Engineering Data
FXFSQ-AVM
50 / 60 Hz
FXFSQ-AVM EDFMT391769C
FXFSQ-AVM
Ceiling Mounted Cassette Type
(Round Flow with Sensing)
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................8
3.1 Standard Panel with Sensing Sensor................................................8
3.2 Standard Panel................................................................................11
3.3 Designer Panel................................................................................14
3.4 Auto Grille Panel..............................................................................17
4. Piping Diagrams........................................................................................20
5. Wiring Diagrams........................................................................................21
6. Electric Characteristics..............................................................................22
7. Safety Devices Setting..............................................................................23
8. Capacity Tables.........................................................................................24
8.1 Cooling Capacity for Te: Auto..........................................................24
8.2 Cooling Capacity for Te: 6°C...........................................................24
8.3 Cooling Capacity for Te: 9°C...........................................................25
8.4 Heating Capacity..............................................................................25
9. Sound Levels.............................................................................................26
10. Centre of Gravity.......................................................................................30
11. Accessories...............................................................................................31
11.1 Optional Accessories (for Unit)........................................................31
11.2 Optional Accessories (for Controls).................................................33
12. Installation Manual....................................................................................34
12.1 FXFSQ25AVM / FXFSQ32AVM / FXFSQ40AVM / FXFSQ50AVM /
FXFSQ63AVM / FXFSQ80AVM / FXFSQ100AVM /
FXFSQ125AVM / FXFSQ140AVM....................................................34
1
FXFSQ-AVM EDFMT391769C
1. Lineup
FXFSQ 25AVM 32AVM 40AVM 50AVM 63AVM 80AVM 100AVM 125AVM 140AVM
FXFSQ 25AVS 32AVS 40AVS 50AVS 63AVS 80AVS 100AVS 125AVS 140AVS
(for Thailand)
FXFSQ 25AV4 32AV4 40AV4 50AV4 63AV4 80AV4 100AV4 125AV4 140AV4
(for Indonesia)
2
FXFSQ-AVM EDFMT391769C
2. Specifications
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
3
FXFSQ-AVM EDFMT391769C
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
4
FXFSQ-AVM EDFMT391769C
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
5
FXFSQ-AVM EDFMT391769C
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
6
FXFSQ-AVM EDFMT391769C
Model FXFSQ140AVM
Power supply 1 phase, 220-240/220-230 V, 50/60 Hz
kcal/h 13,800
1 3 Cooling capacity Btu/h 54,600
kW 16.0
kcal/h 13,800
2 3 Heating capacity Btu/h 54,600
kW 16.0
50 Hz kW 0.194
Cooling
60 Hz kW 0.194
Power input
50 Hz kW 0.183
Heating
60 Hz kW 0.183
Casing / Colour Galvanised steel plate
Dimensions: (H×W×D) mm 298×840×840
Model QTS48G15M
Type Turbo fan
Motor output × W 106×1
Number of units
Fan m /min
3
35.5/32.5/29.5/26.5/23
Airflow rate
(H/HM/M/ML/L) l/s 592/542/492/442/383
cfm 1,253/1,147/1,041/935/812
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Polyurethane form
Liquid pipes mm φ9.5
Piping Gas pipes mm φ15.9
connections
Drain pipe mm φ26 (hole)
Mass kg 26
4 Sound pressure level (H/HM/M/ML/L) dB(A) 46.0/43.5/40.5/38.0/35.0
Safety devices Fuse
Refrigerant control Electronic expansion valve
Model BYCQ125EAF
Decoration Colour Fresh white
panel Dimensions: (H×W×D) mm 50×950×950
(option) Air filter Resin net (with mould resistance)
Mass kg 5.5
Operation manual, Installation manual, Pattern for installation, Drain hose, Clamp metal, Washer
Standard accessories fixing plate, Sealing pads, Clamps, Screws, Washer for hanging bracket, Insulation for fitting,
Installation guide
Specification C: 3D112945B
Drawing No.
Sound level C: 4D509731A
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB, 24°CWB / equivalent piping length: 7.5 m, Conversion formulae
level difference: 0 m. kcal/h=kW×860
+2. Indoor temp.: 20°CDB, 15°CWB / outdoor temp.: 7°CDB, 6°CWB / equivalent piping length: 7.5 m, Btu/h=kW×3412
level difference: 0 m. cfm=m3/min×35.3
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. l/s=m3/min×1000/60
+4. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual
operation, these values are normally somewhat higher as a result of ambient conditions.
7
FXFSQ-AVM EDFMT391769C
3. Dimensions
3.1 Standard Panel with Sensing Sensor
FXFSQ25AVM / FXFSQ32AVM / FXFSQ40AVM / FXFSQ50AVM
Unit: mm
3D112984B
8
FXFSQ-AVM EDFMT391769C
FXFSQ63AVM / FXFSQ80AVM
Unit: mm
3D112982B
9
FXFSQ-AVM EDFMT391769C
3D112977B
10
FXFSQ-AVM EDFMT391769C
3D112987B
11
FXFSQ-AVM EDFMT391769C
FXFSQ63AVM / FXFSQ80AVM
Unit: mm
3D112983B
12
FXFSQ-AVM EDFMT391769C
3D112979B
13
FXFSQ-AVM EDFMT391769C
3D112988B
14
FXFSQ-AVM EDFMT391769C
FXFSQ63AVM / FXFSQ80AVM
Unit: mm
3D112985B
15
FXFSQ-AVM EDFMT391769C
3D112980B
16
FXFSQ-AVM EDFMT391769C
3D112991B
17
FXFSQ-AVM EDFMT391769C
FXFSQ63AVM / FXFSQ80AVM
Unit: mm
3D112986B
18
FXFSQ-AVM EDFMT391769C
3D112981B
19
FXFSQ-AVM EDFMT391769C
4. Piping Diagrams
4D024460P
20
FXFSQ-AVM EDFMT391769C
5. Wiring Diagrams
3D112965B
21
FXFSQ-AVM EDFMT391769C
6. Electric Characteristics
C: 3D112911B
22
FXFSQ-AVM EDFMT391769C
23
FXFSQ-AVM EDFMT391769C
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
24
FXFSQ-AVM EDFMT391769C
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXFSQ25AVM 25 1.4 1.4 1.8 1.8 2.1 2.1 2.3 2.3 2.4 2.4 2.5 2.3 2.7 2.2
FXFSQ32AVM 32 1.8 1.8 2.2 2.2 2.8 2.8 3.0 2.9 3.1 2.8 3.2 2.7 3.4 2.6
FXFSQ40AVM 40 2.3 2.3 2.8 2.8 3.5 3.5 3.8 3.7 3.9 3.7 4.1 3.6 4.3 3.4
FXFSQ50AVM 50 2.5 2.5 3.3 3.3 4.1 4.1 4.5 4.4 4.7 4.3 5.0 4.0 5.2 3.7
FXFSQ63AVM 63 3.3 3.3 4.2 4.2 5.2 5.1 5.8 5.3 5.9 5.2 6.3 5.0 6.6 4.7
FXFSQ80AVM 80 4.3 4.3 5.3 5.2 6.7 6.0 7.3 6.2 7.5 6.1 8.0 5.9 8.4 5.7
FXFSQ100AVM 100 5.2 5.2 6.4 6.4 8.2 7.6 8.9 7.8 9.2 7.6 9.7 7.5 10.3 7.4
FXFSQ125AVM 125 6.4 6.2 8.3 7.6 10.4 8.8 11.3 9.0 11.7 9.0 12.3 8.7 13.0 8.7
FXFSQ140AVM 140 7.4 7.1 9.6 8.6 11.9 10.0 13.0 10.2 13.5 10.2 14.3 10.0 15.0 9.7
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
25
FXFSQ-AVM EDFMT391769C
9. Sound Levels
FXFSQ25AVM / FXFSQ32AVM
4D112880A
FXFSQ40AVM
4D112874A
26
FXFSQ-AVM EDFMT391769C
FXFSQ50AVM
4D112898A
FXFSQ63AVM
4D112879B
27
FXFSQ-AVM EDFMT391769C
FXFSQ80AVM
4D112878B
FXFSQ100AVM
4D509733A
28
FXFSQ-AVM EDFMT391769C
FXFSQ125AVM
4D509732A
FXFSQ140AVM
4D509731A
29
FXFSQ-AVM EDFMT391769C
Unit: mm
4D052237U
30
FXFSQ-AVM EDFMT391769C
11. Accessories
11.1 Optional Accessories (for Unit)
Model
Item
FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM
Standard panel with Fresh white BYCQ125EEF
sensing sensor Black BYCQ125EEK
Fresh white BYCQ125EAF
Standard panel
Black BYCQ125EAK
Designer panel
Fresh white BYCQ125EAPF
(Note 1)
Auto grille panel Fresh white BYCQ125EASF
(Note 2,3)
For usage of 3-, 4-way KDBH551C160
Sealing material of flow
air discharge outlet
(Note 4) For usage of 2-way KDBH552C160
flow
Panel spacer KDBP55H160FA
Chamber Without KDDP55B160 [Components : KDDP55C160-1, KDDP55B160-2]
type T-duct joint
(Note With T-duct
Fresh air intake kit 5,6,8) KDDP55B160K [Components : KDDP55C160-1, KDDP55B160K2]
joint
Direct installation type KDDP55X160A
(Note 7)
High efficiency filter (Colormetric method
KAFP556C80
unit (Including filter 65%)
chamber) (Colormetric method
(Note 9) KAFP557C80
90%)
(Colormetric method
Replacement high KAFP552B80
65%)
efficiency filter
(Note 9,10) (Colormetric method KAFP553B80
90%)
Filter chamber KDDFP55C160
Replacement long-life filter KAFP551K160
Replacement long-life filter KAFP551H160
(Auto grille panel)
Ultra long-life filter unit KAFP55C160
(Including filter chamber) (Note 9)
Replacement ultra long-life filter (Note 9,10) KAFP55H160H
Branch duct chamber (Note 4) KDJP55C80
Insulation kit for high humidity (Note 9,11) KDTP55K80
C: 3D112950A
Notes:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate
2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit.
Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when
more fresh air is necessary.
8. Please order using the name of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature / humidity inside ceiling may get over 30°C, 80%RH.
These panels do not contain the sensing function.
31
FXFSQ-AVM EDFMT391769C
Model
Item
FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM
Standard panel with Fresh white BYCQ125EEF
sensing sensor Black BYCQ125EEK
Fresh white BYCQ125EAF
Standard panel
Black BYCQ125EAK
Designer panel
Fresh white BYCQ125EAPF
(Note 1)
Auto grille panel Fresh white BYCQ125EASF
(Note 2,3)
For usage of 3-, 4-way KDBH551C160
Sealing material of flow
air discharge outlet
(Note 4) For usage of 2-way KDBH552C160
flow
Panel spacer KDBP55H160FA
Chamber Without KDDP55B160 [Components : KDDP55C160-1, KDDP55B160-2]
type T-duct joint
(Note With T-duct
Fresh air intake kit 5,6,8) KDDP55B160K [Components : KDDP55C160-1, KDDP55B160K2]
joint
Direct installation type KDDP55X160A
(Note 7)
High efficiency filter (Colormetric method
KAFP556C160
unit (Including filter 65%)
chamber) (Colormetric method
(Note 9) KAFP557C160
90%)
(Colormetric method
Replacement high KAFP552B160
65%)
efficiency filter
(Note 9,10) (Colormetric method KAFP553B160
90%)
Filter chamber KDDFP55C160
Replacement long-life filter KAFP551K160
Replacement long-life filter KAFP551H160
(Auto grille panel)
Ultra long-life filter unit KAFP55C160
(Including filter chamber) (Note 9)
Replacement ultra long-life filter (Note 9,10) KAFP55H160H
Branch duct chamber (Note 4) KDJP55C160
Insulation kit for high humidity (Note 9,11) KDTP55K160
C: 3D112950A
Notes:
1. When installing designer panel, body height (ceiling required dimension) is 42 mm higher than standard panel. Designer panel cannot operate
2 and 3 way flow.
2. A dedicated wireless remote controller (BRC16A2) for the auto grille panel is included for lowering and raising the suction grille.
3. When installing auto grille panel, body height (ceiling required dimension) is 55 mm higher than standard panel.
4. Circulation airflow is not available with this option.
5. When installing a fresh air intake kit (chamber type), two air outlet corners are closed.
6. It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit.
Introducing higher quantities will increase the operating sound and may also influence temperature sensing.
7. The volume of fresh air for direct installation type is approximately 1% of the indoor unit airflow. The chamber type is recommended when
more fresh air is necessary.
8. Please order using the name of both components instead of set name.
9. This option cannot be installed to designer panel and auto grille panel.
10. Filter chamber is required.
11. Please use in case temperature / humidity inside ceiling may get over 30°C, 80%RH.
These panels do not contain the sensing function.
32
FXFSQ-AVM EDFMT391769C
Model
Item
FXFSQ25AVM FXFSQ32AVM FXFSQ40AVM FXFSQ50AVM FXFSQ63AVM FXFSQ80AVM
Remote Cooling Only BRC7M635F(Fresh white) / BRC7M635K (Black) (Note 4)
Wireless
controller Heat Pump BRC7M634F(Fresh white) / BRC7M634K (Black) (Note 4)
Navigation remote controller BRC1E63 (Note 4)
(Wired remote controller)
Adaptor for wiring (Note 1) KRP1C11A
Wiring adaptor for electrical KRP4AA53
appendices (Note 1)
Installation box for adaptor printed KRP1H98A (Note 2, 3)
circuit board
Remote sensor (for indoor KRCS01-5B
temperature)
External control adaptor for outdoor
unit (Note 1) DTA104A62
Adaptor for multi tenant (Note 1) DTA114A61
Model
Item
FXFSQ100AVM FXFSQ125AVM FXFSQ140AVM
Remote Cooling Only BRC7M635F(Fresh white) / BRC7M635K (Black) (Note 4)
Wireless
controller Heat Pump BRC7M634F(Fresh white) / BRC7M634K (Black) (Note 4)
Navigation remote controller BRC1E63 (Note 4)
(Wired remote controller)
Adaptor for wiring (Note 1) KRP1C11A
Wiring adaptor for electrical
appendices (Note 1) KRP4AA53
Installation box for adaptor printed KRP1H98A (Note 2, 3)
circuit board
Remote sensor (for indoor KRCS01-5B
temperature)
External control adaptor for outdoor
DTA104A62
unit (Note 1)
Adaptor for multi tenant (Note 1) DTA114A61
C: 3D112950A
Notes:
1. Installation box for adaptor printed circuit board (KRP1H98A) is necessary.
2. Up to 2 adaptors can be fixed for each installation box.
3. Only one installation box can be installed for each indoor unit.
4. Some function can be set only via wired remote controller BRC1E63. Cannot be set via other remote controllers. Please see Function List
below.
Function List
FXFSQ-A with FXFSQ-A with
Item Wired type remote controller Wireless type remote controller
Wired BRC1E63 —
Remote
controller Cooling Only — BRC7M635F(Fresh white) / BRC7M635K (Black)
Wireless
Heat Pump — BRC7M634F(Fresh white) / BRC7M634K (Black)
Dual sensors 1
Direct airflow 1
Sensing sensor low mode 1
Sensing sensor stop mode 1
Circulation airflow
Individual airflow direction control
Switchable 5 step fan speed
Auto airflow rate
Auto swing
Swing pattern selection
High ceiling application
33
FXFSQ-AVM EDFMT391769C
3P468397-1F
34
FXFSQ-AVM EDFMT391769C
3P468397-1F
35
FXFSQ-AVM EDFMT391769C
Name
(5) Installation (6) Screw (7) Washer Joint insulating CARRY OUT THE WORK GIVING CAUTION
pattern paper (M4) clamp material
TO THE FOLLOWING ITEMS AND AFTER THE
Quantity 1 sheet 4 pcs. 4 pcs. 1 each
WORK IS COMPLETED CHECK THESE AGAIN.
Upper part
of packing
(8) For gas 1. Items to be checked after the installation work is
piping completed
Shape
3
3P468397-1F
36
FXFSQ-AVM EDFMT391769C
3P468397-1F
37
FXFSQ-AVM EDFMT391769C
Fig. 5
BYCQ125EEF/EEK
All round 4-way 3-way 2-way Decoration Panel BYCQ125EAPF BYCQ125EASF
BYCQ125EAF/EAK
*: Refrigerant piping
[mm] 125~130 167~172 180~185
Fig. 3
5
3P468397-1F
38
FXFSQ-AVM EDFMT391769C
CAUTION
5. INSTALLATION OF INDOOR UNIT
• Reduce the distance between the unit and ceiling to 35 mm
or below in order to maintain an overlapping panel margin of <<It is easy to attach the optional parts (except for
20 mm for the opening on the ceiling. decoration panel) before installing the indoor unit. Refer
• If the distance exceeds 35 mm, attach a ceiling material to to also the installation manual attached to the optional
the part marked or replace the ceiling. (Refer to Fig. 6) parts.>>
For installation, use the attached installation parts and
specified parts.
[Install the indoor unit in the order of steps (1), (2), (3), (4),
840
910
(1) Install the indoor unit temporarily.
• Fix the hanger to the hanging bolt.
Make sure to securely the hanger with the nut and
the washer for hanger (3) from the upper and lower side.
(Refer to Fig. 7)
840 If the washer clamp (7) is used, the upper side washer
910 for hanger (3) may be protected from falling off.
(Dimension inside frame) (Refer to Fig. 8)
(unit [mm])
[To fix hanger] Hanging bolt
Frame Nut
(Field supply) Washer for hanger (3)
(accessory)
Ceiling
material ≤35 ≤35
Ceiling surface
3P468397-1F
39
FXFSQ-AVM EDFMT391769C
Center of the Center of (4) Check the level of the unit. (Refer to Fig. 9)
indoor unit ceiling opening (5) Remove the washer clamp (7) used for preventing the
Center mark washer for hanger (3) from dropping and tighten the upper
Installation
of the unit side nut.
pattern
paper (5)
(accessory)
Screw (6)
Screw (6) (accessory)
(accessory)
Lower ceiling
surface Underside
of the unit
Lower ceiling
surface Underside
of the unit
7
3P468397-1F
40
FXFSQ-AVM EDFMT391769C
Table 3
6. REFRIGERANT PIPING WORK
Piping Tightening Dimension for
• For the outdoor unit refrigerant piping, refer to the installation size torque processing flare Flare shape
manual attached to the outdoor unit. (mm) (N·m) A (mm)
• Carry out insulation of both gas and liquid refrigerant piping φ 6.4 15.7 ± 1.5 8.9 ± 0.2
°
securely. If not insulated, it may cause water leakage. For
2
°±
gas piping, use insulation material of which heat resistant
45
φ 9.5 36.3 ± 3.6 13.0 ± 0.2 R0.6±0.2
temperature is not less than 120°C.
90°±2°
For use under high humidity, strengthen the insulation φ 12.7 54.9 ± 5.4 16.4 ± 0.2
A
material for refrigerant piping. If not strengthened, the
surface of insulation material may sweat.
φ 15.9 68.6 ± 6.8 19.5 ± 0.2
• Before installation work, make sure that the refrigerant
is R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.)
CAUTION
CAUTION Do not have oil adhere to the screw part of resin
This air conditioner is a dedicated model for new parts.
refrigerant R410A. Make sure to meet the requirements If oil adheres, it may weaken the strength of screwed part.
shown below and carry out installation work. Do not tighten nuts too tight.
• Use dedicated piping cutters and tools for If a flare nut cracks, the refrigerant may leak.
R410A.
• When making a connection, coat the inner • If there is no torque wrench, use Table 4 as a rule of
surface only with ether oil or ester oil. thumb.
• Use only the nuts attached to the air conditioner. When tightening a nut with a spanner harder and
If other nuts are used, it may cause refrigerant harder, there is a point where the tightening torque
leakage. suddenly increases.
• To prevent contamination or moisture from getting From that position, tighten the nut additionally the angle
into the piping, take measures such as pinching or shown in Table 4.
taping the pipings. After the work is check securely that there is no
Do not mix substance other than the specified gas leak.
refrigerant such as air into the refrigeration circuit. If the nut is not tightened as instructed, it may cause slow
If the refrigerant leaks during the work, ventilate the refrigerant leak and result in malfunction (such as does
room. not cool or heat).
Fig. 11
3P468397-1F
41
FXFSQ-AVM EDFMT391769C
Gas side piping insulating method • Before brazing refrigerant piping, have nitrogen flow
through the refrigerant piping and substitute air with
Joint insulating nitrogen (NOTE 2) (Refer to Fig. 13). Then, carry out
material (8) brazing (NOTE 3).
(accessory)
After all the brazing works are carry out
Flare nut Piping insulating connection with the indoor unit. (Refer to Fig. 12)
connection material (main unit) Wind around the
piping until top of the
Bring the flare nut connection, Pressure reducing valve
seam Do not leave beginning at the base.
to the top. clearance. Taping
Brazing place
Indoor unit
Nitrogen
Clamp (4)
Piping (accessory) Sealing material
insulating
Tighten the portion (11) Medium-1 Refrigerant piping Stop valve
material
where overlapped by (accessory) Nitrogen
(field supply)
the piping insulating Fig. 13
Do not expose the material.
piping in order to
prevent the vapor NOTE
condensation.
1. After indoor unit installation completed, in case will
perform the air tight test of field pipe and indoor unit,
for air tight test pressure, refer the installation manual
attached in outdoor unit.
2. The proper pressure for having nitrogen through the
piping is approximately 0.02 MPa, a pressure that makes
one feel like breeze and can be obtained through a
pressure reducing valve.
Gas piping 3. Do not use when brazing refrigerant piping.
Piping holding plate screw Use phosphor copper brazing metal (BCuP-2: JIS Z
Liquid piping
(2 points) 3264/B-Cu93P-710/795: ISO 3677) that does not require
Liquid side piping insulating method
(If chlorinated is used, the piping will be corroded and,
Joint insulating in addition if is contained, the refrigerant oil will
material (9) be deteriorated and the refrigerant circuit will be affected
(accessory)
badly.)
Flare nut Piping insulating
connection material (main unit) 4. When carrying out leakage test of refrigerant piping and
Wind around the the indoor unit after the installation of indoor unit is
Bring the piping, beginning finished, confirm the connecting outdoor unit installation
seam Do not leave at the base.
to the top. clearance. manual for test pressure.
Refer to also the outdoor unit installation manual or
technical document for refrigerant piping.
Indoor unit 5. In case of refrigerant shortage due to forgetting additional
refrigerant charge etc., it will result in malfunc tion such as
Piping Clamp (4) Sealing material does not cool or does not heat.
insulating (accessory) (12) Medium-2
material Refer to the outdoor unit installation manual or technical
Tighten the portion (accessory) document for refrigerant piping.
(field supply)
where overlapped by
Do not expose the the piping insulating
material. CAUTION
piping in order to
prevent the vapor Do not use antioxidant when brazing piping.
condensation. It may result in malfunction of components and clogging of
piping due to residue.
Fig. 12
9
3P468397-1F
42
FXFSQ-AVM EDFMT391769C
(850 or less)
Wrong
Adjustable
Metal clamp (2) (accessory) (675 or less)
Fig. 14
Drain hose (1) (accessory)
Upward drain piping
CAUTION Drain riser
If drain stagnates in the drain piping, the piping may be
clogged.
Drain hose (1)
(accessory)
• If downward inclination cannot be ensured,
carry out upward drain piping.
• Install supports at a distance of 1 to 1.5 m so that the
piping may not deflect. (Refer to Fig. 14)
• Make sure to use the attached drain hose (1) and the
metal clamp (2). Level or upward
inclination
CAUTION Keep the drain hose level or make a slight up-grade so
Using old drain hose, clamp fixture may cause water that air may not stagnate in the drain hose.
If air stagnates, the drain may flow oppositely when
leakage.
the drain pump stops and generate abnormal sound.
• Insert the drain hose (1) into the drain socket up to the
point where the socket diameter becomes larger. Fig. 16
Put the metal clamp (2) to the taped hose end and
tighten the metal clamp (2) with torque 1.35±0.15 N·m
(135±15 N·cm).
Hose end
Drain socket Drain hose (1)
(accessory)
Tape
Fig. 15
10
3P468397-1F
43
FXFSQ-AVM EDFMT391769C
CAUTION
• To avoid the attached drain hose (1) getting excessive
force, do not bend nor twist it.
It may cause water leakage.
• In case of centralized drain piping, carry out piping work
according to the procedure shown in the following Fig. 17.
Sealing material (14)
0 ~ 675 mm
(accessory)
Fig. 19
CAUTION
Do not add the external force to float switch.
Centralized drain piping It may cause failure.
Make a downward inclination of 1/100
or more to avoid stagnancy of air. [When the electric wiring work is not finished]
If water stagnates in the drain • For electric wiring operation shall refer the details in
piping, it may cause clogging of “8. ELECTRIC WIRING WORK”
drain piping. • The electric wiring works (including earthing) must be
carried out by a electrician.
Fig. 17
• If a person is not present, after the electric wiring
• As for the size of centralized drain piping, select the size work is check the drainage according to the
that meet the capacity of indoor units to be connected. method in [When the electric wiring work is
(Refer to the technical document) .
• At replacement with new indoor unit, use the attached 1. Open the control box lid and connect the single phase
new drain hose (1) and the metal clamp (2). 220 - 240 V power supply to the terminal (L, N) on the
If an old drain hose or a metal clamp is used, it may terminal block (X2M).
cause water leakage. Connect the earth wiring to the earth terminal. (Refer
to Fig. 20)
Drain piping
11
3P468397-1F
44
FXFSQ-AVM EDFMT391769C
12
3P468397-1F
45
FXFSQ-AVM EDFMT391769C
13
3P468397-1F
46
FXFSQ-AVM EDFMT391769C
The lengths of remote controller wiring and transmission (Abnormal heating may occur if the wirings are not tightened
wirings are as follows: securely.)
(1) Remote controller wiring • Use the required wirings, connect them securely and fix
(indoor unit - remote controller).....................Max. 500 m these wirings securely so that external force may not apply to
(2) Transmission wirings .............Total wiring length 2000 m the terminals.
• Outdoor unit - Indoor unit.............................Max. 1000 m • Use a proper screw driver for tightening the terminal screws.
• Outdoor unit - BS unit ..................................Max. 1000 m If an improper screw driver is used, it may damage the screw
• BS unit - Indoor unit .....................................Max. 1000 m head and a proper tightening cannot be carried out.
• Indoor unit - Indoor unit ...............................Max. 1000 m • If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
NOTE terminals.
1. Shows only in case of protected piping. Use H07RN-F in
Tightening torque (N·m)
case of no protection.
Terminal block for remote controller
2. Supply cords shall not be lighter than polychloroprene 0.88 ± 0.08
and transmission wirings
sheathed flexible cord (code designation 60245 IEC 57)
Terminal for power supply 1.20 ± 0.12
3. Vinyl cord with sheath or cable (Insulated thickness : 1 mm
Earth terminal 1.20 ± 0.12
or more)
4. Wiring size and length must comply with local codes or • Do not carry out soldering when stranded wirings
IEC 60335-1 (Table 11)
are used.
14
3P468397-1F
47
FXFSQ-AVM EDFMT391769C
Transmission
Terminal block for wiring
power supply wiring/
earth wiring (X2M)
Remote
controller wiring
Wiring penetrating
hole (low voltage)
Printed
[Power supply wiring, Earth wiring] Circuit Board
Terminal block for
remote controller wiring/
Sheathed transmission wiring (X1M)
part
wiring
off allowance.)
70 - 90 mm
clamped, cut
off the extra
part.
R10
or more Earth terminal
Fig. 23
15
3P468397-1F
48
FXFSQ-AVM EDFMT391769C
Wiring penetrating hole < No. 2 system: When carrying out group control or 2
remote controller control. >
Power supply wiring/earth
Power supply
wiring or remote controller
220-240 V
wiring/transmission wiring
1~
Sealing material 50 Hz
(Small) (13) or
(accessory) 220-230 V
1~ Outdoor
Putty or insulation 60 Hz unit Note) It is not needed to set the
(field supply) L N indoor unit address when
using group control.
IN/D OUT/D
F1 F2 F1 F2
220-240 V
1~ Indoor unit A
50 Hz
or Remote controller
P1 P2
220-230 V (option)
1~ Outdoor
60 Hz unit
L N
NOTE
IN/D OUT/D
F1 F2 F1 F2 1. Remote controller wiring and transmission wiring have no
polarity.
WARNING
Indoor
unit B Be sure to install an earth leakage breaker.
Failure to do so may cause electric shocks and a
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
16
3P468397-1F
49
FXFSQ-AVM EDFMT391769C
17
3P468397-1F
50
FXFSQ-AVM EDFMT391769C
18
3P468397-1F
51
FXFSQ-AVM EDFMT391769C
CAUTION
After test operation is completed, check the items mentioned
in the clause 2 “2. Items to be checked at delivery” on
page 4.
If the interior work is not completed when the test
operation is for protection of the air conditioner,
ask the customer not operate the air conditioner until the
interior work is completed.
If the air conditioner is operated, the inside of the indoor
units may be polluted by substances generated from the
coating and adhesives used for the interior work
and cause water splash and leakage.
19
3P468397-1F
52
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
●Specifications, designs and other content appearing in this brochure are current as of August 2018 but subject to change without notice.