You are on page 1of 24

CURTAIN

FIRE DAMPER

7
http://qadnet.com
FIRE DAMPERS
Fire dampers are UL555 tested and labeled devices installed in ducts and air transfer openings of air distribution
systems, designed to close upon the detection of heat, fire dampers, when closed interrupt migratory airflow, resist
the passage of flame and maintain the integrity of the fire rated barrier.

INDEX
STATIC CURTAIN FIRE DAMPER
150 A...................................................................................................... 03
150 B...................................................................................................... 04
300 A..................................................................................................... 05
300 B..................................................................................................... 06

STATIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER


150 - 12A, 14A, 16A.................................................................................. 07
150 - 12B, 14B, 16B.................................................................................. 08
300 - 12A, 14A, 16A.................................................................................. 09
300 - 12B, 14B, 16B.................................................................................. 10

DYNAMIC CURTAIN FIRE DAMPER


D - 150A.................................................................................................. 11
D - 150B.................................................................................................. 12

4 D - 300A.................................................................................................. 13
D - 300B................................................................................................. 14

DYNAMIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER


D 150 - 12A, 14A, 16A............................................................................... 15
D 150 - 12B, 14B, 16B............................................................................... 16
D 300 - 12A, 14A, 16A............................................................................... 17
D 300 - 12B, 14B, 16B............................................................................... 18

BLADED FIRE DAMPER


D-175, D-175-3........................................................................................ 19
INSTALLATION INSTRUCTION................................................................... 21

CURTAIN FIRE DAMPER

2
STATIC CURTAIN FIRE DAMPER - MODEL 150A
Features
U. L. rated for 1-½ hour fire damper, for use in a 2 hour
fire partition. • Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” Deep, 22 gauge galvanized steel
Blades
3-3/8” wide, 22 gauge galvanized steel
Undersized
1/4” under ordered size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Vertical - Optional
Horizontal - Standard
Minimum Size
4” w x 4” h (Vertical & Horizontal)
Maximum Single Section Size
Vertical - 60”w x 60”h
Horizontal - 48”w x 48”h
Maximum Multiple Section Size
Vertical - 120”w x 80”h (40” x 40” Single Section)
Horizontal - 97”w x 42”h (36” x 42” Single Section)

OPTIONAL CONSTRUCTION
Spring - Available in Vertical Mount

4
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel
Fusible Link - Electrically Triggered Lin (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga. galvanized
steel to 30” in length. - Transitions available in; round,
oval, rectangular, or custom. Factory can install access
door, retaining angles, flange connections or security
bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

3
STATIC CURTAIN FIRE DAMPER - MODEL 150B
Features
• U. L. rated for 1-½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” Deep, 22 gauge galvanized steel
Blades
3-3/8” wide, 22 gauge galvanized steel
Undersized
1/4” under ordered size unless specified otherwise Duct Height Dim. (X)
Fusible Link 4” thru 15” 2”
1650F Standard (others available)
16” thru 27” 3”
Spring
Stainless Steel - 301 Negator type 28” thru 39” 4”
(Standard for horizontal mount only)
40” thru 55”
Minimum Size
40” thru 43” 5”
4”w x 4”h (Vertical & Horizontal)
(Horizontal Only)
Maximum Single Section Size (Duct Size)
Vertical - 60”w x 55”h
Horizontal - 48”w x 43”h
Maximum Multiple Section Size
Vertical - 120”w x 75”h (40” x 40” single section)
Horizontal - 97”w x 37”h (36” x 42” single section)

OPTIONAL CONSTRUCTION

4
Spring - Available in Vertical Mount
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel
Fusible Link - Electrically Triggered Lin (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga. galvanized
steel to 30” in length. - transitions available in; round,
oval, rectangular, or custom. Factory can install access
door, retaining angles, flange connections or security
bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

4
STATIC CURTAIN FIRE DAMPER - MODEL 300A
Features
• U. L. rated for 3 hour fire damper, for use in a 4 hour
fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” Deep, 22 gauge galvanized steel
Blades
3-3/8” wide, 22 gauge galvanized steel
Undersized
1/4” under ordered size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Vertical - Optional
Horizontal - Standard
Minimum Size
4” w x 4” h (Vertical & Horizontal)
Maximum Single Section Size
Vertical - 24”w x 24”h / 36”w x 16”h
Horizontal - 48”w x 48”h
Maximum Multiple Section Size
Vertical - 48”w x 48”h
Horizontal - 72”w x 72”h

OPTIONAL CONSTRUCTION

4
Spring - Available in Vertical Mount
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel
Fusible Link - Electrically Triggered Lin (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga. galvanized
steel to 30” in length. - transitions available in; round,
oval, rectangular, or custom. Factory can install access
door, retaining angles, flange connections or security
bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

5
STATIC CURTAIN FIRE DAMPER - MODEL 300B
Features
• U. L. rated for 3 hour fire damper, for use in a 4 hour
fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” Deep, 22 gauge galvanized steel
Blades
Duct Height Dim. (X)
3-3/8” wide, 22 gauge galvanized steel
Undersized 4” thru 15” 2”
1/4” under ordered size unless specified otherwise 16” thru 27” 3”
Fusible Link 28” thru 39” 4”
1650F Standard (others available)
40” thru 55”
Spring
Stainless Steel - 301 Negator type 40” thru 43” 5”
(Standard for horizontal mount only) (Horizontal Only)
Minimum Size
4” w x 4” h (Vertical & Horizontal)
Maximum Single Section Size (Duct Size)
Vertical - 24”w x 21”h
Horizontal - 48”w x 43”h
Maximum Multiple Section Size
Vertical - 48”w x 43”h
Horizontal - 72”w x 68”h

OPTIONAL CONSTRUCTION

4
Spring - Available in Vertical Mount
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel
Fusible Link - Electrically Triggered Lin (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga. galvanized
steel to 30” in length. - transitions available in; round,
oval, rectangular, or custom. Factory can install access
door, retaining angles, flange connections or security
bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

6
STATIC INTEGRAL SLEEVE CURTAIN
FIRE DAMPER MODEL - 150-12A, 14A, 16A
Features
• U. L. rated for 1 ½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
150-12A 12” x 20 gauge galvanized steel
150-14A 14” x 20 gauge galvanized steel
150-16A 16” x 20 gauge galvanized steel
Blades
3-3/8” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 6”w x 6”h
Horizontal: 6”w x 6”h
Maximum Single Section
Vertical: 48”w x 48”h
Horizontal: 48”w x 48”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
(Standard on horizontal mount only)

OPTIONAL CONSTRUCTION

4
Retaining Angles - Shipped Loose
Security Bars - Mounted in Sleeve
Fusible Link - Electronically Triggered Link (ETL)

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

7
STATIC INTEGRAL SLEEVE CURTAIN
FIRE DAMPER MODEL - 150-12B, 14B, 16B
Features
• U. L. rated for 1½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
150-12B 12” x 20 gauge galvanized steel
150-14B 14” x 20 gauge galvanized steel
150-16B 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 6”w x 6”h
Horizontal: 6”w x 6”h
Maximum Single Section
Vertical: 48”w x 43”h
Horizontal: 48”w x 43”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
(Standard on horizontal mount only) Duct Height Dim. (X)
4” thru 15” 2”
OPTIONAL CONSTRUCTION

4
Retaining Angles - Shipped Loose 16” thru 27” 3”
Security Bars - Mounted in Sleeve 28” thru 39” 4”
Fusible Link - Electronically Triggered Link (ETL) 40” thru 55”
40” thru 43” 5”
(Horizontal Only)

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

8
STATIC INTEGRAL SLEEVE CURTAIN
FIRE DAMPER MODEL - 300-12A, 14A, 16A
Features
• U. L. rated for 3 hour fire damper, for use in a 4 hour
fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
300-12A 12” x 20 gauge galvanized steel
300-14A 14” x 20 gauge galvanized steel
300-16A 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 6”w x 6”h
Horizontal: 6”w x 6”h
Maximum Single Section
Vertical: 48”w x 48”h
Horizontal: 48”w x 48”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
(Standard on horizontal mount only)

OPTIONAL CONSTRUCTION

4
Retaining Angles - Shipped Loose
Security Bars - Mounted in Sleeve
Fusible Link - Electronically Triggered Link (ETL)

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

9
STATIC INTEGRAL SLEEVE CURTAIN
FIRE DAMPER MODEL - 300-12B, 14B, 16B
Features
• U. L. rated for 3 hour fire damper, for use in a 4 hour
fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
300-12B 12” x 20 gauge galvanized steel
300-14B 14” x 20 gauge galvanized steel
300-16B 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 6”w x 6”h
Horizontal: 6”w x 6”h
Maximum Single Section
Vertical: 48”w x 43”h
Horizontal: 48”w x 43”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
(Standard on horizontal mount only)
Duct Height Dim. (X)
OPTIONAL CONSTRUCTION 4” thru 15” 2”

4
Retaining Angles - Shipped Loose
16” thru 27” 3”
Security Bars - Mounted in Sleeve
28” thru 39” 4”
Fusible Link - Electronically Triggered Link (ETL)
40” thru 55”
40” thru 43” 5”
(Horizontal Only)

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

10
DYNAMIC CURTAIN FIRE DAMPER -
MODEL D-150A
Features
• U. L. rated for 1-½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” deep, 22 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Undersized
¼” under order size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Minimum Size
4”w x 4”h
Maximum Size
24”w x 24”h
Maximum Static Pressure (Damper Closed)
4” WG @ 3000 FPM

OPTIONAL CONSTRUCTION
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel

4
Fusible Link - Electrically Triggered Link (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga.
galvanized steel to 30” in length. - transitions
available in; round, oval, rectangular, or custom.
Factory can install access door, retaining angles,
flange connections or security bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

11
DYNAMIC CURTAIN FIRE DAMPER -
MODEL D-150B
Features
• U. L. rated for 1-½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” deep, 22 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Undersized
¼” under order size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Minimum Size
4”w x 4”h
Maximum Size
24”w x 21”h
Maximum Static Pressure (Damper Closed)
4” WG @ 3000 FPM

OPTIONAL CONSTRUCTION
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel

4
Fusible Link - Electrically Triggered Link (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga.
galvanized steel to 30” in length. - transitions
available in; round, oval, rectangular, or custom.
Factory can install access door, retaining angles,
flange connections or security bars.

Duct Height Dim. (X)


4” thru 15” 2”
16” thru 24” 3”

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

12
DYNAMIC CURTAIN FIRE DAMPER -
MODEL D-300A
Features
• U. L. rated for 3 hour fire damper, for use in a 4
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” deep, 22 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Undersized
¼” under order size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Minimum Size
4”w x 4”h
Maximum Size
24”w x 24”h
Maximum Static Pressure (Damper Closed)
4” WG @ 3000 FPM

OPTIONAL CONSTRUCTION
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel

4
Fusible Link - Electrically Triggered Link (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga.
galvanized steel to 30” in length. - transitions
available in; round, oval, rectangular, or custom.
Factory can install access door, retaining angles,
flange connections or security bars.

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

13
DYNAMIC CURTAIN FIRE DAMPER -
MODEL D-300B
Features
• U. L. rated for 3 hour fire damper, for use in a 4
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-7/8” deep, 22 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Undersized
¼” under order size unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Minimum Size
4”w x 4”h
Maximum Size
24”w x 21”h
Maximum Static Pressure (Damper Closed)
4” WG @ 3000 FPM

OPTIONAL CONSTRUCTION
Frame - Available in Stainless Steel
Blade - Available in Stainless Steel

4
Fusible Link - Electrically Triggered Link (ETL)
Sleeve & Duct Connection - 10 ga. to 20 ga.
galvanized steel to 30” in length. - transitions
available in; round, oval, rectangular, or custom.
Factory can install access door, retaining angles,
flange connections or security bars.

Duct Height Dim. (X)


4” thru 15” 2”
MANUFACTURER’S
16” thru 24” 3” RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

14
DYNAMIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER -
MODEL D-150 - 12A, 14A, 16A
Features
• U. L. rated for 1 ½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
150-12A 12” x 20 gauge galvanized steel
150-14A 14” x 20 gauge galvanized steel
150-16A 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 4”w x 4”h
Maximum Single Section
Vertical: 24”w x 24”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Maximum Static Pressure
(Damper Closed)
4” WG @ 3000 FPM
OPTIONAL CONSTRUCTION
Retaining Angles - Shipped Loose
Security Bars - Mounted in Sleeve
Fusible Link - E
 lectronically Triggered Link
(ETL)
4

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

15
DYNAMIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER -
MODEL D-150 - 12B, 14B, 16B
Features
• U. L. rated for 1½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555
STANDARD CONSTRUCTION
Frame and Sleeve
150-12B 12” x 20 gauge galvanized steel
150-14B 14” x 20 gauge galvanized steel
150-16B 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 4”w x 4”h
Maximum Single Section
Vertical: 24”w x 21”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Maximum Static Pressure
(Damper Closed)
4” WG @ 3000 FPM
OPTIONAL CONSTRUCTION
Retaining Angles - Shipped Loose

4
Security Bars - Mounted in Sleeve
Fusible Link - E
 lectronically Triggered Link
(ETL)

Duct Height Dim. (X)


4” thru 15” 2”
16” thru 24” 3”

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

16
DYNAMIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER -
MODEL D-300 - 12A, 14A, 16A
Features
• U. L. rated for 1½ hour fire damper, for use in a 2
hour fire partition.
• Meets NFPA 90A & UL555
STANDARD CONSTRUCTION
Frame and Sleeve
300-12A 12” x 20 gauge galvanized steel
300-14A 14” x 20 gauge galvanized steel
300-16A 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Minimum Size
Vertical: 4”w x 4”h
Maximum Single Section
Vertical: 24”w x 24”h
Maximum Static Pressure
(Damper Closed)
4” WG @ 2000 FPM
OPTIONAL CONSTRUCTION
Retaining Angles - Shipped Loose

4
Security Bars - Mounted in Sleeve
Fusible Link - E
 lectronically Triggered Link
(ETL)

MANUFACTURER’S
RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

17
DYNAMIC INTEGRAL SLEEVE CURTAIN FIRE DAMPER -
MODEL D-300 - 12B, 14B, 16B
Features
• U. L. rated for 3 hour fire damper, for use in a 4
hour fire partition.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame and Sleeve
300-12B 12” x 20 gauge galvanized steel
300-14B 14” x 20 gauge galvanized steel
300-16B 16” x 20 gauge galvanized steel
Blades
3-⅜” wide, 22 gauge galvanized steel
Minimum Size
Vertical: 4”w x 4”h
Maximum Single Section
Vertical: 24”w x 21”h
Undersized
¼” undersize unless specified otherwise
Fusible Link
1650F Standard (others available)
Spring
Stainless Steel - 301 Negator type
Maximum Static Pressure
(Damper Closed)
4” WG @ 2000 FPM
OPTIONAL CONSTRUCTION
Retaining Angles - Shipped Loose

4 Security Bars - Mounted in Sleeve


Fusible Link - E
 lectronically Triggered Link
(ETL)

Duct Height Dim. (X)


4” thru 15” 2”
MANUFACTURER’S
16” thru 21” 3” RECOMMENDATIONS
All moving parts of the damper must be inspected and
cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
recommended.
Specifications are correct at time of printing, However,
as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

18
BLADED FIRE DAMPER
MODEL D-175 & D-175-3
Features
• U. L. rated for dynamic closure, Model D-175 is
a 1-1/2 hour fire damper, D-175-3 is a 3 hour fire
damper.
• Meets NFPA 90A & UL555

STANDARD CONSTRUCTION
Frame
4-5/16” deep, 16 gauge galvanized steel
Blades
6” wide, 16 gauge galvanized steel
(Bottom blade width may vary depending on damper
height)
Blade Axles & Bearings
Axles - 7/16” (11) Plated hex mechanically fastened to
blade
Bearings - Bronze Oil Impregnated
Linkage
Plated steel in opposed blade configuration, concealed
inside the jamb.
Fusible Link
1650F Standard (others available)
Maximum Size UL Classified
36” w x 36” h - 175 (1-1/2 hour rated)
(Vertical and Horizontal)
36” w x 36” h - 175-3 (3 hour rated)
(Vertical and Horizontal)

4
Minimum Size UL Classified
8”w x 6”h
Undersized
¼” under order size unless specified Exact or Actual
Finish
Galvanized

OPTIONAL CONSTRUCTION
Specified Material - Available in stainless Steel
Sleeve and Ductwork Connection - 10 ga. to 20
ga. galvanized steel to 30” in length. Transitions
available in: round, oval, rectangular or custom. MANUFACTURER’S
Factory can install access door, retaining angles, flange RECOMMENDATIONS
connections, or security bars. All moving parts of the damper must be inspected and
*Dampers 11” (279) high and under will be single cycled at intervals not greater than every six months
blade, and extend from the frame proportionately. and in accordance with the latest editions of NFPA
90A, 92A, In addition, fuse links shall be removed
and inspected for corrosion. Dry lubricants are
ACCESSORIES recommended.
Indicator Switches Specifications are correct at time of printing, However,
Monitoring Station as part of our continuous improvement program,
we reserve the right to make further improvements
without notice.

CURTAIN FIRE DAMPER

19
175 & 175-3 PERFORMANCE
Model 175 rated 1-1/2 hour UL Classified
Damper
Model 175-3 rated 3 hour UL Classified Damper

CALCULATING PRESSURE LOSS:


Based upon a given flow rate (in CFM), the flowing
pressure loss maybe determinate from the “air
performance graph, knowing the sq. ft. of free
area of the damper. Alternately, the free area may
be determined based upon a volumetric flow rate
and a maximum pressure loss. Utilizing the “Air
Performance” graph.

__________________ in. W.C. Max Pressure Loss


Intake or Exhaust

__________________ FPM (Free Area Velocity From


“Air Performance” Graph)

__________________ CFM / __________________


FPM Free Area Velocity = __________________ Sq. Ft.
Free Area

FREE AREA CALCULATIONS IN SQ. FT.


WIDTH
IN. 12 16 20 24 28 32 36

4
12 0.56 0.78 1.00 1.22 1.44 1.67 1.89
16 0.83 1.17 1.50 1.83 2.17 2.50 2.83
HEIGHT

20 1.06 1.48 1.91 2.33 2.75 3.18 3.60


24 1.28 1.80 2.31 2.83 3.34 3.85 4.37
28 1.51 2.11 2.72 3.32 3.93 4.53 5.14
32 1.79 2.50 3.22 3.93 4.65 5.36 6.08
36 2.01 2.82 3.63 4.43 5.24 6.04 6.85

PERFORMANCE DATA MANUFACTURER’S


RECOMMENDATIONS
Damper Width Maximum Static Maximum All moving parts of the damper must be inspected and
Inches Pressure (W.G.) Velocity cycled at intervals not greater than every six months
and in accordance with the latest editions of NFPA
12 (305) 6" 2000 FPM
90A, 92A, In addition, fuse links shall be removed
18 (457) 5.5" 2000 FPM and inspected for corrosion. Dry lubricants are
recommended.
24 (610) 5.5" 2000 FPM Specifications are correct at time of printing, However,
30 (762) 5" 2000 FPM as part of our continuous improvement program,
we reserve the right to make further improvements
36 (914) 5" 2000 FPM without notice.

CURTAIN FIRE DAMPER

20
FIRE DAMPER
MASONRY/CONCRETE OR METAL STUD WALL
INSTALLATION INSTRUCTIONS IN ACCORDANCE WITH UL550

(F) S
 ecure damper to sleeve 8" on centers with:
• 1/2" long welds or
• 1/4" Bolts and nuts in holes provided or
• No. 10 steel screws, or
• Minimum 1/16" steel rivets
(G) Connect ducts to sleeve with approved or equal duct
collar connections / break-away connections.
(H) Grille to be supplied by others.
Notes:
Fire damper sleeve clearance within wall opening.
1. C
 learance requirements for damper sleeve within a wall
opening is based on 1/8 inch per foot of width (or height)
unless otherwise stated in the listing of the assembly. The

4
sleeve may rest on the bottom of the opening, and need to
be centered. (Fractional dimensions shall be taken as the
next largest whole foot.) Example: A 30-inch x 24-inch fire
damper sleeve is installed in a wall opening. The opening
shall be 30-3/8 inches wide (1/8 inch x 3 feet) by 24-1/4
inches high (1/8 inch x 2 feet).
Minimum of 1/4" gap on width and height.
2. The sleeve is retained in the wall opening by the use of
steel retaining angles (A). These must over-lap the edge of
the framing by a minimum of one (1) inch over and beyond
all the retaining angle would be 1 - 3/8 inches (good
practice calls for an additional safety factor by making the
TYPICAL INSTALLATION DETAILS angle in this case 1 - 1/2 inches wide). Grill/Louver or shaft
(A) Retaining Angles: Minimum 1 1/2" x 1 1/2" x 0.054 (18ga) mount
Retaining angels must lap structural opening 1" minimum 3. The dimensions required for the opening shall be those
and cover corners of openings. remaining after the opening has been framed and fire
resistive materials provided were required. The fire
(B) Clearance: 1/8" inch per liner foot both dimensions (see resistive materials shall be equal to the requirements for
note 1 below) fire resistive materials used in the constructed wall so that
(C) S
 teel sleeve: See sleeve schedule a continuous rating exists at the wall penetration. The
contractor erecting the wall is responsible for providing
(D) Approved Fire Damper (Curtain or blade type) Damper
the fire resistive material and correct size openings to
must be in the wall.
achieve the required clearance.
(E) Secure retaining angles 8" on centers with: 4. Dampers must be installed in accordance with these
• 1/2" long welds or instructions to meet the requirements of UL555. The
• 1/4" Bolts and nuts, or installation of the damper and all duct connections to
• No. 10 steel screws, or the damper sleeve shall conform to the latest editions of
• Minimum 1/16" steel rivets NFPA 90A, Standard of the installation of Air Conditioning
• For 1-sided only secure angle to wall/floor & sleeve and Ventilation Systems, and the SMACNA Fire, Smoke
• For 2-sided only secure angle to sleeve only and Radiation damper installation guide, and U. L.
• For concrete, use anchors and #10 self-tapping screws Classifications.

CURTAIN FIRE DAMPER

21
FRAMING OPENINGS FOR FIRE DAMPER IN METAL,
WOOD AND CONCRETE WALLS

NOTES
1. Single stud can be used on dampers with 36” x
36” (914 x 914) opening or smaller. (Fig-1.)
2. A single mounting angles may be used, please
refer to single retaining angles installation
instruction under separate sheet.
3. F raming studs next to the damper are not
required to be full length if the spacing is less
than the maximum stud spacing as shown in
(Fig. - 1.)
4. G ypsum panels screwed to all studs and
runner flanges shall be 12” (305) oc. maximum
surrounding opening.
5. A ll metal or wood studs shall be covered with
gypsum wallboard.
6. O pening to be minimum 1/8” (3) per ft. larger
than overall size of assembly. (min. 1/4” (6)
larger than assembly.)
7. D ouble vertical studs are required for dampers
larger than 36” x 36” (Fig. - 2.)

CURTAIN FIRE DAMPER

22
NOTES

CURTAIN FIRE DAMPER

23
OUR BRANDS

QATAR AIR DISTRIBUTION NETWORK


MANUFACTURING FACTORY W.L.L

P.O Box : 40852, Doha Qatar

+974 44680356 / 44503602 / 44600316

info@qadnet.com

http://qadnet.com

QADNET | 022021 | NL | R01 | 1000


PRITHVI: +91 93597 13489