TYPICAL SECONDARY EXCITATION CURVES DESIGN PARAMETERS
10000 STANDARD: IEEE C57.13
TYPE: BUSHING CURRENT TRANSFORMER
INSULATION LEVEL: 0.6kV CLASS
TEMPERATURE CLASS: 105° C.
FREQUENCY: 60 HZ
LEGEND MAXIMUM RATIO: 2000 : 5
TOTAL SECONDARY TURNS: 400
SECONDARY RESISTANCE @ 75° C: ( 1.015 full winding w/ leads ) 0.00254 OHMS/TURN
1000 2000 ACCURACY CLASS: C800 & 0.3B1.8 @ 2000:5
Secondary Exciting Voltage - Es, (RMS)

1600
1500 CONTINUOUS THERMAL RATING FACTOR: 2.0 TIMES RATED @ ALL TAPS
1200 THERMAL RATING @ 1 SECOND: ( 75.1 times nominal ratio ) 150.2 kA RMS SYM. @ FULL RATIO
THERMAL RATING @ 3 SECONDS: ( 43.6 times nominal ratio ) 87.1 kA RMS SYM. @ FULL RATIO
1100
MECHANICAL / DYNAMIC RATING: ( 202.8 times nominal ratio ) 405.5 kA PEAK MAXIMUM
800 DESIGN NOTES RATIO TURNS CONNECTION
100
500 300 : 5 60 X3-X4
400 400 : 5 80 X1-X2
300 500 : 5 100 X4-X5
800 : 5 160 X2-X3
0 1100 : 5 220 X2-X4
0 1200 : 5 240 X1-X3
0 1500 : 5 300 X1-X4
10 1600 : 5 320 X2-X5
0
2000 : 5 400 X1-X5
0 The dashed (---) line represents the knee point (Ek) the point tangent to the
curve at 45° to the exciting current Ie.
TOLERANCE OF CURVE VALUE:
To the right of this line at any current Ie the voltage Es cannot be <95%
To the left of this line at any voltage Es the current Ie cannot be >125%

1 30
TYPICAL PHASE ANGLE CURVES BURDEN: 1.8 OHMS
LEGEND
0.001 0.01 0.1 1 10 100 25 2000
Secondary Exciting Amperes-Ie, (RMS)

Phase Angle - Minutes


0.0
20 0.0
TYPICAL OVER-CURRENT RCF CURVES BURDEN: 8.0 OHMS
2 0.0
15 0.0
0.0
LEGEND 10 0.0
0 0.0
300
0 5
1.1
400
0
500
0 0
Ratio Correction Factor

800
0 1 2.5 5 10 20 50 100 200
Percent Rated Current
1100
300
1200
400 TYPICAL RATIO CORRECTION FACTOR CURVES BURDEN: 1.8 OHMS
1.0080
1.01 1500
500 LEGEND
1600
800
1.0070
2000
Ratio Correction Factor

2000
1100 1.0060 0.0
1200 1.0050
0.0
1500 0.0
1.001 1.0040 0.0
1600
1.0030
0.0
2000
0.0
1.0020 0.0

1.0010
1.0001
10 100 1000 10000 1.0000
Percent Rated Current 1 2.5 5 10 20 50 100 200
Dashed Line - Secondary Coordinate Solid Line - Primary Coordinate Percent Rated Current

REV. DATE CURVE REVISION HISTORY


drawn for: SIEMENS

part number: 72-281-927-003


drawn by: 07/06/10 Drawing Design Number TYPICAL CHARACTERISTIC
09T-034-501 CURVES
REV. 00
checked by: 07/06/10

----

72-381-171-406 C800@2000:5 SMALL TAPE CT'S


DL 7/14/10
DL 7/14/10 72381171403 01
JP 7/14/10
JP 7/14/10 1 1
1 2 3 4 5 6 7 8 9 10
TERM. 6 TERM. 4 TERM. 2 65.8 7.8
[1672] [198]

32.9
[836] 29.3
A [744] A

TERM
3 & 4

LIFTING LUGS
(4 PLACES) BREAKER
47.4
66.4 PHASES
[1205]
[1686]
23.7 CONDUIT OPENING
[602] WITH REMOVABLE
COVER
B B

BASE PLATE, 5.0 [127] SQ X .75 [19] THICK

TERM. 5 TERM. 3 TERM. 1


WITH Ø1.25 [32] HOLE AT ITS CENTER FOUNDATION PLAN
FOR 1.000-8 UNC ANCHOR BOLT OF STM A36 OR HIGHER GRADE
TYP 4 PLACES (ANCHOR BOLTS TO BE FURNISHED BY CUSTOMER).
80.4
138.7 [2043]
[3522] SHIPPING AND INSTALLED WIDTH
SHIPPING AND INSTALLED LENGTH
1.38 2.
1.75
67.5 67.5 [35] 73.7
[44]
[1714] [1714] [1871]
C 10.9 C
55.8 61.5
[1418] [277] OVERALL HEIGHT [1563]

TERM. TERMINALS TERMINALS


1.75
TERM. 3 & 4 TERM. .562 1,3 & 5 2,4 & 6
[44]
5 & 6 1 & 2 [14.27]
LIVE PART TO GROUND
4 HOLES

TERMINAL DETAIL
1.00 [25.4] THICK ALUMINUM
26.8
[680] TYP 6 PLACES
119.5
D D
[3036]
SHIPPING 30°
HEIGHT RUPTURE DISC
TOP OF FLANGE
(FACING UPWARD)

CENTER OF GRAVITY CURRENT TRANSFORMER


(WHEN REQUIRED)

167.03
[4243]
PADLOCKABLE 147.6
E [3748] LIFT-OFF DOORS E
HANDLE 38.7
[982] WITH LOCKING
SF6 GAS
106.8 HANDLE
DENSITY [2713]
BOTTOM
MONITOR
OF CAB 97.9
[2487]
GROUND PAD
(2) .500-13UNC
66.1
[1678] HOLES ON 1.75
47.8 OPERATIONS COUNTER [44.5] CENTERS.
[1214] & POSITION INDICATOR
F F
WINDOW

35.8 21.9 1.8


[910] [556] [46]
16.7 47.4
65.8 [423] ( [1205] )
( [1672] )

G G
NOTES:

1. METRIC DIMENSIONS [XX.X] IN MILLIMETERS.


2. 20.0 [508] CLEARANCE REQUIRED FOR INSULATOR REMOVAL.
3. REPRESENTS BREAKER CENTER OF GRAVITY. MACHINED
SURFACE
-Confidential- Property of
TEXTURE
CENTER OF GRAVITY CALCULATED WITH EQUAL ---

NUMBER OF CT'S ON EACH OF SIX BUSHINGS. UNLESS


OTHERWISE
SPECIFIED
DWG NAME
OUTLINE, SPS2S, O/S DS
H 4. APPROX. WEIGHTS: BREAKER COMPLETE...............6384 LB [2840 KG] THIRD
ANGLE
PROJ
SIMILAR TO
145kV, SEISMIC H

SF6..........................................58 LB [26 KG]


C
DRAWN BY DATE FSCM NO. DWG NO. ISSUE

CHECK BY DATE
72381386406 01
FOUNDATION REACTION..........NEGLIGIBLE APVD BY DATE
WT
ISSUE BY DATE
SCALE 1:25 R F SHEET 1 OF 1

1 2 3 4 5 6 7 8 9 10
E-1047
CONTRATO E-1047 09-14-2018