DEEP SEA ELECTRONICS Auto


Transfer
Switch
Issue 4
VH 03/04/03

DESCRIPTION
The 500 is an automatic transfer Should the mains supply return to
switch control module, designed to with-in limits the ‘Mains Available’
monitor the incoming AC mains LED will illuminate and the module will
supply (3 phases) for under voltage. energise the ‘Run Generator’ Relay
causing the ‘Run’ contacts to open, on
Should the voltage fall out of limits, removal of the ‘Load transfer’ signal
the module will issue a start the ‘Generator Close’ relay will de-
command to the generating set energise and the ‘Generator Close’
controller. Once the set is available, contacts will open. The ‘Generator
the ATS module will control the On load’ LED will extinguish.
transfer devices and switch the load Following the ‘transfer delay’ the SPECIFICATION
from the mains to the generating set. module will de-energise the ‘Mains
DC Supply:
Should the mains supply return to close’ relay and the ‘Close mains’
The module DC is powered from
within limits the module will contacts will close. The ‘Mains On the plant battery or from a low
command a return to the mains Load’ LED will illuminate. When the voltage supply between 8 to 35V
supply and stop requesting the ‘Engine Running’ signal is removed Continuous. It is able to operate
generator. the module will then extinguish the at 0V for 50ms during cranking,
A clear mimic diagram with ‘Generator Available’ LED. The providing supply was at least 10V
‘International’ symbols and LED module will then await the next mains before dropout and supply
indications provide ‘at a glance’ failure event. recovers to 5V. This is achieved
information as to supply availability without the need for internal
The 500 ATS module is intended for
and load switching status. batteries.
use with the DSE 52x range of
Max. Operating Current:
In the event of a mains failure the Remote Start controllers. The ‘RUN’
85mA @ 12V, 92mA @ 24V.
module operation would normally be contacts connect to the ‘Remote Start’
1 Low Voltage Auxilliary Relay
as follows: input, and ‘ENGINE RUNNING’ and Contact:
‘Mains available’ LED extinguishes ‘LOAD TRANSFER’ are fed from relay 5Amp DC rated - NC connected
and the module de-energises the outputs on the 52x configured internally to -Ve.
‘Run Generator’ Relay, causing the accordingly. Sequence timers (Start 2 Mains Rated Relay Contacts:
‘Run’ contacts to close. A Delay, Warm-up, Stop Delay and 8Amp RMS rated 1 of each -
generator start module receives this Cooling) are configured in the 52x NO (Voltage Free)
signal and initiates the engine start. module. NC (Voltage Free)
Dimesnions:
Once the generator is running and Although designed for use with DSE 72mm x 72mm x 76mm
the ‘Engine Running’ signal is engine controllers, the flexibility of the 2.8’’ x 2.8’’ x 3.0’’
present, the ‘Generator available’ module also allows it to be connected Operating Temperature Range:
o
LED will illuminate. The module will directly to a range of commercially -25 to +55 C
then await the ‘Load transfer’ signal available, and custom built, generator Indications:
from the generator controller, once control systems. Mains Available LED (Green)
this is present the Module will then Mains on Load LED (Amber)
energise the ‘Close mains’ relay Generator Available LED (Green)
which causes the ‘Close mains’ The module is mounted in a Generator On load LED (Amber)
contacts to open, thus opening the robust plastic case. Operating Voltage:
Connection to the module is 100-300V NOMINAL RMS Input
mains contactor. The ‘Mains on
via plug and socket Range.
load’ LED will extinguish. After a
connectors Mains Trip 75V-275V AC RMS
short time delay, (Transfer Delay
0.7) allowing the mains contactor to (Adjusted via a potentiometer
accessible from the rear of the
open, the ‘Close generator’ relay is
module.)
energised causing the ‘Close
Transfer Delay :
generator’ contacts to close, thus
0.8Sec (+/- 0.1sec) (Fixed)
causing the generator contactor to
close. The ‘Generator on load’
LED will illuminate.
Deep Sea Electronics plc reserve the right to change
specification without notice.
CASE DIMENSIONS

1 2 34 5
72.0mm
65.5mm
2.8’’
1.4’’ 6 7 8 910111213

76.0mm
3.0’’ 72.0mm
2.8’’
Panel Cut-out: 68mmx68mm
8.5mm 2.7’’ x 2.7’’

0.3’’

TYPICAL CONNECTIONS Mechanical Interlock

LOAD

Generator Output Mains Input


L1
L2

L3
N
Electrical Interlock FUSES
FUSE
G M

6 7 8 9 10
Close Gen. Relay (N/O) Close Mains Relay (N/C) 11
FUSE 12
2 500 Automatic Transfer Switch Control Module 13
+V
3 To -Ve
-V 1 4 5

Refer to Operator Manual for input


Start/Run
and output function details and Generator Relay
suggested connection schemes
(Normally Closed)

Engine Running Input Load Generator Input


Optional: Else
Connect 'Load Generator'
to a suitable 'Gen
Available' Signal only.

+V +V
(Suggested 52x Output (Suggested 52x Output ('Remote Start' )
'Delayed Alarms Active') 'Load Transfer') IF USING 52x REMOTE START CONTROLLER

Deep Sea Electronics plc Deep Sea Electronics inc.


Highfield House, Hunmanby Industrial Estate, North Yorkshire, 5301 East State St. – Suite 202
YO14 0PH, England Rockford, IL 61108, USA
Tel: +44 (0) 1723 890099 Phone +1 (815) 316-8706
Fax: +44 (0) 1723 893303 Fax +1 (815) 316-8708
E-mail sales@deepseaplc.com Email – dsesales@deepseausa.com
Web- www.deepseaplc.com Web – www.deepseausa.com