Professional Documents
Culture Documents
95 8533 22.2 (Eqp)
95 8533 22.2 (Eqp)
Appendices
APPENDIX A – FM APPROVAL DESCRIPTION....A-1
Section 1 – Safety
All field devices are tied into a communication The EQP Controller utilizes several mechanisms
loop that starts and ends at the EQP Controller. to continuously check the LON loop for fault
Each device connected to the communication conditions, thereby providing the highest level
loop is assigned a unique identity by setting of reliable communication.
its address switches. All other device operation
parameters are configured through Det-Tronics Every device on the LON loop has the ability
“Safety System Software.” These selections to communicate with the EQP Controller at
define the type of device and how it is to any time. This design allows immediate alarm
operate. This system configuration data is then messages to be sent from the field devices to
downloaded into the EQP Controller. the EQP Controller.
A programmed EQP Controller is configured All messages are kept short in order to
to automatically download the configuration maximize network performance. This minimizes
data into the individual devices when they first network bottlenecks.
communicate with the EQP Controller.
The EQP System is easily modified to
In addition to Det-Tronics advanced flame accommodate design changes or plant
and gas detectors, the EQP System offers expansions. This can involve adding LON
the capability of incorporating third party sections, repositioning LON sections, or
fire and gas protection equipment into the removing LON sections from the loop. There
system. These can be either input or output are LON communication implementation
devices. Typical input devices include manual details that affect and limit how the LON loop
fire alarm "call boxes," heat detectors, and is changed.
analog combustible or toxic gas measurement
instruments. Typical output equipment includes
solenoids, strobes, and horns. All equipment is
COMBUSTIBLE, TOXIC, OR
OTHER 4-20 MA INPUT CONFIGURABLE
DRY CONTACT INPUTS OUTPUT POINTS
ANALOG
PIRECL INPUT 8 4-20 MA INPUTS
GAS MODULE
DETECTOR
RELAY 8 UNSUPERVISED
MODULE RELAY OUTPUT POINTS
LS2000
GAS UNSUPERVISED INPUTS AND OUTPUTS
DETECTOR FIRE
SUPPRESSION
(SOLENOID)
8 RELAY EIO
8 DRY CONTACT INPUTS
OUTPUT POINTS
APOLLO MODULES
DEVICES HORNS
&
TROUBLE RELAY BEACONS
(NC CONTACT)
ASM/ASH POWER
NETWORK EQP CONTROLLER
MODULE SUPPLY 8 CHANNEL EDIO MODULE
EXTENDER
MONITOR
– + – +
12 CHANNEL HSDM MODULE
RS-232 CONFIGURATION
PC
RS-485
HSSL
ETHERNET
ETHERNET
or RS-232
or RS-232
Only devices that have been approved for use the loop.
with the EQP System can be connected to the The field devices use the heartbeat as
LON. All approved devices have been tested a mechanism to ensure that there is a
and certified to operate properly on the LON. communication path back to the EQP
Controller. If the field device does not receive
LON COMMUNICATION HEARTBEAT a heartbeat for a period of time, the device will
go into a LON fault isolation. In this situation,
The EQP Controller continuously broadcasts the device opens one side of the LON and
a heartbeat signal over the LON loop. This listens for a heartbeat on the other side. If the
heartbeat is used for verifying the integrity device doesn’t receive a heartbeat, it listens
of the LON loop and for keeping the field on the other side of the LON and opens the
devices from going into a fault isolation mode. opposite LON connection.
Once every second, the heartbeat contains
the current time and date, which are used THEORY OF OPERATION
by the field devices to log status events and
calibrations. During normal operation, the EQP Controller
continuously checks the system for fault
The EQP Controller continuously tests LON conditions and executes user defined
continuity by sending out a heartbeat on programmed logic that coordinates the control
one LON port and then listening for it on the of the field devices. At the same time, the field
other LON port. The EQP Controller also devices are continuously monitoring for device
broadcasts the heartbeat signal in the opposite based fault and alarm conditions.
direction around the loop. This ensures that
all field devices, the LON Network Extenders When a fault condition occurs, the EQP
(EQ24xxNE), and communication wiring are Controller displays the fault condition on the
correctly passing the digital information around Vacuum Fluorescent Text Display, activates
EQP Controller Faults Trouble LON Trouble Field Device Faults Trouble Trouble
Shown on Text Display LED Fault Relay Shown on Text Display LED Relay
LED
290 Volt Fault X X
EQP Controller Fault X X
AC Failed X X
Program Mode X X
ADC Saturation X X
Wrong Device Type X X
Battery Fault X X
LON A Interface Fault X X
Beam Block X X
LON B Interface Fault X X
Blinding IR Fault X X
Option Board Fault X X
Cal Active at Start X X
Device Download Active X X
Calibration Fault X X
Logic Engine Fault X X
Channel Open X X
RS485 Ground Fault X X
Channel Short X X
Comm Option Board X X
Fault Control Message Fault X X
NODE 2
EQP
NODE 7
During normal operation, the EQP Controller
is continuously broadcasting a heartbeat
CONTROLLER
DET-TRONICS
®
NODE 1 NODE 8
around the communication loop as shown in
Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
Time & Date High Gas Cntrl Flt Out Inhibit Supr
D1851
Cancel Enter Next Previous Reset Acknowledge Silence
NODE 8
When a field device fails to receive the heartbeat
Time & Date High Gas Cntrl Flt Out Inhibit Supr
High Gas
Low Gas
Trouble
Cntrl Flt
Lon Fault
Inhibit
Out Inhibit
Ack
Power
Supr
Silence
NODE 8
D1853
is located or a LON fault time out period of two
Cancel Enter Next Previous Reset Acknowledge Silence
ETHERNET OR ETHERNET
MAJOR COMPONENT
RS-232 OR MODBUS
SERIAL LINK RS-485
DCS/PLC/HMI
DESCRIPTIONS EQP
CONTROLLER A
The EQP System has three main component S3
CONFIGURATION LON ADDRESS 1
The EQP Controller (see Figure 2-5) Figure 2-6—Block Diagram of EQP System
performs all communication, command, and with Redundant EQP Controllers
Table 2-7—Ports on Ethernet DLR Interface Board LOCAL OPERATING NETWORK (LON)
Port Name Comm Function The LON is a fault tolerant, two wire, digital
Port 1 Ethernet Ethernet DLR Com- communication network. The circuit is
DLR munication arranged in a loop starting and ending at the
Port 2 Ethernet Ethernet DLR Com- EQP Controller. The circuit supports up to 246
DLR munication intelligent field devices spread over a distance
of up to 10,000 meters (32,500 feet).
QP Controller-to-Controller Communica-
tion (SLC485) NOTE
All LON devices support NFPA 72 Class
The EQP Controllers can be configured to X communication with the EQP Controller.
communicate with up to 12 EQP Controllers via
RS-485 communication. The EQP Controller-to- EQP EQ24xxNE / EQ24xxPLR may be
Controller scheme provides the ability to meet necessary to establish network segments
NFPA 72 SLC requirements with the following for communication integrity within a
primary features: large system. A network segment is
the combination of the number of LON
• Modular trouble and alarm network devices and the length of wire
configuration between 2 network extenders or 1
network extender and the EQP Controller.
• Multiple zone application with EQP
Up to 40 LON network devices may be
Controller-to-Controller communication
installed in a network segment, and the
• Multiple media options LON cable wire segment lengths are
dependent upon physical and electrical
IMPORTANT characteristics of the cable. Refer to the
installation section for LON cable wire
When using RS-485 communications P8 information.
(Port 1) and P10 (Port 2) wiring must be
less than 20 feet and placed into conduit. EQ24xxNE Network Extender
Or, fiber optic converters (see table 3-9
for performance verified units) shall be The purpose of the EQ24xxNE is to transmit
used. Or,, the EQ2230 RSP can be used LON communication signals beyond 2,000
to protect against electrical surge and meters of wire length. A network extender
transient EMI. The fiber optic converter (see Figure 2-8) must be installed near or at
and RSP must be placed inside the 2,000 meters of wiring length to re-broadcast
cabinet with the EQP Controller. the communications into the next network
X7050 xWatch® Explosion-Proof Camera The EDIO module can be mounted directly to
a panel, or it can be DIN rail mounted. System
The xWatch high resolution color camera status can be determined using the trouble-
operates in an explosion–proof enclosure and shooting procedures, Eagle Quantum Safety
can be used to view an area in alarm or to System Software (S³) and the status indicators
record activity in an area. It can be used as on the module.
a stand-alone unit or attached to any of the
X-series flame detectors. Users have an option Refer to the Enhanced Discrete Input/Output
to include a digital video recorder (DVR) as Module Specification Data sheet (form number
part of the solution to capture a digital video of 90-1189) for additional information.
hazard events.
Refer to the DCIO Specification Data sheet The Analog Input Module (AIM) provides 8
(form number 90-1149) for additional configurable channels that can be set for either
information. combustible gas mode or universal mode. The
combustible gas mode provides a number
of automatically programmed settings, and
alarm thresholds that are limited to approval
body requirements. The universal mode is
used for generic devices where control over
all configuration parameters is required. All
devices must provided their own calibration
facilities.
For fire detector 4–20 mA inputs, the AIM
Figure 2-11—EQ3700 DCIO Module
is certified for use as an NFPA 72 Class B
Approved input.
The UD10-DCU is designed for use with most As part of providing the total solution to
currently available Det‑Tronics gas detectors. commercial and industrial customers globally,
The UD10-DCU with CGS conditioning board Det-Tronics offers several performance
is designed for use with combustible gas, see approved hazardous area (EQ3900N
manual 95-8656 for more information. and EQ3900E) and non-hazardous area
(EQ3900G) enclosure solutions. These are
For a list of compatible gas detectors, as well custom solutions that can include 1 or more
as information regarding installation, operation, of the following components: EQP Controller,
maintenance, specifications and ordering EDIO, HSDM, AIM, RM, DCIO, PSM, and GFM.
information, refer to form number 95-8656. Refer to Instruction Manuals (95-8559 and 95-
8641) for additional information.
PIRECL PointWatch Eclipse
EQ3900RPS Explosion-Proof Power
The Pointwatch Eclipse® Model PIRECL is Supply
a diffusion-based, point-type infrared gas
detector that provides continuous monitoring of The EQ3900RPS is an industrial power supply
combustible hydrocarbon gas concentrations that accepts two independent AC inputs and
in the range of 0–100% LFL. produces 24 Vdc with up to 18 amps output
current. It can be configured with various
The LON supervision meets Signaling Line numbers of 24 Vdc power outputs, ground fault
Circuit (Class X) requirements per NFPA72: test operator, status indicators, fuse monitoring
2010 for the Model PIRECL. and window. Ordinary location or Class 1
Division 1 enclosure configurations can be
For PIRECL installation, operation, provided. Refer to Instruction Manual 95-8745
maintenance, specifications and ordering for additional information.
information, refer to form number 95-8526. EQ3780HSDM High Speed Deluge Mod-
NOTE ule
The low alarm range for the EQP model The EQ3780HSDM High Speed Deluge
of the PIRECL is 5–40% LFL (the Module (HSDM) is specifically designed to
standard PIRECL is 5–60% LFL). expand the capability of the EQP System by
providing the capability to activate ultra-high
For information regarding USCG Approval speed suppression systems for hazardous
of the PIRECL Detector, refer to 57-1009 applications such as munitions manufacturing
Addendum. (see Figure 2-20).
LS2000 Line-of-Sight
The HSDM provides up to six configurable
The FlexSight™ Line-of-Sight Infrared input channels and up to six configurable
Hydrocarbon Gas Detector Model LS2000 is a output channels that can be programmed
gas detection system that provides continuous for supervised or unsupervised operation.
monitoring of combustible hydrocarbon gas Typical initiating devices include optical flame
concentrations in the range of 0–5 LFL-meters, detectors, heat detectors, and manual pull
over a distance of 5–200 meters. stations. Output channels are designed to
activate FM-approved solenoids. Solenoids
Figure 2-20—EQ3780HSDM
A power supply wiring diagram should contain Answer: If the Authority Having Jurisdiction
information describing wire distances and (AHJ) requires a voltage loss of 10% or less,
current draws associated with all devices only 16 AWG wire could be used, since the end
connected to the wire segment. A typical device would require 21.4 Vdc. If there is no
power supply wiring recommendation is that local requirement, then 18 AWG wire could be
the voltage drop from the power source to the used to provide power to the devices.
end device should not exceed 10%. Using 24
Vdc as a reference, the maximum voltage drop
should not exceed 2.4 Vdc. A wire gauge must
be selected to ensure that the end device has
at least 21.6 Vdc or higher.
24 vdc Power 18 AWG Single Wire Resistance: R = 0.6385 Ohms per 100 ft
Supply 2 Conductor Resistance: CR = 2 • R
Total Current
695 mA Device 1
50 ft Device 1 Voltage = Supply Voltage – (Voltage Drop)
0.6385 Ohms = 24 – (I • CR)
65 mA
Current Draw = 24 – (0.695 • 0.6385)
= 23.55 vdc
Total Current
630 mA
150 ft =
1.9155 Ohms Device 2
+
Device 3 Device 2
Device 2 Voltage = Device 1 Voltage – (Voltage Drop)
65 mA = 23.55 – (I • CR)
Current Draw = 23.55 – (0.630 • 1.9155)
= 22.35 vdc
Total Current
565 mA
150 ft =
1.9155 Ohms Device 3
Device 3
Device 3 Voltage = Device 2 Voltage – (Voltage Drop)
565 mA = 22.35 – (I • CR)
Current Draw = 22.35 – (0.565 • 1.9155)
= 21.27 vdc
Number of Standby
Device Type Total Current for Device Type
Devices Current
EQP Controller X 0.360 =
EQ3LTM X 0.001 =
EQ3730EDIO X 0.075 =
EQ3780HSDM X 0.075 =
EQ3700DCIO X 0.075 =
EQ2001 EQP Monitor X 0.360 =
EQ2100PSM X 0.060 =
X3301 - without heater X 0.160 =
X3301 - with heater X 0.565 =
X3302 - without heater X 0.160 =
X3302 - with heater X 0.565 =
X2200 X 0.135 =
X9800 - without heater X 0.085 =
X9800 - with heater X 0.420 =
X5200 - without heater X 0.155 =
X5200 - with heater X 0.490 =
EQ3720RM X 0.120 =
EQ3710AIM X 0.160 =
EQ2220GFM X 0.018 =
PIRECL X 0.270 =
LS2000 Transmitter without heater X 0.149 =
LS2000 Transmitter with heater X 0.336 =
LS2000 Receiver without heater X 0.116 =
LS2000 Receiver with heater X 0.258 =
EQ24xxNE X 0.030 =
EQ24xxPLR X 0.090 =
EQ3760ASM X 0.560 =
EQ21xxPS Power Supply X 0.350 =
UD10-DCU - with heater off X 0.054 =
UD10-DCU - with heater on X 0.167 =
UD10-DCU CGS - w/ heater
X 0.221 =
off
UD10-DCU CGS - w/ heater
X 0.333 =
on
Other X =
Total Standby Current for EQP System (in amperes) =
Notes: Standby
Notes: Standbycurrent
current isis the
the average current
current draw
draw for
forthe
thedevice
deviceininnormal
normalmode.
mode.
Thistable
This tableisisfor
forbattery
battery calculations
calculations only.
only.
ForOPECL
For OPECLstandby
standby current
current requirements,
requirements, reference
referenceversions
versions16.1
16.1and
andearlier
earlierofofthis manual.
this manual.
21.2 3-3 95-8533
Number of
Device Type Alarm Current Total Current for Device Type
Devices
EQ3LTM X 0.001 =
EQ3780HSDM X 0.100 =
EQ3720RM X 0.120 =
EQ2100PSM X 0.060 =
X2200 X 0.135 =
EQ3710AIM X 0.300 =
EQ2220GFM X 0.018 =
PIRECL X 0.275 =
EQ24xxNE X 0.030 =
EQ24xxPLR X 0.090 =
EQ3760ASM X 0.560 =
Other X =
Supply Rating 20 10
All junction boxes must be electrically In applications where the network wiring is
connected to earth ground. installed in conduit, the use of watertight
conduit seals, drains, breathers, or equivalent
is recommended to prevent damage caused
Response Time vs. EQP System Size by condensation within the conduit.
When designing an EQP System, it is important Electrostatic Discharge
to realize that by increasing the number of
nodes (devices) on the communication loop, An electrostatic charge can build up on the
the amount of time required for a status change skin and discharge when an object is touched.
message from a detection device to reach the ALWAYS use caution when handling devices,
EQP Controller also increases. taking care not to touch the terminals or
electronic components.
6 7 8 9 10
EQ2220GFM INSTALLATION
COMMON NO NC N/C EARTH
GROUND
MOUNTING
NOTE: RELAY CONTACTS ARE SHOWN IN THE REST STATE,
NO POWER APPLIED. RELAY IS ENERGIZED WITH
The EQ2220GFM is a DIN rail mountable POWER APPLIED AND NO GROUND FAULT
device designed to be mounted in the same (TERMINALS 6 & 7 CLOSE, TERMINALS 6 & 8 OPEN).
enclosure as the EQP Controller. Figure 3-1—Terminal Configuration for Ground Fault Monitor
WIRING NOTE
1. Connect power wiring from the EQP Cable meeting the specifications listed in
Controller power terminals 1 and 2 to the Table 3-6 is suitable for distances up to
GFM terminals 1 and 2. 2000 meters.
2. Connect power wiring from the GFM Any of the cable types listed in Table 3-7 can
terminals 3 and 4 to the EQP Controller be used for wiring the LON for the distances
power terminals 3 and 4. indicated.
3. Connect earth ground to terminal 5 or 10. NOTE
4. Connect the relay contacts as required. If no network extenders are used, the
distances listed are for the entire
Refer to Figure 3-1 for terminal block loop. If network extenders are used,
identification. the distances listed are for the wiring
length between network extenders or
between a network extender and the
NETWORK AND EQ24XXNE EQP Controller.
INSTALLATION
IMPORTANT
MOUNTING
Det-Tronics recommends the use of
shielded cable (required by ATEX)
The device should be securely mounted to a
to prevent external electromagnetic
vibration free surface. (See the “Specifications”
interference from affecting field devices.
section in this manual for device dimensions.)
WIRING WARNING
Be sure that the selected cable meets
All devices on the LON are wired in a loop all job specifications and is rated for
that starts and ends at the EQP Controller. To the installation per local and national
ensure proper operation, the LON should be codes and practices. The use of other
wired using high speed communication grade cable types can degrade EQP System
cable, as specified on the next page. operation. If necessary, consult factory for
further suggested cable types.
1. Remove the cover from the Network Table 3-7—LON Maximum Cable Lengths
Extender enclosure.
Note: *Use the same type of cable in each wiring
2. Connect 24 Vdc power lead wires and segment between network extenders.
communication network cable to the **Maximum wire lengths represent the linear
terminal block. (See Figure 3-2 for terminal wire distance of LON communications wiring
location and Figure 3-3 for terminal between network extenders.
Be sure that selected cable meets all job
identification). specifications, indoor, outdoor and direct
burial.
If necessary, consult factory for further
See Table 3-8 to determine maximum wiring suggested cable types.
length.
Table 3-6—Typical Specification for 16 AWG (1.5 mm2) LON Wiring Cable per Echelon
7 –
3. Connect shields to the designated "shield"
terminals. The two shield terminals are 8 +
CAUTION 11 B COM 2
The EQP Controller is designed for direct Figures 3-6A and 3-6B show the location
panel mounting or DIN rail mounting. See of wiring connectors on the EQP Controller
“Specifications” section of this manual for module. Figure 3-7 identifies individual
mounting dimensions. terminals.
NOTE
Connector P1, Terminals 1 to 4 —
Clips for DIN rail mounting are available,
24 Vdc Input Power
but must be specified at the time of
ordering. Connect the power supply to terminals 1 and 2
NOTE of the EQP Controller. Terminals 3 and 4 must
also be connected to power.
A minimum clearance of 4 inches
between the EQP Controller and nearby
When EQP Controller and power supplies
equipment is required to provide room
are installed in separate NRTL cabinets, two
for wiring and ventilation. power cables from two distribution circuits
are required, so that if one is lost, the EQP
SERIAL INTERFACE BOARD Controller will continue to operate and signal
a trouble condition. The power circuit must be
A Serial Interface Board is available for the protected against physical damage.
COMMON 21 +
INPUT, + 5
N. O. 22
COMMON, – 6
N. C. 23
–
Figure 3-4—Unsupervised Input Wiring
Figure 3-5—Unsupervised Relay Output
Shields on power cables must be connected to Controller’s LON COM 1 is connected to the
chassis ground (earth). field device’s COM 2 connection. The field
device’s COM 1 is wired to the next device’s
Connector P2, Terminals 5 to12 — COM 2 connection. This continues through
Unsupervised Digital Input Channels 1 to 4 the last field device on the loop. The last field
Connector P3, Terminals 13 to 20 — device’s COM 1 is then wired back to the EQP
Unsupervised Digital Input Channels 5 to 8 Controller’s COM 2 connection. LON A and
B polarities must be maintained throughout
See Figure 3-4 for example. Only channel 1 is the loop (i.e., always wire A to A and B to B
shown in Figure 3-4. The information is typical between the devices).
for channels 1-8.
Port Pinout (6-position connection terminal
Connector P4, Terminals 21 to 32 —
Unsupervised Relay Output Channels 1 to 4
block)
48 — COM 1 shield connection
49 — "B" side of signaling circuit for COM 1
Connector P5, Terminals 33 to 44 — 50 — "A" side of signaling circuit for COM 1
Unsupervised Relay Output Channels 5 to 8 51 — COM 2 shield connection
52 — "B" side of signaling circuit for COM 2
See Figure 3-5 for example. Only channel 1 is 53 — "A" side of signaling circuit for COM 2
shown in Figure 3-5. The information is typical
for channels 1-8. NOTE
22.2
P11: TERMINALS 63 TO 65 – PORT 3
P13: HIGH SPEED SERIAL LINK (HSSL) RS-232 MODBUS RTU MASTER/SLAVE
RS-232 (REDUNDANCY ONLY) OR S3 CONFIGURATION
59
ETHERNET DLR RJ45 DET-TRONICS P9: TERMINALS 57 TO 59
CONNECTOR PORT 2 RS-232 S3 CONFIGURATION PORT
56 57
EAGLE QUANTUM PREMIER
RS-485 Modbus RTU Master/Slave
54
Safety System Controller RS-485 MODBUS RTU MASTER/SLAVE
CONTROLNET
BNC CONNECTOR A
53
Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
OR
ETHERNET DLR RJ45 Time & Date High Gas Cntrl Flt Out Inhibit Supr
P7: TERMINALS 48 TO 53
Connector P8, Terminals 54, 55 & 56 , Port 1—
CONNECTOR PORT 1 Low Gas Lon Fault Ack Silence LON CONNECTIONS
48
Software selectable baud rates are 2400, 4800,
9600,19200, 38400, 57600, and 115200. Software
transmission baud rate, parity check for the
Configuration data downloaded into the EQP
3-13
Cancel Enter Next Previous Reset Acknowledge Silence
G2105
1 4 5 12 13 20 21 32 33 44 45 47
56 — A
55 — B
P6: TERMINALS 45 TO 47
54 — GND
P5: TERMINALS 33 TO 44
RELAYS 5 TO 8
P4: TERMINALS 21 TO 32
RELAYS 1 TO 4
P3: TERMINALS 13 TO 20
DIGITAL INPUTS 5 TO 8
P2: TERMINALS 5 TO 12
DIGITAL INPUTS 1 TO 4
Port Pinout (3-position terminal block)
P1: TERMINALS 1 TO 4
24 VDC INPUT POWER
95-8533
Figure 3-6A—Location of Wiring Terminals on EQP Controller with Serial Interface Board
Port 4, ETHERNET, MODBUS TCP/IP MASTER/SLAVE
22.2
Port 3, ETHERNET, MODBUS TCP/IP MASTER/SLAVE
P13: HIGH SPEED SERIAL LINK (HSSL) or S3 CONFIGURATION
RS-232 (REDUNDANCY ONLY)
59
ETHERNET DLR RJ45 DET-TRONICS P9: TERMINALS 57 TO 59
CONNECTOR PORT 2 RS-232 S3 CONFIGURATION PORT
56 57
EAGLE QUANTUM PREMIER
P8: TERMINALS 54 TO 56 - PORT 1
54
Safety System Controller RS-485 MODBUS RTU MASTER/SLAVE
CONTROLNET
Connector P9, Terminals 57, 58 & 59 —
BNC CONNECTOR A
53
Fire Alarm Trouble Inhibit Power
selectable parity is None, Odd, and Even.
ETHERNET DLR RJ45 Time & Date High Gas Cntrl Flt Out Inhibit Supr
P7: TERMINALS 48 TO 53
CONNECTOR PORT 1 Low Gas Lon Fault Ack Silence LON CONNECTIONS
48
2400, 4800, 9600,19200, 38400, 57600, and
serial port. Software selectable baud rates are
transmission baud rate and parity check for the
3-14
Cancel Enter Next Previous Reset Acknowledge Silence
A2632
1 4 5 12 13 20 21 32 33 44 45 47
59 — TXD
58 — RXD
P6: TERMINALS 45 TO 47
57 — GND
P5: TERMINALS 33 TO 44
RELAYS 5 TO 8
P4: TERMINALS 21 TO 32
RELAYS 1 TO 4
P3: TERMINALS 13 TO 20
DIGITAL INPUTS 5 TO 8
P2: TERMINALS 5 TO 12
DIGITAL INPUTS 1 TO 4
Port Pinout (3-position terminal block)
P1: TERMINALS 1 TO 4
24 VDC INPUT POWER
95-8533
Figure 3-6B—Location of Wiring Terminals on EQP Controller with Ethernet Interface Board
+ 1 48 SHIELD
P1
– 2 COM 1 49 1B
24 VDC INPUT POWER + 3 50 1A
P7
– 4 51 SHIELD LON
1+ 5 COM 2 52 2B
RESET*
1– 6 53 2A
2+ 7 54 GND
ACKNOWLEDGE* P8
P2
2– 8 55 B RS-485
PORT 1
DIGITAL INPUTS 1 TO 4 3+ 9 56 A
SILENCE*
3– 10 57 GND
P9
4+ 11 58 RxD RS-232
INHIBIT ENABLE** CONFIG
4– 12 59 TxD PORT
5+ 13
ENTER*
5– 14
6+ 15
CANCEL*
16 SERIAL INTERFACE BOARD
6–
P3
DIGITAL INPUTS 5 TO 8 17
7+ 60 A
NEXT* P10
7– 18 61 B RS-485
PORT 2
8+ 19 62 GND
PREVIOUS*
8– 20 63 TxD
P11
1 C 21 64 RxD RS-232
PORT 3
1 NO 22 FIRE ALARM* 65 GND
1 NC 23 66 TxD
P12
2 C 24 67 RxD RS-232
PORT 4
2 NO 25 SUPERVISORY* 68 GND
P4
2 NC 26
RELAYS 1 TO 4 P13
3 C 27 RS-232 - HSSL
(Custom Connector,
3 NO 28 LOW GAS ALARM*
for Redundancy Only)
3 NC 29
4 C 30
ETHERNET INTERFACE BOARD
4 NO 31 HIGH GAS ALARM*
4 NC 32 60 A
P10
33 61 B RS-485
5 C
PORT 2
34 INHIBIT*
62 GND
5 NO
5 NC 35
ETHERNET
36 RJ45 PORT 3
6 C
6 NO 37 OUTPUT INHIBIT*
P5
6 NC 38
ETHERNET
RELAYS 5 TO 8 RJ45
7 C 39 PORT 4
7 NO 40 LON FAULT*
7 NC 41
P13
8 C 42 RS-232 - HSSL
(Custom Connector,
8 NO 43 BEEPER* for Redundancy Only)
8 NC 44
C 45
P6 * DIGITAL INPUTS AND RELAY OUTPUTS CAN BE
NO 46 CONFIGURED AS THE STATIC FUNCTION NAME (AS
TROUBLE RELAY
SHOWN) OR CAN BE USER DEFINED.
NC 47
H2104 **INHIBIT ENABLE FOR SIL EQP CONTROLLERS ONLY.
3 3
P3 P25
1 1
DET-TRONICS
O
®
RS-485 Transmit LED (Yellow) P24 R
3 T
1
EAGLE QUANTUM PREMIER
A B Safety System Controller
Channel RS-485 Termination Jumper
Indicators Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
LON COM 2
Time & Date High Gas Cntrl Flt Out Inhibit Supr
RS-485 Receive LED (Green) P26 Termination Jumper
Low Gas Lon Fault Ack Silence
1 3
1 3
P25
LON COM 1
Termination Jumper
Figure 3-8A—Location of Termination Jumpers, Communication Indicator LEDs, and Communication Ports
for EQP Controller with Serial Interface Board
1 3 1 3
P6 P5
DET-TRONICS
O
®
RS-485 Transmit LED (Yellow) P24 R
3 T
1
EAGLE QUANTUM PREMIER
A B Safety System Controller
Channel RS-485 Termination Jumper
Indicators Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
LON COM 2
Time & Date High Gas Cntrl Flt Out Inhibit Supr
RS-485 Receive LED (Green) P26 Termination Jumper
Low Gas Lon Fault Ack Silence
1 3
1 3
P25
LON COM 1
Termination Jumper
Figure 3-8B—Location of Termination Jumpers, Communication Indicator LEDs, and Communication Ports
for EQP Controller with Ethernet Interface Board
The media converter can be connected to either The maximum distance of a particular optic
of the EQP Controller RS-485 communication link given the optical budget is calculated as:
ports (Port 1 or Port 2). Figure 3-10 illustrates
a typical Class B wiring connection (single Fiber Length = [Optical budget] – [Link Loss]
mode) between two EQP Controllers in a [Fiber Loss / km]
redundant configuration using Port 1. Note: If
Port 2 is preferred, the Serial Interface Board where link loss includes number of end
must be purchased. connectors, splices and safety margin.
For more information regarding selection and Max. Distance = 10 – (2 x 0.5) – 3.0 = 15 km
installation of fiber optic media, please contact 0.4
Det-Tronics customer service.
68 67 66 65 64 63 62 61 60 68 67 66 65 64 63 62 61 60
GND B A GND B A
3 3 3 3
P3 P25 P3 P25
1 1 1 1
DET-TRONICS DET-TRONICS
® ®
56 56
EAGLE QUANTUM PREMIER EAGLE QUANTUM PREMIER
55 55
A B Safety System Controller 54 A B Safety System Controller 54
Eagle Quantum Premier Fire Alarm Trouble Inhibit Power Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
Time & Date High Gas Cntrl Flt Out Inhibit Supr Time & Date High Gas Cntrl Flt Out Inhibit Supr
Low Gas Lon Fault Ack Silence Low Gas Lon Fault Ack Silence
Cancel Enter Next Previous Reset Acknowledge Silence Cancel Enter Next Previous Reset Acknowledge Silence
E2276
Figure 3-9A—EQP Controller-to-Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72,
for EQP Controllers with Serial Interface Board
TO
ADDITIONAL
CONTROLLER(S)
62 61 60 62 61 60
GND B A GND B A
1 3 1 3 1 3 1 3
P6 P5 P6 P5
DET-TRONICS DET-TRONICS
® ®
56 56
EAGLE QUANTUM PREMIER EAGLE QUANTUM PREMIER
55 55
A B Safety System Controller 54 A B Safety System Controller 54
Eagle Quantum Premier Fire Alarm Trouble Inhibit Power Eagle Quantum Premier Fire Alarm Trouble Inhibit Power
Time & Date High Gas Cntrl Flt Out Inhibit Supr Time & Date High Gas Cntrl Flt Out Inhibit Supr
Low Gas Lon Fault Ack Silence Low Gas Lon Fault Ack Silence
Cancel Enter Next Previous Reset Acknowledge Silence Cancel Enter Next Previous Reset Acknowledge Silence
A2633
Figure 3-9B—EQP Controller-to-Controller Communication with Class A Signaling Line Circuit Classification per NFPA 72,
for EQP Controllers with Ethernet Interface Board
T+ T+
T– T–
R+D+ R+D+
Moxa Moxa
R–D– R–D–
TCF-142-S TCF-142-S
Tx Tx
Rx Rx
A 56 56 A
PORT 1 PORT 1
B 55 55 B
RS-485 RS-485
GND 54 54 GND
B2328
SINGLE MODE
FIBER OPTIC CABLE
Rx Tx Rx Tx
T+ T+
T– T–
A 60 Tx Tx 60 A
PORT 2 PORT 2
B 61 Rx Rx 61 B
RS-485 RS-485
GND 62 GND GND 62 GND
SINGLE MODE
FIBER OPTIC CABLE
Rx Tx Rx Tx
A 56 56 A
PORT 1 T+ T+ PORT 1
B 55 55 B
RS-485 RS-485
T– T–
GND 54 54 GND
R+D+ Moxa Moxa R+D+
TCF-142-S TCF-142-S
R–D– R–D– B2371
Tx Tx
Rx Rx
GND GND
Figure 3-11—Single Mode EQP Controller-to-Controller NFPA 72 Approved Fiber Optic Link, Class X
GND 62 ATD ARD BTD BRD BTD BRD ATD ARD 62 GND
D(P) D(P)
Phoenix Phoenix
D(N) PSI-MOS- PSI-MOS-
D(N)
RS485W2/FO RS485W2/FO
A 60 60 A
PORT 2 PORT 2
RS-485 B 61 61 B RS-485
GND 62 62 GND
B2372
Figure 3-12—Multi-Mode EQP Controller-to-Controller NFPA 72 Approved Fiber Optic Link, Class X
A 50
ENCLOSURE REQUIREMENTS
COM 1 B 49
MOUNTING
EQP
The EQP Controllers are designed for direct CONTROLLER
3 A 6
WIRING A 50
COM 1 TO
COM 1 B 49 2 B 5 FIELD
DEVICES
Power supplies require unrestricted air 4. Connect external wiring to the appropriate
flow for proper cooling. points on Power Supply. Refer to Figure
3-14 for terminal block locations and
MOUNTING Figures 3-15, 3-16, and 3-18 for terminal
identification. Connect the 24 Vdc power
Mount the power supply monitor in a Nationally wires and the LON network cable to the
Recognized Test Laboratory (NRTL) labeled appropriate points on J1. (Redundant “+,”
enclosure. Refer to the “Specifications” section “–,” and shield terminals are connected
for mounting dimensions. internally.)
WIRING NOTE
Do not ground any shield at the monitor
/ power distribution cabinet. Insulate the
CAUTION
shields to prevent shorting to the device
The power supply should be properly housing or to any other conductor.
connected to an earth ground. A ground
1 TERMINAL NO. 1
TERMINAL J2-1 TO
TERMINAL B
TERMINAL J2-2 TO
TERMINAL C 1
SWITCH NO. 1
TERMINAL J2-3 TO
TERMINAL C
+ –
J2 4 3 2 1
1
YELLOW LED
GREEN LED
C1949
0.0005 OHM SHUNT
J2: BATTERY TEST POINTS TERMINAL NO. 1 ALARM CURRENT LEVEL SWITCH SETTINGS
NOTE: J2 TERMINALS 3 AND 4 ARE CONNECTED TO J1 TERMINALS 7 AND 8 INTERNALLY 800 mA O X Fault Disabled* -- X
ON THE PC BOARD. J1 TERMINALS 7 AND 8 ARE ALSO CONNECTED TO THE 2 AMP X X *When switch 4 is closed, the power supply must
BATTERY CIRCUIT BREAKER VIA POWER DIST CKT. be monitored through the power supply relay and
the proper initiation circuit for NFPA 72
X = CLOSED compliance.
O = OPEN
2 NOT USED
11 B COM 2
3 NOT USED
12 SHIELD
A1947
4 AC INPUT 120 / 240 VAC
A1950
Figure 3-15—J1: Power and LON Wiring Terminal Figure 3-16—J3: AC Input Terminal
See Note 2
– + – +
12 VDC 12 VDC
See Note 5
E1951 BACKUP BATTERIES
6. ANY PRIMARY AND SECONDARY POWER SUPPLY UNITS MAY BE INSTALLED EXTERNALLY TO THE
NRTL EQ3900G POWER DISTRIBUTION/MONITORING ENCLOSURE, PROVIDED THEY ARE PROTECTED
AGAINST PHYSICAL DAMAGE. ALL DEDICATED BRANCH CIRCUITS AND CONNECTIONS BETWEEN
NOTES PRIMARY AND SECONDARY POWER SUPPLY UNITS AND THE NTRL EQ3900G POWER
1. AC INPUT SELECTABLE (THROUGH THE OIS) FOR 120 / 208 / 240 VAC. DISTRIBUTION/MONITORING ENCLOSURE SHALL ALSO BE PROTECTED AGAINST PHYSICAL DAMAGE.
2. BATTERY SIZE CALCULATED BASED ON SYSTEM LOAD. 7. SUPERVISION (SINGLE OPENS & GROUNDS) OF THE INTERCONNECTIONS BETWEEN POWER SUPPLY
3. CIRCUIT BREAKER SHALL PROTECT AGAINST EXCESSIVE CURRENT LOAD. (24 VDC OUTPUT) TO NRTL EQ3900G POWER DISTRIBUTION/MONITORING ENCLOSURE AND BACKUP
4. NRTL EQ3900G POWER DISTRIBUTION/MONITORING ENCLOSURE IS KEY LOCKED ENCLOSURE. BATTERIES TO NRTL EQ3900G POWER DISTRIBUTION/MONITORING ENCLOSURE IS PERFORMED BY
EQ2100PSM POWER SUPPLY MONITOR.
5. DASH LINES DENOTE PROTECTION AGAINST PHYSICAL DAMAGE.
8. THE CIRCUIT DISCONNECTING MEANS (AC & DC BREAKERS) SHALL BE ACCESSIBLE ONLY TO
AUTHORIZED PERSONNEL.
9. AC WIRING CABLE MUST BE ≤20 FEET IN CONDUIT.
Figure 3-17— Wiring Connections for a Power Supply Monitor, EQ21XXPS Series Power Supply and Backup Batteries
1 CURRENT SENSE +
WARNING
Make sure a.c. power is OFF at main a.c.
breaker before beginning power supply 2 CURRENT SENSE –
installation.
3 BATTERY –
IMPORTANT
Power supplies require unrestricted air
flow for proper cooling. 4 BATTERY +
CB
PRIMARY POWER L –
24 VDC –
See Notes 1 & 2 N
OUTPUT
G + + + + POWER DIST CKT #1 –
+ IN OUT
+ + + POWER DIST CKT #2 –
EQP2120PS(-x) POWER SUPPLY
– – + POWER DIST CKT #3 –
D2445
NOTES: 1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz (CUSTOMER SUPPLIED).
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO ONE POWER SUPPLY AND SECONDARY SOURCE IS
CONNECTED TO THE OTHER.
3. A MAXIMUM OF 8 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-19A—Wiring Connections for a 20 amp DC (Maximum) Power Supply with Primary and Secondary AC Sources
CB
PRIMARY POWER L –
24 VDC –
See Notes 1 & 2 N
OUTPUT
G + + + + POWER DIST CKT #1 –
+ IN OUT
+ + + POWER DIST CKT #2 –
EQP2120PS(-x) POWER SUPPLY
– – + POWER DIST CKT #3 –
EQP2410PS(-P) CONVERTER
E2543
NOTES: 1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz. BOTH AC AND DC INPUTS ARE CUSTOMER SUPPLIED.
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO AC POWER SUPPLY AND SECONDARY SOURCE IS
CONNECTED TO DC CONVERTER.
3. A MAXIMUM OF 8 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC/DC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-19B—Wiring Connections for a 10amp (Maximum) Power Supply with an AC Primary and DC Secondary Source
CB
PRIMARY POWER L –
24 VDC –
See Notes 1 & 2 N
OUTPUT
G + + +
+ IN OUT
+ +
EQP2120PS(-x) POWER SUPPLY
– –
– –
CB
SECONDARY POWER + – REDUNDANCY
24 VDC – MODULE +
See Notes 2 & 4 –
OUTPUT
+
+ + + POWER DIST CKT #1 –
+ +
EQP2410PS(-P) CONVERTER IN OUT + POWER DIST CKT #2 –
+ +
+ POWER DIST CKT #3 –
– –
– + POWER DIST CKT #4 –
+
– –
24 VDC –
–
OUTPUT
+ REDUNDANCY –
+ MODULE
EQP2410PS(-P) CONVERTER
A2566
NOTES: 1. AC INPUT IS AUTO-SELECTABLE FOR 120–220 VAC, 60/50 Hz. BOTH AC AND DC INPUTS ARE CUSTOMER SUPPLIED.
2. PRIMARY SOURCE OF INPUT SUPPLY IS CONNECTED TO AC POWER SUPPLY AND SECONDARY SOURCE IS
CONNECTED TO DC CONVERTER.
3. A MAXIMUM OF 8 REDUNDANT PAIRS CAN BE CONNECTED TO INPUT AC/DC POWER.
4. THE SECONDARY SOURCE IS CONTINUOUSLY POWERED.
Figure 3-19C—Wiring Connections for a 20amp (Maximum) Power Supply with an AC Primary and DC Secondary Source
To EDIO
PS 1 PS PS PS n
L PHOENIX –
L PHOENIX –
L PHOENIX –
L PHOENIX –
QUINT-PS – QUINT-PS – QUINT-PS – QUINT-PS –
N N N N
+ + + +
DC + DC + DC + DC +
13 14 OK 13 14 OK 13 14 OK 13 14 OK
D2438
Figure 3-20—Power Supply and Converter Relays Wired in Series for Trouble Monitoring (up to 16 Power Supplies/Converters)
in each diagram. The information is typical for Figure 3-22—Unsupervised Input Configuration
channels 2-8.
Supervised Input (IDC) Open Circuit
Connector P4, Terminals 13 to 24 Supervision
Terminals A, B & C
Connect external system wiring to the
Channels 5 to 8 Input / Output Terminals appropriate terminals on the terminal block.
For Class B wiring, see Figure 3-23. For
Refer to individual wiring configurations for
Class A wiring, see Figure 3-24. Note that two
terminal descriptions. Only channel 1 is shown
channels are used for one circuit when using
in each diagram. The information is typical for
Class A wiring.
channels 2-8.
The input to the EDIO module consists of one
Unsupervised Input or more normally open switches, with a 10 K
ohm, 1/4 watt EOL resistor in parallel across
Connect external system wiring to the the last switch.
appropriate terminals on the terminal block.
See Figure 3-22. Make no connection to “+ Supply” terminal.
COMMON C 3
The input to the EDIO consists of one or more
EOL
normally open or normally closed switches. An RESISTOR
EOL resistor is not required. 10 K Ω
IN– / OUT+ B 2
EQ3730EDIO
COMMON C 24
IN–/OUT+ B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM CLASS A
B 5 COM 2 B
PREVIOUS DEVICE CHANNEL 7
A 4 COM 2 A COMMON C 21
INLINE
IN– / OUT+ B 5 IN– / OUT+ B 5 RESISTOR
3.3 K Ω
+ SUPPLY A 4 + SUPPLY A 4
COMMON C 3 COMMON C 3
EOL
EOL
RESISTOR
RESISTOR
10 K Ω
10 K Ω
IN– / OUT+ B 2
IN– / OUT+ B 2
+ SUPPLY A 1
+ SUPPLY A 1 B2292
B2291
Figure 3-26—Supervised Input Configuration
Figure 3-24—Supervised Input Configuration – Class A for Opens and Shorts – Class A
Connect external system wiring to the The initiating device circuit(s) for use with the
appropriate terminals on the terminal block. deluge and pre-action system configuration
For Class B wiring, see Figure 3-25. For Class A must use Class A wiring or be wired within 20
wiring, see Figure 3-26. Note that two channels feet and in conduit from the EDIO, as per FM
are used for one circuit when using Class A standard 1011/1012/1013.
wiring. Both wiring configurations provide
indication of open and short circuit fault. The Two-Wire Devices
input to the EDIO module consists of normally
open switches, with a 10 K ohm, 1/4 watt EOL Figure 3-27 shows the wiring for a 2-wire
resistor in parallel across the return channel, device connection to an EDIO channel for
and a 3.3 K ohm, 1/4 watt resistor in series with Class B wiring
each switch.
Four-Wire Devices
NOTE
Figure 3-28 shows the wiring for a 4-wire
COMMON C 3
INLINE device connection to an EDIO channel for
RESISTOR EOL Class A wiring
3.3 K Ω RESISTOR
10 K Ω
If using more than one switch, the first Connect external system wiring to the
active condition (switch closed) must be appropriate terminals on the terminal block.
latched. Any subsequent closed switch See Figure 3-29.
will indicate a short circuit fault condition.
No connection should be made to “+ Supply”
Make no connection to “+ Supply” terminal. terminal.
IN IN IN
+ SUPPLY A 1 + + +
EOL
RESISTOR
5K
+ C + C + C
OUT OUT OUT
IN–/OUT+ B 2 A2283-102019
COMMON C 3 UNUSED
Figure 3-27— 2-Wire Devices (Class B)
COMMON C 3
COMMON
EOL
RESISTOR COMMON C 3
10 K
IN– / OUT+ B 2
+ SUPPLY A 1
COMMON C 3
Figure 3-30—Supervised Output Configuration
(Notification)— Class B
+ SUPPLY A 1
IN– / OUT+ B 5
A2321
appropriate terminals on the terminal block. For Figure 3-31—Supervised Output Configuration
Class B wiring, refer to Figure 3-30. (Notification)— Class A
+ SUPPLY A 4
Det-Tronics S³ Safety System Software is used
for device configuration. The following shows COMMON C 3
Table 3-10—Typical Maximum Wire Length for FM Approved Solenoids for Deluge and Pre-Action Applications
Viking PN 11601
Viking PN 11602
Kidde-Fenwal 897494
130
Cat # 202-749-260563
Kidde-Fenwal 895630
1500
Cat # 81-895630-000
Kidde-Fenwal 890181
1500
Det-Tronics PN 00219-209
Ansul 570537
200
Macron 304.209.001
*Note: Alternate secondary power source when accept by Local AHJ, may increase permissible wire voltage drops. Actual
secondary voltage must be determined. Voltage and current at solenoid must be known and used in the equation.
EQ3700DCIO
COMMON C 24
IN–/OUT+ B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A COMMON C 21
COMMON C 15
IN–/OUT+ B 14 CHANNEL 5
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
IN–/OUT+ B 11 CHANNEL 4
+ SUPPLY A 10
COMMON C 9
IN–/OUT+ B 8 CHANNEL 3
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC 5 –
– COMMON C 6
INPUT VOLTAGE
+ 4 + IN–/OUT+ B 5 CHANNEL 2
SHLD* 3 SHLD + SUPPLY A 4
24 VDC 2 –
–
INPUT VOLTAGE
+ 1 + COMMON C 3
All electrical connections are made to the field Connect external system wiring to the
wiring connectors furnished with the module. appropriate terminals. See Figure 3-36.
See Figure 3-35 for terminal identification.
Power Connector, Terminals 1 to 6
24 Vdc Power Input COMMON C 3
solenoid. It is essential to use a releasing + SUPPLY A 1 NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
TO BE INSTALLED ON THE FIELD DEVICE.
device approved for use with this output CIRCUIT PROTECTION IS PROVIDED
WITHIN THE DCIO.
A2323
module.
Figure 3-41—Unsupervised Output Configuration
NOTE
This type of output does not require NOTE
the use of EOL resistors or diodes to No connection should be made to the “+
supervise the circuit. Supply” terminal.
NOTE
CONFIGURATION
For new or retrofit installations, any
manufacturer’s non-water based agent Setting DCIO Network Address
release valves can be wired into the
outputs of the DCIO modules as long One unique network address must be assigned
as the devices utilize 24 Vdc and do not to each DCIO module. The address is set
exceed 2 amperes current draw. by the 8 DIP switch assembly on the DCIO
module. The address is binary coded and is
NOTE the sum of all switches placed in the “closed”
For FM system approval listing, pre- position.
action and deluge applications require Each discrete point of a DCIO module has
that only FM approved deluge valves be a tag number and a descriptor for unique
wired into the EDIO or DCIO modules. identification. A tag number must include zone
Table 3-10 lists the supported solenoid designation, which will be shown on the EQP
groups. Remember that the valves must Controller's display when the point is in alarm.
utilize 24 Vdc and must not exceed 2
amperes current draw. Det-Tronics S³ Safety System Software is used
for device configuration. The following shows
The output can be configured for latching, the minimum software/firmware releases:
continuous or timed response.
The maximum wiring length must not exceed EQP Controller Firmware S³
the values shown in Table 3-10 for deluge Revision Version Version
and pre-action applications. Per FM Approval
A 1.03 2.0.2.0
requirements, the secondary power must
provide capacity for a 90 hour minimum
standby operation followed by a minimum of
10 minutes of releasing and alarm operation.
22.2 3-38 95-8533
EQ3720RM INSTALLATION equipment to provide adequate room for
wiring and ventilation.
The following paragraphs describe how to
properly install and configure the EQ3720RM WIRING
Relay Module.
All electrical connections are made to the field
MOUNTING wiring connectors furnished with the module.
See Figure 3-42 for terminal identification.
The Relay Module must be properly installed
in a suitable enclosure that is rated for the Power Connector, Terminals 1 to 6
location. The enclosure must provide space to 24 Vdc Power Input
install and wire the relay module and must also
provide for ground wire termination. Access into 1— +
the enclosure is gained by using a special tool 2— –
to open the enclosure. The enclosure must be 3— Shield*
rated for the temperature range of the location 4— +
plus the temperature rise of all equipment 5— –
installed inside the enclosure. The enclosure 6— Shield*
must be rated for electrical equipment that is
going to be installed. The device can be panel *Shields on power wires required.
or DIN rail mounted.
Connect the module power supply to terminals
NOTE
1 and 2. If additional terminals are required for
It is recommended to maintain a powering other devices, these devices should
minimum of four inches clearance be connected to terminals 4 and 5. Shields are
b e t we e n t h e m o d u l e a n d o t h e r to be connected to terminals 3 and 6.
EQ3720RM
NC C 24
NO B 23 CHANNEL 8
SHLD 6 COM 2 SHLD COMMON A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A NC C 21
NC C 15
NO B 14 CHANNEL 5
COMMON A 13
TO
EARTH
GROUND NC C 12
NO B 11 CHANNEL 4
COMMON A 10
NC C 9
NO B 8 CHANNEL 3
COMMON A 7
SHLD* 6 SHLD
24 VDC
– 5 – NC C 6
INPUT VOLTAGE
+ 4 + NO B 5 CHANNEL 2
SHLD* 3 SHLD COMMON A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + NC C 3
POWER NO B 2 CHANNEL 1
COMMON A 1
* SHIELDS ON POWER WIRES ARE REQUIRED.
C2206
Be sure to observe polarity when wiring the Each discrete point of a relay module has
LON. a tag number and a descriptor for unique
1 — "A" side of signaling circuit for COM 1 identification.
2 — "B" side of signaling circuit for COM 1
4 — "A" side of signaling circuit for COM 2 Det-Tronics S³ Safety System Software is used
5 — "B" side of signaling circuit for COM 2 for device configuration. The following shows
3 & 6 — shield connections. the minimum software/firmware releases:
EQ3710AIM
COMMON C 24
4-20 MA IN B 23 CHANNEL 8
SHLD 6 COM 2 SHLD + SUPPLY A 22
LON FROM
B 5 COM 2 B
PREVIOUS DEVICE
A 4 COM 2 A COMMON C 21
COMMON C 15
4-20 MA IN B 14 CHANNEL 5
+ SUPPLY A 13
TO
EARTH
GROUND COMMON C 12
4-20 MA IN B 11 CHANNEL 4
+ SUPPLY A 10
COMMON C 9
4-20 MA IN B 8 CHANNEL 3
+ SUPPLY A 7
SHLD* 6 SHLD
24 VDC
– 5 – COMMON C 6
INPUT VOLTAGE
+ 4 + 4-20 MA IN B 5 CHANNEL 2
SHLD* 3 SHLD + SUPPLY A 4
24 VDC
– 2 –
INPUT VOLTAGE
+ 1 + COMMON C 3
All electrical connections are made to the field Figure 3-45—Two-Wire Transmitter with HART Interface
wiring connectors furnished with the module. Module — Non-Isolated 4 to 20 mA Current Output (Sourcing)
(Connectors accept wires 30-12 AWG (0.2-
2.5mm2)). Refer to Figure 3-43 for identification CHANNEL 1 TRANSMITTER
NOTE D.
Exposure to high concentrations of
A dust cover should be installed to combustible gases for extended periods
protect the flame arrester whenever these of time can stress the sensing element and
conditions exist. seriously affect its performance.
The degree of damage to the sensor is
B. Substances that cover or tie up the active sites determined by a combination of contaminant
on the catalytic surface of the active sensing type, contaminant concentration in the
element such as volatile metal organics, atmosphere, and the length of time the sensor
gases, or vapors of hydrides, and volatile is exposed.
compounds containing phosphorous, boron,
NOTE
silicone, etc.
If a sensor has been exposed to a
Examples: contaminant or a high level of combustible
gas, it should be calibrated at the time
RTV silicone sealants of exposure. An additional calibration
Silicone oils and greases a few days later should be performed to
Tetraethyl lead determine whether a significant shift
Phosphine in sensitivity has occurred. If necessary,
Diborane sensor should be replaced.
Silane
NOTE
Trimethyl chlorsilane
Hydrogen fluoride A combination of accessories such
Boron trifluoride as rain shields and dust covers is not
Phosphate esters recommended and can result in slow
response to a gas leak.
C. Materials that remove the catalytic metals
from the active element of the sensor. Some TYPICAL APPLICATIONS
substances react with the catalytic metal
forming a volatile compound that can erode Figure 3-55 is a simplified drawing of a typical
the metal from the surface of the sensor’s EQP System. This EQP System includes an EQP
active element. Controller, DCIO, and various LON field devices.
Halogens and compounds containing halogen
are materials of this nature and others
include:
Examples:
Chlorine
Bromine
Iodine
Hydrogen Chloride, Bromide or Iodide
Organic halides:
Trichloroethylene
Dichlorobenzene
Vinyl chloride
Freons
Halon 1301
(Bromotrifluoromethane).
NOTE
Brief exposure to these materials can
temporarily increase sensor sensitivity due
22.2 3-43 95-8533
22.2
+ +
– –
– POWER –
+ DISTRIBUTION + X3301 / X5200 / X2200 / X9800
+ Flame Detectors
–
+ – + –
CONTROLLER EQ3700DCIO* EQ2100PSM EQ3720RM
P1 P1 P1
6 SHIELD 3 4 SHIELD 9 13 SHIELD 3 13 SHIELD 3 3 SHIELD 6
52 B 49 5 B 2 11 B 3 14 B 4 14 B 4 5 B 2
53 A 50 4 A 1 10 A 2 15 A 5 15 A 5 4 A 1
P6
SHUNT P3
C 45
C 1 N
FAULT NO 46 P4 P3
B 2
NC 47 A + SUPPLY A AC LINE
P9 P8 3
B IN–/OUT+ B + –
CH 1
CH 5
GND 5 57 GND GND 54 24 VDC 4 H
C COMMON C SUPPLY
RXD 2 58 RxD B 55
3-44
TXD 3 59 TxD A 56 A + SUPPLY A
DB-9 H N
P2 P3
CONNECTION B IN–/OUT+ B AC LINE
CH 6
CH 2
TO COM PORT 5 1+ 5+ 13
OF PC
6 1– 5– 14 C COMMON C
+ –
7 2+ 6+ 15
A + SUPPLY A 24 VDC
8 2– 6– 16 BATTERY LS2000
B IN–/OUT+ B
CH 3
CH 7
9 3+ 7+ 17 EQ24xxNE PIRECL RECEIVER
10 3– 7– 18 C COMMON C
4 SHIELD 9 6 SHIELD 3 4 SHIELD 14
11 4+
DIGITAL INPUTS
8+ 19
A + SUPPLY A
12 4– 8– 20 6 24 VDC – 7 4 24 VDC – 1 3 24 VDC – 2
B IN–/OUT+ B
CH 4
CH 8
P4 P5 5 24 VDC + 8 5 24 VDC + 2 13 24 VDC + 12
21 C C 33 C COMMON C
COM2 COM1 COM2 COM1 COM2 COM1
22 NO NO 34
RELAY 1
SHIELD SHIELD SHIELD
RELAY 5
12 1 12 9 17 8
23 NC NC 35
* LON AND POWER TERMINALS ALSO
24 C C 36 VALID FOR AIM, RM, EDIO. 11 B 3 11 B 8 15 B 5
SEE INDIVIDUAL DEVICE FOR
25 NO NO 37
CHANNEL TERMINALS.
RELAY 2
A A A
RELAY 6
10 2 10 7 16 6
26 NC NC 38
THE DEVICE’S CHASSIS GROUND
27 C C 39 TERMINAL SHOULD BE
CALIBRATE 13 CALIBRATE 9
CONNECTED TO EARTH GROUND.
28 NO NO 40
RELAY 3
RELAY 7
29 NC NC 41
30 C C 42
31 NO NO 43
95-8533
RELAY 8
RELAY 4
32 NC NC 44
Figure 3-55—A Typical EQP System
SYSTEM CONFIGURATION
1 X O O O O O O O 61 X O X X X X O O
2 O X O O O O O O 62 O X X X X X O O
3 X X O O O O O O 63 X X X X X X O O
4 O O X O O O O O 64 O O O O O O X O
5 X O X O O O O O 65 X O O O O O X O
6 O X X O O O O O 66 O X O O O O X O
7 X X X O O O O O 67 X X O O O O X O
8 O O O X O O O O 68 O O X O O O X O
9 X O O X O O O O 69 X O X O O O X O
10 O X O X O O O O 70 O X X O O O X O
11 X X O X O O O O 71 X X X O O O X O
12 O O X X O O O O 72 O O O X O O X O
13 X O X X O O O O 73 X O O X O O X O
14 O X X X O O O O 74 O X O X O O X O
15 X X X X O O O O 75 X X O X O O X O
16 O O O O X O O O 76 O O X X O O X O
17 X O O O X O O O 77 X O X X O O X O
18 O X O O X O O O 78 O X X X O O X O
19 X X O O X O O O 79 X X X X O O X O
20 O O X O X O O O 80 O O O O X O X O
21 X O X O X O O O 81 X O O O X O X O
22 O X X O X O O O 82 O X O O X O X O
23 X X X O X O O O 83 X X O O X O X O
24 O O O X X O O O 84 O O X O X O X O
25 X O O X X O O O 85 X O X O X O X O
26 O X O X X O O O 86 O X X O X O X O
27 X X O X X O O O 87 X X X O X O X O
28 O O X X X O O O 88 O O O X X O X O
29 X O X X X O O O 89 X O O X X O X O
30 O X X X X O O O 90 O X O X X O X O
31 X X X X X O O O 91 X X O X X O X O
32 O O O O O X O O 92 O O X X X O X O
33 X O O O O X O O 93 X O X X X O X O
34 O X O O O X O O 94 O X X X X O X O
35 X X O O O X O O 95 X X X X X O X O
36 O O X O O X O O 96 O O O O O X X O
37 X O X O O X O O 97 X O O O O X X O
38 O X X O O X O O 98 O X O O O X X O
39 X X X O O X O O 99 X X O O O X X O
40 O O O X O X O O 100 O O X O O X X O
41 X O O X O X O O 101 X O X O O X X O
42 O X O X O X O O 102 O X X O O X X O
43 X X O X O X O O 103 X X X O O X X O
44 O O X X O X O O 104 O O O X O X X O
45 X O X X O X O O 105 X O O X O X X O
46 O X X X O X O O 106 O X O X O X X O
47 X X X X O X O O 107 X X O X O X X O
48 O O O O X X O O 108 O O X X O X X O
49 X O O O X X O O 109 X O X X O X X O
50 O X O O X X O O 110 O X X X O X X O
51 X X O O X X O O 111 X X X X O X X O
52 O O X O X X O O 112 O O O O X X X O
53 X O X O X X O O 113 X O O O X X X O
54 O X X O X X O O 114 O X O O X X X O
55 X X X O X X O O 115 X X O O X X X O
56 O O O X X X O O 116 O O X O X X X O
57 X O O X X X O O 117 X O X O X X X O
58 O X O X X X O O 118 O X X O X X X O
59 X X O X X X O O 119 X X X O X X X O
60 O O X X X X O O 120 O O O X X X X O
121 X O O X X X X O 191 X X X X X X O X
122 O X O X X X X O 192 O O O O O O X X
123 X X O X X X X O 193 X O O O O O X X
124 O O X X X X X O 194 O X O O O O X X
125 X O X X X X X O 195 X X O O O O X X
126 O X X X X X X O 196 O O X O O O X X
127 X X X X X X X O 197 X O X O O O X X
128 O O O O O O O X 198 O X X O O O X X
129 X O O O O O O X 199 X X X O O O X X
130 O X O O O O O X 200 O O O X O O X X
131 X X O O O O O X 201 X O O X O O X X
132 O O X O O O O X 202 O X O X O O X X
133 X O X O O O O X 203 X X O X O O X X
134 O X X O O O O X 204 O O X X O O X X
135 X X X O O O O X 205 X O X X O O X X
136 O O O X O O O X 206 O X X X O O X X
137 X O O X O O O X 207 X X X X O O X X
138 O X O X O O O X 208 O O O O X O X X
139 X X O X O O O X 209 X O O O X O X X
140 O O X X O O O X 210 O X O O X O X X
141 X O X X O O O X 211 X X O O X O X X
142 O X X X O O O X 212 O O X O X O X X
143 X X X X O O O X 213 X O X O X O X X
144 O O O O X O O X 214 O X X O X O X X
145 X O O O X O O X 215 X X X O X O X X
146 O X O O X O O X 216 O O O X X O X X
147 X X O O X O O X 217 X O O X X O X X
148 O O X O X O O X 218 O X O X X O X X
149 X O X O X O O X 219 X X O X X O X X
150 O X X O X O O X 220 O O X X X O X X
151 X X X O X O O X 221 X O X X X O X X
152 O O O X X O O X 222 O X X X X O X X
153 X O O X X O O X 223 X X X X X O X X
154 O X O X X O O X 224 O O O O O X X X
155 X X O X X O O X 225 X O O O O X X X
156 O O X X X O O X 226 O X O O O X X X
157 X O X X X O O X 227 X X O O O X X X
158 O X X X X O O X 228 O O X O O X X X
159 X X X X X O O X 229 X O X O O X X X
160 O O O O O X O X 230 O X X O O X X X
161 X O O O O X O X 231 X X X O O X X X
162 O X O O O X O X 232 O O O X O X X X
163 X X O O O X O X 233 X O O X O X X X
164 O O X O O X O X 234 O X O X O X X X
165 X O X O O X O X 235 X X O X O X X X
166 O X X O O X O X 236 O O X X O X X X
167 X X X O O X O X 237 X O X X O X X X
168 O O O X O X O X 238 O X X X O X X X
169 X O O X O X O X 239 X X X X O X X X
170 O X O X O X O X 240 O O O O X X X X
171 X X O X O X O X 241 X O O O X X X X
172 O O X X O X O X 242 O X O O X X X X
173 X O X X O X O X 243 X X O O X X X X
174 O X X X O X O X 244 O O X O X X X X
175 X X X X O X O X 245 X O X O X X X X
176 O O O O X X O X 246 O X X O X X X X
177 X O O O X X O X 247 X X X O X X X X
178 O X O O X X O X 248 O O O X X X X X
179 X X O O X X O X 249 X O O X X X X X
180 O O X O X X O X 250 O X O X X X X X
181 X O X O X X O X
182 O X X O X X O X
183 X X X O X X O X
184 O O O X X X O X
185 X O O X X X O X
186 O X O X X X O X
187 X X O X X X O X
188 O O X X X X O X
189 X O X X X X O X
190 O X X X X X O X
CH 2
B
A
SOLENOID COIL CH 1 SOLENOID COIL
B A
NOTE:
CH 1 SHUNT/FLYBACK DIODES DO
NOT NEED TO BE INSTALLED
ON THE FIELD DEVICE. CIRCUIT NOTE: SHUNT/FLYBACK DIODES DO NOT NEED
PROTECTION IS PROVIDED TO BE INSTALLED ON THE FIELD DEVICE.
A
WITHIN THE HSDM MODULE. CIRCUIT PROTECTION IS PROVIDED
WITHIN THE HSDM MODULE.
Figure 3-53A - Supervised Output Configuration Figure 3-53B - Supervised Output Configuration
with Solenoid Disconnect Switch - Class A with Solenoid Disconnect Switch - Class B
Figure 3-53C - Supervised Output Configuration between EDIO and HSDM modules - Class A
Cancel cancels the selected command, Reset resets all EQP Controller latched outputs
and returns the menu to the last option list that are no longer active.
displayed.
Acknowledge silences the internal beeper.
Enter chooses the menu item selected, and
advances the menu to the next options list. Silence turns on the Silence LED and sets
(See “EQP Controller Menu Options“ in this Silence status in user logic.
section for additional information). Pressing
the enter button is required when performing
a configuration download to the EQP Controller
from an Ethernet connected PC running S3.
DET-TRONICS
®
Time & Date High Gas Cntrl Flt Out Inhibit Supr
DET-TRONICS
®
Time & Date High Gas Cntrl Flt Out Inhibit Supr
Time & Date High Gas Cntrl Flt Out Inhibit Supr
Figure 4-2—EQP Controller Message Display and System Status Indicator Location
Main Menu
Device Tagnames*
Display Alarms Alarm Type Off/On Visible if the
Display Devices Tag Name for Device n
Tag Name alarm was
Previous
Enter
Next
Communication Ports*
Configuration Port
Redundancy Info
Serial Port 1
Serial Port 2
Fault: No Fault
Serial Port 3
Lst Flt: Cntr LON
Serial Port 4
Cntr Mode: Master
Redundancy Port
My Config: Primary
Ethernet Port 3
Mem Tx: 304 ms
Ethernet Port 4
Mem Blk: 9 of 200
LON 1
HSSL Status: Good
LON 2
Version Match: Good
SIL Constant: Good
Reduced Node: Good
Diagnostics Parser: Good
Comm Ack: Good
Lamp Test – Enter Cntr LON: Good
Display: Traditional Msg Error: Good
HW Version: X --Master Errors--
Extra Device: 0 Program Flow: Good
Watchdog Count: 0 LON A Inf: Good
SRR0 = XXXXXXXX LON B Inf: Good
Run Time = 66 Hrs User Logic CS: Good
CNET Rev = 002.000 User Logic: Good
CNET Error Code = 0 Config: Good
OSC Value = XXXXXXX Dead LON: Good
SIL: False Cntrl Fault: Good
Reduced Nodes: False --Standby Errors--
HW Option Board: 3 Program Flow: Good
OS 0000 LON A Inf: Good
DR 0000 LON B Inf: Good
LLF = False (6) Sec User Logic CS: Good
Rx 0 0 User Logic: Good
Config: Good
Dead LON: Good
Cntrl Fault: Good
Power 1: Good
Power 2: Good
Option Bd: Good
RTC: Good
LON Gnd: Good
LON Fault: Good
RS485 Gnd Flt: Good
Comm Bd: Good
Rx State: Good
My State: Sending
User Logic
General Info
Program Memory
View Time
Z398-63 U / I
22.2 4-4 95-8533
Add:63 UV / IR Detect
No Fault
SERIAL PORTS displays port information on Cntr Mode
all available ports.
Indicates whether the EQP Controller is in
Serial Ports master or standby mode.
Configuration Port
Serial Port 1 My Config
Serial Port 2
Indicates whether the EQP Controller is the
primary or secondary EQP Controller.
Pressing the NEXT or PREVIOUS pushbutton
allows cycling through ports. Pressing the
CANCEL pushbutton will return the display to Redun Mem
the Main Menu.
Displays how long it takes to transfer the local
DIAGNOSTICS displays information for factory and global memory between EQP Controllers.
field service.
HSSL Status
Diagnostics
Lamp Test -Enter- An error is generated when a problem is
Display: Traditional detected on the high-speed communication
HW Version: 2 link between EQP Controllers. This fault is
annunciated when the standby EQP Controller
is offline.
REDUNDANCY INFO displays the current
status of all redundancy related faults. It can
be used to monitor the health of the master and Version Match
standby EQP Controllers. It can also be used
for diagnostic purposes. To ensure proper redundant operation, the
firmware versions of redundant EQP Controllers
Redundancy faults originate from three general must match. This error is set when a mismatch
areas: is detected. Consult the factory for firmware
• Self detected internal failures of the upgrades.
master EQP Controller
• Inter-controller communications SIL Rating
• A failure in the standby EQP
Controller To ensure proper redundant operation, the
SIL rating of redundant EQP Controllers must
Any redundancy fault is annunciated by the match. An error is indicated if a SIL EQP
master EQP Controller, and the redundancy Controller is paired with a non‑SIL rated EQP
fault code of the highest priority fault is Controller. Consult the factory for details.
displayed. The EQP Controller also provides a
diagnostic menu for more detailed information Parser
on the source of a redundancy problem. All
redundancy related faults must be cleared to As the master EQP Controller configures
insure proper redundancy operation. a standby EQP Controller, configuration
information is extracted from non-volatile
memory and checked for errors.
Fault
A or B Cause Action
Off Channel disabled Program network for redundant media,
if required.
Steady green Normal operation None
Flashing green/off Temporary errors None; unit will self-correct.
Listen only Cycle power.
Flashing red/off Media fault Check media for broken cables, loose
connectors,missing terminators, etc.
No other nodes present on network Add other nodes to the network.
Flashing red/green Incorrect network configuration Cycle power or reset unit. If fault
persists, contact the factory.
0.5 SEC 0.5 SEC 1.5 SEC Flashing - The indicator alternates between
the two defined states (applies to each
FIRE
ALARM indicator viewed independent of the other). If
both indicators are flashing, they must flash
0.1 SEC 0.1 SEC
together, in phase.
2.0 SEC
SUPERVISORY
ETHERNET DLR STATUS INDICATORS
0.5 SEC
(OPTIONAL)
5.0 SEC
Link Status 2
Time & Date High Gas Cntrl Flt Out Inhibit Supr
Steady - The indicator is on continuously in the Cancel Enter Next Previous Reset Acknowledge Silence
defined state.
Figure 4-5—Location of Ethernet DLR Status LEDs
b) Text display’s third line displays time 1. Make sure the LON and HSSL are
(24 hour format) and date (month/day/ connected correctly.
year).
2. Apply power to both EQP Controllers.
NOTE 3. EQP Controllers perform their boot-up
Depending on the condition of the LON routine.
devices, faults may persist for a number 4. The EQP Controller that is connected with
of minutes. the primary end of the HSSL is identified as
the primary EQP Controller and is assigned
EQP CONTROLLER REDUNDANCY address 1.
5. The EQP Controller that is connected with
Pushbuttons the secondary end of the HSSL is assigned
address 2.
The pushbuttons are active on the master EQP
Controller and inactive on the standby EQP 6. If there are no faults present, the primary
Controller. EQP Controller defaults to the master
EQP Controller and the secondary EQP
EQP Controller Status Indicators Controller defaults to the standby EQP
Controller.
The status indicators are active on the master
EQP Controller. All LEDs except the power LED 7. The master EQP Controller executes
are off and the trouble relay is in the no trouble user logic and communicates with the
state. connected LON devices.
EQP Controller Relay Operation 8. The standby EQP Controller indicates that
it is in standby mode and monitors the
The EQP Controller relays are fully functional master EQP Controller.
on the master EQP Controller and the standby 9. The master and standby EQP Controllers
EQP Controller. perform a synchronization process.
Text Display
10. The power-up sequence is complete.
The text display on the master EQP Controller
is fully functional as explained in the previous
Synchronization
section. The text display on the standby EQP
When a master EQP Controller detects
Controller reads **Standby Mode**, Ready.
a standby EQP Controller on the HSSL,
EQP Controller Menu Options it performs the following synchronization
process:
The menu options are active on the master
EQP Controller and inactive on the standby 1. Compare EQP Controller firmware versions
EQP Controller. and SIL rating. If they are not an exact match,
the process stops and a fault is generated.
ControlNet or Ethernet DLR Status
Consult the factory for details.
Indicators
2. Standby EQP Controller indicates the
The ControlNet or Ethernet DLR status synchronization steps.
indicators are active on the master and standby
3. Compare the user application programs.
EQP Controllers. See Table 4-3 for status of
If there is a mismatch, the master will
ControlNet LED indicators and Tables 4-4
configure the standby EQP Controller via
through 4-6 for Ethernet DLR LED indicators.
the HSSL.
4. Initiate the data synchronization process.
Automatic Switchover
WARNING
An automatic transfer will be initiated if the
The EQP System is inactive and master EQP Controller goes into an error
not executing logic/alarm functions (self detected internal EQP Controller failure,
during a program download (in both program flow error in the EQP Controller, user
single and redundant EQP Controller logic checksum error or application checksum
configurations). error). An automatic switchover executes the
following sequence:
When downloading a new configuration to the
master EQP Controller, the following sequence 1. Check that the standby EQP Controller is
is executed: online by verifying that HSSL communication
is good and there are no internal faults in the
1. The S³ software must be connected to the standby EQP Controller.
master EQP Controller. 2. Verify that the synchronization process is
2. Alter the configuration and execute the complete.
download command from S³. 3. The master requests the standby to take
3. The master EQP Controller goes into control.
‘Program’ mode and passes mastership to 4. The standby takes control and becomes the
the standby EQP Controller. master.
4. The updated configuration file is loaded into
the EQP Controller. Replacing a Faulty EQP Controller
5. The EQP Controllers are automatically If the master EQP Controller fails and the
forced to switch over. standby EQP Controller is healthy, an automatic
6. The master EQP Controller puts the standby switchover will occur. To replace the failed EQP
EQP Controller into ‘Program’ mode and Controller, perform the following steps:
downloads the configuration.
1. Remove power. Disconnect plugs and
7. The EQP Controller indicates “Device
remove the failed EQP Controller.
Download Active” until the LON devices
have been successfully updated. 2. Mount the new EQP Controller.
8. The configuration download is now 3. Connect the LON to the new EQP
complete. Controller.
4. Connect the HSSL.
Manual Switchover
5. Connect any other I/O used.
The user can request a manual switchover 6. Apply power to the EQP Controller.
from an externally wired switch. The request
executes the following sequence:
LED indicators.
Table 4-8—EDIO Module - Channel Status Indicators
POWER-UP SEQUENCE
Set the module address switch prior to applying LED Channel Status
power.
Red When On steady indicates the input
circuit is closed or the output circuit
EDIO module power-up sequence illuminates is active
the LEDs for the device and all of its channels.
First the power and fault LEDs are illuminated, Yellow When Blinking indicates a low power
condition is present or channel is not
indicating that the device is in a power-up properly configured. Steady indicates
mode. Next the LEDs are illuminated in the a channel fault.
following sequences:
POWER-UP SEQUENCE
Set the module address switch prior to applying
power.
LED Device Status Once the address has been displayed, the
device’s fault LED will turn off.
Green On when power is present.
Yellow When On steady indicates device After the power-up sequence, the device will
is disabled or must be replaced. either display an unconfigured state or normal
Possible Watchdog Timer problem. operation state. In the unconfigured state, the
NOTE channel fault yellow LEDs flash ON and OFF at
Blinks one time at power-up. the same rate for all channels.
POWER-UP SEQUENCE
Set the module address switch prior to applying
power.
POWER-UP SEQUENCE
+ +
+
+
1 + +
+ +
+
it activates.
+
1
+
AMBER LED
RED LED
GREEN LED
Yellow When On indicates device is disabled. Figure 4-11—Ground Fault Monitor Status Indicator Location
Module must be replaced.
LON
EQ3720RM Module
Rocker switches for each LON device must be
set to the desired address prior to power-up. Verify correct address setting.
Test the loop with no power applied. DC Check for correct output connections.
resistance should be equal on A and B.
Check polarity on A and B (no rolls). COM EQ3710AIM Module
1 connects to COM 2; COM 2 connects to
COM 1. A connects to A and B to B. Verify correct address setting.
Measure voltage. A to chassis ground Check for correct input connections.
measures approximately +7.5 Vdc. B to Check each channel with a loop current input.
ground measures approximately –7.5 Vdc.
Measure signal (400 mv P-P min.). (Use
oscilloscope if possible.) Power Supplies and Power Monitors
Check fault tolerance by introducing a short. Verify all earth ground connections as specified
in the wiring instructions.
Verify correct ac power to supply.
EQP Controller
Check power distribution to ensure that all
The I/O and LON wiring is correctly installed, devices are receiving power.
observing polarity. All cable shields are
Check power trouble indicator by introducing
properly terminated and insulated.
an open to the battery.
Power wiring is installed and power source is
operational.
Ground Fault Monitor
Chassis ground stud must be connected to
earth ground. Verify earth ground connections as specified in
the wiring instructions.
Check power distribution to ensure that all
devices are receiving power.
AIM Startup
WARNING CAUTION
Trouble - LED lit and Any monitored device in the – Using the front panel display/controls, view
relay is active. system including ground fault in all points in alarm/fault and identify faulted
fault condition. device.
– Repair or replace faulted device as necessary.
Digital inputs are – Bad input switch. – Check that P2 and P3 are fully inserted.
not responding – Faulty input channel. – Using a voltmeter, measure input terminals with
– Faulty wiring. contact closed to the input (measures 0 vdc when
– Configuration error. input contact is closed, measures approximately
23 Vdc with circuit open and 24 vdc input at the
EQP Controller).
– If input does not respond to a contact closure,
replace module (verify response with EQ Safety
System Software/textual display).
– Verify configuration.
Relay Outputs are – Bad relay channel. – Check that P4 and P5 are fully inserted.
not respond to an – Faulty output wiring. – When output should be energized, measure
output command – User logic. contact resistance using an ohm meter.
– Verify that wiring from output is not open.
– Using EQ Safety System Software, verify that logic
is trying to operate the channel.
Serial links are not – Faulty wiring. – Check that P8 and P9 are fully inserted.
responding – Incorrect serial link – Verify that communication LEDs are flashing.
configuration. – Verify that serial link configuration matches the
– Text display shows "Invalid host device.
Configuration" – Verify that wiring is not open or shorted.
Ethernet link are not – Faulty wiring. – Check that P3 and P4 are fully inserted.
responding – Incorrect Ethernet link – Verify that communication LEDs are flashing.
configuration. – Verify that Ethernet link configuration is
– Text display shows "Invalid correct.
Configuration" – Verify that wiring is not open or shorted.
Front panel push – Power OFF. – Verify that power is present and P1 is fully
buttons are not – EQP Controller is faulted. inserted.
working – Cycle power to EQP Controller.
Text display Power loss for more than 12 – Using the Safety System Software, execute “Set
indicates a RTC hours RTC”, which downloads the current time into the
Fault EQP Controller’s real time clock. Alternatively,
use the “Set Time and Date” menu in the EQP
Controller.
Hardware memory Device on the LON with a ground – This condition indicates a wiring issue in which
fault fault the alarm will override status. Requires an EQP
Controller reset.
APPROVED
High Gas
Trouble
Cntrl Flt
Inhibit
Out Inhibit
Power
Supr 5.5
(14.0)
including Protected Premises Fire Alarm
Low Gas Lon Fault Ack Silence
Systems and EQP Supervising Systems. Cancel Enter Next Previous Reset Acknowledge Silence
ATEX: FM
APPROVED
®
FM ®
Ex nA nC IIC T4 Gc.
PPROVED
EN 60079-29-1 & EN 60079-29-4. DIN RAIL MOUNTING DIMENSIONS
6.7
Ex nA nC IIC T4 Gc. EAGLE QUANTUM PREMIER
Safety System Controller
(17.0)
Time & Date High Gas Cntrl Flt Out Inhibit Supr 6.7
Low Gas Lon Fault Ack Silence
(17.0)
7.0
(17.78)
VIBRATION—
ATEX: FM
APPROVED
®
ATEX: FM
APPROVED
®
II 3 G.
2.16
(5.5)
Ex nA nC IIC T4 GC EN 60079-29-1.
1.87
(4.75)
UL 20 ATEX 138864X.
Tamb = –40°C to +85°C.
FM ®
APPROVED
A2253
1 6 1 6 1 6 1 6
5.02
(12.7)
4.5
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 (11.3)
4.5
A B C A B C A B C A B C A B C A B C A B C A B C (11.3) A B C A B C A B C A B C A B C A B C A B C A B C
5.2
5.2 1.66 (13.2) 1.9
A2449 (13.2) (4.2) (4.8)
Figure 6-3—Dimensions of the EDIO / DCIO / Relay Module / AIM in Inches (Centimeters)
IECEx: IECEx UL 20.0112X. channels for Class A wiring and connect both
Ex nA nC IIC T4 GC. channels to single contact device(s).
Tamb = –40°C to +85°C.
INPUT CIRCUITS – TWO WIRE SMOKE/HEAT
Note: Refer to Appendix C for ATEX and IECEx TYPE—
approval details and Special Conditions for Supervised Input, Class B:
Safe Use, and refer to 57-1009 Addendum for Up to 15 two wire detectors per circuit.
Maximum line resistance 50 ohms.
USCG Approval details.
5K ohm EOL.
INPUT / INITIATING DEVICE CIRCUITS Open circuit fault impedance 22k ohms.
UNSUPERVISED INPUT—
Two state input (on/off). OUTPUT / NOTIFICATION / RELEASING OR
Normally open contact. UNSUPERVISED DEVICE CIRCUITS
UNSUPERVISED OUTPUT RATING
SUPERVISED INPUT (OPEN CIRCUIT)— (Per Channel)—
For Class A and Class B wiring. 2 amperes at 30 Vdc maximum.
Two state input (active/trouble): Automatic short circuit protection provided.
– End of Line Resistor 10 K ohms nominal Instantaneous short circuit current < 15
– Open Circuit > 11 K ohms amperes.
– Active Circuit < 5 K ohms. Note: Voltage available at outputs is dependent
on input voltage (Vout ≈ Vin – 0.5 Vdc).
SUPERVISED INPUT
(OPEN AND SHORT CIRCUIT)— OUTPUT STYLE—
For Class A and Class B wiring. Form "A" normally off.
Three State input (active/short/open):
– End of Line Resistor 10 K ohms nominal RESPONSE TIME—
– In Line Resistor 3.3 K ohms nominal Output actuates in <0.15 second after
– Open Circuit > 11 K ohms acknowledging an alarm command
– Short Circuit < 250 ohms message.
– Active Circuit 2.5 K ohms to 5 K ohms.
INPUT, TYPES—
Configurable for static logic applications:
– Fire Alarm
– Supervisory
– Trouble
– High Gas Alarm
– Low Gas Alarm
– Other.
For Class A wiring on inputs, configure adjacent
– Timed.
Refer to Appendix A for FM Approval details.
For Class A wiring on outputs, configure
Refer to Appendix B for CSA Approval details.
adjacent channels for Class A wiring and
connect both channels to single output
device(s).
NOTE
ATEX: FM
APPROVED
®
FM ®
Ex nA nC IIC T4 Gc EN60079-29-1.
APPROVED
UL 20 ATEX 138864X.
Note: Refer to Appendix C for ATEX and IECEx Tamb = –40°C to +85°C.
approval details and Special Conditions for FM ®
Safe Use.
IECEx: IECEx UL 20.0112X.
APPROVED
Ex nA nC IIC T4 Gc.
RESPONSE TIME—
Tamb = –40°C to +85°C.
Actuates in <0.15 second after acknowledging
an alarm command message. Note: Refer to Appendix C for ATEX and IECEx
approval details and Special Conditions for
Safe Use. Refer to 57-1009 Addendum for
USCG Approval details.
CERTIFICATION—
FM / CSA: Ordinary locations.
CERTIFICATION—
APPROVED
2.9 1.18
ATEX II 3 G.
FM
APPROVED
®
(7.4) (3.0)
FM ®
Ex nA IIC T4 Gc.
APPROVED
DIMENSIONS—
See Figure 6-5.
CERTIFICATION—
FM / CSA: Ordinary locations.
9
(22.9)
8.5
(21.6)
J3 2.25
J1 (5.7)
4
(10.2)
B C
2.5
(6.4)
A2038
CERTIFICATION—
APPROVED
Type 4X.
Refer to Appendix A for FM Approval details.
ATEX: FM
APPROVED
®
3.77
EQ24XXNE NETWORK (9.6)
EXTENDER/EQ24XXPLR 1.28
INPUT VOLTAGE—
24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage 5.86
INPUTS/OUTPUTS—
Digital, transformer isolated (78.5k Baud). 4.7
(11.9)
HUMIDITY— A2531
INPUT POWER—
EQ3780HSDM HIGH SPEED 9 watts nominal, 12 watts maximum.
DELUGE MODULE
For complete information regarding the HSDM LON COMMUNICATION—
Module, refer to instruction manual number Digital communication, transformer isolated
95-8782. (78.5 kbps).
RS-232 COMMUNICATION—
COMBUSTIBLE GAS SENSOR S³ configuration only.
Refer to the Combustible Gas Sensor (CGS) Digital communication, optically isolated
Specification Data Sheet, form 90-1041, for
specifications. TEMPERATURE RANGE—
Operating (Certified Rating):
ELECTROCHEMICAL See Certification section below.
Storage: –40°F to +185°F (–40°C to +85°C).
SENSORS Excluding communication port optional
Refer to the Electrochemical Gas Sensor modules.
Specifications in the UD10-DCU manual 95-
8656 for additional information. HUMIDITY RANGE—
5 to 95% RH, non-condensing.
UD10-DCU UNIVERSAL
DIMENSIONS—
DISPLAY See Figure 6-1. The EQ2001 EQP Monitor has
For complete information regarding the UD10- the same physical characteristics as the EQP
DCU, refer to Specification Data Sheet 90-1200 Controller.
and instruction manual number 95-8656.
SHIPPING WEIGHT—
EQ21XXPS POWER SUPPLY 5 pounds (2.3 kilograms)
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
For USCG approved EQP Controller models, refer to 57-1009 Addendum.
Note: Contact Customer Service when ordering replacement EQP Controllers for redundant EQP Systems.
*Type "APPROVALS" can use one or more letters to designate the approvals of the product.
Some configurations are not available. Check with factory for additional information.
For other USCG Approved EQP System components, refer to 57-1009 Addendum or contact Det-
Tronics Customer Service.
• National Fire Alarm Code performance verified per NFPA 72®-2013. Refer to Table A-1 for
device and circuit supervision characteristics.
• See section 2 "Field Devices Flame Detectors" for information regarding Det-Tronics
approved flame detectors and associated manuals. Additional two second response time
applied for system communication.
• I/O Modules EQ3700 DCIO series (Class B IDC/NAC), EQ3730 EDIO series (Class A or B
IDC/NAC) and EQ3780HSDM series. Reference Table 3-10 for compatible solenoids used for
automatic release of pre-action and deluge sprinkler and extinguishing systems.
GAS DETECTION
• H2S Toxic Gas Performance verified 0 to 20, 50 or 100 ppm per FM requirements.
Accuracy: ±2 ppm from 0 to 20 ppm, ±10% of concentration from 21 to 100 ppm. Models
C7064E4012 and C7064E5012 Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I,
Div. 1, Groups C and D Hazardous (Classified) Locations per FM 3615. Model C7064E5014
Hydrogen Sulfide (H2S) Sensors Explosion-proof for Class I, Div. 1, Groups B, C and D
Hazardous (Classified) Locations per FM 3615. Operating temperature limits are –40°C to
+40°C.
NOTE: Sensor cross-sensitivity has not been verified by FM.
• Calibration of the above listed sensors has been FM verified using the respective UD10-
DCU and PIRECL with the Det-Tronics 225130-001 (50% LFL methane) and/or 227115-001
H2S Calibration Kits.
• The UD10-DCU Series can be used with any FM Approved 4–20 mA device.
NOTE
FM Approval of the 4–20 mA input does not include or imply approval of the gas detection
apparatus such as sensors, transmitters, or devices connected to the system. In order to
maintain FM Approval of the system, all 4–20 mA gas detection instruments connected to
the input must also be FM Approved.
NOTE
FM Approval allows the presence and operation of serial/Ethernet communications
software in the EQP Controller (Modbus TCP/IP, Allen Bradley protocols, etc.); however, the
communications functions are not included in the Approval.
Hazardous Locations:
Ordinary Locations:
EQ3900G - See Manual 95-8641
EQ3900RPSG - See Manual 95-8745
The EQ2001 is non-interfering and provides no alarm functions. It provides access to system
diagnostics and does not provide functionality as part of the fire safety system.
NOTE
The EQ2001 EQP Monitor spur must come off of either the primary or redundant (if there is
one) EQP Controller.
Power Distribution Module, Input Supervised. Loss of power per NFPA 72, Cl. 10.6.9
Power
Power Distribution Module, Supervised. Loss of power per NFPA 72, Cl. 10.6.9
Controller Power Output
Power Distribution Module, Local Unsupervised per NFPA 72, Cl. 12.6.9
Field Device Power Output
Power Supply Monitor, Input Power Supervised. Loss of power per NFPA 72, Cl. 10.6.9
Power Supply Monitor, Charger Supervised. Loss of charger per NFPA 72 Cl. 10.6.10.6
Power Supply Monitor, Battery Supervised. Loss of battery per NFPA 72 Cl. 10.6.9
EQP Controller, Digital Input Unsupervised per NFPA 72, Cl. 12.6.9
EQP Controller, Relay Output Unsupervised per NFPA 72, Cl. 12.6.9
EQP Controller, Trouble Relay Unsupervised per NFPA 72, Cl. 12.6.9
Output
EQP Controller, 232 Expansion Unsupervised per NFPA 72, Cl. 12.6.9
Output (SIL or Non-SIL)
EQP Controller, Ethernet Expansion Unsupervised per NFPA 72, Cl. 12.6.9
Output (SIL or Non-SIL)
Enhanced Discrete I/O, Input Unsupervised per NFPA 72, Cl. 12.6.9
(software configurable, SIL or
Non-SIL) Initiating Device Circuit (IDC): Class A or Class B
Enhanced Discrete I/O, Output Unsupervised per NFPA 72, Cl. 12.6.9
(software configurable, SIL or
Non-SIL) Notification Appliance Circuit (NAC): Class A or Class B
Discrete I/O, Input (software Unsupervised per NFPA 72, Cl. 12.6.9
configurable)
Initiating Device Circuit (IDC): Class B
Discrete I/O, Output (software Unsupervised per NFPA 72, Cl. 12.6.9
configurable)
Notification Appliance Circuit (NAC): Class B
ASM Loop (Smoke & Heat Loop) Signaling Line Circuit (SLC): Class A or Class B (single spur)
ASM - Addressable Smoke and Unsupervised per NFPA 72, Cl. 12.6.9
Heat Module
Input (software configurable) Initiating Device Circuit (IDC): Class A
ASM - Addressable Smoke and Unsupervised per NFPA 72, Cl. 12.6.9
Heat Module
Output (software configurable) Notification Appliance Circuit (Apollo): Class A
High Speed Deluge Module, Unsupervised per NFPA 72, Cl. 12.6.9
Input (software configurable)
Initiating Device Circuit (IDC): Class A or Class B
High Speed Deluge Module, Unsupervised per NFPA 72, Cl. 12.6.9
Output (software configurable)
Notification Appliance Circuit (NAC): Class A or Class B
SURROUNDING AMBIENT.
FOR 10C ABOVE
CAUTION:USE FIELD WIRING SUITABLE
AU-DESSUS DE LA TERMPERATURE
AMBIENTE
HAZARDOUS LOCATIONS
Eagle Quantum Premier® (EQP) System and Components
Class I Division 2 Groups A, B, C & D, T4
Class I Zone 2 IIC, T4, When installed in a suitable CSA Certified labeled Type rated enclosure:
EQ3xxx Controller Series, EQ3700DCIO Series, EQ3710AIM Series, EQ3730EDIO Series, HIM,
EQ2220GFM, EQ2230RSP, EQ3750ASH Series, EQ3760ASM Series, EQ3LTM, EQ3780HSDM
series.
Ordinary Location:
EQ21xxPS, EQ2100PSM
Ordinary Locations :
EQ3900G Series
EQP System Gas Detector / Sensors Class 4828-01 & 4828-02 (See individual Certificates)
PIRECL® Series, PIR9400 Series, PIRDUCT Series, LS2000 Series, GT3000 Series, NTM Series,
C7064E Series, CGS Series (Note: UD10xxxxxC is required for use with CGS catalytic sensor),
PIRTB Series, STB Series, UD10 Series.
EQP System Flame Detectors Equipment Class 4818 04 (See individual Certificates)
X3301 Series, X3302 Series, X2200 Series, X9800 Series, X5200 Series
Notes:
Note 1: Any CSA certified Combustible or Toxic Gas Sensor / detector with 4-20mA
(industry standard) output may be used with EQ3710AIM and UD10.
Note 2: Detector Electronics combustible gas detection K factors are not CSA verified.
Note 3: CSA Certification of the 4-20mA input does not include or imply approval of the gas
detection apparatus such as sensors, transmitters, or devices connected to the system. In order
to maintain CSA Certification of the system, all 4-20mA gas detection instruments connected to the
input must also be CSA Certified.
Note 4: CSA Certification allows the presence and operation of serial/Ethernet communications
software in the EQP Controller (Modbus TCP/IP, Allen Bradley protocols, etc.); however, the
communications functions are not included in the Certification.
The ATEX/IECEx certified EQP System field devices EQ22..., EQ24... and EQ25... are in compliance
with the following standards, as applicable:
IEC 60079-0: 7th Edition
IEC 60079-1: 7th Edition
EN 60079-0: 2012 + A11:2013
EN 60079-1: 2014
EN 60079-29-1: 2007
EN 60079-29-4: 2010
The ATEX/IECEx certified Ex n modules of the EQP system are in compliance with the following
standards, as applicable:
IEC 60079-0: 7th Edition
EN IEC 60079-0:2018
IEC 60079-15: 4th Edition
EN 60079-15: 2010
EN 60079-29-1: 2016
EN 60079-29-4: 2010
For compliance to EN 60079-29-1/-4, the relevant Ex n module must be used with gas detection apparatus
that are certified for compliance to EN60079-29-1/-4 and that provide a suitable linear 4-20 mA output,
relay contact output or LON communication output relative to the %LFL of the available gas in the area of
the gas detection apparatus. See the Manual for details on the required connection parameters.
The EQP Ex n modules shall be used in an area of no more than pollution degree 2 conforming to
IEC/EN 60664-1, and in an enclosure with a tool removable cover that complies with all relevant
requirements of IEC/EN 60079-15, rated at least IP54, and shall be connected to supply circuits
where the rated voltage cannot be exceeded by 140% caused by transient disturbances.
The measuring function of the EQ3XXX Controller, according to Annex II paragraph 1.5.5, 1.5.6
and 1.5.7 of the Directive 94/9/EC, was covered in this Type Examination Certificate in the following
configurations:
1. Controller Model EQ3XXX with EQ3710AIM or EQ3700DCIO or EQ3730EDIO (tested as a
stand-alone control unit with a calibrated linear 4-20mA simulator input signal or relay contacts
(as applicable)).
2. Controller Model EQ3XXX with CTB and PIRECL (tested as a gas detection system with methane
applied to the PIRECL).
3. Controller Model EQ3XXX with UD10/DCU Emulator and CGS Conditioning Board, in
combination with the Det‑Tronics gas sensor Model CGS (tested as a gas detection system
with methane applied to the CGS).
4. Controller Model EQ3XXX with LS2000.
IMPORTANT NOTE
All applied gas detectors must be ATEX certified to EN60079-29-1/-4 and the configuration
must comply with the gas performance parameters stated in the Installation Manual.
The Eagle Quantum Premier® Fire and Gas Detection/Releasing System was tested and found to
be compliant with EN61000-6-2 and EN61000-6-4.
The following considerations must be given for installation of the EQP System:
• For shielded cable installed in conduit, attach the wire shields to the “shield” connections
on the terminal blocks, or to the earth ground on the case.
• For installations without conduit, use double shielded cable. Terminate the outer shield to
the earth ground on the case. Terminate the inner shield to the “shield” connection on the
terminal blocks.
ADDITIONAL DIRECTIVES
FlexSonic ® Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System
orporate Office
C
6901 West 110 th Street Phone: +1 952.941.5665
Minneapolis, MN 55438 USA Toll-free: +1 800.765.3473
© 2022 Carrier. All Rights Reserved. www.det-tronics.com det-tronics@carrier.com