TROUBLE REPORT
2 1
It is found that Chiller Main Unit (Chiller No.1) ELCB is trip condition. This ELCB
rated ampere is 60 Ampere.
11:39 PM: STNI Technical manager and PIC arrive at JSGI. Check megger on
compressor. It is found that compressor no.1 of chiller unit no.1 megger test not
good (+- 0 M Ohm). STNI try to Switch the ELCB from TRIP to ON , and Chiller
Unit No.1 restart to run. STNI then decide monitoring condition and contact chiller
vendor for schedule checking.
22 March 2023
08:14 PM : Chiller on DCS Status is STOP, ELCB trip again (2nd)
08:39 PM : Operator notice Chiller in DCS Status is STOP and contact STNI PIC.
STNI manager and PIC then request operator to try Switch the ELCB from TRIP to
ON and restart the Chiller.
09:06 PM : Chiller No.1 Stop, ELCB trip again (3rd)
09:25 PM : ELCB switch to ON, and restart chiller unit No.1. STNI then decide to
put blower to blow mist from chiller area. At this point chiller can running.
.
23 March 2023
06:43 AM : Chiller on DCS Status is STOP, ELCB trip again (4th )
07:31 AM : ELCB switch to ON, and restart chiller unit No.1.
09:10 AM : Chiller on DCS Status is STOP, ELCB trip again (5th )
09:18 AM : ELCB switch to ON, and restart chiller unit No.1.
10:09 AM : Chiller on DCS Status is STOP, ELCB trip again (6th )
10:09 AM : STNI manager, technical, and PIC arrive on site. Check chiller no.1
connection cable on compressor. It is found that the connector is rusty.
STNI then try cleaning the connector and dry the wet area, after that install air
dryer hose tubing inside compressor connector and nearby electronic board. This
is for countermeasure for mist.
STNI also check the current of compressor no.1, 2, and 3 of chiller unit no.1 to
check if there are overcurrent. Result show the current is still normal.
10:56 AM : Turn ON ELCB and restart chiller
26 March 2023
06:01 PM : Chiller on DCS Status is STOP, ELCB trip again (7 th ). Try turn ON
ELCB and restart chiller many times but it could not successfully running.
08:06 PM : To protect MS and Nitrogen Generator Unit, STNI decide to shutdown
Nitrogen Generator Unit. Change supply to Backup Tank. STNI then contact
Chiller service vendor for emergency checking and repair.
27 March 2023
12:23 PM : Berca Carrier, Chiller service vendor come and check chiller. It is
found that megger test for Compressor No.2 of chiller Unit No.2 not good. It also
found when try restart chiller and trip, compressor No.2 current recorded is 50 A,
while normal current is 14-15 A, ELCB specification is 60 A. Its suspected
compressor No.2 overcurrent/broken. STNI and Berca carrier then decide to
bypass the compressor no.2. So, chiller unit no.1 only run compressor 1 and 3.
02:53 PM : Bypass work finish and restart Chiller. Chiller can run normally
04:00 PM : Start Nitrogen Generator Unit air compressor. Due to many time chiller
issue, MS Regen conducted for 2 column before continue start-up
28 March 2023
08:45 AM : Supply from Nitrogen Generator Unit
10 April 2023
01:41 PM : Chiller on DCS Status is STOP, ELCB trip again. Try turn ON ELCB
and restart chiller many time but can not.
06:36 PM : STNI manager found that compressor No.1 of chiller unit no.1 megger
test is bad, suspected compressor no.1 also broken. STNI then decide to bypass
compressor no.1. This time chiller unit no.1 only run compressor no.3. Bypass
work finish and chiller can run.
16 April 2023
STOP Nitrogen Generator Unit for Yearly Air Compressor Maintenance and Chiller
Repair
19 April 2023
Change Chiller No.1 compressor. All 3 compressor change with new compressor.
Commissioning chiller, already working properly.
Put additional seal to chiller cover panel to prevent mist and moisture.
Mist
Humidity Monitoring
After Chiller replacement work, STNI conduct moisture monitoring inside the chiller
for 1 week, the result is:
During CGL Mode (Vaporizer NOT Use)
Humidity Night Time =+- 80-88%
Humidity Day Time = +- 50-60 %