked flame inside
a laboratory.

FLOAT/BALL SUPPLY PIPE FROM TOWN


VALVE ASSEMBLY MAIN TO SUCTION TANK

RANGES

SPRINKLER
HEADS
SUCTION TANK
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

RISER
SPRINKLER PUMP
INSTALLATION DISTRIBUTION MAIN
ALARM VALVE
ASSEMBLY
PUMP SUCTION PIPE
AND VALVE

TRUNK MAIN

Schematic showing main elements of a sprinkler system

8
Copyright
Standard specifications, layouts and dimensions
Department for Children, Schools and Families
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Detection of the fire Fire suppression and control
The sprinkler system detects the fire if there The sprinkler water spray should reduce the
is a fire in the vicinity of a sprinkler head. intensity and size of the fire and suppress and
Each sprinkler head has a heat sensitive device control it. In some cases, the fire may be
holding a sprinkler sealing assembly closed extinguished. The characteristics of the water
against the installation water pressure. The heat spray, combined with the sprinkler positioning
sensitive device is a fluid-filled glass bulb or a and spacing, have been proved to suppress
fusible link. This heat sensitive device will fires. The water spray inside a room will directly
operate at a predetermined temperature when be involved in suppressing and controlling the
heated by the fire gases. The thermal response fire, will wet surrounding combustible materials
characteristics of the sprinkler head will so they do not ignite, will wet surfaces to cool
determine when and under what conditions the building structure, will cool the smoky gases
the sprinkler will operate. These characteristics and reduce the likelihood of flashover.
are the sprinkler thermal response rating and
The sprinkler spray characteristics are created by
nominal operating temperature. Sprinkler
the design of the sprinkler head (the shape of
thermal response can be classified as quick,
the frame and deflector plate), the water flow
special, standard response A and standard
rate, the bore size and the location of the head
response B6.
relative to the ceiling and other structures.
Operation of the system and raising the alarm A number of suppliers provide sprinkler head
products, each with their own range of models.
Sprinklers operate by the release of a sprinkler
sealing assembly when the glass bulb shatters
due to the expansion of the liquid or when
the solder link has melted. Then a water flow
A) BEFORE SPRINKLER OPERATION
is released and a spray is discharged onto
the fire. The flow of water initiates an alarm.
The number of sprinklers that operate in a fire
will depend on a variety of factors, such as
where the fire occurs, the nature of the burning B) AFTER SPRINKLER OPERATION

materials and the severity of the fire. School


sprinkler systems are designed so that only
sprinkler heads in the vicinity of the fire are
intended to operate. Schematic showing sprinkler head operating to control
the fire

6 British Standards Institution, BS EN 12259-1 Fixed firefighting systems, components for sprinkler and water spray systems Part 1
Sprinklers, 1999.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 9
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Approvals and certification Under this scheme, a third party Certificate of
Conformity is issued by the sprinkler contractor
Sprinkler installers for each system installed. This certificate states
It is important that sprinkler systems for schools that the sprinkler system complies with all the
are designed, installed and maintained by appropriate requirements of BS EN 12845 and,

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
specialist sprinkler contractors who are suitably where applicable, lists details of any accepted
qualified and experienced to ensure the minor departures. Major non compliances are
effective performance of the system in the not permitted.
event of a fire and to satisfy insurers and/or
approving bodies. The other is operated by Warrington
Certification Limited and comes under the
Third party accreditation of installers of sprinkler FIRAS certification scheme8.
systems provides a means of ensuring that
installations have been conducted by Sprinkler products
knowledgeable contractors to appropriate Components of sprinkler systems should be
standards, thereby increasing the reliability of suitable for use to ensure the effective
the anticipated performance in fire. performance of the system in the event of a fire
Insurers usually require independent schemes and to satisfy insurers and/or approving bodies.
of certification or accreditation of installers of Third party accredited sprinkler product
automatic sprinkler systems for the purposes conformity certification schemes not only
of property protection. provide a means of identifying sprinkler
Building control bodies may accept the products which have demonstrated that they
certification of the installation or maintenance of have the requisite performance in fire, but
sprinkler systems as evidence of compliance with additionally provide confidence that the
the relevant standard. Nonetheless, a building products actually supplied are provided to the
control body will wish to establish, in advance same specification as that tested/assessed.
of the work, that any such scheme is adequate Insurers usually require sprinkler products which
for the purposes of the Building Regulations. are approved and listed to a recognised and
In the UK, there are two third party certification appropriate third party certification scheme
schemes for sprinkler installers that are and comply with appropriate British/European
applicable to school buildings. standards, where available, for the purposes
of property protection.
One is operated by the Loss Prevention
Certification Board (LPCB) and known as the LPS Building control bodies may accept the
1048 scheme. Certificated installers are listed in certification of sprinkler products as evidence
the LPCB List of Approved Fire and Security of compliance with the relevant British/
Products and Services, known as the Red Book7. European standards, where available.

7 The Loss Prevention Certification Board, List of Approved Fire and Security Products and Services, Red Book, BRE Global, available on
www.redbooklive.com
8 FIRAS Scheme for Installers of Commercial and Industrial Sprinkler Systems, Warrington Certification Limited, available on
www.firas-register.co.uk

Standard specifications, layouts and dimensions


10 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Nonetheless, a building control body will wish amplify the requirements of the standard or
to establish, in advance of the work, that any cover additional requirements for insurers.
such scheme is adequate for the purposes of BS EN 12845 in conjunction with Technical
the Building Regulations. Bulletin TB 221, Sprinkler protection of
schools12 and other relevant Technical
In the UK, the Loss Prevention Certification
Bulletins contain insurers’ requirements for
Board (LPCB) operates various certification
sprinkler protection of schools.
schemes for sprinkler products. Certificated
sprinkler products are listed in the LPCB List Note: British Standard BS 5306 Part 2:
of Approved Fire and Security Products and Specification for sprinkler systems13 became
Services, (the ‘Red Book’9). obsolescent in August 2007.

Where a sprinkler system is required to meet


Design, installation and maintenance any recommendations in BB 100, it should be
of sprinklers in schools designed and installed in accordance with either:
Standards for sprinkler systems • for property protection, the recommendations
Sprinkler systems should be designed, installed of LPC Sprinkler Rules, principally BS EN 12845
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

and maintained to a recognised standard to and all applicable Technical Bulletins, with
ensure the effective performance of the system particular reference to TB 221; or
in the event of a fire and to satisfy insurers
• for life safety, the recommendations of
and/or approving authorities.
BS EN 12845, including the relevant hazard
In the UK, the recognised principal standards classification, together with the special
that are relevant to the design, installation and requirements for life safety systems in Annex F
maintenance of sprinklers in schools are: of BS EN 12845 and water supply
requirements in Approved Document B14.
• British/European Standard BS EN 12845:
Fixed firefighting systems – automatic Standards for sprinkler components
sprinkler systems – Design, installation
British/European standard BS EN 1225915 is a
and maintenance10.
series of companion standards to BS EN 12845
• The LPC Sprinkler Rules, BS EN 12845 version11 and covers requirements for components of
– these Rules are for property protection sprinkler systems.
purposes and contain the text of BS EN 12845
and a series of Technical Bulletins, which

9 The Loss Prevention Certification Board, List of Approved Fire and Security Products and Services, Red Book, BRE Global, available
on www.redbooklive.com
10 British Standards Institution, BS EN 12845, Fixed Firefighting systems – Automatic sprinkler systems – Design Installation and
maintenance, 2004.
11 LPC rules for automatic sprinkler installations incorporating BS EN 12845, The Fire Protection Association.
12 Technical Bulletin TB 221: 2005: 1 Sprinkler protection of schools, The Fire Protection Association, 2005.
13 British Standards Institution, BS 5306 Part 2: Specification for sprinkler systems, 1990 (obsolescent).
14 Communities and Local Government, The Building Regulations 2000, Approved Document B, Fire Safety, volume 2 – buildings other
than dwellinghouses, 2006 edition, available on www.planningportal.gov.uk
15 British Standards Institution, BS EN 12259 (various parts), Fixed firefighting systems, components for sprinkler and water spray systems.

Copyright Department for Children, Schools and Families


Sprinklers in schools 11
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Key elements Annex A contains a table relating these key
Fire protection and sprinklers need to be elements to the clause number in BS EN 12845,
considered at an early stage of the design Technical Bulletins, Recommendations, Briefing
process so that the impact of different design Notes and Guidance documents.
choices on the design of fire protection/sprinkler A full specification that covers all these aspects
systems can be considered. of design, installation and maintenance cannot
The key elements that need to be considered be reproduced in this specification – the
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

for the design, installation and maintenance relevant standards and companion documents
of school sprinklers are: will need to be consulted. Instead, attention is
drawn to selected key elements and where
• Documentation. these can be found in the standards and/or
• Extent of sprinkler protection (including companion documents, as follows.
permitted exceptions).
• Classification of occupancies and fire hazards Consultation and planning
(including protection of special hazards). Where a sprinkler system is being considered
• Hydraulic design criteria (including design for a school, the following relevant authorities
density and area of operation). should be consulted at an early stage:

• Water supplies and type (including type of • The water supply company.
water supply). • The fire authority.
• Pumps. • The building control body.
• Installation type and size. • The insurer(s) of the school building and
• Spacing and location of sprinklers. school building contents.
• Pipe sizing and layout. Other parties who also need to be involved
when considering a sprinkler system for a
• Sprinkler design characteristics and uses.
school include:
• Valves.
• School building clients.
• Alarms and alarm devices.
• Local authority officers responsible for
• Pipework.
procuring school capital projects.
• Signs, notices and information.
• Local authority and private sector school
• Commissioning and acceptance tests and designers and specifiers.
periodic inspection (the importance of).
• Specialist sprinkler contractors who design
• Maintenance (regular). and install the sprinkler system.
• Special requirements for property protection.
• Special requirements for life safety systems.

Standard specifications, layouts and dimensions


12 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Details that influence the design and cost of the • selected concealed spaces, see Void sprinkler
sprinkler system and that need to be provided protection, page 22;
by the specifier to the sprinkler contractor at an • rooms protected by other automatic
early stage include the following: extinguishing systems (designed, installed
• Timeframe for the project. and maintained to recognised
British/European standards);
• Details of the school building:
• rooms containing electric power distribution
- number of storeys;
apparatus such as switchgear and transformers;
- dimensions of rooms, corridors and Note: If sprinkler protection is omitted, then
other spaces; the walls, ceiling and floors should have at
- dimensions and details of concealed spaces: least 120 minutes of fire resistance or an
ceiling and floor voids; and roof spaces; alternative fire suppression system.

- details of fire-resisting elements • rooms containing industrial/laboratory


of construction; and processes where water discharge might
present a hazard;
- details of ceiling penetrations/obstructions;
• communicating buildings or storeys separated
• Purpose of system (whether life safety and/or
from the sprinklered building by walls of
property protection).
appropriate fire resistance. See BB 100
• Details of hazards and risks to be protected Appendix A, TB 206 and TB 221; and
and any future changes.
• outbuildings separated from the sprinklered
• Details of sprinkler standard(s) to be used. building by at least 10 m, such as sheds.
• Provision and route of water supply.
Ideally, outbuildings that are school buildings
• Route of electrical supply. should be sprinkler protected.
• Any requirements for sprinkler head type(s), All exceptions to sprinkler protection should be
finishes and metal guards, flexible connectors. agreed with the insurer and other authorities
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

having jurisdiction.
Extent of sprinkler protection
Sprinkler protection should be provided The exact details of the permitted exceptions
throughout the building, so that if a fire starts at are given in BS EN 12845 and TB 221.
any location in the building it is suppressed and
controlled and/or extinguished quickly and
efficiently, preventing fire spread to other parts of
the building. Optional permitted exceptions are:

• enclosed staircases and enclosed


vertical shafts (i.e. which cannot contain
combustible materials);

Copyright Department for Children, Schools and Families


Sprinklers in schools 13
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Classification of occupancies and In BS EN 12845 section 6.2 and Annex A, schools
fire hazards are classified as:
Sprinkler systems are designed to provide • LH: for schools with low fire loads and low
an appropriate level of protection for the combustibility and with no single compartment
occupancy and the hazard. In BS EN 12845, greater than 126 m2 with a fire resistance of at
occupancies are classified in hazard groups, least 30 minutes.
‘Light’ (LH), ‘Ordinary’ (OH) and ‘High’ (HH).
• OH1: for schools with combustible materials
OH and HH are subdivided into groups. For
and a medium fire load and medium
example, OH is divided into OH1, OH2, OH3
combustibility.
and OH4. The hazard classification takes into
account the properties, dimensions, Technical Bulletin TB 221 states that schools
arrangements, quantities and locations of should be classified as at least OH1 and not LH.
combustible materials that are likely to be
found in schools and the expected rate of For sprinklers for property protection and life
growth of the fire in the early stages. safety purposes, schools should be classified as
at least OH1.
A fire hazard review should be carried out a)
to identify all the fire hazards that could be The fire hazard review will determine whether
present in the school, including any special a higher hazard category should be applied.
hazards and b) to determine the appropriate The fire hazard review will also determine
hazard classification of the school for the whether there are any special hazards that need
sprinkler design. separate consideration.
The sprinkler fire hazard classification is the For OH1 systems, it is generally assumed that
responsibility of the specifier for the a fire will be controlled by six sprinkler heads
development of the sprinkler system tender or less. The standard specification for OH1 is:
documentation. This classification should be
carried out by a suitably qualified person. • Area per sprinkler = 12 m2 maximum.
• Area of operation = 72 m2 maximum.
The sprinkler fire hazard classification should be
confirmed with the relevant authorities having • Design density = 5 mm/min minimum,
jurisdiction at the earliest stage, for example, to i.e. 5 litres per m2 per minute over a specific
meet insurers’ requirements. proportion of the area of operation.

Hazard classifications higher than OH1 may be


required if the area of operation (and therefore
a water supply limited to six sprinkler heads)
could be exceeded.

The minimum requirements for design density


and areas of operation for LH, OH1, OH2, OH3
and OH4 for wet systems are shown in the
following table.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
Standard specifications, layouts and dimensions
14 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Hazard class Design density* (mm/min) Area of operation (m2)

LH 2.25 84

OH1 5 72

OH2 5 144

OH3 5 216

OH4 5 360
*for a specific proportion of the area of operation

For tall and large spaces, there may be fire Method of determining correct hazard
scenarios where more than six sprinkler heads classification
could operate, because:
The hazard classification can be determined
• the increased height introduces a time delay using the following steps:
for sprinkler operation (and hence larger fires
1. For each room in a school building:
can develop);
• the increased height reduces the efficiency of • use the table overleaf to identify the room
the water delivery; and type (and size where applicable); and
• large plan areas increase the number of • use the table overleaf to determine the
sprinklers that will be exposed to the fire gases appropriate hazard classification for that
(and potentially more sprinklers could operate). room and tick the appropriate cell.
For spaces with multiple uses, events such as Where a room type could have a range of
clothes sales and theatre productions can possible hazard groups, the hazard group should
introduce a large quantity of combustibles and be determined by a suitably qualified person.
have the potential for large fires.
2. Once the hazard classifications for all the
rooms in the school building have been
determined, find the overall appropriate hazard
classification for the building (which will be the
highest hazard reached for any of the rooms),
i.e. the column that the furthermost right hand
tick is in.
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

3. Repeat this for all the school buildings.

Copyright Department for Children, Schools and Families


Sprinklers in schools 15
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Rooms Hazard Group Notes

O O O O
H H H H
1 2 3 4
Classrooms and OH1
seminar rooms

Basic teaching OH1 when the fire load is typical of a basic teaching room.
rooms for: ICT,
OH2 should be considered for rooms that are > 72 m2 and < 144 m2 and
general teaching, contain fire loads comparable to commercial laboratories, photographic
practical work, film rooms, broadcasting studios, museum, cinema, theatre, concert hall
design and or department stores.
technology, art,
music, drama
Learning OH1
resources areas

Libraries OH1 when the fire load and book/shelf layout are typical of a library.

OH2 should be considered for libraries that are > 72 m2 and < 144 m2
and contain a fire load and book/shelf layout comparable to a
book store.

OH3 should be considered for libraries that are > 144 m2 and contain a
fire load and book/shelf layout comparable to a book store.

Halls: main, OH1 when:


sports, activity
• the storage of combustible equipment, e.g. foam mats, is in a separate
studio dedicated store room; and

• in halls of multiple use, additional fire protection measures may be


required to address the property protection and life safety fire hazards
presented by particular events such as sales, which can introduce a
large quantity of combustibles and have the potential for large fires.

OH2 should be considered for halls of multiple use, that are > 72 m2 and
< 144 m2 containing fire loads similar to those found in a cinema, theatre,
concert hall, department store, commercial book store, museum.

OH3 should be considered for halls of multiple use that are > 144 m2 and
< 216 m2 containing fire loads similar to those found in a cinema, theatre,
concert hall, department store, commercial book store.

OH4 should be considered for halls of multiple use that are > 216 m2
containing fire loads comparable to a cinema, theatre or concert hall.

Theatre OH1 when the fire load is typical of other areas of the school and the
stage is small.

OH4 should be considered for theatres that have stages where there is
a safety curtain between the stage and auditorium – see BS EN 12845
Annex F.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


16 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Staff and OH1
administration
rooms
Storage Storage hazard classification needs to be in accordance with BS EN
(teaching and 12845, which accounts for height, material, and shelving. In addition:
non-teaching) OH1 when the room size is less than 72 m2.

OH2 should be considered for store rooms that are > 72 m2 and < 144 m2.

OH3 should be considered for store rooms that are > 144 m2 and < 216 m2.

OH4 should be considered for store rooms that are > 216 m2.

Dining and social OH1


areas

Kitchens (and OH1


stores)

Toilets (and OH1 when they can be used to store combustible materials.
personal care)
These may be optional permitted exceptions – see Extent of sprinkler
protection, page 13.

Circulation and OH1


corridors

Stair enclosure OH1 when they can be used to store combustible materials.

These may be optional permitted exceptions – see Extent of sprinkler


protection, page 13.

Cloakroom OH1

Plant rooms OH1 when the room size is < 72 m2.

OH2 should be considered for plant rooms that are > 72 m2 and < 144 m2.

OH3 should be considered for plant rooms that are > 144 m2.

Chemical store OH1 when the room size is < 72 m2.

OH2 should be considered for chemical stores that are > 72 m2.
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

and < 144 m2.

OH3 should be considered for chemical stores that are > 144 m2.

Swimming pool OH1 when it cannot be used as a dual purpose space.

For swimming pools that can be used as a dual purpose space, e.g.
covering the pool and using the space for another use, the hazard group
will be that of the relevant room type.

Sleeping OH1
accommodation

Copyright Department for Children, Schools and Families


Sprinklers in schools 17
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Water supplies • Single automatic suction pump drawing from
Sprinkler system water supplies should be a water source, i.e. pump suction tank, gravity
reliable and provide sufficient flow and pressure tank or reservoir, complying with BS EN 12845
to satisfy the system design requirements. clause 9.3.
• Single automatic booster pump, drawing
At the earliest stage, prior to selection of the
water from a town main complying with
water supply, the town main at the site should be
BS EN 12845 clause 9.2.2.
performance tested to determine its pressure and
flow characteristics and the minimum available • Technical Bulletin TB 221 introduces the
pressure. This could occur at peak demand or at additional option of using a reduced water
night when pressure levels are reduced. supply duration for OH1 sprinkler systems,
i.e. 30 minutes reduced from 60 minutes.
The results of the performance test will These sprinkler systems require automatic
determine whether the town main can be used transmission of fire and fault alarms to a
as a water supply for the sprinkler system. central station for alarm signalling, approved
If the town main is used as a water supply, by LPCB or equivalent and assumes fire
regular maintenance will include further brigade attendance times being appropriate
performance tests to check the pressure to the level of risk. This option can result in
and flow characteristics and the minimum reduced: tank size, tank housing size and
available pressure. groundworks for the tank. Where the hazard
exceeds OH1, this option should not be used.
The sprinkler system should fully comply with
A fire brigade inlet should be provided for all
the Water Regulations and permission for a
stored water applications.
water supply connection to the sprinkler system
should be sought from the relevant water Hydrant water supplies are for fire brigade use
supply company. and need manual intervention. Sprinkler systems
need to be automatic and self contained.
A number of types of water supplies can be
used for school sprinkler systems. Sprinkler system water supplies should be
separate from hydrant supplies, hose reels
Water supplies for property protection and risers.
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Water supplies for sprinklers for property


For further information on pumps, see BS EN
protection are detailed in BS EN 12845, TB 221
12845 clause 10 and TB 21017. For power
and TB 22416. These should be:
supplies for sprinkler pumps, see TB 22018
• Single town main complying with BS EN and TB 210.
12845 clause 9.2.1.

16 Technical Bulletin TB 224: 2005: 1 Sprinkler water storage tanks (cisterns), The Fire Protection Association, 2005.
17 Technical Bulletin TB 210: 2007: 1 Automatic sprinkler pump installation, The Fire Protection Association, 2007.
18 Technical Bulletin TB 220: 2004: 1 Power supplies for sprinkler pumps, The Fire Protection Association, 2004, until September 2008.

Standard specifications, layouts and dimensions


18 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
- gravity or suction tanks should satisfy all
the requirements of BS EN 12845 clause
9.6.2 b) other than capacity; and
- any pump arrangements should comply
with BS EN 12845 clause 10.2; and
- the capacity of each tank is equivalent to
half the specified minimum water volume
of a single full capacity tank, appropriate
to the hazard; or
Photograph showing external tank and pump house - one tank should be at least equivalent to
half the specified water volume of a single
full capacity tank and the other should not
be less than the minimum volume of a
reduced capacity tank BS EN 12845 clause
9.3.4, appropriate to the hazard; and
Note 1: The requirement for inflow should
be met.
Note 2: Where two half capacity tanks are
being used, as stated in third and fourth
dashed bullet point above, it is normally
accepted practice for the two ‘half tanks’ to
be formed as two sections of a single tank.
Photograph showing the electric pump and valve set
inside the pump house The relevant authorities having jurisdiction
should be consulted for agreement.
Water supplies for life safety - whichever water storage arrangement is
For systems designed and installed to BS EN used at third and fourth dashed bullet point
12845, water supplies for sprinkler systems above, the total capacity of the water
for life safety for non-residential applications, supply, including any inflow for a reduced
including schools, are detailed in Approved capacity tank, should be at least equivalent
Document B Volume 2, section 018 b)19. to a single full holding capacity tank
These should consist of either: complying with BS EN 12845, Table 9,
Table 10 or clause 9.3.2.3, as appropriate,
• two single water supplies complying with to the hazard and pipework design.
BS EN 12845, clause 9.6.1, where each is
Where pumps are used to draw water from two
independent of the other; or
tanks, then each pump should be arranged to
• two stored water supplies, where: draw water from either tank and arranged so that
any one pump or either tank could be isolated.

19 Communities and Local Government, The Building Regulations 2000, Approved Document B, Fire Safety, volume 2 – buildings
other than dwellinghouses, 2006 edition, available on www.planningportal.gov.uk

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 19
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
The sprinkler water supplies should generally Sprinkler design characteristics
not be used as connections for other services and applications
or other fixed firefighting systems. Sprinklers should detect the fire and operate at
Duplicate pumps can be one electric pump an early stage.
using mains power from a public electricity Thermal sensitivities of sprinklers used in
supply and one diesel pump. Two electric schools for property protection should be
pumps can be used provided their power ‘quick’, ‘special’ or ‘standard’. Unrated sprinkler
supplies are independent of each other, for heads, such as concealed and recessed, can
example, one using mains power and the other be used if they have a ‘quick’ temperature
using power from an onsite diesel generator. sensitive element. See BS EN 12845, BS EN
For further information on pumps, see BS EN 12259-120 and TB 20721.
12845 clause 10, TB 210 and TB 220. Thermal sensitivities of sprinklers for life safety
should be ‘quick’ response, except for rooms
Sprinkler system type
less than 500 m2 and less than 5 m high, where
For property protection and life safety, sprinkler standard ‘A’ and special response can be used.
systems should be of the wet pipe type, i.e. a Concealed and recessed sprinklers should not
system in which the pipework is always charged be used for life safety applications as they are
with water, provided the system is adequately currently thermal sensitivity unrated.
protected from freezing. See Frost protection,
page 24. Sprinkler patterns can be selected for design
characteristics that produce water sprays that
will be suitable for different applications.
A) PENDENT, QUICK A) PENDENT, CONCEALED
RESPONSE, 68°C, SPRAY SPRINKLER BS EN 12845 and TB 221 detail the selection of
SPRINKLER
sprinkler head types covered by EN 12259-1 or
BS DD 25222 suitable for different applications in
the school building.

The types of sprinkler patterns should be used


for different applications, as follows:

• Spray, ceiling or flush pattern sprinklers


with a k factor of 80 can be used for general
Photographs showing different sprinkler heads room protection.
• Spray pattern sprinklers with a k factor of
80 can also be used for protection of floor,
ceiling or roof spaces > 2.4 m high.

20 British Standards Institution, BS EN 12259-1 Fixed firefighting systems, components for sprinkler and water spray systems Part 1
Sprinklers, 1999.
21 Technical Bulletin TB 207: 2005: 1 The selection of sprinkler heads, The Fire Protection Association, 2005.
22 British Standards Institution, BS DD 252, Draft for Development Components for residential sprinkler systems – specification and
test methods for residential sprinklers, 2002 (under revision).

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


20 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
• Ceiling or flush pattern sprinklers with a k • Where it is considered essential to conceal the
factor of 80 are not suitable for the protection presence of sprinklers from school occupants,
of floor, ceiling or roof spaces. concealed pattern sprinklers with a k factor of
• Sidewall pattern sprinklers with a k factor of 80 can be used for general room protection.
80 can be used in corridors, passageways or • Concealed and recessed pattern sprinklers
narrow rooms. should not be used for the protection of floor,
• Conventional pattern sprinklers can be used ceiling or roof spaces.
to protect floor, ceiling or roof spaces not
exceeding 2.4 m in height. Maintenance
• Residential sprinklers described in BS DD 252 A sprinkler system should be regularly serviced,
can be used in small rooms not requiring maintained and periodically inspected so that it
more than two sprinklers where life safety is will work properly in the event of a fire.
a consideration. These should be installed in
Sprinkler systems have an extensive service,
accordance with the manufacturer’s data
maintenance and inspection programme
sheet but should comply with the
covering the whole of their design life,
requirements of BS EN 12845 as a minimum.
including weekly, monthly, quarterly, yearly,
Where residential sprinklers are used, the
three-yearly, up to ten-yearly checks and tests.
design criteria should meet the requirements
of BS EN 12845 Table 3 OH hazard class. Regular service and maintenance should be
Note: Residential sprinklers should not carried out in accordance with BS EN 12845 and
be used at LH design densities or in Technical Bulletin TB 20323 by a sprinkler contractor
HH class applications. for all but the monthly and weekly checks.
However, it is also important that sprinklers are
not damaged or deliberately operated when Special requirements for life
there is no fire. safety systems
Special requirements for life safety sprinkler
In addition:
systems are contained in BS EN 12845 Annex F
• Where the sprinkler patterns above may be and Approved Document B. BS EN 12845
subject to accidental mechanical damage, requires:
they should be fitted with a metal guard.
• increase in number of zones;
• Where exposed sprinklers could be subject to
• system type to be wet type;
accidental damage or tampering, recessed
pattern sprinklers with a k factor of 80 can be • quick response sprinkler heads (except for
used for general room protection. rooms < 500 m2 in area and < 5 m high,
where standard ‘A’ and special response can
be used);

23 Technical Bulletin TB 203: 2004: 1 Care and maintenance of automatic sprinkler systems, The Fire Protection Association, 2004.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 21
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
• duplicate control valve sets; Void sprinkler protection
• at least one superior single water supply; The height of a concealed space (for example,
ceiling and floor voids and roof spaces) and the
• specific requirements for theatres that have
contents of the concealed space in a school
stages where there is a safety curtain between
building will affect the extent of sprinkler
the stage and auditorium; and
protection required.
• additional precautions for maintenance.
Custom and practice in the UK is different from
Approved Document B includes the life safety
the requirements in BS EN 12845.
requirements for sprinkler water supplies.
See Water supplies for life safety, page 19. Technical Bulletin TB 23024 is in consultation.
This will allow some unsprinklered floor and
Special considerations ceiling voids over 0.8m, if they are of non-
combustible construction and contain no
External fires combustible materials, or contain electrical
External fires are not design scenarios within cables with a voltage less than or equal to 250
the sprinkler standards. Prevention and volts, with a low load for normal lighting or a
protection from these fires should be dealt voltage greater than 250 volts, enclosed within
with by housekeeping measures to prevent steel conduits or mineral insulated cable.
accumulation of combustibles outside and
close to the school buildings and additional Void sprinkler protection should be in
external passive fire protection measures for compliance with TB 230 (in consultation).
property protection purposes. See BB 100. Sprinkler protection is required for:
Water-based systems, not sprinklers, for example, • roof spaces that are greater than 0.8 m in
drenchers and window ‘sprinklers’, are available height; or
and could be applied but a number of practical
• roof spaces and concealed spaces between
issues would need to be addressed. Practical
floors that are 0.8 m or less in height and
issues include: adequate exposure of heat sensing
greater than 250 m2 in area and are formed
element to flames for system activation, adequate
of combustible construction or contain
water delivery to all of the exposed areas of the
combustible materials; or
school façade that need to be protected, extent
of area of façade to be protected, and frost • concealed spaces between floors that are
protection of the water delivery system. These between 0.8 m and 2 m in height and have
systems are not covered by standards and some combustible construction or contain
technical evidence should be provided to prove combustible materials; or
these are fit for their intended purpose. • concealed spaces between floors that are
greater than 2 m in height.

24 Technical Bulletin TB 230 2007: 1 Protection of floor voids, ceiling voids and roof spaces, The Fire Protection Association
(in consultation).

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


22 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Sprinkler protection is not required for: Sprinkler protection of theatres
School theatres should be sprinkler protected.
• roof spaces and concealed spaces between
An appropriate hazard classification category
floors that are 0.8 m or less in height and
should be selected. See Classification of
wholly of non-combustible construction and
occupancies and fire hazards, page 14.
contain no combustible materials; or
• roof spaces and concealed spaces between Sprinkler protection of sleeping
floors that are 0.8 m or less in height, which accommodation
are formed of combustible construction or
Some schools include sleeping accommodation.
contain combustible materials where there
Sleeping accommodation areas or buildings as
are vertical cavity barriers installed enclosing
part of a school should be sprinkler protected.
areas 250 m2 or less; or
Residential sprinklers can be used in conjunction
• concealed spaces between floors that are with the design requirements of BS EN 12845.
between 0.8 m and 2 m in height and wholly See Sprinkler design characteristics and
of non-combustible construction and contain applications, sixth bullet point, page 21.
no combustible materials; or
• concealed spaces between floors that are Protection from legionella
between 0.8 m and 2 m in height and wholly Legionnaires’ disease is a form of pneumonia
of non-combustible construction and contain that can be contracted by inhaling water
electrical wiring with a voltage less than 250 droplets or aerosols containing bacteria from
volts with a low load for normal lighting; or the genus legionella. Legionella grows in tepid
stagnant oxygenated water with a supply of
• concealed spaces between floors that are
nutrients. For human infection to occur from a
between 0.8 m and 2 m in height and wholly
sprinkler system, any legionella present in the
of non-combustible construction and contain
system would have to grow to an infectious
electrical wiring with a voltage greater than
level, be present in an aerosol and be inhaled
250 volts enclosed within steel conduits or if
by a susceptible individual.
mineral insulated cable is used.
The selection of the sprinkler head type for use The risk of being infected by legionella from a
in concealed spaces is important. See Sprinkler properly installed and maintained sprinkler
design characteristics and applications, page 20. system is negligible. The likelihood of being
exposed to legionella from a discharging
Sprinkler protection of atria sprinkler during a fire or from a sprinkler system
Atrium spaces require sprinkler protection. New supplied from the town main is equally small.
schools may include tall (>10 m) glazed atria that The likelihood of a school employee being
may need non-standard sprinkler protection. exposed to legionella during
These systems are not covered by standards, and maintenance/testing work involving sprinklers is
technical evidence should be provided to prove very small, although there is a slightly higher risk
they are fit for their intended purpose. in the case of sprinkler contractors who have to
remove sprinkler heads supplied by poorly
maintained private water tanks.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 23
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
The Technical Briefing Note in the LPC Sprinkler Security
Rules on legionella and firefighting systems25 Security measures should be taken to prevent
gives further information on this subject and tampering with components of a sprinkler
recommends control measures. system that would isolate the water supply from
the rest of the sprinkler system, including:
All water supplies and pipework should be
protected from legionella. • The control valves and any pump sets should
be located in a secure location.
Frost protection
• Each stop valve should be provided with a
Water leakage and burst pipes could occur
tamper-proof device to monitor its status.
if water in the sprinkler system freezes,
Each of the monitoring devices should be
causing water damage and/or an ineffective
electrically connected to a control and
sprinkler system.
indicating panel, installed at an accessible
All water supplies and pipework should be location on the school premises.
adequately protected from freezing. See BS EN • Signs for the sprinkler stop valve and the
12845, Technical Bulletin TB 221 and sprinkler control valves may be omitted,
Recommendations RC3826. provided the fire authority agrees.
Trace heating systems or a subsidiary dry pipe
Use of specialised sprinkler types
or alternate extension can be used in areas
where there is a possibility of freezing. Specialised sprinkler types that are not yet
included in BS EN 12845 or BS EN 12259-1
Trace heating systems should be in accordance may be suitable for use in sprinkler systems for
with BS EN 12845 clause 11.1.2.2. school applications. Technical evidence should
be provided to prove these are fit for their
Subsidiary dry pipe and alternate extensions
intended purpose and should be confirmed
should be in accordance with BS EN 12845
with the relevant authorities having jurisdiction
clause 11.5 and limited to ten sprinklers on any
at the earliest stage.
subsidiary extension.
One example is the EPEC (Enhanced Protection
Extended Coverage) sprinkler. See Technical
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Bulletins TB 22227 and TB 22328.

25 Technical Briefing Note Legionella and firefighting systems, The Fire Protection Association.
26 Loss Prevention Recommendations RC38: Recommendations for frost protection measures for sprinklers, The Fire Protection
Association.
27 Technical Bulletin TB 222: 2004: 2 Ordinary Hazard Group 3 protection using enhanced protection extended coverage sprinklers, The
Fire Protection Association, 2004.
28 Technical Bulletin TB 223: 2004: 2 Sprinkler protection of concealed spaces in OH3 EPEC sprinklered buildings, The Fire Protection
Association, 2004.

Standard specifications, layouts and dimensions


24 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Use of plastic pipe Use of flexible connectors
Plastic pipe is not specified in BS EN 12845. One type of flexible connector connects a range
There are a number of types of plastic, all with pipe to a single sprinkler. This type of flexible
their own properties. Plastic pipe seems an connector, unlike rigid pipe, has a susceptibility

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
attractive alternative to metallic pipe where to deformation and kinking, which would
cleanliness and/or ease of installation are detrimentally affect system performance, so
important. However, there are several issues caution and care are needed in its installation
with plastic pipe that restrict its use. For and continued use.
example, plastic pipe can weaken after
Any flexible connectors connecting range pipes
prolonged exposure to sunlight, can deform
to single sprinklers should be approved to LPS
or melt on exposure to heat, is less rigid than
1261 (under revision)32 or equivalent and installed
metallic pipe and needs more support, and
in accordance with all the requirements of TB 22733.
cementing of joints needs sufficient curing time
to prevent water leakage and/or a weakening
Use of unusual materials
of the structure. Therefore, care and caution
are needed to ensure that a particular type Whenever unusual materials or designs are
of plastic pipe is suitable and only used in used, for example, ETFE for roofs, a fire
appropriate circumstances as part of a school engineering solution should be used. See
sprinkler system. BB 100. It should be determined that the
material, for example, ETFE, does not
Plastic pipework should not be painted unless detrimentally affect the performance of the
the paint is stated to be suitable for use by sprinkler system when exposed to a fire.
the manufacturer.
Sprinklers as a compensatory feature
When plastic pipe is used in sprinkler
installations in schools it should be approved to For a sprinkler system being proposed as a
LPS 1260 (under revision)29 or equivalent and compensatory feature to other fire protection
should be installed in accordance with TB 21130 systems to meet the requirements of the
and TB 22731. Building Regulations or other Regulatory
requirements, see BB 100.
The use of exposed and unprotected plastic
pipe is not allowed.

29 Loss Prevention Certification Board, LPS 1260 Requirements for testing plastic pipes for sprinkler systems, BRE Global, available on
www.redbooklive.com (under revision).
30 Technical Bulletin TB 211: 2004: 1 CPVC plastic pipe, The Fire Protection Association, 2004.
31 Technical Bulletin TB 227: 2006: 1 Pipework, The Fire Protection Association, 2006.
32 Loss Prevention Certification Board, LPS 1261 Requirements for testing flexible hoses for sprinkler systems, BRE Global, available on
www.redbooklive.com (under revision).
33 Technical Bulletin TB 227: 2006: 1 Pipework, The Fire Protection Association, 2006.

Copyright Department for Children, Schools and Families


Sprinklers in schools 25
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Cost comment Whole-life costs
The cost figures in this section have been taken It is important to consider whole-life costs of
from recent work by EC Harris for DCSF34. These sprinkler systems rather than capital costs alone.
figures were adjusted by EC Harris to the third
Sprinkler systems have an extensive service,
quarter of 2006.
maintenance and inspection programme
covering the whole of their design life. Typically,
Capital costs
a well maintained sprinkler system will still be
The capital cost of a new sprinkler system in a available for operation in 50 years.
secondary school ranges between 1.7% and
3.0% of the total construction cost (in a primary The annual cost associated with regular
school ranges between 1.4% and 4.5%). servicing, maintenance and inspection of
the sprinkler system is approximately £1,100.
The capital cost ranges from £23/m2 to £37/m2 This comprises internal and external costs.
for secondary schools (£29/m2 to £68/m2 for Annual indicative internal costs are £180 for
primary schools)35. These figures include the inspection and checking work by a trained
total sprinkler construction costs and the school caretaker. Annual indicative external
additional associated works but do not include costs are £180 for off-site sprinkler alarm
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

professional fees. The design details that monitoring, £500 for six-monthly sprinkler
influence the cost variability the most are water contractor maintenance, £120 for water costs
supplies (see Water supplies, page 18) and and up to £120 for fuel costs.
ceiling void sprinkler protection (see Void
sprinkler protection, page 22). The fire insurance costs that need to be
considered are the premium and the deductible
The addition of sprinklers during a school (excess). The fire insurance premium costs are
refurbishment can be significantly more likely to be reduced if a school is sprinklered.
expensive than for a new school. To date, This reduced premium reflects the improved
there have been a few cases where property protection afforded by the sprinkler
refurbishments have been undertaken which system. Also, the insurance deductible (excess)
have involved installing sprinkler protection. for an unsprinklered school can typically be
The total costs could be more than 50% higher £100,000 based on a school valued at
than for a new building. £10,500,000 for insurance purposes, in an
Capital cost savings are a possibility with the insurance application for a group of schools.
addition of a sprinkler system as a This excess is likely to be reduced or removed
compensatory feature. Consideration can be for a sprinklered school.
given to other fire protection provisions, such as
structural fire resistance and compartment sizes.
See BB 100 and BS DD 999936 for further details.

34 EC Harris LLP, A cost analysis of sprinklers in schools, report prepared for DCSF, January 2007, available on www.teachernet.gov.uk/fire
35 All costs at third quarter 2006 prices.
36 British Standards Institution, DD 9999 Draft for Development Code of Practice for fire safety in the design, construction and use of
buildings, 2005 (under revision).

Standard specifications, layouts and dimensions


26 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
However, each case is considered on its merits In contrast, the indirect benefit of a sprinkler
and any fire insurance cost savings will include system in a school is that there is the
an appraisal of a) the number of sprinklered opportunity for quick reinstatement of the
schools in the group of schools and b) for the school following a potentially large fire incident,
individual school, the incidence of fire, perhaps achieved in a few days.
environment and buildings, fire safety and fire
Detailed cost benefit calculations for installing
protection measures, consequences and impact
a sprinkler system in a particular school can be
of fire. See37,38 for further details.
performed using the DCSF CBA tool38.
In unsprinklered schools, there have been cases
where a large fire has completely destroyed a
large part of the school and this has led to
displaced education and a re-build programme.
The many associated losses that are not covered
by insurance are hard to quantify and include:

• the loss of education (loss of coursework,


teaching materials, etc), loss of specialised
facilities (hall, sports, music/drama,
laboratories), time wasted travelling to
alternative sites, head teacher and staff
distracted from key roles, time wasted in
planning temporary accommodation, planning
rebuilding, re-scheduling lessons, etc);
• a loss of facilities (temporary accommodation
may not be suitable for all activities, problems
with site planning/access, planning
permission required and this may be time-
consuming, vulnerability to arson attack); --`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

• loss for the community (stigma due to arson,


teacher morale, loss of community facility
(e.g. sports halls), blow to area regeneration
efforts); and
• associated logistical problems.

37 DCSF, Risk assessment tool for fire precautions in schools, available on www.teachernet.gov.uk/fire
38 DCSF, Cost-benefit analysis for fire precautions in schools, available on www.teachernet.gov.uk/fire

Copyright Department for Children, Schools and Families


Sprinklers in schools 27
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Design examples

The following design examples show Example 1 Sprinklers to protect


typical design arrangements in parts classroom and corridor for property
protection
of a sprinkler system. It is for those
Sprinklers are installed at ceiling level to protect
involved to decide what would be the
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

the classroom and corridor and in the void


most appropriate final design solution above the corridor. The ceilings in both cases
for their particular situation. are constructed from non-combustible
materials. Sprinklers are installed in the corridor
Examples 1, 2 and 3 illustrate different void as the depth of the void exceeds 0.8 m and
sprinkler/ceiling arrangements. the corridor void is likely to contain combustible
materials in the future. Sprinklers are not
Examples 4, 5 and 6 illustrate different installed in the classroom void as it contains
types of water supplies. no combustibles. The two voids are separated
by non-combustible construction.

Sprinkler system specification:

• Standards = BS EN 12845, TB 221, TB 207,


TB 230.
• The hazard classification is OH1.
• Pipework = wet pipe system, steel pipe,
pre-calculated tables used for pipe sizes.
• Ceiling sprinklers = concealed type, 68°C,
k80, ‘unrated’ response sprinkler with ‘quick’
response bulbs.
• Void sprinklers = conventional type, 68°C,
k80, ‘quick’ response sprinkler.

Standard specifications, layouts and dimensions


28 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
This design has:

• sprinkler protection of the classroom and no


sprinkler protection in the classroom ceiling
void; and
• sprinkler protection of the corridor and
sprinkler protection in the corridor ceiling void.

CLASSROOM CORRIDOR

A side view of sprinklers and pipework in a classroom


and corridor, section B-B.

KEY
VOID SPRINKLER AND DROP TO
CEILING SPRINKLER
MECHANICAL GROOVED COUPLING
CLASSROOM MAINS DISTRIBUTION PIPE
RANGE PIPE
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

FINAL DROP TO CEILING HEAD


PIPE DIAMETER = 32mm
BRACKET LOCATION OF TYPE A
(specific to the design)

CORRIDOR

A plan view of sprinklers and pipework in a classroom and corridor, showing the location of section B-B

Copyright Department for Children, Schools and Families


Sprinklers in schools 29
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Example 2 Sprinklers to protect roof • The hazard classification is OH1
space for property protection • Pipework = wet pipe system, steel pipe,
Sprinklers are installed at ceiling level to protect pre-calculated tables used for pipe sizes
the roof space, classroom and the corridor. • Ceiling sprinklers = concealed type, 68°C,
The roof space is protected as it is greater than k80, ‘unrated’ response sprinkler with ‘quick’
0.8 m deep. response bulb
Sprinkler system specification: • Void sprinklers = conventional type, 68°C,
k80, ‘quick’ response sprinkler
• Standards = BS EN 12845, TB 221,
TB 207, TB 230

KEY
SPRINKLER HEAD
CONCEALED SPRINKLER HEAD
DRAIN VALVE
MAINS DISTRIBUTION PIPE
RANGE PIPE
PIPE DIAMETER = 65mm
ROOF SPACE

CLASSROOM CORRIDOR

A side view of sprinklers and pipework in roof space, classroom and corridor

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
Standard specifications, layouts and dimensions
30 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Example 3 Sprinklers to protect Sprinkler system specification:
sports hall and storage room for
• Standards = BS EN 12845, TB 221
property protection
• The hazard classification is OH1, OH2 or OH3
Sprinklers are installed at ceiling level to protect
the sports hall and storage room. The sports • Pipework = wet pipe system, steel pipe,
hall is a large, tall space with multiple use. pre-calculated tables used for pipe sizes
The shape of the roof requires the installation • Ceiling sprinklers = conventional type, 68°C,
of sprinkler range pipes at varying height to k80, ‘quick’ response
comply with standard sprinkler locations.
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

SPORTS HALL

STORAGE
ROOM

KEY
DRAIN VALVE
MECHANICAL GROOVED COUPLING
MAINS DISTRIBUTION PIPE
RANGE PIPE

A side view of sprinklers and pipework in a sports hall and storage room

Copyright Department for Children, Schools and Families


Sprinklers in schools 31
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
SPORTS HALL

STORAGE
ROOM

KEY
SPRINKLER ON DROP
SPRINKLER ON RISE
DRAIN VALVE
MECHANICAL GROOVED COUPLING
MAINS DISTRIBUTION PIPE
RANGE PIPE
PIPE DIAMETER = 32mm
PIPE DIAMETER = 40mm
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

A plan view of sprinklers and pipework in a sports hall and storage room

Standard specifications, layouts and dimensions


32 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Example 4 Single town main water In this example, the tested water is found to be
supply for property protection sufficient for the system design requirements at
In this example, the school requires sprinklers the valve set. The system design requirements
for property protection and therefore a single are calculated by taking account of the highest
water supply is sufficient. sprinkler, friction loss (due to pipe lengths,
bends, height) and pressure/flow requirements
The water supply to the sprinklers is from the at the most remote sprinklers.
town main. Prior to selection of the water
supply, the town main at the site is tested – For this example, a 150 mm water supply is
its pressure and flow characteristics are found required. A new connection to the town main
and the minimum available pressure and flow is made, a trench is dug and new pipe installed
is determined. See Water supplies, page 18. to the site of the sprinkler valve room.

HYDRAULIC GONG
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

STRAINER

PRESSURE
SWITCH FOR
REMOTE SIGNAL

PRESSURE
STOP VALVE GAUGE
WET ALARM VALVE

ALARM TEST VALVE

PIPE TO DRAIN
DRAIN
VALVE
CHECK GATE
80mm 0H 1 VALVE VALVE
150 mm SUPPLY

PROVING PIPE
PIPE TO DRAIN

PIPE TO DRAIN 150mm MONITORED


BUTTERFLY STOP VALVE

PIPE TO DRAIN

FINISHED FLOOR LEVEL

UNDERGROUND SUPPLY MAIN

An example town main water supply and sprinkler valve arrangement

Copyright Department for Children, Schools and Families


Sprinklers in schools 33
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Sprinkler system specification:

• Standards = BS EN 12845, TB 221


• The hazard classification is OH1
• Pipework = wet pipe system, steel pipe,
pre-calculated tables used for pipe sizes
• Water supply = 150 mm underground water
supply main, single supply, wet alarm valve

The town main water supply may be subject


to change and therefore consultation with the
water supply company is essential to ensure
continuity of supply. In many cases, contingency
plans are necessary for alternative water supplies
(such as pump and tank) if there is a possibility
that the available water pressure/flow could be
reduced in the future.

Currently, few secondary schools have town


main supplies as the system design requirements
are often greater than the available
pressure/flow.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


34 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Example 5 Pump and tank water • The hazard classification is OH1
supply for property protection • Pipework = wet pipe system, steel pipe,
In this example, the school requires sprinklers pre-calculated tables used for pipe sizes
for property protection and therefore a single • Water supply = inflow water supply from
water supply is sufficient. main, single tank 27.5 m3, one electric sprinkler
The water supply to the sprinklers is from a tank pump, 150 mm wet alarm valve
via an electric pump. The tank is sized to deliver A single electric pump and single tank are
water for 30 minutes. The highest sprinkler is less employed for property protection sprinklers
than 15 m so the minimum tank size is designed to comply with TB 221.
27.5 m3. The electric pump is selected to meet
the system design requirements of water A 30 minute water supply is only acceptable
pressure and flow, at the valve set. The system to the insurance industry if the hazard
design requirements are calculated by taking classification is OH1, the local fire service can
account of the highest sprinkler, friction loss (due arrive and attack the fire in 30 minutes and
to pipe lengths, bends, height) and pressure/flow there is full compliance with the requirements
requirements at the most remote sprinklers. of TB 221 (for example, provision should be
made to transmit fire and fault alarm automatically
For this example, a new connection to the town to a central station for fire alarm signalling
main is made for the water infill, a trench is dug approved by a nationally accredited,
and new pipe installed to the site of the independent, third party approvals organisation).
sprinkler tank.
Most secondary schools have pump and
Sprinkler system specification: tank supplies.
• Standards = BS EN 12845, TB 205, TB 220, TB 221

PRESSURE
MAINTENANCE PUMP
SPRINKLER TANK

INFILL
FROM
TOWN
BALL FLOAT VALVE MAIN
PUMP
SINGLE ELECTRIC PUMP SUCTION

TO INSTALLATION
ALARM VALVE
ASSEMBLY ACCESS
LADDER

An example pump and tank water supply

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 35
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Example 6 Pump and tank water Sprinkler system specification:
supply for life safety
• Standards = BS EN 12845, TB 205, TB 220, TB 221
In this example, the school requires sprinklers
• The hazard classification is OH1
with additional life safety features and therefore
requires duplicate water supplies. • Pipework = wet pipe system, steel pipe,
pre-calculated tables used for pipe sizes
The water supply to the sprinklers is from a
tank via two electric sprinkler pumps from two • Water supply = inflow water supply from
separate and independent electricity supplies. main, 70 m3 tank divided into two, two electric
See Water supplies for life safety, page 19. pumps, two independent electrical supplies,
The tank is sized to deliver water for 60 minutes. 150 mm wet alarm valve
The highest sprinkler is over 15 m high, therefore Duplicate electric pumps and duplicate tanks
the minimum tank size is 70 m3. The tank is are employed for life safety sprinklers. All control/
divided into half and the electric pumps can gate valves are monitored but not shown.
draw water from each half tank. The electric
pumps are selected to meet the system design Other additional requirements for life safety
requirements of water pressure and flow, at the systems are given in Special requirements for
valve set. The system design requirements are life safety systems, page 21.
calculated by taking account of the highest Currently, only a few secondary schools have
sprinkler, friction loss (due to pipe lengths, life safety sprinkler systems with the associated
bends, height) and pressure/flow requirements additional life safety features.
at the most remote sprinklers.
However, new schools with large open
For this example, a new connection to the town areas and multiple use facilities may include
main is made for the water infill, a trench is dug life safety sprinkler systems as part of fire
and new pipe installed to the site of the engineered solutions.
sprinkler tank.

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


36 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
BUTTERFLY VALVE SUCTION PIPEWORK

VORTEX INHIBITOR PRESSURE


GATE MAINTENANCE
PRESSURE RELIEF PUMP
PIPEWORK TO BE VALVE
RETURNED BACK
INTO TANK
SUCTION TANK
TANK CONTENTS
GAUGE

ELECTRIC
DROP INTO TANK SPRINKLER TO PUMP
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

INITIATION
PUMP INITIATION PANEL
ARRANGEMENT
BALL FLOAT VALVE
PUMP DELIVERY
PIPEWORK
INFILL FROM DRAIN VALVE
TOWN MAIN

PUMP TEST PIPEWORK


TO INSTALLATION
ALARM VALVE ASSEMBLY

An example duplicate pump and tank water supply

Copyright Department for Children, Schools and Families


Sprinklers in schools 37
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
References

This document was published in Department for Children, Schools


February 2008. After this date readers and Families
should ensure they use the latest • Risk assessment tool for fire precautions in
schools, available at
edition of all references. www.teachernet.gov.uk/fire
• Cost-benefit analysis for fire precautions in
schools, available at
www.teachernet.gov.uk/fire
• Building Bulletin 100 Design for fire safety in
schools, available at
www.teachernet.gov.uk/fire
• EC Harris LLP, A cost analysis of sprinklers in
schools, report prepared for DCSF, January
2007, available at www.teachernet.gov.uk/fire

The Building Regulations


• The Building Regulations 2000, Approved
Document B, Fire Safety, volume 2 – buildings
other than dwellinghouses, 2006 edition,
available at www.planningportal.gov.uk
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


38 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
British Standards Other standards
• BS 5306 Part 2: Specification for sprinkler • The Loss Prevention Certification Board
systems, 1990 (obsolescent) LPS 1260 Requirements for testing plastic pipes
• BS EN 12259 (various parts), Fixed firefighting for sprinkler systems, BRE Global, available at
systems, components for sprinkler and water www.redbooklive.com (under revision)
spray systems • The Loss Prevention Certification Board
• BS EN 12259-1 Fixed firefighting systems, LPS 1261 Requirements for testing flexible hoses
components for sprinkler and water spray for sprinkler systems, BRE Global, available at
systems Part 1 Sprinklers, 1999 www.redbooklive.com (under revision)

• BS EN 12845, Fixed Firefighting systems – • LPC rules for automatic sprinkler installations
Automatic sprinkler systems – Design Installation incorporating BS EN 12845, and including
and maintenance, 2004 Technical Bulletins, Recommendations,
Technical Briefing Notes and Guidance
• BS DD 252, Draft for Development Components documents, The Fire Protection Association
for residential sprinkler systems – specification
and test methods for residential sprinklers, 2002 Technical Bulletins relevant to schools
(under revision)
• TB 201 Suitable sprinkler components and services
• BS DD 9999 Draft for Development Code of
• TB 202 Approved sprinkler equipment
Practice for fire safety in the design, construction
and use of buildings, 2005 (under revision) • TB 203 Care and maintenance of automatic
sprinkler systems
• TB 204 Sprinkler system grading
• TB 205 Consultation and acceptance for
sprinkler system approval by fire insurers
• TB 206 Passive fire protection of
sprinklered buildings
• TB 207 The selection of sprinkler heads
• TB 208 Supplementary requirements for sprinkler
installations which can operate in the dry mode
• TB 209 ESFR sprinkler protection
• TB 210 Automatic sprinkler pump installation
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,

Copyright Department for Children, Schools and Families


Sprinklers in schools 39
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
• TB 211 CPVC plastic pipe, until April 2008 Recommendations
• TB 213 Upkeep and testing of multiple controls • RC19: Recommendations for the storage
of aerosol products
• TB 214 Sprinkler protection of flammable
liquid stores • RC38: Recommendations for frost protection
measures for sprinklers
• TB 215 Sprinkler protection of idle pallet storage
• TB 216 Sprinkler protection of aerosols Technical Briefing Note
• TB 217 Categorisation of goods in storage • Legionella and firefighting systems
• TB 218 Water supply diagrams
Guidance documents
• TB 219 Sprinkler protection of cold stores
• Guidelines for the supply of water to fire
• TB 220 Power supplies for sprinkler pumps, sprinkler systems
until September 2008
• FPA guide on the management of fire water
• TB 221 Sprinkler protection of schools in sprinkler-protected properties
• TB 222 Ordinary Hazard Group 3 protection using • FPA guide on working in confined spaces
enhanced protection extended coverage sprinklers
• TB 223 Sprinkler protection of concealed spaces Other publications
in OH3 EPEC sprinklered buildings • British Automatic Fire Sprinkler Association,
• TB 224 Sprinkler water storage tanks (cisterns) Sprinklers for safety – Uses and benefits of
• TB 225 BS EN 12845: 2004 incorporating sprinklers in buildings and
structures, 2006
• TB 226 Design, installation and maintenance
of underground pump chambers • The Loss Prevention Certification Board,
List of Approved Fire and Security Products and
• TB 227 Pipework
Services, Red Book, BRE Global, available at
• TB 228 Revision to BS EN 12845 Table 1 www.redbooklive.com
• TB 229 LPC Rules for automatic sprinkler • FIRAS Scheme for Installers of Commercial
installations variations to BS EN 12845: 2003 and Industrial Sprinkler Systems, Warrington
and 2004 Certification Limited, available at
• TB 230 Protection of floor voids, ceiling voids www.firas-register.co.uk
and roof spaces (in consultation) • UK Fire Statistics, 1994-2002
• TB 231 Pipe sizing • A Lewis, FPA Large Loss Analysis 2004,
Fire Engineers Journal and Fire Prevention,
February 2007

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


40 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Sprinklers in schools 41
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Annex A

Table relating key elements of sprinkler system design and installation to BS EN


12845 Clauses and LPC Technical Bulletins

Key elements of sprinkler system design BS EN 12845 clause number and LPC
Technical Bulletin number*
Contract planning and documentation BS EN 12845 clause 4, TB 205 and TB 221 clause 5

Extent of sprinkler protection (including BS EN 12845 clause 5, TB 206, TB 221 clause 3 and TB 230
permitted exceptions)

Classification of occupancies and fire hazards BS EN 12845 clause 6, TB 215, TB 217, TB 228,
(including protection of special hazards) TB 221 clause 8 and TB 229 clause 3

Hydraulic design criteria (including design density and BS EN 12845 clause 7, TB 221 clause 9 and TB 229 clause 3
area of operation)

Water supplies and type (including type of water supply) BS EN 12845 clauses 8 and 9, TB 204, TB 218, TB 224, TB
226, TB 221 clauses 6 and 7 and TB 229 clause 3

Pumps BS EN 12845 clause 10, TB 210 and TB 220

Installation type and size BS EN 12845 clause 11, TB 208, TB 219, TB 221 clause 4,
TB 229 clause 3 and RC 38.

Spacing and location of sprinklers BS EN 12845 clause 12 and TB 229 clause 3

Pipe sizing and layout BS EN 12845 clause 13, TB 229 clause 3 and TB 231

Sprinkler design characteristics and uses BS EN 12845 clause 14, TB 207 and TB 221 clause 10

Valves BS EN 12845 clause 15 and TB 229 clause 3

Alarms and alarm devices BS EN 12845 clause 16 and TB 221 clause 11


--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Pipework BS EN 12845 clause 17, TB 211 and TB 227

Signs, notices and information BS EN 12845 clause 18 and TB 221 clause 12

Commissioning and acceptance tests and BS EN 12845 clause 19 and TB 205


periodic inspection

Standard specifications, layouts and dimensions


42 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
Key elements of sprinkler system design BS EN 12845 clause number and LPC
Technical Bulletin number*
Maintenance BS EN 12845 clause 20, Annex F and Annex J, TB 203,
TB 213, TB 219 and TB 221 clause 13

Classification of typical hazards BS EN 12845 Annex A and TB 229 clause 3

Special requirements for life safety systems BS EN 12845 Annex F

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---
Protection of special hazards BS EN 12845 Annex G, TB 214, TB 215, TB 216,
TB 229 clause 3 and RC 19

Security TB 221 clause 12

Specialised sprinkler types TB 209, TB 222 and TB 223

Approved sprinkler equipment TB 202

Suitable sprinkler components and services TB 201


*Titles of LPC Technical Bulletins relevant to schools – see References.

Copyright Department for Children, Schools and Families


Sprinklers in schools 43
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Standard specifications, layouts and dimensions


44 Department for Children, Schools and Families
Copyright
Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---

Copyright Department for Children, Schools and Families


Provided by Accuris Licensee=UNIVERSITY COLLEGE LONDON/8213316001, User=Hamadeh, Samer
No reproduction or networking permitted without license from Accuris Not for Resale, 08/05/2023 13:23:43 MDT
You can download this publication or order copies
online at: www.teachernet.gov.uk/publications
Search using the ref: 01002-2007
Copies of this publication can also be obtained from:
DCSF Publications
PO Box 5050
Sherwood Park
Annesley
Nottingham NG15 ODJ
Tel 0845 60 222 60
Fax 0845 60 333 60
Textphone 0845 60 555 60
Please quote ref: 01002-2007BKT-EN
ISBN: 978-1-84775-090-7
© Crown Copyright 2008
Published by the Department for
Children, Schools and Families
Extracts from this document may be reproduced
for non-commercial research, education or training
purposes on the condition that the source is
acknowledged. For any other use please contact
hmsolicensing@opsi.x.gsi.gov.uk

--`,`````,,,,`,`,,``````,,`,,`,,-`-`,,`,,`,`,,`---