You are on page 1of 36

EDMFMT391803

201810

Engineering Data

FXMQ-PVM
50 / 60 Hz
FXMQ-PVM EDMFMT391803

FXMQ-PVM
Ceiling Mounted Duct Type
50 / 60 Hz

1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
3. Dimensions..................................................................................................4
4. Piping Diagrams..........................................................................................5
5. Wiring Diagrams..........................................................................................6
6. Electric Characteristics................................................................................7
7. Safety Devices Setting................................................................................8
8. Capacity Tables...........................................................................................9
8.1 Cooling Capacity for Te: Auto............................................................9
8.2 Cooling Capacity for Te: 6°C.............................................................9
8.3 Cooling Capacity for Te: 9°C.............................................................9
9. Fan Performances.....................................................................................10
10. Airflow Auto Adjustment Characteristics...................................................12
11. Sound Levels.............................................................................................14
12. Centre of Gravity.......................................................................................15
13. Accessories...............................................................................................16
13.1 Optional Accessories (for Unit)........................................................16
13.2 Optional Accessories (for Controls).................................................16
14. Installation Manual....................................................................................17

1
FXMQ-PVM EDMFMT391803

1. Lineup

22.4 kW 28.0 kW
Capacity range
8 HP 10 HP
Capacity index 200 250

FXMQ 200PVM 250PVM

VM : 1 phase, 220-240/220 V, 50/60 Hz

2
FXMQ-PVM EDMFMT391803

2. Specifications

Model FXMQ200PVM FXMQ250PVM


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 19,300 24,100
1 2 Cooling capacity Btu/h 76,400 95,500
kW 22.4 28.0
50 Hz kW 0.55 0.67
6 Power input
60 Hz kW 0.55 0.67
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 470×1,490×1,100 470×1,490×1,100
Model KH9X9-PR708 KH9X9-PR708
Type Sirocco fan Sirocco fan
Motor output × W 750 × 1 1,100 × 1
Number of units
m³/min 74/61/50 84/71/58
Fan Airflow rate l/s 1,233/1,017/833 1,400/1,183/967
(HH/H/L)
cfm 2,612/2,153/1,765 2,965/2,506/2,047
External static Pa Rated 150 (250-50) H3 Rated 150 (250-50) H3
pressure
Drive Direct drive Direct drive
Temperature control Microprocessor thermostat for cooling Microprocessor thermostat for cooling
Air filter — H4 — H4
Liquid mm f9.5 (Flare connection) f9.5 (Flare connection)
Piping
connections Gas mm f19.1 (Flange connection) f22.2 (Flange connection)
Drain BSP 1 inch internal thread BSP 1 inch internal thread
Mass kg 95 105
5 Sound pressure level (HH/H/L) dB(A) 42/38/35 44/40/37
Safety devices Fuse, Fan driver overload protector Fuse, Fan driver overload protector
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Operation manual, Installation manual,
Standard accessories Connection pipe with flange, Screws, Clamps Connection pipe with flange, Screws, Clamps
Specification C: 3D117713 C: 3D117713
Drawing No.
Sound level C: 3D118400 C: 3D118342

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / Outdoor temp.: 35°CDB / Rated external static pressure / Equivalent piping Conversion formulae
length: 7.5 m, level difference: 0 m.
kcal/h=kW×860
+2. Capacities are net, including a deduction for cooling for indoor fan motor heat. Btu/h=kW×3412
+3. External static pressure is changeable in 15 stages within the ( ) range by remote controller. cfm=m³/min×35.3
+4. Pre-filter is an optional accessory. There is a slot for pre-filter at the suction flange. l/s=m³/min×1000/60
Other type of filter is not standard accessory, but please mount it in the duct system of the suction side.
Select its dust collection efficiency (gravity method) 50% or more.
+5. Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
These values are normally somewhat higher during actual operation as a result of ambient conditions.
+6. Power input values are based on conditions of rated external static pressure.
7. Refer to Electric Characteristics for the power input when the airflow rate is maximum at maximum external
static pressure.

3
FXMQ-PVM EDMFMT391803

3. Dimensions

FXMQ200PVM / FXMQ250PVM
Unit: mm

3D117990

4
FXMQ-PVM EDMFMT391803

4. Piping Diagrams

FXMQ200PVM / FXMQ250PVM

3D117738

„„ Refrigerant pipe connection port diameters

Unit: mm
Model Gas Liquid
FXMQ200PVM φ19.1
φ9.5
FXMQ250PVM φ22.2

5
FXMQ-PVM EDMFMT391803

5. Wiring Diagrams

FXMQ200PVM / FXMQ250PVM

3D118424A

6
FXMQ-PVM EDMFMT391803

6. Electric Characteristics

FXMQ200PVM / FXMQ250PVM

Power supply IFM Input (W)


Model
Hz Volts Voltage range MCA MFA kW FLA Cooling
FXMQ200PVM Max. 264 6.9 15 0.75 5.5 640
50 220-240
FXMQ250PVM Min. 198 8.8 15 1.10 7.0 810
FXMQ200PVM Max. 242 6.9 15 0.75 5.5 640
60 220
FXMQ250PVM Min. 198 8.8 15 1.10 7.0 810

Symbols:
MCA : Min. Circuit Amps (A)
MFA : Max. Fuse Amps (See note 5)
kW : Fan Motor Rated Output (kW)
FLA : Full Load Amps (A)
IFM : Indoor Fan Motor

Notes:
1. Voltage range
Units are suitable for use on electrical systems where voltage supplied to unit terminals is not below or above listed range limits.
2. Maximum allowable voltage unbalance between phases is 2%.
3. MCA / MFA
MCA = 1.25×FLA
MFA ≤ 4×FLA
(Next lower standard fuse rating. Min. 15 A)
4. Select wire size based on the MCA.
5. Instead of fuse, use circuit breaker.
6. The above IFM and Input is the value when airflow rate is maximum at maximum external static pressure.

3D118443

7
FXMQ-PVM EDMFMT391803

7. Safety Devices Setting

Model FXMQ200PVM FXMQ250PVM


Printed circuit board fuse 250 V, 3.15 A 250 V, 3.15 A
Printed circuit board fuse 250 V, 20 A 250 V, 20 A
(fan driver)
3D117689

8
FXMQ-PVM EDMFMT391803

8. Capacity Tables
8.1 Cooling Capacity for Te: Auto

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ200PVM 200 19.8 15.5 21.0 16.4 22.0 17.2 22.4 17.1 22.7 16.9 23.2 16.3 23.7 15.4
FXMQ250PVM 250 24.7 19.6 26.3 20.9 27.5 21.9 28.0 21.7 28.3 21.4 29.0 20.7 29.6 20.4

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.2 Cooling Capacity for Te: 6°C

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ200PVM 200 15.1 12.9 18.0 14.8 21.0 16.7 22.4 17.1 23.6 17.3 24.2 16.8 24.6 15.9
FXMQ250PVM 250 18.9 16.5 22.5 19.0 26.2 21.3 28.0 21.7 29.5 22.0 30.2 21.3 30.8 20.9

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.3 Cooling Capacity for Te: 9°C

For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXMQ200PVM 200 10.3 10.2 12.6 12.0 16.0 14.1 17.7 14.6 19.1 15.0 20.2 14.7 21.1 14.0
FXMQ250PVM 250 13.0 13.0 16.1 15.5 20.5 18.3 22.4 18.8 24.0 19.1 25.4 18.9 26.6 19.0

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

9
FXMQ-PVM EDMFMT391803

9. Fan Performances

FXMQ200PVM

3D118402

10
FXMQ-PVM EDMFMT391803

FXMQ250PVM

3D119002

11
FXMQ-PVM EDMFMT391803

10. Airflow Auto Adjustment Characteristics

FXMQ200PVM

3D118399

12
FXMQ-PVM EDMFMT391803

FXMQ250PVM

3D118401

13
FXMQ-PVM EDMFMT391803

11. Sound Levels

FXMQ200PVM

C: 3D118400
FXMQ250PVM

C: 3D118342

14
FXMQ-PVM EDMFMT391803

12. Centre of Gravity

FXMQ200PVM / FXMQ250PVM

Unit: mm

3D117734

15
FXMQ-PVM EDMFMT391803

13. Accessories
13.1 Optional Accessories (for Unit)

Model
Item
FXMQ200PVM FXMQ250PVM
8mm pre-filter BAFL501A250
30mm long life replacement filter BAFL502A250
65% BAFM503A250
High efficiency filter
90% BAFH504A250
Filter chamber (long life filter, high efficiency filter) BDD500A250
Drain pump kit BDU510A250VM
Insulation kit for high humidity BDT520A250
3D117737

13.2 Optional Accessories (for Controls)

Model
Item
FXMQ200PVM FXMQ250PVM
Wireless (Note 1) BRC4C66
Remote controller
Wired (Note 1) BRC1C62
Navigation remote controller (Wired remote controller)
BRC1E62 / BRC1E63
(Note 1, 2)
Wired remote controller with weekly schedule timer BRC1D61
Simplified remote controller (Exposed type) BRC2C51
Remote controller for hotel use (Concealed type) BRC3A61
Adaptor for wiring KRP1C13A
Wiring adaptor for electrical appendices (1) KRP2A61
Wiring adaptor for electrical appendices (2) KRP4AA51
Remote sensor (for indoor temperature) KRCS01-6B
External control adaptor for outdoor unit DTA104A61
(Must be installed on indoor units)
Adaptor for multi tenant DTA114A61
Central Remote Controller DCS302CA61
Electrical box with earth terminal (3 blocks) KJB311AA
Unified On/Off Controller DCS301BA61
Electrical box with earth terminal (2 blocks) KJB212AA
Noise filter (for electromagnetic interface use only) KEK26-1A
Schedule Timer DST301BA61
C: 3D118343
Notes:
1. Wireless remote controller does not have AUTO fan mode. Use wired remote controller to select AUTO fan mode.
2. Auto airflow rate can be set only via wired remote controllers BRC1E62/BRC1E63. Cannot be set via other remote controllers.

16
FXMQ-PVM EDMFMT391803

14. Installation Manual

VRV SYSTEM Inverter Air Conditioners Installation manual

CONTENTS • Be sure to use only the specified accessories and parts for installation
work.
1. SAFETY PRECAUTIONS ........................................................1 Failure to use the specified parts may result in the unit falling, water
2. BEFORE INSTALLATION ........................................................2 leakage, electric shocks or fire.
3. SELECTING INSTALLATION SITE .........................................3 • Install the air conditioner on a foundation strong enough to withstand
4. PREPARATIONS BEFORE INSTALLATION ............................4 the weight of the unit.
A foundation of insufficient strength may result in the equipment falling
5. INDOOR UNIT INSTALLATION ...............................................5 down and causing injury.
6. REFRIGERANT PIPING WORK .............................................5 • Carry out the specified installation work after taking into account strong
7. DRAIN PIPING WORK ............................................................7 winds, typhoons or earthquakes.
8. DUCT WORK...........................................................................8 Failure to do so during installation work may result in the unit falling and
causing accidents.
9. ELECTRIC WIRING WORK.....................................................8
• Make sure that a separate power supply circuit is provided for this
10. WIRING EXAMPLE AND HOW TO SET THE REMOTE unit and that all electrical work is carried out by qualified personnel
CONTROLLER ........................................................................9 according to local laws and regulations and this installation manual.
11. FIELD SETTING ....................................................................11 An insufficient power supply capacity or improper electrical construction
12. TEST OPERATION................................................................12 may lead to electric shocks or fire.
• Make sure that all wiring is secured, the specified wires are used, and
13. APPENDIX ............................................................................13 that there is no strain on the terminal connections or wires.
Improper connections or securing of wires may result in abnormal heat
1. SAFETY PRECAUTIONS build-up or fire.
Please read these “SAFETY PRECAUTIONS" carefully before installing • When wiring the power supply and connecting the remote controller
air conditioning unit and be sure to install it correctly. After completing the wiring and transmission wiring, position the wires so that the control box
installation, make sure that the unit operates properly during the start-up lid can be securely fastened. Improper positioning of the control box lid
operation. may result in electric shocks, fire or the terminals overheating.
After completing installation, conduct a trial operation to check for faults • If the supply cord is damaged, it must be replaced by manufacturer, its
and explain to the customer how to operate the air conditioner and take service agent or similarly qualified persons in order to avoid hazard.
care of it with the aid of the operation manual. Ask the customer to store the • If refrigerant gas leaks during installation, ventilate the area immediately.
installation manual along with the operation manual for future reference. Toxic gas may be produced if the refrigerant comes into contact with
This air conditioner comes under the term “appliances not accessible fire.
to the general public”. • After completing installation,check for refrigerant gas leakage. Toxic gas
may be produced if the refrigerant gas leaks into the room and comes
Safety Precaution into contact with a source of fire, such as a fan heater, stove or cooker.
This unit is a class A product. In a domestic environment this product may • Be sure to switch off the unit before touching any electrical parts.
cause radio interference in which case the user may be required to take • Be sure to earth the air conditioner.
adequate measures. Do not earth the unit to a utility pipe, lightning conductor or
Meaning of WARNING and CAUTION notices telephone earth lead. Imperfect earthing may result in electric shocks
Failure to follow these instructions properly may or fire.
WARNING result in personal injury or loss of life. A high surge current from lightning or other sources may
cause damage to the air conditioner.
Failure to observe these instructions properly
CAUTION may result in property damage or personal
• Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in electric shocks
injury, which may be serious depending on the
or fire.
circumstances.
• Do not directly touch refrigerant that has leaked from refrigerant pipes
WARNING or other areas, as there is a danger of frostbite.
• Do not allow children to climb on the outdoor unit and avoid placing
• Ask your dealer or qualified personnel to carry out installation work. objects on the unit.
Do not attempt to install the air conditioner yourself. Improper Injury may result if the unit becomes loose and falls.
installation may result in water leakage, electric shocks or fire. • After turning off the power, do not open the lid of the electric box for 10
• This appliance is not intended for use by persons (including children) minutes in order to avoid electric shocks by high voltage . After opening
with reduced physical, sensory or mental capabilities, or lack of the lid, measure the voltage at the location using a tester, and make
experience and knowledge, unless they have been given supervision or sure that the voltage is 50VDC or lower. Do not touch the live parts
instruction concerning use of the appliance by a person responsible for during the measurement.
their safety. Children should be supervised to ensure that they do not
play with the appliance.
CAUTION
• Install the air conditioner in accordance with the instructions in this
installation manual. • While following the instructions in this installation manual, install
Improper installation may result in water leakage, electric shocks or fire. drain piping to ensure proper drainage and insulate piping to prevent
• Consult your local dealer regarding what to do in case of refrigerant condensation.
leakage.When the air conditioner is to be installed in a small room, Improper drain piping may result in indoor water leakage and property
it is necessary to take proper measures so that the amount of any damage.
leaked refrigerant does not exceed the concentration limit in the event • Install the indoor and outdoor units, power cord and connecting wires
of a leakage. Otherwise, this may lead to an accident due to oxygen at least 1 meter away from televisions or radios to prevent picture
depletion. interference and noise. (Depending on the incoming signal strength, a
• Please instruct the customer on how to operate the unit and keep it distance of 1 meter may not be sufficient to eliminate noise.)
maintained.

English 1

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 1 10/9/2018 6:26:27 PM
17
FXMQ-PVM EDMFMT391803

• Remote controller (wireless kit) transmitting distance can be shorter Disposal requirements
than expected in rooms with electronic fluorescent lamps (inverter or
Dismantling of the unit, treatment of the refrigerant, of oil and of other parts
rapid start types). must be done in accordance with relevant local and national legislation.
Install the indoor unit as far as possible from fluorescent lamps as
possible. Follow national standards for installation work.
• Make sure to provide for adequate measure in order to prevent that the
outdoor unit be used as a shelter by small animals.
2. BEFORE INSTALLATION
• Small animals making contact with electrical parts can cause
malfunctions, smoke or fire. Please instruct the customer to keep the • When moving the unit while removing it from the carton box, be
area around the unit clean. sure to lift it by holding on to the four lifting lugs without exerting
• Do not install the air conditioner in the following locations: any pressure on other parts, especially, the refrigerant piping,
drain piping, and other resin parts.
1) Where there is a high concentration of mineral oil spray or vapour
• Be sure to check the type of R410A refrigerant to be used before
(e.g. a kitchen).
installing the unit. (Using an incorrect refrigerant will prevent normal
Plastic parts will deteriorate, parts may fall off and water leakage operation of the unit.)
could result. • The accessories needed for installation must be retained in your
2) Where corrosive gas, such as sulphurous acid gas, is produced. custody until the installation work is completed. Do not discard them!
Corroding of copper pipes or soldered parts may result in • Decide upon a line of transport. Decide transportation medium.
refrigerant leakage. • Leave the unit inside its packaging while moving, until reaching the
3) Near machinery emitting electromagnetic radiation. installation site. Where unpacking is unavoidable, use a sling of soft
Electromagnetic radiation may disturb the operation of the control material or protective plates together with a rope when lifting, to avoid
system and result in a malfunction of the unit. damage or scratches to the unit.
4) Where flammable gas may leak, where there is carbon fibre or • For the installation of an outdoor unit, refer to the installation manual
ignitable dust suspensions in the air, or where volatile flammables attached to the outdoor unit.
such as paint thinner or gasoline are handled. • Do not install or operate the unit in rooms mentioned below.
Operating the unit in such conditions may result in fire. 1) Laden with mineral oil, or filled with oil vapor or spray like in
• The air conditioner is not intended for use in a potentially explosive kitchens. (Plastic parts may deteriorate which could eventually
atmosphere. cause the unit to fall out of place, or could lead to leaks.)
• Do not touch the heat exchanger fins. 2) Where corrosive gas like sulfurous gas exists.
Improper handling may result in injury. (Copper tubing and brazed spots may corrode which could
• Be very careful about product transportation. eventually lead to refrigerant leaks.)
• Some products use PP bands for packaging. Do not use any PP bands 3) Where exposed to combustible gases and where volatile
for a means of transportation. It is dangerous. flammable gas like thinner or gasoline is used.
• Safely dispose of the packing materials. (Gas in the vicinity of the unit could ignite.)
• Packing materials, such as nails and other metal or wooden parts, may 4) Where machines can generate electromagnetic waves. (Control
cause stabs or other injuries. system may malfunction.)
Tear apart and throw away plastic packaging bags so that children will
5) Where the air contains high levels of salt such as that near
not play with them. If children play with a plastic bag which was not torn
the ocean and where voltage fluctuates greatly such as that in
apart, they face the risk of suffocation.
factories.
• Do not turn off the power immediately after stopping operation. Always Also in vehicles or vessels.
wait at least 5 minutes before turning off the power. • This unit, both indoor and outdoor, is suitable for installation in a
Otherwise, water leakage and trouble may occur. commercial and light industrial environment.
• In a domestic environment this product may cause radio interference in If installed as a household appliance it could cause electromagnetic
which case the user may be required to take adequate measures. interference.
• Wear protective gloves when working on the unit. Failure to do so may
result in injury 2-1 PRECAUTIONS
• Be sure to read this manual before installing the indoor unit.
• Entrust installation to the place of purchase or a qualified serviceman.
Special notice of product Improper installation could lead to leaks and, in worse cases, electric
• The refrigerant R410A requires that strict precautions be observed for shock or fire.
keeping the system clean, dry and tightly sealed. • Use only parts provided with the unit or parts satisfying required
1) Clean and dry specifications. Unspecified parts could cause the unit to fall out of place,
Strict measures must be taken to keep impurities (including SUNISO or could lead to leaks and, in worse cases, electric shock or fire.
oil and other mineral oils as well as moisture) out of the system. • Be sure to mount an air filter (part to be procured in the field) in the
2) Tight sealed suction air passage in order to prevent water leaking, etc.
R410A will contribute only slightly to the greenhouse effect if
released into the atmosphere. Therefore, sealing tightness is
particularly important in installation. Carefully read the chapter
"REFRIGERANT PIPING" and strictly observe the correct
procedures.
• Since design pressure is 4.0 MPa or 40 bar, the thickness of pipes
must be greater than previously. Since R410A is a mixed refrigerant,
the required additional refrigerant must be charged in its liquid state.
(If the system is charged with refrigerant in its gaseous state, due to
composition change, the system will not function normally) The indoor
units is designed for R410A use. See the catalogue for indoor unit
models that can be connected. (Normal operation is not possible when
connecting units that are originally designed for other refrigerants)

2 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 2 10/9/2018 6:26:27 PM
18
FXMQ-PVM EDMFMT391803

2-2 ACCESSORIES Items to be checked If not properly done, what is Check


likely to occur
Check that the following accessories are provided and that each accessory
is correct in amount. Are refrigerant piping length and The refrigerant charge in the
Refer to the Fig. 1 of this sheet. additional refrigerant charge noted system is not clear.
down?
[PRECAUTION] Did you check that no wiring
connection screws were loose? Electric shock or fire.
The accessories are required for the installation of the air conditioner. Be
sure to keep them until the installation work is completed.
Also review the "SAFETY PRECAUTIONS".
b. Items to be checked at the time of delivery
Items to be checked Check
Operation manual Are you sure the control box lid, air filter, air inlet grille, and air
Instruction manual outlet grille are mounted?
Did you explain about operations while showing the operation
(1) - (6) manual to your customer?
Did you deliver the operation manual along with the installation
Fig. 1 manual to the customer?
Attached Screws for duct Did you explain the customer the handling and cleaning methods
Name Washer (3) Clamp (4) of the field supplies (e.g., the air filter, air inlet grilles, and air
piping (1) flanges (2)
Quantity 1 pc. 45 pcs. 8 pcs. 1 pc. outlet grille)?
Did you deliver instruction manual, if any, for the field supplies to
Shape the customer?
M5x12
c. Points for explanation about operations
Hexagon head Spring washer (6)
Name (Other)
bolt (5) The items with WARNING and CAUTION marks in the instruction
Quantity 2pcs. 2pcs. 1 each. manual are the items pertaining to possibilities for bodily injury and
material damage in addition to the general usage of the product.
• Operation manual
Shape • Installation manual Accordingly, it is necessary that you make a full explanation about the
M10x40 described contents and also ask your customers to read the instruction
manual.
2-3 OPTIONAL ACCESSORIES
• These are two types of remote controllers: wired and wireless. Select 2-4 NOTE TO INSTALLER
a remote controller according to customer request and install in an
appropriate place. • Be sure to instruct customers how to properly operate the unit
(especially cleaning filters, operating different functions, and
Table 1 adjusting the temperature) by having them carry out operations
Remote controller themselves while looking at the manual.
Wired type
Wireless type
Heat pump type 3. SELECTING INSTALLATION SITE
Cooling only type
Hold the hanging brackets in the case of moving the indoor and
NOTE outdoor units at the time of and after opening the packages. Do not
• If you wish to use a remote controller that is not listed in Table 1, select impose undue force on other parts, such as the refrigerant piping,
a suitable remote controller after consulting catalogs and technical drain piping, or flanges, in particular.
materials. Add heat insulation material to the indoor unit if the temperature
FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE above the ceiling is likely to exceed 30°C and a relative humidity of
DURING CONSTRUCTION AND CHECK AFTER 80%.
Make sure that the insulation material is made of glass wool or
INSTALLATION IS FINISHED. polyethylene foam, which has a minimum thickness of 10 mm, and
a. Items to be checked after completion of work can be accommodated in the opening on the ceiling.
If not properly done, what is (1) Select an installation site where the following conditions are fulfilled
Items to be checked likely to occur Check and that meets with your customer's approval.
Are the indoor and outdoor unit The units may drop, vibrate or • A place where cool (warm) air is delivered to the entire room.
fixed firmly? make noise. • In the upper space (including the back of the ceiling) of the
Was the installation of the outdoor The unit may malfunction or indoor unit where there is no possible dripping of water from
unit completed? the components burn out. the refrigerant pipe, drain pipe, water pipe, etc.
Is the gas leak test finished? No cooling or heating. • Where optimum air distribution can be ensured.
Is the unit fully insulated? • Where nothing blocks the air passage.
(Refrigerant piping, drain piping, Condensate water may drip. • Where condensation can be properly drained.
and duct) • If supporting structural members are not strong enough to
Does drainage flow smoothly? Condensate water may drip. take the unit's weight, the unit could fall out of place and cause
Does the power supply voltage serious injury.
The unit may malfunction or • Where the false ceiling is not noticeably on an incline.
confirm to the indication on the the components burn out.
name plate? • Where there is no risk of flammable gas leakage.
Are wiring and piping correct? The unit may malfunction or • Where sufficient clearance for maintenance and service can be
the components burn out ensured. (Refer to Fig. 2)
Is the air conditioner properly Dangerous in case of current • Where piping between indoor and outdoor units is possible
grounded? leakage. within the allowable limit.
Is wiring size according to The unit may malfunction or (Refer to the installation manual of the outdoor unit.)
specifications? the components burn out. • Install in a machine room that is free of moisture. The unit is
Is something blocking the air outlet designed for indoor use.
or inlet of either the indoor or No cooling or heating.
outdoor units?
Did you set the external static No cooling or heating.
pressure?

English 3

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 3 10/9/2018 6:26:27 PM
19
FXMQ-PVM EDMFMT391803

CAUTION 4. PREPARATIONS BEFORE INSTALLATION


(1) Relative positions of indoor unit and suspension bolt.
• Install the indoor and outdoor units, power supply wiring and
connecting wires at least 1 meter away from televisions or radios in
1101 Suspension
order to prevent image interference or noise. (Depending on the radio bolt (x4)
1028
waves, a distance of 1 meter may not be sufficient enough to eliminate
the noise.)
• In the case of the installation of a wireless remote controller, the
transmission distance of the wireless remote controller may be
shortened if the room has a fluorescent light of electronic lighting type
(i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent light as far
as possible.
Indoor unit

1526
1490
(2) Use suspension bolts for installation. Check whether the celling is
strong enough to support the weight of the unit or not. If there is a Air outlet Air inlet
risk, reinforce the ceiling before installing the unit
Min. 20
H1=470
H2=Min. 790

(Service space)

Approx. 150mm
650 or more
(if no ceiling board is provided)
Min. 300

Ceiling Inspection hatch


(600 x 600)
Min. 2500

1143 or more
(Service space)
(Length in mm)
Floor surface
Side view Top view

Fig 3

(2) Mount the canvas ducts to the air outlet and inlet so that the
vibration of the air conditioner will not be transmitted to the duct
or ceiling. Apply a sound-absorbing material (insulation material)
to the inner wall of the duct and vibration insulation rubber to the
hanging bolts (refer to 8. DUCT WORK).
(3) Open installation holes (if the ceiling already exists).
• Open the installation holes on the ceiling. Lay the refrigerant piping,
drain piping, power line, transmission wiring, and remote controller
wiring for the piping and wiring connection port of the unit.
In the case of the installation of a wireless remote controller, refer to
the installation manual provided with the wireless remote controller.
Refer to 6. REFRIGERANT PIPING WORK, 7. DRAIN PIPING
(Services Space)

WORK, and 10. WIRING EXAMPLE AND HOW TO SET THE


Min. 650

REMOTE CONTROLLER.
• The ceiling framework may need reinforcement in order to keep the
Min. 1143 (Services Space)
ceiling horizontal and prevent the vibration of the ceiling after the
(Length in mm)
installation holes are opened. For details, consult your construction
Top view or interior contractor.

Fig. 2
• The H1 dimension indicates the height of the product.
[Required installation place]
The dimensions indicate the minimum required space of installation.
• Determine the H2 dimension by maintaining a downward slope of at
least 1/100 as specified in “7. DRAIN PIPING WORK”.

4 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 4 10/9/2018 6:26:27 PM
20
FXMQ-PVM EDMFMT391803

(4) Install the hanging bolts. Make sure that the hanging bolts are M10
in size. CAUTION
• Use hole-in anchors if the hanging bolts already exist; otherwise Setting the unit at an angle opposite to the drain piping might cause
use embedded inserts and embedded foundation bolts so that they water leaks.
will withstand the weight of the unit.
Adjust the distance to the ceiling surface in advance.
6. REFRIGERANT PIPING WORK
(Installation example) As for the refrigerant piping of the outdoor unit, refer to the
Ceiling slab
installation manual provided to the outdoor unit.
Anchor Perform heat insulation work on both gas piping and liquid piping, or
Long nut or turn-buckle otherwise water leakage may occur.
Use the insulation material that withstands a temperature of 120°C.
Reinforce the insulation material for the refrigerant piping if the
ambient temperature is high, or otherwise dew condensation may
occur on the surface of the insulation material.
Indoor unit Make sure that the refrigerant Is R410A before refrigerant piping
Note) All the above parts are field supplied
work. If the refrigerant is different, the air conditioner will not operate
5. INDOOR UNIT INSTALLATION normally.
It may be easier to install accessories (sold separately) before CAUTION
installing the indoor unit. Refer to the installation manuals provided to
the accessories as well. This product uses new refrigerant (R410A) only. Be sure to keep the
Be sure to use the accessories and specified parts for installation items on the right-hand side and conduct the installation work.
work. • Use an appropriate pipe cutter and flare tool for R410A.
(1) Fix the hanger bracket to the suspension bolt. Tighten both upper and • When connecting the flare, apply ether oil or ester oil only to inner
lower nuts firmly using washers. side of the flare.
• Be sure to use the flare nut provided with the unit. (Do not use
Nut (Upper side) a different flare nut (such as a type-1 flare nut), or otherwise
(Field Supply) refrigerant leakage may result.)
Washer (3) (Accessory) • Perform the curing of the piping with pinching or taping of the
piping in order to prevent the intrusion of dirt, dust, and moisture
into the piping.
Hanging Bracket
CAUTION
Tighten from • Be sure to use the specified type of refrigerant for the refrigeration
above and Double nut (Lower side) cycle and do not contaminate the refrigerant with air.
below (Field Supply) • Ventilate the room in case of refrigerant leakage during installation
work.
(2) Make adjustments so that the unit will be in the right position.
(3) Make sure the unit is level. (1) Connect the liquid piping.
• The outdoor unit is filled with refrigerant.
• Use the level and check that the unit is installed horizontally • When connecting or disconnecting piping to or from the unit, be
(4-directions). sure to use two spanners and two torque wrenches. (Refer to
• In the case of using a vinyl tube in place of the level, put the both Fig.4)
edges of the vinyl tube in close contact with the bottom of the Torque wrench
product to make levelness adjustment.
Level

Spanner
Flare nut

Piping union
Hanging bracket
Fig. 4
• Refer to Table 2 for the processing dimensions of the flare.
Bottom of product • Use the flare nut provided with the unit.
Vinly tube
• Apply ether oil or ester oil only to inner side of the flare and
screw in the flare nut three to four turns first by hand at the time of
(4) Tighten the nuts on the upper side of hanging bracket. connecting the flare nut.
(Refer to Fig.5)

English 5

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 5 10/9/2018 6:26:28 PM
21
FXMQ-PVM EDMFMT391803

(4) Refer to the illustration on the right-hand side and be sure to perform
Apply ester oil or ether oil
only to inner side of flare. heat insulation work on the piping joints after gas leakage checks.
(Refer to Fig. 6)
Heat insulation procedure for liquid piping

Insulation material for piping


Fig. 5 (On unit side) Insulation
• Refer to Table 2 for the corresponding tightening torque. Attached to the surface
(field supply)
Flare nut joint Make sure the seam
Table 2 (Unit:mm) faces upward

Flare
Pipe
Tightening torque dimensions Flare shape
size Main unit
A (mm)
Insulation material for piping
Clamp (Field supply)
45°±2°
(field supply)
R0.4-0.8
90°±2°

ø 9.5 32.7 - 39.9N.m 12.8 - 13.2


A

CAUTION
• Do not excessively tighten the flare nut. Insulation
(Field supply)
Liquid pipe
Doing so will break the flare nut and refrigerant leakage may occur.
• Make sure that all parts around the flare are free of oil.
The drain pan and the resin part may be deteriorated if oil is
attached. Gas pipe

• If no torque wrenches are available, refer to Table 3 as a standard.


When the flare nut is tightened with the spanner, the tightening
torque should increase suddenly. Tighten the flare nut further for the
corresponding angle shown in Table 3. Fig. 6
Table 3 (Unit:mm)
Pipe size Further tightening angle Recommended arm lenght of tool Heat insulation procedure for gas piping

ø 9.5 60 to 90 degrees Approx. 200mm


Insulation (Field supply)
(2) On completion of installation work, check that there is no gas Attached to the surface
leakage. Attached piping (1)
(Accessory)
(3) Be sure to perform heat insulation work on the piping joints after gas
leakage checks. Main unit
NOTE Hexagon head bolt (5)
Insulation material for piping & spring washer (6)
• Attached piping is needed for connecting gas piping. Use attached (On unit side) (Accessory)
piping according to the size of the piping to be connected.
When connecting the included piping, use the included piping flange
hex bolts (5) and spring washers (6).
• Connect refrigerant piping and branching according to the attached
installation manuals that come with the outdoor unit. • Use the insulation (field supply) to the liquid piping and gas piping
respectively, and conduct heat insulation work.
(Unit:mm) (Tighten both edges of the insulation for each joint with the clamp (field
Indoor units to be supply)).
Gas piping diameter Liquid piping diameter
connected
ø19.1
FXMQ200PVM ø9.5
Use attached piping (1).
ø22.2
FXMQ250PVM ø9.5
Use attached piping (1).

6 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 6 10/9/2018 6:26:28 PM
22
FXMQ-PVM EDMFMT391803

CAUTION BSP 1" internal thread

• Be sure to perform the heat insulation of the local piping up Safety drain tray
to the piping joint.

Slope
(Field supply)
1° or more
If the piping is exposed, dew condensation may result.
Furthermore, a burn may be caused if a human body comes in
contact with the piping.

• Perform nitrogen substituent or apply nitrogen into the


refrigerant piping (see as below NOTE 1) in the case of
refrigerant piping brazing (see NOTE 2).Then perform the flare
connection of the indoor unit. (Refer to Fig.7)

Refrigerant Pressure reducing valve


piping Part to be Taping
brazed
hands
valve

Nitrogen
Fig.7
Fig. 9
CAUTION (2) After piping work is finished, check drainage flows smoothly by
pouring approximately 1 Liter of water gradually into the drain tray and
• Do not use any antioxidant at the time of piping brazing. check drainage flow (Fig. 10).
The piping may be clogged with a residual antioxidant and parts
may malfunction.

NOTE
1. At the time of brazing, set the pressure of nitrogen to approximately
0.02 MPa (close to the pressure of a breeze coming in contact with the
cheek) with a decompression valve.
2. Do not use flux at the time of brazing and connecting the refrigerant Watering can Refrigerant pipes
piping. Use a copper phosphorus brazing alloy (BCuP-2: JIS Z 3264/ Drain outlet
Drain pan
BCu 93P-710/795: ISO3677), which does not require flux, for brazing.
(Flux has a bad influence on the refrigerant piping. Chlorine-based flux Fig. 10
will cause piping corrosion. Furthermore, if it contains fluorine, the flux
will deteriorate refrigerant oil.) CAUTION
3. As for the branching of the refrigerant piping or refrigerant, refer to the
installation manual provided with the outdoor unit. • Drain piping connections.
Do not connect the drain piping directly to sewage pipes that
7. DRAIN PIPING WORK smell of ammonia. The ammonia in the sewage might enter
Rig the drain pipe as shown below (Fig. 8) and take measures against the indoor unit through the drain pipes and corrode the heat
condensation. Improperly rigged piping could lead to leaks and exchanger.
eventually wet furniture and belongings. • To ensure the proper drainage of water, please follow Fig. 11
Insulate the drain hose inside the building. during installing the unit.
• Be sure the suction side or drain socket side of the unit is not
BSP 1" internal thread higher than unit, otherwise will result in water leakage from the
Attached to the Adapter (Field unit.
surface supply) Make sure that the seam
Metal clamp face upward
(Field supply)

Suction Side Drain Socket


Main unit

Insulation material for drain pipe


(Field supply)

Suction Side Drain Socket


Fig. 8
(1) Carry out the drain piping.
• A drain trap need not be installed. 1° or less 1° or less
• Route the pipes so as to ensure that drainage can occur with no
problems. (Fig. 9).
• The diameter of the piping is the same as that of the connecting pipe Suction Side
Drain Socket
(BSP 1 inch), and should be kept equal to or greater than that of the
connecting pipe.
Fig. 11
• Make sure that the piping is short enough with a downward slope
of at least 1/100 and that there is no air bank formed. No drain trap
is required.
• Conduct drain-up piping work if the gradient is insufficient.
• Attach a support bracket at 1 to 1.5 m intervals for the prevention of
piping deflection.

English 7

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 7 10/9/2018 6:26:28 PM
23
FXMQ-PVM EDMFMT391803

8. DUCT WORK 9. ELECTRIC WIRING WORK


Pay utmost attention to the following items and conduct the ductwork. 9-1 GENERAL INSTRUCTIONS
• Check that the duct will not be in excess of the setting range of external
static pressure for the unit. (Refer to the technical datasheet for the Shut off the power before starting any work.
setting range. Each model has each setting range of external static • All field supplied parts and materials and electric works must conform to
pressure.) local codes.
• Attach a canvas duct each to the air outlet and air inlet so that the • Use copper wire only.
vibration of the equipment will not be transmitted to the duct or ceiling. • For electric wiring work, refer to also "Wiring diagram label" attached to
Use a sound-absorbing material (insulation material) for the lining of the the control box lid.
duct and apply vibration insulation rubber to the hanging bolts. • For remote controller wiring details, refer to the installation manual
• At the time of duct welding, perform the curing of the duct so that the attached to the remote controller.
spatter will not come in contact with the drain pan or the filter. • All wiring must be performed by an authorized electrician.
• If the metal duct pass through a metal lath, wire lath, or metal plate of a • This system consists of multiple indoor units. Mark each indoor unit as
wooden structure, separate the duct and wall electrically. unit A, unit B..., and be sure the terminal board wiring to the outdoor
• Be sure to heat insulate the duct for the prevention of dew condensation. unit and BS unit are properly matched. If wiring and piping between the
(Material: Glass wool or styrene foam; Thickness: 25 mm) outdoor unit and an indoor unit are mismatched, the system may cause
• Be sure to attach the air filter (optional accessory, can be purchase a malfunction.
separately) to the air inlet of the unit. (Be sure to select an air filter with • A circuit breaker capable of shutting down power supply to the entire
a dust collection efficiency of 50 percent weight.) system must be installed.
• Explain the operation and washing methods of the locally procured • Refer to the installation manual attached to the outdoor unit for the size
components (i.e., the air filter, air inlet grille, and air outlet grille) to the of power supply wiring connected to the outdoor unit, the capacity of the
customer. circuit breaker and switch, and wiring instructions.
• Locate the air outlet grille on the indoor side for the prevention of drafts • Be sure to ground the air conditioner.
in a position where indirect contact with people. • The grounding resistance value should be 100  or less. When an earth
• The air conditioner incorporates a function to adjust the fan to rated leakage circuit breaker is installed, the protective earth resistance value
speed automatically. (11. FIELD SETTING) can be applied and it can be set to 500  or less
Therefore, do not use booster fans midway in the duct. • The type of earthing is equipment earthing.
• Do not connect the ground wire to gas and water pipes, lightning rods,
Connection method of ducts on air inlet and outlet sides. or telephone ground wires.
• Connect the field supply duct in alignment with the inner side of the • Gas pipes : might cause explosions or fire if gas leaks.
flange. • Water pipes : no grounding effect if hard vinyl piping is used.
• Connect the flange and unit with the flange connection screw (2). • Telephone ground wires or lightning rods : might cause abnormally
• Wrap aluminum tape around the flange and duct joint in order to high electric potential in the ground during lighting storms.
prevent air leakage.
9-2 ELECTRICAL CHARACTERISTICS
Flange on air inlet side Flange on air outlet side Power
(provided with the unit) (provided with the unit) Units Fan motor
supply
Screws for duct Insulation material Voltage
Model Hz Volts MCA MFA kW FLA
flanges (2) (field supply) range
(accessory) FXMQ200PVM 6.9 15 0.750x1 5.5
220- Max. 264
Air inlet Unit Air outlet 50
FXMQ250PVM 240 Min. 198 8.8 15 1.100x1 7.0
Screws for duct
flanges (2) FXMQ200PVM 6.9 15 0.750x1 5.5
Max. 242
(accessory) 60 220
Insulation material FXMQ250PVM Min. 198 8.8 15 1.100x1 7.0
Canvas duct
(field supply) (field supply)
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
CAUTION kW: Fan Motor Rated Output (kW); FLA: Full Load Amps (A)

Connect the flange and unit with the flange connection screw (2)
9-3 SPECIFICATIONS FOR FIELD SUPPLIED FUSES
regardless of whether the duct is connected to the air inlet side. AND WIRE
Remote controller wiring
Power supply wiring
Transmission wiring
Model Field
fuses Wire Size Wire Size

FXMQ200PVM Sheathed
H07RN-F 2.5mm2 0.75 - 1.25
15A wire (2 wire)
(Note 2) (Note 4) mm2
FXMQ250PVM (Note 3)

NOTE
1. Allowable length of transmission wiring between indoor/outdoor units
and between the indoor unit and the remote controller is as follows.
(a) Outdoor unit - Indoor unit:
Max.1000 m (Total wiring length: 2000 m)
(b) Indoor unit - Remote controller:
Max. 500m
2. Shows only in case of protected piping.
3. Vinyl cord with sheath or cable (Insulated thickness : 1 mm or more).
Use H07RN-F or compatible with it.
4. This size is based on IEC 60335-1 (Table 11), and this size must
comply with local codes.
5. Recommended to use slow blow fuse type.

8 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 8 10/9/2018 6:26:28 PM
24
FXMQ-PVM EDMFMT391803

10. WIRING EXAMPLE AND HOW TO SET THE [PRECAUTIONS FOR POWER SUPPLY WIRING]
REMOTE CONTROLLER • Connect round crimp-style terminals provided with insulation sleeves to
the terminal block for power supply.
10-1 HOW TO CONNECT WIRINGS Attach insulation sleeve
1) Remove the control box lid and wire as shown in the figure below.

Round crimp-style terminal


Electric wire
Be sure to follow the instructions provided below if the specified
terminals cannot be used.
Otherwise, abnormal heat may be generated as a result of the
loosening of the wires.
Connect the Do not connect a Do not connect wires
wires evenly. wire to the single different from each
side only. other in diameter.

• If stranded wires are used, do not solder the front end of the wires.
2) Lay the wires in the control box through the wire inlet on the front of the • Connect proper wires securely and fix the wires so that external force
control box. will not be imposed on the terminals.
Low voltage wiring Remote
• Use an appropriate screwdriver to tighten the terminal screws. The
connection method
About
control wiring screw heads may be damaged if the screwdriver is too small and the
• If stranded of sleeve area
wires are used, 7 mm terminal screws will not be tightened properly.
do not solder After
the front end of scalping
• Do not tighten the terminal screws excessively, or otherwise the screw
High voltage wiring connection method
the wires. wiring,
twisted 70~90mm
heads may be damaged.
PROHIBITED together
Operation
Sleeve area Power supply terminal
strip (X1M)
• Refer to the table below for the required tightening torque values of the
Never connect
the power supply terminal strip
(X2M) Transmission terminal screws.
wiring. wiring
70~90mm
(No polarity)
Tightening torque (N·m)
P1 P2 F1 F2 T1 T2

(Sleeve stripping
length) L N
Terminal block for remote controller and
Power Earth 0.80 - 0.96
Remote
controller wiring
supply wire
wiring
transmission wires
(No polarity)
Terminal block for power supply 1.18 - 1.44

[ PRECAUTIONS ]
• Do not connect wires of different gauge to the same grounding terminal.
Looseness in the connection may deteriorate protection.
Terminal block for
Remote Controller
Power Supply
Terminal block
• Outside of the unit, keep transmission wiring at least 50 mm away from
power supply wiring. The equipment may malfunction if subjected to
electrical (external) noise.
Clamp
(accessory) Remote controller wiring • For remote controller wiring, refer to the “INSTALLATION MANUAL OF
Transmission wiring
Power supply wiring, ground wiring REMOTE CONTROLLER” attached to the remote controller.
• Never connect power supply wiring to the terminal block for
remote controller wiring. A mistake of the sort could damage the
CAUTION entire system.
• Be sure to attach the sealing material or putty (field supplied) to • Use only specified wire and tightly connect wires to terminals. Be
hole of wiring to prevent the infiltration of water as well as any careful wires do not place external stress on terminals. Keep wiring in
insects and other small creatures from outside. neat order and so as not to obstruct other equipment such as popping
Otherwise a short-circuit may occur inside the control box. open the control box lid. Make sure the lid closes tight. Incomplete
• When clamping the wires, be sure no pressure is applied to the connections could result in overheating, and in worse case, electric
wire connections by using the included clamping material to shock or fire.
make appropriate clamps. Also, when wiring, make sure the lid
on the control box fits snugly by arranging the wires neatly and
attaching the control box lid firmly. When attaching the control
box lid, make sure no wires get caught in the edges. Pass wiring
through the wiring through holes to prevent damage to them.
• Make sure the remote controller wiring, the wiring between the
units, and other electrical wiring do not pass through the same
locations outside of the unit, separating them by at least 50mm,
otherwise electrical noise (external static) could cause mistaken
operation or breakage.

English 9

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 9 10/9/2018 6:26:28 PM
25
FXMQ-PVM EDMFMT391803

10-2 WIRING EXAMPLE 3. When including BS unit


Power
WARNING supply Outdoor unit
220- Control box
Install an earth leakage breaker and miniature circuit breaker 240V
IN/D OUT/D
F1 F2 F1 F2
or molded case circuit breaker. 1~
L N
BS unit BS unit
The installation of an earth leakage breaker is imperative for the 50Hz or No. 3 Control box Control box
prevention of electric shocks and fire accidents. 220V System OUT/D IN/D
F1 F2 F1 F2
OUT/D IN/D
F1 F2 F1 F2
1~
Selection of earth circuit breaker 60Hz
• To prevent electric shock accidents, a current-operating-type
leakage breaker shall be used, and the sensed current shall
be selected according to the protective grounding resistance Indoor unit A L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
Most
so that the contact voltage does not exceed 50V. The operation downstream
time shall be 0.1 second or less. indoor unit

• Fit the power supply wiring of each unit with a switch and fuse
as shown in the drawing. P1 P2 P1 P2

COMPLETE SYSTEM EXAMPLE (3 SYSTEMS) [ PRECAUTIONS ]


• If no earth leakage breaker is required, install a breaker or load
Power supply Power supply wiring switch with a fuse for the wiring. If an earth leakage breaker is
Transmission wiring required, make sure that the earth leakage breaker is designed
Main to protect the air conditioner from ground faults, overloads, and
switch Switch
short-circuiting.
Fuse • The remote controller wiring (P1 and P2) and transmission
wiring (F1 and F2) have no polarity.
• VRT Smart is only applicable for outdoor models with Smart
function.
• If a system has indoor units subject to both VRT smart and VRT
BS unit (Only control, the system is operated under VRT control.
for Heat • If the system has both outdoor-air processing air conditioners
recovery and outdoor-air processing type indoor units, VRT smart control
system) and VRT control are disable.

10-3 CONTROL BY 2 REMOTE CONTROLLERS


(Controlling 1 indoor unit by 2 remote controllers)
Indoor unit • Set one of the remote controllers to main and the other to sub in
the case of remote control with two remote controllers.
Remote controller Switching Main/Sub

1. When using 1 remote controller for 1 indoor unit. (1) Insert a screwdriver into the clearance between the grooves of
(Normal operation) the lower casing and the upper casing to remove the upper casing.
(2 grooves) (The remote controller PCB is attached to the upper
Outdoor unit casing.)
Power Control box
IN/D OUT/D Upper part of
supply F1 F2 F1 F2

remote controller
220- No. 1
240V L N System
1~50Hz
or 220V
1~ Most
60Hz downstream
Indoor unit B Indoor unit C indoor unit
Indoor LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2

unit A Lower part of


remote controller
P1 P2 P1 P2 P1 P2 P1 P2

Insert the screwdriver here and gently work off


the upper part of remote controller.
2. For group control or use with 2 remote controllers
(2) Set the main/sub switch on one of the remote controller PCBs to sub.
Power
Note: It is not necessary to designate
(Keep the switch of the other remote controller PCB set to main.)
supply Outdoor unit
220- indoor unit address when using
group control. The address is
Control box
IN/D OUT/D
240V L N F1 F2 F1 F2

automatically set when power


1~ No. 2 is activated.
50Hz or (Factory setting)
System
220V Most
1~60Hz downstream Remote controller
Indoor unit A Indoor unit B Indoor unit C indoor unit PC board
LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2

Only one remote controller


needs to be changed
P1 P2 P1 P2 P1 P2
if factory settings have
remained untouched.
For use with 2
remote controllers

10 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 10 10/9/2018 6:26:28 PM
26
FXMQ-PVM EDMFMT391803

10-4 COMPUTERISED CONTROL (FORCED OFF AND With Wireless Remote Controller Used
ON/OFF OPERATION) Set the wireless remote controller address before using the wireless
remote controller.
(1) Wire specifications and how to perform wiring For the setting method of the address, refer to the operation manual
• Connect the input from outside to terminals T1 and T2 of the provided with the wireless remote controller.
terminal block for remote controller.
NOTE
• A “MODE NO.” is set on a group basis. To make a mode setting
on a room unit basis or check the setting made, however, set the
corresponding mode number in the parentheses.
1. Settings for Optional Accessories
Input A • In the case of connecting optional accessories, refer to the
operation manuals provided with the optional accessories and make
necessary settings.
Wire specification Sheathed vinyl cord or cable (2 wire)
2. External Static Pressure Settings
Gauge 0.75- 1.25 mm2 Make settings in either method (a) or method (b) as explained below.
Length Max.100 m (a) Use the airflow auto adjustment function to make settings. Airflow
Contact that can ensure the minimum applicable load
auto adjustment: The volume of blow-off air is automatically
External terminal
of 15 V DC, 1 mA. adjusted to the rated quantity.
(1) Check that power supply wiring to the air conditioner is
completed along with duct installation. If a closing damper is
(2) Actuation installed in the air-conditioning system, make sure that the
• The following table explains FORCED OFF and ON/OFF closing damper is opened. Furthermore, check that the air
OPERATIONS in response to Input A. filter as a field supply is attached to the air passage on the
suction side.
FORCED OFF ON/OFF OPERATION (2) If there are a number of air outlets and inlets, adjust the
Input “ON” stops operation (impossible by Input OFF ON turns throttles so that the airflow rate of each air outlet and inlet will
remote controllers.) ON unit. coincide with the designed airflow rate. At that time, operate
the air conditioner in “fan operation mode”. To change the
Input OFF enables control by remote controller. Input ON OFF turns airflow rate, press and set the airflow adjustment button of the
OFF unit. remote controller to HH, H, or L.
(3) Make settings for airflow automatic adjustment. After setting the
(3) How to select FORCED OFF and ON/OFF OPERATION air conditioner to “fan operation mode”, stop the air conditioner,
• Turn the power on and then use the remote controller to select go to “FIELD SET MODE”, select “MODE NO. 21” (11 in the
operation. case of group settings), set the setting “FIRST CODE NO.” to 7,
and set the setting “SECOND CODE NO.” to 03.
10-5 CENTRALIZED CONTROL Return to normal mode after these settings, and press the
ON/OFF OPERATION button. Then the operation lamp will
• For centralized control, it is necessary to designate the group be lit and the air conditioner will go into fan operation for
No. For details,refer to the manual of each optional controllers airflow automatic adjustment. Do not adjust the throttles of
for centralized control. the air outlets or inlets during automatic adjustment of the air
conditioner. After the air conditioner runs approximately one to
eight minutes, the air conditioner will finish airflow adjustment
11. FIELD SETTING automatically, the operation lamp will be turned OFF, and the
air conditioner will come to a stop.
NOTE Table 4
• Before the test operation of the outdoor unit as explained in 12. TEST MODE NO. FIRST CODE NO. Setting contents
OPERATION, be sure to make the following field settings as explained
in 11. FIELD SETTING. 11 (21) 7 Airflow adjustment

Make sure the control box lids are closed on the indoor and SECOND CODE NO.
outdoor units. 01 02 03
Field setting must be made from the remote controller in
accordance with the installation condition. Completion of Start of airflow
OFF
airflow adjustment adjustment
• Setting can be made by changing the “MODE NO.”, “FIRST CODE NO.”,
and “SECOND CODE NO.”.
• For setting and operation, refer to the “FIELD SETTING” in the (4) After the air conditioner stops operating, check with “MODE NO. 21”
installation manual of the remote controller. on an indoor unit basis that 02 is set for the “SECOND CODE NO.” in
Table 4. If the air conditioner does not stop operating automatically
SECOND or the “SECOND CODE NO.” is not 02, repeat steps from (3). If the
CODE NO. outdoor unit is not turned ON, U4 or UH as explained in Table 8 will
MODE NO. be displayed. This display is not problematic, because this function is
FIRST set for the indoor unit. Continue setting the function. After setting this
CODE NO. function, be sure to turn ON the outdoor unit before the test operation
FIELD SET of the outdoor unit. If any other error is displayed, refer to Table 8 and
MODE the operation manual provided with the outdoor unit and check the
defective point.

• Set the remote controller to the “FIELD SET MODE”. For details, refer to
the “HOW TO SET IN THE FIELD”, in the remote controller manual.
• When in the “FIELD SET MODE”, select “MODE NO. 12” , then set the
“FIRST CODE NO.” to “1”. Then set “SECOND CODE NO.” to “01” for
FORCED OFF and “02” for ON/OFF OPERATION. (FORCED OFF at
factory set)

English 11

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 11 10/9/2018 6:26:28 PM
27
FXMQ-PVM EDMFMT391803

4. Switching time of the dry operation at VRTsmart control


CAUTION setting.
• If you change the operation mode to “Dry” when VRTsmart control
• If there is any change after airflow adjustment in the ventilation
is in effect, the operation mode is change to “Cooling” after certain
paths (e.g., the duct and air outlet), be sure to make airflow auto
period of time.
adjustment again.
If you want to continue dry operation longer, please change the
• Consult your Daikin representative if there is any change in
setting position as mentioned in the table below.
the ventilation paths (e.g., the duct and air outlet) after the test
(Setting position of factory setting is “0”.)
operation of the outdoor unit is finished or the air conditioner is
 If you keep dry operation longer, energy saving performance
moved to another place.
decrease.
(b) Select External Static Pressure with Remote Controller Check that Mode Setting switch Setting position
Dry operation
01 (OFF) is set for the “SECOND CODE NO.” in “MODE NO. 21” for number number number
airflow adjustment on an indoor unit basis in Table 4. The “SECOND 30 min 01
CODE NO.” is set to 01 (OFF) at factory set. Change the “SECOND
CODE NO.” as shown in Table 5 according to the external static 60 min 02
pressure of the duct to be connected. 90 min 10 10 03
(1) The “SECOND CODE NO.” is set to 06 (an external static
pressure of 150 Pa) at factory set. Continuous (Not return
04
to Cooling)
Table 5
External Static FIRST SECOND  At the time of Group control setting, Dry operation time for the indoor
MODE NO. units in the same group shall be the same setting value.
Pressure (Pa) CODE NO. CODE NO.
50 01
NOTE
75 02
For VRTsmart control function it is necessary to connect with an outdoor
100 03 unit with a compatible function.
115 04
130 05 12. TEST OPERATION
150 06 Refer to the installation manual of the outdoor unit.
160 07 • The operation lamp of the remote controller will flash when any
malfunction occurs. Check the malfunction code on the liquid
175 13 (23) 06 08
crystal display to identify the point of trouble.
190 09 An explanation of malfunction codes and the corresponding
200 10 trouble is provided in “CAUTION FOR SERVICING” of the
outdoor unit. lf any of the items in Table 4 are displayed, there
210 11 may be a problem with the wiring or power, so check the wiring
220 12 again.
230 13 Table 7
240 14 Remote controller dislplay Contents
250 15 Error in power supply voltage to indoor
“A8” lit
unit.
CAUTION Fan driver PCB of indoor unit indoor
“C1” lit
Keep in mind that a shortage of airflow quantity or water leakage control PCB transmission error.
will result because the air conditioner will be operated outside the Improper combination of fan driver
rated range of airflow quantity if the external static pressure is “C6” lit PCB of indoor unit or setting failure in
wrongly set. control PCB type.
Test operation of outdoor unit has not
“U3” lit
been finished.
3. Filter Sign Settings
• The remote controller is provided with an LCD that tells the time of Table 8
air filter cleaning. Remote control display Content
• If the air conditioner is used in places with excessive dust, change
the “SECOND CODE NO.” as shown in Table 6. “ ” is lit up
• There is a short circuit at the
The “SECOND CODE NO.” is set to 01 (standard) at factory set. FORCED OFF terminals (T1, T2)
Table 6 • The power on the outdoor unit is off.
FIRST SECOND • The outdoor unit has not been wired
Dirt Time for display MODE NO. “U4” is lit up
CODE NO. CODE NO. for power supply.
“UH” is lit up
• Incorrect wiring for the transmission
Approximately wiring and / or FORCED OFF wiring.
Standard 01
2500 hours
0 • The power on the indoor unit is off.
Approximately 10 (20)
Excessive dust • The indoor unit has not been wired
1250 hours 02 for power supply.
No display (*) 3 No display • Incorrect wiring for the remote
controller wiring, the transmission
* Select “No display” under conditions in which the cleaning display is wiring and / or the FORCED OFF
not required, such as the time of regular maintenance. wiring.

CAUTION
If interior finish work is continuing on completion of the test
operation of the air conditioner, explain the customer not to operate
the air conditioner until the interior finish work is completed for the
protection of the air conditioner. Otherwise, substances that will
be generated from interior finish work materials, such as paint and
adhesive agents, may contaminate the air conditioner.

12 English

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 12 10/9/2018 6:26:28 PM
28
FXMQ-PVM EDMFMT391803

13. APPENDIX
3P550452-1
FXMQ 200 . 250 PVM
SERVICE MANUAL - METHOD DISASSEMBLE SERVICE PARTS FROM UNIT
Be sure to read this manual before disassembly process and follow the instructions contained in it.
• Before disassemble part, be sure to stop unit operation, turn the breaker off or remove the power cord.
• Please wait for 5 minutes for the rotating fan to completely stop before start disassemble.
CAUTION • Removing heavy part require 2 or more people to handle to avoid injury.
• High-place work is required, to which utmost attention must be taken.
• Improper handling may result in injury or property damage, or even serious consequence under some circumstances.
• Please securely hold the panel with hand during removing the screw.
WARNING • Remove all the screws at once will cause the panel falls off.
• Improper handling may result in major accidents such as death and serious injury.

Note B. DRAIN PAN


• Re-assembly the parts following the same method in reversing steps.
1 Remove the Bottom Panel at the discharge side.
A. FAN MOTOR

1 Remove the motor wire from control box.

CONTROL BOX
25X BOTTOM PANEL
Screw: M5XL12mm (DISCHARGE SIDE)

REMOVE MOTOR WIRE CONNECTION 2 Remove the Drain Pan.


(INSIDE THE CONTROL BOX)
• During remove Drain Pan, be sure to remove the drain
CAUTION water inside it, to prevent water flow out from Drain Pan.
2 Remove the bottom panel at the return side. • Please take care the insulation below Drain Pan,
WARNING insulation damage will cause dew condensation.

BOTTOM PANEL
(RETURN SIDE) 1 TURN THE
HOOK
DRAIN PAN

DRAIN PAIN 2 PULL OUT IN


23X THIS DIRECTION
Screw: M5XL12mm 6X TO RELEASE
THE HOOK
Screw: M5XL12mm DRAIN PAIN

3 Remove the Fan deck together with fan and motor C. HEAT EXCHANGER << Continue from Drain Pan Disassembly >>
<< Be sure to follow 1~6 orders as below gure >>
<< Total Weight of Fan Deck + Fan + Motor >>
3 Remove all the Thermistors and Electronic Expansion
Valve Coil connectors from PCB inside Control Box.
CAUTION
FXMQ200PVM 24KG 4 Remove all the Side Service Panel and the Triangle Plate.
1 REMOVE 11X
FXMQ250PVM 30KG SCREW
FAN DECK
FAN MOTOR FAN
A

11X
Screw: M5XL12mm
A
15X SIDE SERVICE PANELS
2X Screw: M5XL12mm TRIANGLE PLATE
KEYHOLE
Screw: M6XL40mm
2 LOOSEN
THESE SCREWS 5 Remove the Heat Exchanger. ELECTRONIC EXPANSION
(DO NOT REMOVE) VALVE COIL
UNLOCK
3 UNSCREW GRADUALLY
(LEFT AND RIGHT SIDE, M6XL40MM) LOCK
5 DETACHED THE LIQUID
HEAT PIPE
LOOSEN SCREW EXCHANGER
FROM KEY HOLE

GAS
PIPE
6 REMOVE FAN DECK
4 REMOVE THIS SCREW FROM FAN DECK TOGETHER WITH
THERMISTOR (LIQUID)
(BOTH LEFT AND RIGHT, M6XL40MM) FAN & MOTOR 7X THERMISTOR (GAS)
SECTION A-A Screw: M5XL12mm

English 13

3P546641-1
1-IM-VRV_FXMQ-3P546641-1-EN-DAIKIN.indd 13 10/9/2018 6:26:28 PM
29
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

●Specifications, designs and other content appearing in this brochure are current as of October 2018 but subject to change without notice.

©All rights reserved 10/18 AK

You might also like