CONTRACT NO.

CNT/ENP/112310 FACILITIES

UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI

TERMINAL PROJECT

ELECTRICAL LOAD LIST

TABLE OF CONTENTS

1 19-01-2023 ISSUED FOR TENDER NB ZA HR


0 06-12-2022 ISSUED FOR TENDER NB ZA HR
B 04-11-2022 ISSUED FOR APPROVAL NB ZA HR
A 13-10-2022 ISSUED FOR CLIENT REVIEW NB ZA HR
Rev. Date Description/issued for By Ckd. Appd.
Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 1 of: 8
CONTRACT NO. CNT/ENP/112310 : :
1 INTRODUCTION ............................................................................................ 3
1.1 Purpose of the Document .................................................................... 3

2 DEFINITIONS AND ABBREVIATIONS .......................................................... 3


2.1 Definitions ........................................................................................... 3
2.2 Abbreviations ...................................................................................... 4

3 ORDER OF PRECEDENCE ........................................................................... 5

4 REFERENCE DOCUMENTS .......................................................................... 5


4.1 Project Documents .............................................................................. 5

5 DESIGN CRITERIA ........................................................................................ 5


5.1 Definitions ........................................................................................... 5
5.2 Basis and Assumptions ....................................................................... 6

6 LOAD SUMMARY .......................................................................................... 7

7 APPENDICIES ............................................................................................... 7
Appendix 1 – Electrical Load List .................................................................... 8

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 2 of: 8
CONTRACT NO. CNT/ENP/112310 : :
1 INTRODUCTION

The Jebel Ali Terminal (JAT) of Emirates General Petroleum Corporation (EMARAT) for storage and
distribution of petroleum products is located at Petrochemical Zone of Plot No. EW103 of Jebel Ali
Free Zone (JAFZA).

Automotive fuels such as Gas Oil and Unleaded Gasoline and LPG are stored and handled at JAT,
for distributing petroleum products to the filling stations in the emirate of Dubai and Northern Emirates
from Jebel Ali Terminal (JAT) along with LPG cylinder filling and bulk supplies. The Terminal has been
in service for more than twenty years with refurbishment and add-on development over the years.

As a part of JAT2020 project an Adequacy Check for Fire Fighting Facility of JAT was carried out. In
line with EMARAT management directive, EMARAT HSE guidelines and considering future
developments, an improvement of the firefighting pumping system is initiated.

The objective of this project is to upgrade the firefighting system at Jebel Ali terminal by installing a
new firewater pump.

Emirates General Petroleum Corporation (EMARAT), the CLIENT, has appointed Bilfinger Tebodin
Middle East (BTME) the CONSULTANT, to provide consultancy services for the upgrade of firewater
pumping system at Jebel Ali Terminal, Dubai.

1.1 Purpose of the Document

The purpose of the document is to summarize the electrical loads for the new additional diesel driven
pump envisaged in this project scope.

2 DEFINITIONS AND ABBREVIATIONS

For the purpose of this document, the words and expressions listed below shall have the meanings
assigned as follows

2.1 Definitions

CLIENT Emirates General Petroleum Corporation (EMARAT)

CONTRACTOR The selected party, firm or company identified in the contract


agreement who undertakes the performance of applicable
residual engineering, procurement, construction, testing and
commissioning works under the Project Contract Agreement.
The contractor shall resume all responsibilities of
Supplier/Vendor/Manufactures specified herein.

CONSULTANT Bilfinger Tebodin Middle East Ltd.

PROJECT Upgrading of Fire Water Pumping System at Jebel Ali Terminal

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 3 of: 8
CONTRACT NO. CNT/ENP/112310 : :
SUB-CONTRACTOR Any person, firm, corporation or combination thereof to whom
any part of the project has been subcontracted.

MANUFACTURER/SUPPLIER/ The Party which manufactures and/or supplies material,


VENDOR equipment and services to perform the duties as specified by
CONTRACTOR in the scope of supply.

SUB-SUPPLIER Any VENDOR used by the SUPPLIER or VENDOR and


approved by CONTRACTOR and EMARAT for supplying
equipment material for completing the scope of supply.

SHALL The use of the word “Shall” Indicates a mandatory requirement.

SHOULD The use of the word “Should” Indicates a strong


recommendation to comply with the requirements of this
document

2.2 Abbreviations

AC Alternating Current

DB Distribution Board

EPC Engineering, Procurement, and Construction

IEC International Electro-technical Commission

kV Kilo Volts

kVA Kilo Volt Ampere

kW Kilo Watt

LED Light Emitting Diode

LV Low Voltage ≤1000V

SLD Single line Diagram

UAE United Arab Emirates

V Voltage

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 4 of: 8
CONTRACT NO. CNT/ENP/112310 : :
3 ORDER OF PRECEDENCE

In case of conflict between various documents, codes or standards, the order of precedence that shall
be followed is:

 UAE Local Statutory Regulations

 Project Datasheets

 Project Specifications

 CLIENT Standards

 International Codes & Standards

In case of conflict between this specification and other specifications, codes or standards referred in
this document, the most stringent requirement as interpreted by CLIENT shall be entertained and
written CLIENT confirmation on the same shall be obtained before proceeding. CLIENT decision shall
be binding in this regard.

4 REFERENCE DOCUMENTS

4.1 Project Documents

Document No. Document Title

112310-PROJ-DDM-0002 Project Design Basis

112310-MECH-DTS-0001 Datasheet for Fire Water Pump

112310-QHSE-PID-0001 Construction P&ID New Fire Pump and Sprinkler System

5 DESIGN CRITERIA

Relevant definition, formulas, basis and assumptions which are used to form the design criteria for
this document are as follows:

5.1 Definitions

Absorbed Loads Loads that are absorbed by the driven equipment or the maximum
power taken during a given period of time as below:

 For pumps, shaft load on duty point


 For instrumentation, computers, communication, air conditioning,
the required load during full operation of plant.

 For lighting during dark hours


Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 5 of: 8
CONTRACT NO. CNT/ENP/112310 : :
Consumed Load The ratio of the absorbed load to the efficiency at load factor. Consumed
load may be categorized as Continuous, Intermittent or Standby.

Continuous Loads All loads that may be required continuously for normal operation
or which may be reasonably expected to occur simultaneously.

Intermittent Loads All process and utility loads required for normal operation but neither
operating continuously nor simultaneously e.g. monorail hoists will
operate intermittently, coming on when they are required to lift
equipment.

Standby Loads All loads required during maintenance, change-over from duty to
standby or during abnormal circumstances e.g. for a 2x100% pump
installed, pump ‘A’ will run continuously while pump ‘B’ will be on
standby

5.2 Basis and Assumptions

Electrical load list has been prepared based on the following basis and assumptions:

 Electrical Loads are divided into following three classes according to use:

a) Continuous Load – Which draws power at continuous rate

b) Intermittent Load – Which draws power as per duty cycle for short duration

c) Stand-by Load – which is connected with power supply and ready to act as and when
required.

 Electrical load list is prepared based on various Electrical and Process loads.

 Load factor 1 for power feeders, Power factor(0.8) & Efficiency(0.85) considered for load
calculation are preliminary, to be updated the same based on final vendor data.

 Total Plant Load = (100% of Continuous load) + (30% of Total Intermittent load or Largest
Intermittent load whichever is higher) + (10% of Total Standby load or Largest Standby load
whichever is higher)

 All equipment tag numbers shown in this document is preliminary, it shall be updated in the next
revision in consult wi.

 All equipment ratings shown in this document are preliminary, to be updated the same based on
final vendor data.

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 6 of: 8
CONTRACT NO. CNT/ENP/112310 : :
 Due to un-availability of native file of the original load list for the Auxilairy DB (Tag.No. DB-FPS)
at Pump house, this document has been prepared as a new document for the new loads
envisaged in this project scope. Refer Appendix-1 of this document.

6 LOAD SUMMARY

LOAD SUMMARY

Maximum Running Load Peak Load


S. No. Description
in (kW) in (kVA) in (kW) in (kVA)

New Load requirement under this project 5.71 6.71 5.71 6.71
scope (Refer Appendix – 1)

7 APPENDICIES

Appendix 1 – Electrical Load List

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 7 of: 8
CONTRACT NO. CNT/ENP/112310 : :
Appendix 1 – Electrical Load List

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-LST-0001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: ELECTRICAL LOAD LIST

Office: Dubai Order: AET00878-00 Document No. 4100001 Rev 1 Sheet 8 of: 8
CONTRACT NO. CNT/ENP/112310 : :
APPENDIX - 1 : ELECTRICAL LOAD LIST (NEW)

EQUIPMENT LOAD CALCULATION CONSUMED LOAD


Load Efficiency Power A
kW = D kVar = kW . tan f
Voltage Type of Absorbed Rated Factor at Load Factor at Load
A REMARKS
Equipment Rating Load Load Load Factor C Load Factor Duty: Continuous Intermittent Stand-By
Item

B
Description C
Tag Number B
C/I/S
A C D E F G

V (P/M) kW kW pu pu cosf kW kVar kW kVar kW kVar

240V AUXILAIRY DB (TAG.NO. DB-FPS) LOCATED IN ELECTRICAL ROOM (EXISTING)

New Load under this project Scope.


1 C-112 Diesel Engine Controller for Pump (P-112) 240 P 1.00 1.00 1 0.90 0.85 I 0.00 0.00 1.11 0.69 0.00 0.00 Estimated load based on Vendor data
M/s TORNATECH
New Load under this project Scope.
2 H-112 Diesel Engine Heater for Pump (P-112) 240 P 2.50 2.50 1 0.90 0.85 C 2.78 1.72 0.00 0.00 0.00 0.00 Load rating is considered based on
Vendor data M/s CLARKE

Exisitng Lighting feeder loads to be re-


3 PH-LC-1 Pump House New Shelter Lighting Circuit-1 240 P 0.13 0.13 1 0.90 0.85 C 0.14 0.09 0.00 0.00 0.00 0.00 used for the new light fixtures. (3 nos of
light fixtures for each circuit)

Exisitng Lighting feeder loads to be re-


4 PH-LC-2 Pump House New Shelter Lighting Circuit-2 240 P 0.13 0.13 1 0.90 0.85 C 0.14 0.09 0.00 0.00 0.00 0.00 used for the new light fixtures. (3 nos of
light fixtures for each circuit)

Exisitng Lighting feeder loads to be re-


5 PH-LC-3 Pump House New Shelter Lighting Circuit-3 240 P 0.08 0.08 1 0.90 0.85 C 0.09 0.06 0.00 0.00 0.00 0.00 used for the new light fixtures. (2 nos of
light fixtures for each circuit)
Anti Fouling System control panel for new Diesel
6 AF-112 240 P 1.00 1.00 1 0.90 0.85 C 1.11 0.69 0.00 0.00 0.00 0.00 New Estimated Load
Driven Pump
7 FACP-01 FACP Panel 240 P 1.00 1.00 1 0.90 0.85 C 1.11 0.69 0.00 0.00 0.00 0.00 New Estimated Load

TOTAL In kW and kVar 5.4 3.3 1.1 0.7 0.0 0.0


LOAD 6.3 1.31 0
kVA = √ (Kw² + kVar²)
Maximum running load, kW = ( x% . SE ) + ( y% . SF ) 5.71 kVA = 6.71
Peak Load, kW = ( x% . SE ) + ( y% . SF ) + ( z% . SG ) 5.71 kVA = 6.71
Coincidence factors x(100%), y(30%) and z(10%) defined as Continuous, Intermittent and Stand-by loads respectively
Client EMARAT
Project UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT
Title ELECTRICAL LOAD LIST
DOC. NO. 112310-ELEC-LST-0001

Page 1 of 1
CONTRACT NO. CNT/ENP/112310 FACILITIES

UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI

TERMINAL PROJECT

LIGHTING CALCULATION

0 06-12-2022 ISSUED FOR TENDER NB ZA HR


B 04-11-2022 ISSUED FOR APPROVAL NB ZA HR
A 13-10-2022 ISSUED FOR CLIENT REVIEW NB ZA HR
Rev. Date Description/issued for By Ckd. Appd.
Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 1 of: 8
CONTRACT NO. CNT/ENP/112310 : :
TABLE OF CONTENTS
1 INTRODUCTION ............................................................................................ 3
1.1 Purpose of the Document .................................................................... 3
2 DEFINITIONS AND ABBREVIATIONS .......................................................... 3
2.1 Definitions ........................................................................................... 3
2.2 Abbreviations ...................................................................................... 4
3 ORDER OF PRECEDENCE ........................................................................... 4
4 REFERENCE DOCUMENTS .......................................................................... 5
4.1 International Standards ....................................................................... 5
4.2 Project Documents .............................................................................. 5
5 BASIS AND ASSUMPTIONS ......................................................................... 5
6 RESULTS AND RECOMMENDATION ........................................................... 6
7 ATTACHMENTS............................................................................................. 6
APPENDIX – 1 : OUTDOOR LIGHTING CALCULATION ............................................ 7
APPENDIX – 2 : LIGHTING FIXTURE CATALOGUE .................................................. 8

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 2 of: 8
CONTRACT NO. CNT/ENP/112310 : :
1 INTRODUCTION

The Jebel Ali Terminal (JAT) of Emirates General Petroleum Corporation (EMARAT) for storage and
distribution of petroleum products is located at Petrochemical Zone of Plot No. EW103 of Jebel Ali Free
Zone (JAFZA).

Automotive fuels such as Gas Oil and Unleaded Gasoline and LPG are stored and handled at JAT, for
distributing petroleum products to the filling stations in the emirate of Dubai and Northern Emirates from
Jebel Ali Terminal (JAT) along with LPG cylinder filling and bulk supplies. The Terminal has been in service
for more than twenty years with refurbishment and add-on development over the years.

As a part of JAT2020 project an Adequacy Check for Fire Fighting Facility of JAT was carried out. In line
with EMARAT management directive, EMARAT HSE guidelines and considering future developments, an
improvement of the firefighting pumping system is initiated.

The objective of this project is to upgrade the firefighting system at Jebel Ali terminal by installing a new
firewater pump.

Emirates General Petroleum Corporation (EMARAT), the CLIENT, has appointed Bilfinger Tebodin Middle
East (BTME) the CONSULTANT, to provide consultancy services for the upgrade of firewater pumping
system at Jebel Ali Terminal, Dubai.

1.1 Purpose of the Document


The purpose of this document is to design lighting system requirements for the new fire water pump
shelter envisaged as part of this project scope.

2 DEFINITIONS AND ABBREVIATIONS

For the purpose of this document, the words and expressions listed below shall have the meanings
assigned as follows:

2.1 Definitions
CLIENT Emirates General Petroleum Corporation (EMARAT)

CONTRACTOR The selected party, firm or company identified in the contract


agreement who undertakes the performance of applicable
residual engineering, procurement, construction, testing and
commissioning works under the Project Contract Agreement.
The contractor shall resume all responsibilities of
Supplier/Vendor/Manufactures specified herein.

CONSULTANT Bilfinger Tebodin Middle East Ltd.

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 3 of: 8
CONTRACT NO. CNT/ENP/112310 : :
PROJECT Upgrading of Fire Water Pumping System at Jebel Ali
Terminal

SUB-CONTRACTOR Any person, firm, corporation or combination thereof to whom


any part of the project has been subcontracted.

MANUFACTURER/SUPPLIER/VENDOR The Party which manufactures and/or supplies material,


equipment and services to perform the duties as specified by
CONTRACTOR in the scope of supply.

SUB-SUPPLIER Any VENDOR used by the SUPPLIER or VENDOR and


approved by CONTRACTOR and EMARAT for supplying
equipment material for completing the scope of supply.

SHALL The use of the word “Shall” Indicates a mandatory


requirement.

SHOULD The use of the word “Should” Indicates a strong


recommendation to comply with the requirements of this
document.

2.2 Abbreviations
AC Alternating Current

DB Distribution Board

EPC Engineering, Procurement, and Construction

IEC International Electro-technical Commission

kW Kilo Watt

LED Light Emitting Diode

LV Low Voltage ≤1000V

3 ORDER OF PRECEDENCE

In case of conflict between various documents, codes or standards, the order of precedence that shall be
followed is:

 UAE Local Statutory Regulations


 Project Datasheets
 Project Specifications
 CLIENT Standards
 International Codes & Standards
Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 4 of: 8
CONTRACT NO. CNT/ENP/112310 : :
In case of conflict between this specification and other specifications, codes or standards referred in this
document, the most stringent requirement as interpreted by CLIENT shall be entertained and written
CLIENT confirmation on the same shall be obtained before proceeding. CLIENT decision shall be binding
in this regard.

4 REFERENCE DOCUMENTS

4.1 International Standards

Document No. Document Title

IEC 60079 Electrical Apparatus for Explosive Gas Atmospheres

IEC 60529 Classification of Degrees of Protection Provided by Enclosures

IEC 60598-1 Luminaires - Part 1: General Requirements and Tests

IEC 62717 LED Modules for General Lighting - Performance


Requirements

4.2 Project Documents

Document No. Document Title

112310-PROJ-DDM-0002 Project Design Basis

112310-PIPG-LAY-8002 Equipment Layout Plan for Fire Water Pump House

5 BASIS AND ASSUMPTIONS

The lighting calculation is based on the recommended illumination level as described below:

Location Emean (Lux)

Fire water pump house Shelter 75

The software used to perform the lighting calculations is Dialux 4.13.

A maintenance factor of 0.80 is considered for lighting calculations.

The type of fittings and lamps used for lighting calculation is based on Chalmit lighting catalogue. Contactor
can choose other types and manufacturer, provided that luminous flux of each fixture shall match as a
minimum with those selected for calculation.

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 5 of: 8
CONTRACT NO. CNT/ENP/112310 : :
The luminaire and lamp type used in this calculation are summarized below:

Manufacture Luminaire Model No. & Mounting Luminou Power


S. No
Name Type Arrangement s Flux (W)

Chalmit Lighting ST3I/06L/LE


Sterling III LED Surface
1 Chalmit 6241 lm 42
mounted
(LED Floodlight, Zone-2)

6 RESULTS AND RECOMMENDATION

Illumination levels & Lighting Fixture details are as follow:

Required Actual Luminaire Quantity, Mounting


Area Average Average Model No. & Type Height (m) Remarks
Lux (Lux) Lux (Lux)

6 Nos. Of ST3I/06L/LE
Fire water pump Sterling III LED Refer
75 129 4.9
house Shelter-1 Attachment-1
(LED Linear)

2 Nos. Of ST3I/06L/LE
Fire water pump Sterling III LED Refer
75 92 4.9
house Shelter-2 Attachment-1
(LED Linear)

The calculation result tabulated above and as shown in Attachment-1 is complying with the illumination
requirement. Hence, the selected number of lamp fixture and rating is adequate.

Lighting fixture herein shall be for the basis of calculation and minimum requirement only. Type of lighting
fixture to be used shall be from approved vendor list.

7 ATTACHMENTS

Appendix 1 – Outdoor Lighting Calculation

Appendix 2 – Lighting Fixture Catalogue

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 6 of: 8
CONTRACT NO. CNT/ENP/112310 : :
APPENDIX – 1 : OUTDOOR LIGHTING CALCULATION

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 7 of: 8
CONTRACT NO. CNT/ENP/112310 : :
APPENDIX – 2 : LIGHTING FIXTURE CATALOGUE

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3002


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: LIGHTING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4100008 Rev 0 Sheet 8 of: 8
CONTRACT NO. CNT/ENP/112310 : :
CONTRACT NO. CNT/ENP/112310 FACILITIES

UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI

TERMINAL PROJECT

CABLE SIZING CALCULATION

0 19-01-2023 ISSUED FOR TENDER ZA NB HR


B 12-12-2022 ISSUED FOR APPROVAL ZA NB HR
A 15-11-2022 ISSUED FOR CLIENT REVIEW NB ZA HR
Rev. Date Description/issued for By Ckd. Appd.
Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 1 of: 13
CONTRACT NO. CNT/ENP/112310 : :
TABLE OF CONTENTS

1 INTRODUCTION ............................................................................................ 3
1.1 Purpose of the Document .................................................................... 3

2 DEFINITIONS AND ABBREVIATIONS .......................................................... 3


2.1 Definitions ........................................................................................... 3
2.2 Abbreviations ...................................................................................... 4

3 ORDER OF PRECEDENCE ........................................................................... 5

4 REFERENCE DOCUMENTS .......................................................................... 5


4.1 Project Documents .............................................................................. 5

5 CODES AND STANDARDS ........................................................................... 5

6 SERVICE CONDITIONS ................................................................................. 7


6.1 Environmental Conditions .................................................................... 7

7 BASIS AND ASSUMPTION ........................................................................... 7

8 PRINCIPLE FOLLOWED FOR THE LV CABLE SIZING CALCULATION ..... 8

9 DERATING FACTORS ................................................................................... 8

10 CONCLUSION ................................................................................................ 9
10.1 Cable Selection Chart.......................................................................... 9

11 APPENDICIES ............................................................................................... 9
Appendix 1 – Current Rating for LV Cables................................................... 10
Appendix 2 – Cable Derating Factor ............................................................. 11
Appendix 3 – Resistance and Reactance Table ............................................ 12
Appendix 4 – Electrical Cable Selection Chart .............................................. 13

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 2 of: 13
CONTRACT NO. CNT/ENP/112310 : :
1 INTRODUCTION

The Jebel Ali Terminal (JAT) of Emirates General Petroleum Corporation (EMARAT) for storage and
distribution of petroleum products is located at Petrochemical Zone of Plot No. EW103 of Jebel Ali
Free Zone (JAFZA).

Automotive fuels such as Gas Oil and Unleaded Gasoline and LPG are stored and handled at JAT,
for distributing petroleum products to the filling stations in the emirate of Dubai and Northern Emirates
from Jebel Ali Terminal (JAT) along with LPG cylinder filling and bulk supplies. The Terminal has been
in service for more than twenty years with refurbishment and add-on development over the years.

As a part of JAT2020 project an Adequacy Check for Fire Fighting Facility of JAT was carried out. In
line with EMARAT management directive, EMARAT HSE guidelines and considering future
developments, an improvement of the firefighting pumping system is initiated.

The objective of this project is to upgrade the firefighting system at Jebel Ali terminal by installing a
new firewater pump.

Emirates General Petroleum Corporation (EMARAT), the CLIENT, has appointed Bilfinger Tebodin
Middle East (BTME) the CONSULTANT, to provide consultancy services for the upgrade of firewater
pumping system at Jebel Ali Terminal, Dubai.

1.1 Purpose of the Document

The scope of this document is to define the technical basis, parameters and criteria used for the Cable
Sizing calculation for the project.

2 DEFINITIONS AND ABBREVIATIONS

For the purpose of this document, the words and expressions listed below shall have the meanings
assigned as follows

2.1 Definitions

CLIENT Emirates General Petroleum Corporation (EMARAT)

CONTRACTOR The selected party, firm or company identified in the contract


agreement who undertakes the performance of applicable
residual engineering, procurement, construction, testing and
commissioning works under the Project Contract Agreement.
The contractor shall resume all responsibilities of
Supplier/Vendor/Manufactures specified herein.

CONSULTANT Bilfinger Tebodin Middle East Ltd.

PROJECT Upgrading of Fire Water Pumping System at Jebel Ali Terminal

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 3 of: 13
CONTRACT NO. CNT/ENP/112310 : :
SUB-CONTRACTOR Any person, firm, corporation or combination thereof to whom
any part of the project has been subcontracted.

MANUFACTURER/SUPPLIER/ The Party which manufactures and/or supplies material,


VENDOR equipment and services to perform the duties as specified by
CONTRACTOR in the scope of supply.

SUB-SUPPLIER Any VENDOR used by the SUPPLIER or VENDOR and


approved by CONTRACTOR and EMARAT for supplying
equipment material for completing the scope of supply.

SHALL The use of the word “Shall” Indicates a mandatory requirement.

SHOULD The use of the word “Should” Indicates a strong


recommendation to comply with the requirements of this
document

2.2 Abbreviations

AC Alternating Current

DB Distribution Board

EPC Engineering, Procurement, and Construction

IEC International Electro-technical Commission

kV Kilo Volts

kVA Kilo Volt Ampere

kW Kilo Watt

LED Light Emitting Diode

LV Low Voltage ≤1000V

SLD Single line Diagram

UAE United Arab Emirates

V Voltage

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 4 of: 13
CONTRACT NO. CNT/ENP/112310 : :
3 ORDER OF PRECEDENCE

In case of conflict between various documents, codes or standards, the order of precedence that shall
be followed is:

 UAE Local Statutory Regulations

 Project Datasheets

 Project Specifications

 CLIENT Standards

 International Codes & Standards

In case of conflict between this specification and other specifications, codes or standards referred in
this document, the most stringent requirement as interpreted by CLIENT shall be entertained and
written CLIENT confirmation on the same shall be obtained before proceeding. CLIENT decision shall
be binding in this regard.

4 REFERENCE DOCUMENTS

4.1 Project Documents

Document No. Document Title

112310-PROJ-DDM-0002 Project Design Basis

112310-ELEC-LST-3001 Load List (updation)

112310-ELEC-SCH-3001 Lighting DB schedule / SLD (update)

112310-ELEC-LYT-3001 Cable Routing Layout

112310-ELEC-LYT-3002 Lighting layout

5 CODES AND STANDARDS

Codes and Standards referred to herein, form part of the requirements of this Specification and unless
otherwise specified the date of edition or revision of such codes/standards shall be the latest.

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 5 of: 13
CONTRACT NO. CNT/ENP/112310 : :
The VENDOR shall be familiar with the requirements of these documents and shall make them readily
available to all persons concerned with carrying out the scope of work specified in this Specification.

Document No. Document Title

IEC 60183 Guidance for the selection of high-voltage A.C. cable systems

IEC 60228 Conductors of insulated cables

Electric cables – Calculation of the Current Rating – Part 1 -1:


IEC 60287-1-1 Current Rating Equations (100 % Load Factor) and Calculation of
Losses – General

Electric Cables - Calculation of the Current Rating - Part 2 -1:


IEC 60287-2-1
Thermal Resistance - Calculation of Thermal Resistance

Electric Cables - Calculation of the Current Rating - Part 3 -1:


IEC 60287-3-1 Sections on Operating Conditions - Reference Operating
Conditions and Selection of Cable Type

Low Voltage Electrical Installations – Part 5-52: Selection and


IEC 60364-5-52
Erection of Electrical Equipment – Wiring systems

Cables for Rated Voltages from 6kV (Um = 7.2kV) upto 30kV (Um
IEC 60502-2
= 36kV)

BS EN 60228 Conductors of insulated cables

Electric cables – Armoured cables with thermosetting insulation for


BS 6622 rated voltages from 3.8/6.6 kV to 19/33 kV – Requirements and test
methods.

ERA REPORT 69-30 Part III Sustained Current Ratings for PVC Insulated Cables to BS 6346

Sustained Current Ratings for Armored Cables with Thermosetting


ERA REPORT 69-30 Part V
Insulation to BS 5467 and BS 6724

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 6 of: 13
CONTRACT NO. CNT/ENP/112310 : :
6 SERVICE CONDITIONS

6.1 Environmental Conditions

Altitude : Approx. at Mean Sea Level +4M

Relative Humidity : Average 60 / 80%

: Maximum 100%

Ambient Temperature : Mean Monthly Maximum 42 Deg C

: Mean Monthly Minimum 14 Deg C

: Highest Maximum 50 Deg C

: Lowest Minimum 4 Deg C

Atmosphere : Salipherous, often containing fine dust and pollutants

Surface Temperature : Solar radiation may increase surface temperature up to

84 Deg C

Rainfall : Rainfall of 30 mm in 90 min with the return period of 5 years as

recommended by DM.

Wind : Design gust 162 km/h over 10 seconds


Design Ambient Temp : 50 Deg C plus allowance for solar radiation

7 BASIS AND ASSUMPTION

 Type of Installation = Ground, & Air.

 Design Ambient Temperature = 50°C

 Ground Temperature = 42°C

 Soil Thermal Resistivity = 2.5°C m/W

 Depth of lying = 0.8 mtr

 Max. Conductor Operating Temperature = 90 °C

The following Steady state cable voltage drop limits are considered for the cable sizing calculation.

Power distribution feeders - 2%

Lighting distribution feeder - 1%

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 7 of: 13
CONTRACT NO. CNT/ENP/112310 : :
Motor branch circuits - 5%

Voltage drop in Motor cable while starting - 15%

 Cable length is based on the cable routing layout.

 Power and control cables shall be of annealed stranded copper conductors, XLPE insulated,
steel wire armoured, and overall PVC sheathed. Lead sheath cables or equivalent eco-friendly
sheathing shall be used for outdoor cables.

8 PRINCIPLE FOLLOWED FOR THE LV CABLE SIZING CALCULATION

 Minimum required current rating Iflc / TDF

Where,
Iflc = Full Load current
TDF = Total De-rating factor for the cables laid in ground

 Voltage Drop at Steady State

Voltage drop = [Iflc x (mV/A/m) x L / (n x 1000)]

% Voltage drop = Voltage drop X 100/Operating Voltage

mV/A/m = Voltage drop factor per Amp per meter (mV)

9 DERATING FACTORS

De-rating factors considered for cables laid in directly ground:

 De-rating factors for ground temperature (42 °C) = 0.82


(Table 2 of Ducab cable catalogue, 40°C has been considered )

 De-rating factors for variation in thermal resistivity of soil (2.5°C m/W) = 0.75
(Table 3 of Ducab cable catalogue)

 De-rating factors for depth of laying (0.8 Mtr) = 0.96


(Table 4 of Ducab Cable catalogue)

 De-rating factors for grouping ( 4no. of circuit at 0.15m spacing) = 0.74


(Table 6 of Ducab Cable catalogue)

Total De-rating factor (T.D.F.) for Underground installation (0.82x0.75x0.96x0.74) = 0.44

De-rating factors considered for cables laid in Air / Metallic cable trays:

 De-rating factors for air temperature (50°C) = 0.82


(Table 11 of Ducab cable catalogue)

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 8 of: 13
CONTRACT NO. CNT/ENP/112310 : :
 Grouping factor for 4 touching circuits on a metal tray = 0.77
(Table 12 of Ducab cable catalogue)

Total De-rating factor (T.D.F.) for cable tray installation (0.82 x 0.77) = 0.63

10 CONCLUSION

The selected cables are suitable to carry the full load current within temperature limits and acceptable
voltage drops at operating conditions.

10.1 Cable Selection Chart

LV cable sizes are calculated and Electrical Cable Selection Chart is prepared in Attachment-4 ready
for selection of cables for all voltage level applied in this PROJECT.

11 APPENDICIES

Appendix 1 – Current Rating for LV cables

Appendix 2 – Cable Derating Factor

Appendix 3 – Resistance and Reactance Table

Appendix 4 – Electrical Cable Selection Chart

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 9 of: 13
CONTRACT NO. CNT/ENP/112310 : :
Appendix 1 – Current Rating for LV Cables

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 10 of: 13
CONTRACT NO. CNT/ENP/112310 : :
Appendix 1 - Doc. No. 112310-ELEC-CAL-3001

CURRENT RATINGS (ac)

600/1000V LEAD SHEATHED 3 CORE POWER CABLES Table 7

Stranded Copper Conductors Stranded Aluminium Conductors


Approximate voltage drop per Current Ratings Approximate voltage drop per
Current Ratings ampere per metre ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV
16* 115 94 99 2.5 2.5 2.5 89 72 74 4.2 4.2 4.2
25* 150 125 131 1.7 1.7 1.7 115 98 98 2.7 2.7 2.7
35* 180 150 162 1.2 1.2 1.2 135 120 120 1.9 1.9 1.9
50 215 175 197 0.9 0.9 0.9 165 145 145 1.4 1.4 1.4
70 265 215 251 0.6 0.6 0.6 200 185 185 1.0 1.0 1.0
95 315 260 304 0.5 0.5 0.5 240 224 224 0.7 0.7 0.7
120 360 300 353 0.4 0.4 0.4 275 264 264 0.6 0.6 0.6
150 405 335 406 0.3 0.3 0.3 310 305 305 0.5 0.5 0.5
185 460 380 463 0.3 0.3 0.3 350 350 350 0.4 0.4 0.4
240 530 440 546 0.2 0.2 0.2 410 418 418 0.3 0.3 0.3
300 590 495 628 0.2 0.2 0.2 460 488 488 0.3 0.3 0.3
400 667 570 728 0.2 0.2 0.2 520 562 562 0.2 0.2 0.2

* Circular conductors, all others are sector shaped

600/1000V LEAD SHEATHED 4 CORE POWER CABLES Table 8

Stranded Copper Conductors Stranded Aluminium Conductors


Approximate voltage drop per Current Ratings Approximate voltage drop per
Current Ratings ampere per metre ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV
16* 115 94 99 2.5 2.5 2.5 89 72 74 4.2 4.2 4.2
25 150 125 131 1.7 1.7 1.7 115 94 98 2.7 2.7 2.7
35 180 150 162 1.2 1.2 1.2 135 110 120 1.9 1.9 1.9
50 215 175 197 0.9 0.9 0.9 165 135 145 1.4 1.4 1.4
70 265 215 251 0.6 0.6 0.6 200 165 185 1.0 1.0 1.0
95 315 260 304 0.5 0.5 0.5 240 200 224 0.7 0.7 0.7
120 360 300 353 0.4 0.4 0.4 275 230 264 0.6 0.6 0.6
150 405 335 406 0.3 0.3 0.3 310 255 305 0.5 0.5 0.5
185 460 380 463 0.3 0.3 0.3 350 295 350 0.4 0.4 0.4
240 530 440 546 0.2 0.2 0.2 410 340 418 0.3 0.3 0.3
300 590 495 628 0.2 0.2 0.2 460 385 488 0.3 0.3 0.3
400 667 570 728 0.2 0.2 0.2 520 443 562 0.2 0.2 0.2

* Circular conductors, all others are sector shaped

14 BICC
Appendix 1 - Doc. No. 112310-ELEC-CAL-3001

CURRENT RATINGS (ac)


STRANDED COPPER & ALUMINIUM CONDUCTORS –
THREE CORE CABLES

600/1000 V Armoured PVC sheathed cables Table 24


Stranded Copper Conductors Stranded Aluminium Conductors
Approximate voltage drop per Approximate voltage drop per
Current Ratings Current Ratings
ampere per metre ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV

16 115 94 99 2.5 2.5 2.5 89 72 74 4.2 4.2 4.2


25 150 125 131 1.7 1.7 1.7 115 94 98 2.7 2.7 2.7
35 180 150 162 1.2 1.2 1.2 135 110 120 1.9 1.9 1.9
50 215 175 197 0.9 0.9 0.9 165 135 145 1.4 1.4 1.4
70 265 215 251 0.6 0.6 0.6 200 165 185 1.0 1.0 1.0
95 315 260 304 0.5 0.5 0.5 240 200 224 0.7 0.7 0.7
120 360 300 353 0.4 0.4 0.4 275 230 264 0.6 0.6 0.6
150 405 335 406 0.3 0.3 0.3 310 255 305 0.5 0.5 0.5
185 460 380 463 0.3 0.3 0.3 350 295 350 0.4 0.4 0.4
240 530 440 546 0.2 0.2 0.2 410 340 418 0.3 0.3 0.3
300 590 495 628 0.2 0.2 0.2 460 385 488 0.3 0.3 0.3
400 667 570 728 0.2 0.2 0.2 520 443 562 0.2 0.2 0.2

600/1000 V Unarmoured PVC sheathed cables Table 25


Stranded Copper Conductors Stranded Aluminium Conductors

Approximate voltage drop per Approximate voltage drop per


Current Ratings Current Ratings ampere per metre
ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV

16 120 93 100 2.5 2.5 2.5


25 145 125 127 1.7 1.7 1.7 115 92 97 2.7 2.7 2.7
35 180 145 158 1.2 1.2 1.2 135 110 120 1.9 1.9 1.9
50 215 175 192 0.9 0.9 0.9 165 135 146 1.4 1.4 1.4
70 265 215 246 0.6 0.6 0.6 200 165 187 1.0 1.0 1.0
95 315 255 298 0.5 0.5 0.5 240 195 227 0.7 0.7 0.7
120 365 300 346 0.4 0.4 0.4 275 225 263 0.6 0.6 0.6
150 405 330 399 0.3 0.3 0.3 310 255 304 0.5 0.5 0.5
185 465 380 456 0.3 0.3 0.3 350 290 347 0.4 0.4 0.4
240 540 440 538 0.2 0.2 0.2 415 340 409 0.3 0.3 0.3
300 600 500 621 0.2 0.2 0.2 465 385 471 0.3 0.3 0.3
400 675 575 741 0.2 0.2 0.2 523 443 570 0.2 0.2 0.2

Direct in ground – Cables touching Installation conditions for above ratings:


Single way ducts - ducts touching Ambient air temperature:30˚C
Note: Unarmoured cables are as per IEC 60502 (Part 1) Ground temperature: 15˚C
Depth of laying:0.5 m
Soil thermal resistivity: 1.2˚C m/W
Maximum conductor operating temperature at rated current is 90˚C
For rating factors see Tables 2 to 6 and 8 to 12

BICC 25
Appendix 1 - Doc. No. 112310-ELEC-CAL-3001

CURRENT RATINGS (ac)


STRANDED COPPER & ALUMINIUM CONDUCTORS –
Four CORE CABLES

600/1000 V Armoured PVC sheathed cables Table 27


Stranded Copper Conductors Stranded Aluminium Conductors

Approximate voltage drop per Approximate voltage drop per


Current Ratings Current Ratings
ampere per metre ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV
16 115 94 99 2.5 2.5 2.5 89 72 74 4.2 4.2 4.2
25 150 125 131 1.7 1.7 1.7 115 94 98 2.7 2.7 2.7
35 180 150 162 1.2 1.2 1.2 135 110 120 1.9 1.9 1.9
50 215 175 197 0.9 0.9 0.9 165 135 145 1.4 1.4 1.4
70 265 215 251 0.6 0.6 0.6 200 165 185 1.0 1.0 1.0
95 315 260 304 0.5 0.5 0.5 240 200 224 0.7 0.7 0.7
120 360 300 353 0.4 0.4 0.4 275 230 264 0.6 0.6 0.6
150 405 335 406 0.3 0.3 0.3 310 255 305 0.5 0.5 0.5
185 460 380 463 0.3 0.3 0.3 350 295 350 0.4 0.4 0.4
240 530 440 546 0.2 0.2 0.2 410 340 418 0.3 0.3 0.3
300 590 495 628 0.2 0.2 0.2 460 385 488 0.3 0.3 0.3
400 667 570 728 0.2 0.2 0.2 520 443 562 0.2 0.2 0.2
500 720 605 800 0.2 0.2 0.2 561 470 618 0.2 0.2 0.2

600/1000 V Unarmoured PVC sheathed cables Table 28


Stranded Copper Conductors Aluminium Conductors

Approximate voltage drop per Approximate voltage drop per


Current Ratings Current Ratings
ampere per metre ampere per metre
Nominal
area of Direct in In single Installed Ground Duct Air Direct in In single Installed Ground Duct Air
conductor ground way ducts in air ground way ducts in air
mm2 amps amps amps mV mV mV amps amps amps mV mV mV
16 120 93 100 2.5 2.5 2.5 89 72 74 4.2 4.2 4.2
25 145 125 127 1.7 1.7 1.7 115 92 97 2.7 2.7 2.7
35 180 145 158 1.2 1.2 1.2 135 110 120 1.9 1.9 1.9
50 215 175 192 0.9 0.9 0.9 165 135 146 1.4 1.4 1.4
70 265 215 246 0.6 0.6 0.6 200 165 187 1.0 1.0 1.0
95 315 255 298 0.5 0.5 0.5 240 195 227 0.7 0.7 0.7
120 365 300 346 0.4 0.4 0.4 275 225 263 0.6 0.6 0.6
150 405 330 399 0.3 0.3 0.3 310 255 304 0.5 0.5 0.5
185 465 380 456 0.3 0.3 0.3 350 290 347 0.4 0.4 0.4
240 540 440 538 0.2 0.2 0.2 415 340 409 0.3 0.3 0.3
300 600 500 621 0.2 0.2 0.2 465 385 471 0.3 0.3 0.3
400 675 575 741 0.2 0.2 0.2 523 443 570 0.2 0.2 0.2
500 730 610 814 0.2 0.2 0.2 565 470 626 0.2 0.2 0.2

Direct in ground – Cables touching Installation conditions for above ratings:


Single way ducts - ducts touching Ambient air temperature: 30˚C
Note: Unarmoured cables are as per IEC 60502 (Part 1) Ground temperature: 15˚C
Depth of laying: 0.5 m
Soil thermal resistivity: 1.2˚C m/W
Maximum conductor operating temperature at rated current is 90˚C
For rating factors see Tables 2 to 6 and 8 to 12

BICC 27
Appendix 2 – Cable Derating Factor

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 11 of: 13
CONTRACT NO. CNT/ENP/112310 : :
Appendix 2 - Doc. No. 112310-ELEC-CAL-3001

RATING FACTORS
Where the conditions of installation differ from those defined in the current rating tables, the following rating factors may be used
for cables size selection.

CABLES LAID DIRECTLY IN GROUND


Ratings for cables installed directly in the ground are based on values of soil temperature and soil thermal resistivity which are
generally representative of conditions in the United Kingdom. Rating factors to take account of variation in ground temperatures
are given in Table 2. Where conditions of operation can be fairly accurately estimated and knowledge of the soil along the route is
available, it is possible to determine the ratings more precisely by the use of the soil thermal resistivity factors, grouping factors, and
factors for the depths of laying given in Tables 3 to 6. These factors are more fully tabulated in ERA Report 69 - 30 Part II Tables
61 - 71.

Rating factors for ground temperature Table 2


Ground temperature 15˚C 20˚C 25˚C 30˚C 35˚C 40˚C 45˚C
Cable Type Rating factor
XLPE Insulated 1.0 0.97 0.93 0.89 0.86 0.82 0.76

Rating factors for variation in thermal resistivity of soil Table 3


(average values)
Size of cables Soil thermal resistivity in ˚C m/W
mm2
0.8 0.9 1.0 1.5 2.0 2.5 3.0

Single core cables


Up to 150 1.16 1.12 1.07 0.91 0.81 0.73 0.66
From 185 to 300 1.17 1.12 1.07 0.91 0.80 0.73 0.66
From 400 to 1000 1.17 1.12 1.07 0.91 0.80 0.73 0.66
Multicore cables
Up to 16 1.12 1.08 1.05 0.93 0.84 0.77 0.72
From 25 to 150 1.14 1.10 1.06 0.92 0.82 0.75 0.69
From 185 to 500 1.15 1.10 1.07 0.92 0.81 0.74 0.67

In ERA Report 69-30 Part III, the types of load are classified under three headings, viz:

Type A Cables carrying a constant load throughout the year.


Type B Cables carrying varying loads, maximum in summer period.
Type C Cables carrying varying loads, maximum in winter period.

With knowledge of the type of load to be imposed on the cable it is then possible to determine the soil thermal resistivity along the
cable route in accordance with recommendations in ERA Report 69-30.

BICC 11
Appendix 2 - Doc. No. 112310-ELEC-CAL-3001

Rating factors for depth of laying (to centre of cable or trefoil


group of cables) Table 4
Depth of laying 600/1000 Volt 1900/3300 Volt
70mm2
m Up to 50mm2 Above 300mm2 Up to 300mm2 Above 300mm2
to 300mm2

0.50 1.00 1.00 1.00 - -


0.60 0.99 0.98 0.97 - -
0.80 0.97 0.96 0.94 1.00 1.00
1.00 0.95 0.93 0.92 0.98 0.97
1.25 0.94 0.92 0.89 0.96 0.95
1.50 0.93 0.90 0.87 0.95 0.93
1.75 0.92 0.89 0.86 0.94 0.91
2.00 0.91 0.88 0.85 0.92 0.89
2.50 0.90 0.87 0.84 0.91 0.88
3.00 0.89 0.85 0.82 0.90 0.86
or more

Group rating factors for circuits of three single core cables in


trefoil or laid flat touching, in horizontal formation Table 5

SPACING
SPACING

Number of Circuits Spacing of Circuits

Touching +

Trefoil Laid flat 0.15 m* 0.30 m 0.545 m 0.60 m


2 0.78 0.81 0.83 0.88 0.91 0.93
3 0.66 0.70 0.73 0.79 0.84 0.87
600/1000 4 0.61 0.64 0.68 0.73 0.81 0.85
Volt cables 5 0.56 0.60 0.64 0.73 0.79 0.85
6 0.53 0.57 0.61 0.71 0.78 0.82

2 0.78 0.80 0.82 0.86 0.89 0.91


3 0.66 0.68 0.71 0.77 0.80 0.83
1900/3300 4 0.59 0.62 0.65 0.72 0.77 0.80
Volt cables 5 0.55 0.58 0.61 0.68 0.74 0.78
6 0.52 0.55 0.58 0.66 0.72 0.76

* This spacing will not be possible for some of the larger diameter cables.

+ For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most
appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.

12 BICC
Appendix 2 - Doc. No. 112310-ELEC-CAL-3001

Group rating factors for multicore cables in horizontal formation Table 6

SPACING

Number of Cables in Group


Spacing

Touching+ 0.15 m 0.30 m 0.45 m 0.60 m

2 0.81 0.87 0.91 0.93 0.95


3 0.70 0.78 0.84 0.88 0.90
600/1000
4 0.63 0.74 0.81 0.86 0.89
volt cables
5 0.59 0.70 0.78 0.84 0.87
6 0.55 0.68 0.77 0.83 0.87

2 0.80 0.85 0.89 0.91 0.93


3 0.68 0.76 0.81 0.84 0.87
1900/3000
4 0.62 0.71 0.77 0.81 0.84
volt cables
5 0.57 0.66 0.73 0.78 0.82
6 0.54 0.64 0.71 0.77 0.81

+ For high current carrying cables (i.e. large size) it is advisable to allow spacing between circuits. Alternatively the most
appropriate group rating factor must be applied when determining the cable size and required number of cables in parallel.

CABLES INSTALLED IN DUCTS


The term ducts applies to single way earthenware, fibre or ferrous pipes.

Recommended duct dimensions and cable sizes Table 7

Overall cable diameter Duct

Inside diameter Outside diameter


mm mm mm
Up to and including 65 100 130

Above 65 up to and including 90 125 160

Ratings for cables installed in single way ducts, underground, have been based on values of soil temperature and soil thermal
resistivity which are generally representative of conditions in the United Kingdom. Rating factors to take account of variations in
ground temperatures are given in Table 3. Where conditions of operation can be fairly accurately estimated, and knowledge of the
soil along the route is available, it is possible to determine the ratings more precisely by the use of estimated maximum ground
temperature, the soil thermal resistivity factors, grouping factors, and factors for the depths of laying given in Tables 8 to 11.

Rating factors for ground temperature


Note: Same as for direct in ground, refer to Table 2.

BICC 13
Appendix 2 - Doc. No. 112310-ELEC-CAL-3001

CURRENT RATINGS (AC)

XLPE INSULATED CABLES PVC INSULATED CABLES


(Maximum conductor temperature 90˚C) (Maximum conductor temperature 70˚C)
Installed in free air (Reference Method 11 on cable tray or Installed in free air (Reference Method 11 on cable tray or
Method 13 in free air, IEE Wiring Regulations, 16th Method 13 in free air, IEE Wiring Regulations, 16th
Edition) Table 7 Edition) Table 9
Nominal Two core Three and Four core Nominal Two core Three and Four core
area of Current Volt drop per Current Volt drop per area of Current Volt drop per Current Volt drop per
Conductor rating amp per rating amp per Conductor rating amp per rating amp per
metre metre metre metre
mm2 amp mV amp mV mm2 amp mV amp mV
1. 5 29 31 25 27 1. 5 22 29 19 25
2. 5 39 19 33 16 2. 5 31 18 26 15
4 52 12 44 10 4 41 11 35 9.5
6 66 7.9 56 6.8 6 53 7.3 45 6.4
10 90 4.7 78 4.0 10 72 4.4 62 3.8

Ratings based on Ambient air temp 30˚C Ratings based on Ambient air temp 30˚C
Laid directly in ground, run in single-way ducts Table 8 Laid directly in ground, run in single-way ducts Table 10
Two core Three and Four core Two core Three and Four core
Nominal Nominal
area of Current rating Volt drop Current rating Volt drop area of Current rating Volt drop Current rating Volt drop
Conductor In In duct per amp In In duct per amp Conductor In In duct per amp In In duct per amp
ground per metre ground per metre ground per metre ground per metre
mm2 amp amp mV amp amp mV mm2 amp amp mV amp amp mV
1.5 38 31 31 32 26 27 1. 5 32 26 29 27 22 25
2. 5 49 41 19 42 34 16 2. 5 41 34 18 35 29 15
4 65 53 12 55 45 10 4 55 45 11 47 38 9.5
6 81 67 7.9 69 56 6.8 6 69 57 7.3 59 48 6.4
10 109 89 4.7 92 75 4.0 10 92 76 4.4 78 64 3.8

Ratings based on Ground temp 15˚C, Soil thermal resistivity 1.2˚Cm/W. Ratings based on Ground temp 15˚C, Soil thermal resistivity 1.2˚Cm/W.
Depth of laying 0.5m. All circuits thermally independent. 100mm diameter Depth of laying 0.5m. All circuits thermally independent. 100mm diameter
single-way ducts. single-way ducts.
Current Ratings for cables having more than four cores are available on request. Current Ratings for cables having more than four cores are available on request.

RATING FACTORS
Rating factors for variation in thermal
Rating factors for ambient air temperature Table 11 resistivity of soil (average values) Table 14
Ambient air temperature 25˚C 30˚C 35˚C 40˚C 45˚C 50˚C 55˚C Soil thermal resistivity in ˚Cm/W
Cable type Rating factor Type of installation 0.8 0.9 1.0 1.5 2.0 2.5
Multicore cables laid directly
XLPE and LSF cable 1.02 1.00 0.96 0.91 0.87 0.82 0.76
in ground 1.09 1.06 1.04 0.93 0.84 0.77
PVC cable 1.03 1.00 0.94 0.87 0.79 0.71 0.61 Multicore cables installed
in single way ducts 1.03 1.02 1.02 0.97 0.91 0.87

Correction factors for Groups of Cables, installed in air Table 12 Rating factors for ground temperature
(cables laid direct or in ducts) Table 15
Arrangement of Number of circuits or multicore cables
cables 2 3 4 5 6 7 8 9 10 Ground temperature 15˚C 20˚C 25˚C 30˚C 35˚C 40˚C 45˚C

In conduit, XLPE insulated 1.0 0.97 0.93 0.89 0.86 0.82 0.76
trunking or
bunched and PVC insulated 1.0 0.95 0.90 0.85 0.80 0.74 0.67
clipped directly 0.8 0.7 0.65 0.6 0.57 0.54 0.52 0.5 0.48 Group rating factors for multicore cables
in horizontal formation (average values) Table 16
On metal tray and
Number Spacing between cable centres
cables touching 0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71
of cables Touch- 0.15m 0.3m 0.45m 0.6m
in group ing
Rating factors for depth of laying 2 0.81 0.87 0.91 0.93 0.94
(to centre of cable or to centre of duct) Table 13 Cables direct 3 0.70 0.78 0.84 0.87 0.90
in ground 4 0.63 0.74 0.81 0.86 0.89
Depth of laying Multicore Cables 5 0.59 0.70 0.78 0.83 0.87
m Direct in ground In single way ducts 6 0.55 0.67 0.76 0.82 0.86
0.50 1.00 1.00 2 0.90 0.93 0.95 0.96
0.60 0.99 0.99 Cables in single 3 0.82 0.87 0.90 0.93
0.80 0.97 0.97 way ducts 4 0.78 0.85 0.89 0.91
1.00 0.95 0.96 5 0.76 0.82 0.87 0.90
1.25 0.94 0.95 6 0.72 0.81 0.86 0.90

8 ")##
Appendix 3 – Resistance and Reactance Table

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 12 of: 13
CONTRACT NO. CNT/ENP/112310 : :
Atatchment-3 OF CLIENT DOC.NO.
112310-ELEC-CAL-3001

RESISTANCE
NOMINAL
(REF. TABLE II, COLUMN 8 OF IEC Reactance at 50 Hz
AREA OF
SR.NO. 60228)
CONDUCT
OR (mm2) R in ohm / km mH/kM Ohm/kM
20°C 90°C 'L' 'X'
1 2.5 7.41 9.50 0.297 0.0932

2 4 4.61 5.91 0.279 0.0875

3 6 3.08 3.95 0.266 0.0837

4 10 1.83 2.35 0.250 0.0785

5 16 1.15 1.47 0.242 0.0761

6 25 0.727 0.93 0.244 0.0768

7 35 0.524 0.67 0.237 0.0743

8 50 0.387 0.50 0.235 0.0739

9 70 0.268 0.34 0.231 0.0726

10 95 0.193 0.25 0.225 0.0708

11 120 0.153 0.20 0.224 0.0705

12 150 0.124 0.16 0.226 0.0709

13 185 0.0991 0.13 0.227 0.0712

14 240 0.0754 0.10 0.224 0.0703

15 300 0.0601 0.08 0.222 0.0697

16 400 0.047 0.06 0.221 0.0694

17 500 0.0366 0.047 0.220 0.0691

18 630 0.0283 0.036 0.218 0.0685

19 800 0.0221 0.028 0.216 0.0679


NOTES:
Temperature correction factor for copper conductor (for t = 90°C)
= [254.5 / 234.5 + t] = 0.78 - (Refer IEC 60228- Annexure 8)

X' can be derived from the formula X = 2πfL/1000 (where f = 50Hz)

\\10.161.14.4\Projtech\PROJECTS 2022\aeT00878 EMARAT-Upgrading of Fire Water\9 TME DOCS-DWGS\341 Elect\1 CURRENT\4.


Cable Sizing\112310-ELEC-CAL-3001-A- Appendix 3.xlsx Page 1 of 1
Appendix 4 – Electrical Cable Selection Chart

Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-CAL-3001


Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SIZING CALCULATION

Office: Dubai Order: AET00878-00 Document No. 4132001 Rev 0 Sheet 13 of: 13
CONTRACT NO. CNT/ENP/112310 : :
240V CABLE SELECTION CHART (POWER FEEDER)
(LAID IN GROUND)
CABLES HAVING COPPER CONDUCTORS
MAXIMUM PERMISSIBLE VOLT DROP = 2% AT FEEDER F.L.C.
DERATlNG FACTOR = 0.44
VOLTAGE = 240 V

CABLE CSA IN mm2 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2 95 mm2 120 mm2 150 mm2 185 mm2 240 mm2
STANDARD CABLE RATING (Refer
42 55 69 92 140 180 215 255 315 381 410 472 539 632
Appendix-A)
SITE CABLE RATING 18.5 24.2 30.4 40.5 61.6 79.2 94.6 112.2 138.6 167.6 180.4 207.7 237.2 278.1
CABLE RESIST. IN OHM / km (20˚ C) 7.410 4.610 3.080 1.830 1.150 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 0.075
CABLE RESIST. IN OHM / km (90˚ C) 9.500 5.910 3.950 2.350 1.470 0.930 0.670 0.500 0.340 0.250 0.200 0.160 0.130 0.100
CABLE INDUCTANCE IN mH / km 0.297 0.279 0.266 0.250 0.242 0.244 0.237 0.235 0.231 0.225 0.224 0.226 0.227 0.224
CABLE REACTANCE IN OHM / km 0.093 0.088 0.084 0.079 0.076 0.077 0.074 0.074 0.073 0.071 0.071 0.071 0.071 0.070
FEEDER FEEDER
COS SIN MAXIMUM PERMISSIBLE ROUTE LENGTH IN METER
RATING F.L.C.
PHI PHI
kW AMPS
0.25 1.23 0.85 0.60 241 386 575 958 1512 2341 3189 4173 5889 7681 9225 10969 12782 15399
1 4.90 0.85 0.60 60 96 144 239 378 585 797 1043 1472 1920 2306 2742 3195 3850
2.5 12.25 0.85 0.60 24 39 57 96 151 234 319 417 589 768 922 1097 1278 1540
0.13 0.64 0.85 0.60 463 742 1105 1842 2908 4502 6133 8024 11325 14770 17740 21094 24580 29613
0.13 0.64 0.85 0.60 463 742 1105 1842 2908 4502 6133 8024 11325 14770 17740 21094 24580 29613
0.08 0.39 0.85 0.60 753 1206 1796 2993 4725 7315 9966 13040 18403 24002 28827 34278 39943 48121
1.00 4.90 0.85 0.60 60 96 144 239 378 585 797 1043 1472 1920 2306 2742 3195 3850
3.00 14.71 0.85 0.60 20 32 48 80 126 195 266 348 491 640 769 914 1065 1283
3.70 18.14 0.85 0.60 16 26 39 65 102 158 215 282 398 519 623 741 864 1040
4.00 19.61 0.85 0.60 - 24 36 60 95 146 199 261 368 480 577 686 799 962
5.50 26.96 0.85 0.60 - - 26 44 69 106 145 190 268 349 419 499 581 700
7.50 36.76 0.85 0.60 - - - 32 50 78 106 139 196 256 307 366 426 513
11.00 53.92 0.85 0.60 - - - - 34 53 72 95 134 175 210 249 290 350
15.00 73.53 0.85 0.57 - - - - - 39 53 70 99 129 155 185 216 261
18.50 90.69 0.85 0.57 - - - - - - 43 57 80 105 126 150 175 212
22.00 107.84 0.85 0.57 - - - - - - - 48 67 88 106 126 147 178
30.00 147.06 0.85 0.57 - - - - - - - - - 65 78 93 108 130
37.00 181.37 0.85 0.57 - - - - - - - - - - - 75 88 106
45.00 220.59 0.85 0.57 - - - - - - - - - - - - 72 87
55.00 269.61 0.85 0.54 - - - - - - - - - - - - - 72
75.00 367.65 0.85 0.54 - - - - - - - - - - - - - -
90.00 441.18 0.85 0.54 - - - - - - - - - - - - - -
110.00 539.22 0.85 0.54 - - - - - - - - - - - - - -
132.00 647.06 0.85 0.54 - - - - - - - - - - - - - -
150.00 735.29 0.85 0.53 - - - - - - - - - - - - - -
Project No. 112310
Doc. No. ATTCHMENT 4 of Doc. No. 112310-ELEC-CAL-3001
ATTCHMENT 4: CABLE SELECTION CHART Rev 0
Date 15/11/2022

\\10.161.14.4\Projtech\PROJECTS 2022\aeT00878 EMARAT-Upgrading of Fire Water\9 TME DOCS-DWGS\341 Elect\1 CURRENT\4. Cable Sizing\112310-ELEC-CAL-3001-A- Appendix 4.xlsx 1 of 2
240V CABLE SELECTION CHART (POWER FEEDER)
(LAID IN AIR)
CABLES HAVING COPPER CONDUCTORS
MAXIMUM PERMISSIBLE VOLT DROP = 2% AT FEEDER F.L.C.
DERATlNG FACTOR = 0.63
VOLTAGE = 240 V

CABLE CSA IN mm2 2.5 mm2 4 mm2 6 mm2 10 mm2 16 mm2 25 mm2 35 mm2 50 mm2 70 mm2 95 mm2 120 mm2 150 mm2 185 mm2 240 mm2
STANDARD CABLE RATING (Refer
42 55 69 92 115 152 188 228 291 354 430 480 540 636
Appendix-A)
SITE CABLE RATING 26.5 34.7 43.5 58.0 72.5 95.8 118.4 143.6 183.3 223.0 270.9 302.4 340.2 400.7
CABLE RESIST. IN OHM / km (20˚ C) 7.410 4.610 3.080 1.830 1.150 0.727 0.524 0.387 0.268 0.193 0.153 0.124 0.099 0.075
CABLE RESIST. IN OHM / km (90˚ C) 9.500 5.910 3.950 2.350 1.470 0.930 0.670 0.500 0.340 0.250 0.200 0.160 0.130 0.100
CABLE INDUCTANCE IN mH / km 0.297 0.279 0.266 0.250 0.242 0.244 0.237 0.235 0.231 0.225 0.224 0.226 0.227 0.224
CABLE REACTANCE IN OHM / km 0.093 0.088 0.084 0.079 0.076 0.077 0.074 0.074 0.073 0.071 0.071 0.071 0.071 0.070
FEEDER FEEDER
COS SIN MAXIMUM PERMISSIBLE ROUTE LENGTH IN METER
RATING F.L.C.
PHI PHI
kW AMPS
0.25 1.23 0.85 0.60 241 386 575 958 1512 2341 3189 4173 5889 7681 9225 10969 12782 15399
0.37 1.81 0.85 0.60 163 261 388 647 1022 1582 2155 2819 3979 5190 6233 7411 8636 10404
0.55 2.70 0.85 0.60 109 175 261 435 687 1064 1450 1897 2677 3491 4193 4986 5810 6999
0.75 3.68 0.85 0.60 80 129 192 319 504 780 1063 1391 1963 2560 3075 3656 4261 5133
1.10 5.39 0.85 0.60 55 88 131 218 344 532 725 948 1338 1746 2097 2493 2905 3500
1.50 7.35 0.85 0.60 40 64 96 160 252 390 532 695 981 1280 1537 1828 2130 2566
2.20 10.78 0.85 0.60 27 44 65 109 172 266 362 474 669 873 1048 1246 1452 1750
3.00 14.71 0.85 0.60 20 32 48 80 126 195 266 348 491 640 769 914 1065 1283
3.70 18.14 0.85 0.60 16 26 39 65 102 158 215 282 398 519 623 741 864 1040
4.00 19.61 0.85 0.60 15 24 36 60 95 146 199 261 368 480 577 686 799 962
5.50 26.96 0.85 0.60 - 18 26 44 69 106 145 190 268 349 419 499 581 700
7.50 36.76 0.85 0.60 - - 19 32 50 78 106 139 196 256 307 366 426 513
11.00 53.92 0.85 0.60 - - - 22 34 53 72 95 134 175 210 249 290 350
15.00 73.53 0.85 0.57 - - - - - 39 53 70 99 129 155 185 216 261
18.50 90.69 0.85 0.57 - - - - - 32 43 57 80 105 126 150 175 212
22.00 107.84 0.85 0.57 - - - - - - 36 48 67 88 106 126 147 178
30.00 147.06 0.85 0.57 - - - - - - - - 49 65 78 93 108 130
37.00 181.37 0.85 0.57 - - - - - - - - 40 52 63 75 88 106
45.00 220.59 0.85 0.57 - - - - - - - - - 43 52 62 72 87
55.00 269.61 0.85 0.54 - - - - - - - - - - 43 51 60 72
75.00 367.65 0.85 0.54 - - - - - - - - - - - - - 53
90.00 441.18 0.85 0.54 - - - - - - - - - - - - - -
110.00 539.22 0.85 0.54 - - - - - - - - - - - - - -
132.00 647.06 0.85 0.54 - - - - - - - - - - - - - -
150.00 735.29 0.85 0.53 - - - - - - - - - - - - - -
Project No. 112310
Doc. No. ATTCHMENT 4 of Doc. No. 112310-ELEC-CAL-3001
ATTCHMENT 4: CABLE SELECTION CHART Rev 0
Date 15/11/2022

\\10.161.14.4\Projtech\PROJECTS 2022\aeT00878 EMARAT-Upgrading of Fire Water\9 TME DOCS-DWGS\341 Elect\1 CURRENT\4. Cable Sizing\112310-ELEC-CAL-3001-A- Appendix 4.xlsx 2 of 2
CONTRACT NO. CNT/ENP/112310 FACILITIES

UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI

TERMINAL PROJECT

CABLE SCHEDULE

0 20-01-2023 ISSUED FOR TENDER ZA NB HR


B 12-12-2022 ISSUED FOR APPROVAL ZA NB HR
A 16-11-2022 ISSUED FOR CLIENT REVIEW ZA NB HR
Rev. Date Description/issued for By Ckd. Appd.
Client: EMARAT EMARAT DOCUMENT NO : 112310-ELEC-SCH-3002
Project: UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT

Title: CABLE SHEDULE

Office: Dubai Order: AET00878-00 Document No. 4143001 Rev 0 Sheet 1 of: 1
CONTRACT NO. CNT/ENP/112310 : :
FROM TO
Sr. Voltage NO. OF LENGTH
CABLE TAG NO. CABLE CONSTRUCTION CABLE SIZE REMARKS
No. grade (kV) RUNS (m)
EQUIPMENT TAG NO. DESCRIPTION GLAND EQUIPMENT TAG NO. DESCRIPTION GALND

Diesel Engine Controller for Pump


1 XX-XXXX-001 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 C-112 M20 35.00
(P-112)

Diesel Engine Controller for Pump


2 XX-XXXX-PE001 CU/PVC 0.45/0.75 1 1C X 4 sq.mm DB-FPS 240V AUXILAIRY DB C-112 35.00
(P-112)

Diesel Engine Heater for Pump (P-


3 XX-XXXX-002 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 10 sq.mm DB-FPS 240V AUXILAIRY DB M25 H-112 M25 35.00
112)

Diesel Engine Heater for Pump (P-


4 XX-XXXX-PE002 CU/PVC 0.45/0.75 1 1C X 10 sq.mm DB-FPS 240V AUXILAIRY DB H-112 35.00
112)

Anti Fouling System control panel


5 XX-XXXX-003 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 AF-112 M20 35.00
for new Diesel Driven Pump

Anti Fouling System control panel


6 XX-XXXX-PE003 CU/PVC 0.45/0.75 1 1C X 4 sq.mm DB-FPS 240V AUXILAIRY DB AF-112 35.00
for new Diesel Driven Pump

5 XX-XXXX-003 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 FACP-01 FACP Panel M20 10.00

6 XX-XXXX-PE003 CU/PVC 0.45/0.75 1 1C X 4 sq.mm DB-FPS 240V AUXILAIRY DB FACP-01 FACP Panel 10.00

0.23kV (lighting Cables circuit - R3)

7 XX-XXXX-004 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 JBL-01 1Ph Lighting JB - 01 M20 12.00

8 XX-XXXX-005 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-01 1Ph Lighting JB - 01 M20 LF-01 Light Fixture - 01 M20 2.00

9 XX-XXXX-006 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-01 1Ph Lighting JB - 01 M20 JBL-02 1Ph Lighting JB - 02 M20 8.00

10 XX-XXXX-007 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-02 1Ph Lighting JB - 02 M20 LF-02 Light Fixture - 02 M20 2.00

11 XX-XXXX-008 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-02 1Ph Lighting JB - 02 M20 JBL-03 1Ph Lighting JB - 03 M20 8.00

12 XX-XXXX-009 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-03 1Ph Lighting JB - 03 M20 LF-03 Light Fixture - 03 M20 2.00

0.23kV (lighting Cables circuit - Y3)

Page 1 of 2
FROM TO
Sr. Voltage NO. OF LENGTH
CABLE TAG NO. CABLE CONSTRUCTION CABLE SIZE REMARKS
No. grade (kV) RUNS (m)
EQUIPMENT TAG NO. DESCRIPTION GLAND EQUIPMENT TAG NO. DESCRIPTION GALND

13 XX-XXXX-010 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 JBL-04 1Ph Lighting JB - 01 M20 12.00

14 XX-XXXX-011 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-04 1Ph Lighting JB - 01 M20 LF-04 Light Fixture - 01 M20 2.00

15 XX-XXXX-012 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-04 1Ph Lighting JB - 01 M20 JBL-05 1Ph Lighting JB - 02 M20 8.00

16 XX-XXXX-013 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-05 1Ph Lighting JB - 02 M20 LF-05 Light Fixture - 02 M20 2.00

17 XX-XXXX-014 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-05 1Ph Lighting JB - 02 M20 JBL-06 1Ph Lighting JB - 03 M20 8.00

18 XX-XXXX-015 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-06 1Ph Lighting JB - 03 M20 LF-06 Light Fixture - 03 M20 2.00

0.23kV (lighting Cables circuit - B3)

19 XX-XXXX-016 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 4 sq.mm DB-FPS 240V AUXILAIRY DB M20 JBL-07 1Ph Lighting JB - 01 M20 12.00

20 XX-XXXX-017 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-07 1Ph Lighting JB - 01 M20 LF-07 Light Fixture - 01 M20 2.00

21 XX-XXXX-018 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-07 1Ph Lighting JB - 01 M20 JBL-08 1Ph Lighting JB - 02 M20 8.00

22 XX-XXXX-019 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-08 1Ph Lighting JB - 02 M20 LF-08 Light Fixture - 02 M20 2.00

23 XX-XXXX-020 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-08 1Ph Lighting JB - 02 M20 JBL-09 1Ph Lighting JB - 03 M20 8.00

24 XX-XXXX-021 CU/XLPE/PVC/GSWA/PVC 0.6/1 1 3C X 2.5 sq.mm JBL-09 1Ph Lighting JB - 03 M20 LF-09 Light Fixture - 03 M20 2.00

Client EMARAT
Project UPGRADE OF FIRE WATER PUMPING SYSTEM AT JEBEL ALI TERMINAL PROJECT
Title CABLE SCHEDULE
DOC. NO. 112310-ELEC-SCH-3002

Page 2 of 2