Systems. Featuring:: SONOHEAT 2WR5 For The Measurement of Energy & Volume in Heating or Cooling
Systems. Featuring:: SONOHEAT 2WR5 For The Measurement of Energy & Volume in Heating or Cooling
SONOHEAT
Applications
Firmware versions earlier than 2.12 have 18 months for automatic monthly readings for:
• Energy
• Volume
• MD power
• MD flow
Tariffication
Additional tariff registers allow energy to be recorded in a separate register upon preset
criteria being met.
For heat/cool applications the heat energy is recorded in one register and the cooling
energy recorded in a separate register upon the measurered temperature falling below
a threshold of 18°C (default). The sum of these two registers equals the total energy
consumed.
In all these cases, the main register always registers the total energy consumed while
the tariff register only indicates the energy consumed during the time the tariff threshold
was breached (the total register increments in parallel with the tariff register).
2/19
The 16-digit type designation specifies the heat meter completely. In special cases
(such as cooling application), order number supplements (ATGs) are necessary. See
the Basic Documentation for the complete guide to order code creation.
Basic type
Nominal flowrate
Integration
Temperature sensor
Calculator design
Power supply
Communication mod-
ule
Manufacturer's label
Country
Unit of energy
Certification
ATG(s)
3/19
As defined in the EN 1434 standard for energy meters, the main flow points to consider
when selecting a flow tube are as follows:
Please note that a correctly ordered meter will be supplied complete with sensors and
modules etc. The following sections are for selecting spares, replacement parts and
modules for retro-fitting already installed meters.
qp 3.5 – 6 / 260mm
sensor pair its 8
qp 10 - 60
and 9)
4/19
260mm
300mm
1 ½“
¾“
1“
Meter fitting set Installation of flow sensor in pipe R3/4 x G1 B (in pairs, WZM-E1 z
with gaskets)
Meter fitting set Installation of flow sensor in pipe R1 x G1 ¼ B (in pairs, WZM-E54 z
with gaskets)
Spacer Spacer for heat meter G 1 - 190 mm, incl. Sealing disks WZM-G190 z
Spacer Spacer for heat meter G 1 1/4 - 260 mm, incl. Sealing WZM-G260 z
disks
Sealing disk thread Sealing disk thread G 1, for threaded connection R 3/4" 9060944003 z
G1
Sealing disk thread Sealing disk thread G 1 1/4, for threaded connection R 9060944004 z
G1¼ 1"
5/19
6/19
Pressures Losses
7/19
8/19
Calculator
9/19
qp10 to 60 m3/h:
10/19
General information • All 2WR5 meters are certified to EN 1434 based on the data and limit values listed
below
• The applications are always determined by the most unfavorable data of the individ-
ual component (e.g. temperature range of temperature sensors or working range of
the meter)
•
Flow measurement All 2WR5 meters satisfy the measurement accuracy requirements of class 2 to
EN 1434.
Large meters
Nominal flowrate
qp 3.5 6 10 15 25 40 60 m3/h
Metrological class 1:100 1:100 1:100 1:100 1:100 1:100 1:100
Maximum flow qs 7.0 12 20 30 50 80 120 m3/h
Minimum flow qi 35 60 100 150 250 400 600 l/h
Operating limit 7 12 20 30 50 80 120 l/h
Pressure drop at qp, ∆p 60 170 120 120 70 120 140 mba
r
Flowrate at ∆p = 1 bar KV 14 14 29 43 94 115 160 m3/h
Mounting orientation any
Temperature range 10 to 130 °C
Maximum temperature tmax 150 °C for 2000h
Nominal pressure PN 1,6 MPa 2.5 MPa (PN 25) 1.6MPa
2,5 MPa 4.0 MPa (PN 40) 2.5MPa
11/19
Electrical data:
12 . . . 24 V direct voltage
Type Safety extra low voltage
Power consumption up to 0.6 VA
12 . . . 24 V alternating voltage
Type Safety extra low voltage
Frequency 50 / 60 Hz
Galvanic isolation None
Power consumption Up to 0.6 VA
Battery modules
Characteristics of the lithium battery:
Voltage 3.6 V
Life 9 years
Ambient temperature Up to 55 ° C
12/19
Volume measuring
Temperature in the volume measuring unit *)
units
Continuously 130 °C
Briefly up to 2000h in 150 °C
total
*) If temperatures inside the flow sensor exceed 90 °C, the calculator must be detached from
the flow sensor
13/19
14/19
Combi module CL + With the combi modules, both the functions of the pulse module ( terminals 16, 17, 18 )
pulses and of the CL modules ( terminals 19, 20, 21 ) are implemented at the same time. It is
important to note that the reference potentials 17, 19 are assigned to a common termi-
nal.
15/19
• Use with the M-bus central unit OZW10, Apogee or NIMEB gateways
• With heating controllers equipped with an integrated M-bus master interface (RVD)
Fixed data
structure
Variable
data structure
Data
16/19
Combi module M-bus The combi module M-bus plus (M-bus+pulses) is used if data of the 2WR5 heat meter
+ pulses is processed in a master-capable M-bus unit and at the same time pulses are to be
transmitted to systems or district heating controllers for limitation and closed-loop con-
trol.
Modem The analogue modem allows for reading the meter data and setting of meter date and
time. It can be called as well as call itself a settable number at settable times
The modem takes its energy from the telephone network. It does not use any battery or
accumulator and is therefore maintenance free. It can operate in parallel to an ana-
logue telephone. With password protection for readout and administration.
A call back number and 10 call back times or one call back interval can be set.