You are on page 1of 15

MESSKO® PRODUCT CATALOGUE

TRANSFORMER SOLUTIONS.
WW W.R EIN HAU S E N.COM
TRANSFORMER SOLUTIONS MESSKO® PORTFOLIO
MESSKO® - Precision since 1911 Product and service cycle

Testing, measuring, analyzing, evaluating – this meters, oil level indicators, pressure relief devices,
is what the MESSKO® brand stands for. The dehydrating breathers, flow indicators, sensor
MESSKO® product brand is defined by the con- systems for oil analysis, and a complete range of
stant pursuit of precision and perfection. As a services focusing on up-to-date laboratory analy-
result, it has developed since 1911 from a small, sis and diagnosis. MESSKO® products, systems
local brand for cooler thermometers, air pressure and services contribute towards a reliable power
gauges and remote thermometers into a product supply, making utility companies and industrial PRODUCTS Oil level indicator
brand setting global standards for all aspects of enterprises fit for the future and ensuring that Buchholz relay Starting on page 8
II Thermometer
monitoring, protection, open and closed-loop their systems run smoothly and reliably even Page 16
II Oil level indicator
control and automation technology that relate to under the most demanding conditions. II Pressure relief device
transformers. The current range covers thermo- II Dehydrating breather
II Flow indicator SYSTEMS
II Transport monitoring
A few highlights from our company history: II Monitoring and analysis systems
II Testing, measuring, and service
1999 systems
1911 MR acquires
Dr. Albert Hauser 1935 the company 2011
founds the "Fein­ The MESSKO® brand and transforms Messko 100-year
mechanische An- is created from into one of the most anniversary Pressure relief device
stalt für Präzisionswaagen combining the Ger- renowned suppli- Page 10
und Gewichte" (Precision- man terms "Mes- ers of measurement
engineering institute sen" (measuring) equipment for energy
for precision scales and and "Kontrollieren" utility companies and
weights). (monitoring). industry worldwide. Oil analysis sensor Dehydrating breather
Page 17 Page 11

1932 1960 2013


The company develops the Thermometers for The new MESSKO® Gas-in-oil analysis
first remote thermometer that power transformers PrimeLab® –Diagnostic Page 25
applies the Bourdon measur- capture the atten- Services program
ing principle and in so doing tion offers compre-­ Flow indicator
sets the definitive standard of the hensive, Page 12
that still lays the market. professional
foundation for condition
analysis. Thermometer Thermometer
today's cele­ Starting on page 4 Oil level indicator
brated line of Pressure relief device
thermo­meters. Dehydrating breather
Flow indicator
What does MESSKO products stand for? Transport monitoring
Secure SERVICE Monitoring and analysis systems
Testing, measuring, and service systems
We make no compromises when it comes to quality, which starts with selecting premium mate- II Services Accessories
rials and continues through to thorough quality and functional testing carried out on state-of- Services
the-art production test rigs developed in house. Every product is inspected in detail. The results
speak for themselves as our products are durable, highly precise, and versatile. With testcertifi-
cate.
Reliable
Total reliability doesn't stop at the products we offer. Our production lines, testing p­ rocedure,
and research program are also characterized by painstakingly high levels of detail and accuracy.
Ongoing product advancement and development activities testify to our commitment to listen-
ing to what customers want and delivering the innovative solutions they need. Nothing less is


expected of us, since we are the centre of excellence regarding sensor technology within the MR.
Networked
Focus on the customer – We have established an efficient sales and service network to ensure These products are also These products are ideal
that we always stay close to our customers. We pride ourselves in offering t­ horough analyses, available in an offshore for retrofit solutions.
individual consulting, and first-class support. This, in turn, allows us to devise exactly the solu- configuration.
tion a customer needs.

2 3
MESSKO® TRASY2 MESSKO® COMPACT
Modular temperature measuring system with a wide variety Temperature measuring system for direct display and remote
of matching accessories transmission without additional equipment
Matching accessories Matching accessories
The MESSKO TRASY2 temperature mea-
®
The MESSKO® COMPACT line of thermo­
suring system is specially designed for meters is specially designed for measuring
measuring oil and winding temperatures MOUNTING WELL oil and winding temperatures (thermal
For measuring oil FOOT STEP PROTECTION
(thermal image) in medium and large-sized image) in medium and large-sized distribu-
­temperature
distribution transformers, power trans- tion transformers, power transformers,
formers, reactors, and similar applications. reactors, and similar applications.
The indicator thermometer comprises a The temperature sensor of the indicator
temperature sensor that connects to a COMBI WELL thermometer connects to the measure-
measurement unit (Bourdon spring) via a For measuring oil TT30 SIGNAL CONVERTER ment unit (Bourdon spring) via a capillary
­temperature
capillary tube. tube.

ZT-F2.1
TEMPERATURE COMPACT MT-ST160SK
IgT-MU
TRASY2 MT-ST160F TRANSMITTER Indicator thermometer for measuring
MEASURING TRANSDUCER
Indicator thermometer for measuring For measuring winding oil temperature, with direct display
oil temperature, with direct display temperature and protective stainless steel tube

Advantages Pt-MU EI100/160 Advantages


MEASURING TRANSDUCER ELECTRONIC INDICATOR
II Bourdon tube measuring system with no II Automatic compensation for ambient II Bourdon tube measuring system with no II Temperature sensor compatible with all
additional mechanical parts temperature additional mechanical parts common thermometer pockets and wells
II Extremely durable and reliable II Laminated safety glass with built-in II Extremely durable and reliable II Quick and easy configuration of gradi-
II No readjustment or recalibration ever UV filter II No readjustment or recalibration ever ents via potentiometer (thermal image of
D1272AT
needed II Installation in thermometer pockets as needed winding temperature)
EI100/160 DIGITAL INDICATOR
II Reliable operation, even when subjected per EN 50216-4 (previously DIN 42554) II Closed system with pressure cell to pro- II Laminated safety glass with built-in
ELECTRONIC INDICATOR For digital remote
to vibrations and extreme outdoor condi- possible tect against external influences such as UV filter
­indication
tions dust and humidity
II Quick and easy configuration of II Reliable operation, even when subjected to
gradients via DIP switches in the ZT-F2.1 vibrations and extreme outdoor conditions
D1272AT PQ96/PQ144
(thermal image of winding temperature)
DIGITAL INDICATOR MOVING COIL METER
For digital remote For analog remote
­indication ­indication Variants and options
Variants and options II Oil temperature measurement: –20 to +140 °C or 0 to +160 °C
II Oil temperature measurement: –20 to +140 °C II Winding temperature measurement: 0 to +160 °C or 0 to +180 °C
PQ96/PQ144
II Winding temperature measurement (thermal image): 0 to +160 °C II 2, 4, 5, or 6 micro-switches
MOVING COIL METER
II 2, 4, 5, or 6 micro-switches SNT36 POWER SUPPLY II With temperature transmitter (analog output 4–20 mA) for remote transmission of
For analog remote
II Two redundant measurement points in conjunction with combi well or ZT-F2.1 winding measured values
­indication
temperature transmitter II With IEC- or ANSI-compliant design
II Offshore configuration II Offshore configuration
II Protective tube made from PVC or V4A stainless steel II Protective tube made from PVC or V4A stainless steel

PSLC242 POWER SUPPLY PSLC242 POWER SUPPLY


Sample configurations Sample configurations

MULTI-BALLAST MULTI-BALLAST
TRANSFORMER TRANSFORMER
Thermometer

Thermometer
TRASY2 MT-STW160F2
for measuring winding tempera- COMPACT MT-ST160WR COMPACT MT-ST160RM COMPACT MT-ST160SK/TT
tures (thermal image), with direct for measuring winding tem- for measuring oil temperature, for measuring oil temperature,
display peratures, with direct display and with direct display and with with temperature transmitter
stainless steel protective tube IEC- or ANSI-compliant design (analog output)

Additional information Additional information


www.reinhausen.com/messko-trasy2 www.reinhausen.com/messko-compact

4 5
MESSKO® BeTech MESSKO® SMART-VT, MESSKO® SMART-IN
Thermometer with bellow type technology Thermometer for distribution transformers and industrial applications

MESSKO® BeTech thermometers are MESSKO® SMART-VT thermometers are


designed for measuring oil and winding used for taking temperature measurements
temperatures (thermal image) in power at distribution transformers.
transformers.
Matching accessories MESSKO® SMART-IN thermometers were
The thermometers comprise a temperature developed for industrial applications
sensor that connects to the expansion involving pumps, turbines, generators,
bellows via a capillary tube for displaying compressors, electroplating equipment,
measurements and a separate expansion Pt-MU and die-casting machines.
bellows that compensates for ambient MEASURING TRANSDUCER
temperature.

D1272AT
SMART-VT KLKA-F80 E
DIGITAL INDICATOR
MESSKO® BeTech Indicator thermometer without micro-switch,
For digital remote
Pointer thermometer for measuring the oil tempera- with bracket for wall mount attachment
­indication
ture, with direct display, with protective tube made
from V4A stainless steel

Advantages
SNT36 POWER SUPPLY II Bourdon tube measuring system with no II Temperature sensor compatible with all
Advantages additional mechanical parts common thermometer pockets and wells
II Expansion bellows technology II Hysteresis selectable II Extremely durable and reliable II For taking temperature measurements in
II Extremely durable and reliable II Compensation for ambient temperature II No readjustment or recalibration ever a variety of process media, including oils,
II No readjustment or recalibration ever II Laminated safety glass with built-in needed coolants, and water
needed UV filter
II Multiple gradients PSLC242 POWER SUPPLY
II Contacts individually adjustable
Variants and options
II Housing diameter 60, 80, or 100 mm
II With fixed temperature sensor or flexible capillary tube
Variants and options II Snap-on or clamping bracket attachment in control cabinet or wall mount attachment
MULTI-BALLAST
II Measuring range: 0 to +150 °C, –20 to +130 °C, 0 to +160 °C, or –40 to +160 °C II Switchless or with up to 4 micro-switches
TRANSFORMER
II Measuring accuracy: ±3 °C (+30 to +150 °C), ±2 °C, or ±1.5 °C (optional) II Temperature range –40 °C to +400 °C, special designs available on request
II 2, 3, 4, or 5 micro-switches II Variable sensor length (min. 50 mm), special design available on request
II Laminated safety glass with built-in UV filter
II Degree of protection as per EN 60529: IP 55 or IP 65 (optional)
II Analog output: 4–20 mA, 0–5 V DC, Pt100, or 4–20 mA and 0-5 V DC
Sample configurations
II Magnetic blow out (MBO)
II Micro-switches: Single-pole or double-pole changeover switches, magnetic blow out
Combinable products
(MBO), or single-pole changeover switches with gold-plated contacts
II Threaded sensor connection: G 3/4", G 1", 7/8" - 14 UNF
II Offshore configuration
MESSKO® MZT1650S
Calibration bath
Sample configurations Page 18

MESSKO® MCTA-5
CT current simulator
Thermometer

Thermometer
Page 18
SMART-VT MTG-F80 E SMART-IN MTS 80 SMART-IN MTW 60
Indicator thermometer Indicator thermometer with Indicator thermometer without
with micro-switches capillary tube for flush panel capillary tube for horizontal
MESSKO® BeTech mounting mounting
Pointer thermometer for measu-
ring the winding temperature
(thermal image), with direct
display and protective tube made
from V4A stainless steel Additional information
Additional information
www.reinhausen.com/messko-smartVT
www.reinhausen.com/messko-betech
www.reinhausen.com/messko-smartIN
6 7
MESSKO® MTO MESSKO® MMK
Oil level indicator for transformers Oil level indicator with magnetic flaps for transformers

MESSKO® MTO oil level indicators indicate The oil level indicator MESSKO® MMK with
the oil level in the transformer oil conser- magnetic flaps allows the fill level to be
vator. displayed without having to position a
float in the reservoir and uses existing
Separating the sensor from the display unit
connections.
prevents any possibility of the oil escaping
from the oil conservator. This makes the device a suitable replace-
ment for an oil level indicator with a glass
The oil level is permanently monitored and
tube.
operation errors (improper filling of the
transformer in particular) are avoided. Matching accessories

EI100
MTO-STF ELECTRONIC INDICATOR
Oil level indicator with direct display with bracket

Advantages EI100
II Extremely durable and reliable II Laminated safety glass with built-in ELECTRONIC INDICATOR
II No readjustment or recalibration ever UV filter with clamping bracket
needed II With additional EI100/160 indicator for
II 160 mm version suitable for distribution good legibility at eye level, even in ap-
and power transformers plications involving larger transformers
EI100/160
ELECTRONIC INDICATOR
Variants and options Matching accessories
II Radial or axial design with different floats to adapt to different tank geometries MESSKO® MMK
II Switchless or with up to 3 fixed switches or 2 variable switches that can be freely Oil level indicator with magnetic flaps
adjusted over the scale range EI100
II Individual scales possible ELECTRONIC INDICATOR LIMIT SWITCH
II Horizontal or angled installation position (inclination angles of 15, 30, and 45 degrees) with bracket
II IEC- or ANSI-compliant design
Advantages
II Integrated signal converter for remote transmission of measured values (TT model) II No external power supply required II Limit switch and equipment for remote
II Analog output 0–1 mA, 0–20 mA, or 4–20 mA II Indicator rail made from impact-resistant transmission of measured values can be
II RS-485 interface EI100 and torsionally rigid Makrolon, weather- retrofitted
II Offshore configuration ELECTRONIC INDICATOR REMOTE INDICATOR proof and clear as glass for many years II Fill level is easy to read, including when
with clamping bracket II Easy replacement of indicator rail (oil viewed from the side or below
conservator does not need to be drained)
Sample configurations

EI100/160 Variants and options


ELECTRONIC INDICATOR
II Switchless or with limit value switch
Complementary products
II Integrated signal converter for remote transmission of measured values
II Analog output 4–20 mA
II RS-485 interface
MESSKO® MTO
Oil level indicator

Oil level indicator


SNT36 POWER SUPPLY Oil level indicator
Page 8

MTO-STF/TT MTO-STF RM
with integrated signal c­ onverter with IEC- or ANSI-compliant
for remote transmission of design
­measured values

Additional information Additional information


www.reinhausen.com/messko-mto www.reinhausen.com/messko-mmk

8 9
MESSKO® MPreC® MESSKO® MTraB®
Pressure relief device for protecting transformers and tap changers Maintenance-free dehydrating breather with self-regulating heating
element for regenerating the desiccant

MESSKO® MPreC® pressure relief devices The maintenance-free MESSKO® MTraB®


protect medium and large-sized distribu- dehydrating breather is used in oil-insula­
tion transformers, power transformers, and ted transformers, reactors or tap changers
tap changers during periods of increased to dry the air which is suctioned in by the
oil system pressure. oil conservator.
When the permissible tripping pressure of Incoming air is directed toward the desic-
the valve is exceeded, the valve opens – all cant (silica gel) and dried.
within milli­seconds.
The desiccant is regenerated/dehumidified
As soon as the value drops below this pres- by an installed heating element that is
MPreC® LMPRD sure, the valve closes again and forms an sensor-controlled and self-regulating.
Pressure relief device with standard cover, impermeable seal.
terminal box, and semaphore

MTraB® DB100(HT)
For transformers in rated power classes ≤40 MVA,
Advantages with α or β control
II Opens in 2 ms; closes within 70 ms II Reliable foot step protection
II Valve stroke of approx. 4 mm up to II Computer-controlled (trip) tests, includ-
forced activation of switching contacts ing plant certificate for every valve
II Aluminum signal pin with two notches II Helium leak detection tests
Advantages
to prevent fallback of a pin that has not II Clear signal indication, no false tripping II No routine, expensive replacement and II Sensor-controlled heating apparatus
fully extended or wear-related faults no environmental impact as a result of II All measured values queried via
II Protection for micro-switches and II Easy to exchange used desiccant RS-485 interface
springs via protective cover made from II Use of glass cylinders to optimize the II Intelligent data recording
marine-grade aluminum regeneration process and for excellent II Self-monitoring of system with output of
II CDP-coated springs as per DIN 2095 weather resistance operational condition
(cathodic corrosion protection) and ad- Matching accessories II Easy retrofitting thanks to a variety of II Full protection against external influ-
ditional, internal seals flange solutions ences

FLANGE WITH INTERNAL


Variants and options THREAD Variants and options
for MESSKO® MPreC®
II Triggering pressure of 4–30 psi (0.28–2.07 bar) II Optional α, β, or γ control for transformers in different rated power classes
LMPRD OD Matching accessories
II With cable connection inclusive cable gland, terminal box, ANSI or II Supply voltage of 230 V AC/DC or 120 V AC/DC
Westinghouse connector II Additional overvoltage protection
II Up to two micro-switches II Cable connection M20 x 1.5 or 1/2" (14 NPT)
II Seals made from Perbunan or Viton WELDING FLANGE II Analog output 0–1 mA, 0–20 mA, or 4–20 mA
II Cover for defined oil drainage for MESSKO® MPreC® II DIN flange, RM flange, or flange for 1/2" bolts
MTraB® DATA LOGGER
II Semaphore LMPRD OD II Offshore configuration
For recording the func-
II Offshore configuration II Test button for initiating the device self test and verifying functionality
tional operating sequence
II Additional filter heating for ambient temperatures permanently below –5 °C over a
over time
period of 20 days (HT version)
Sample configurations II Lateral mounting
II Protection of electrical cables from damage such as animal bite
Combinable products CABLE PROTECTION
(optional) Sample configurations

Dehydrating breather
MESSKO® MPreC®
Pressure relief device

TEST BENCH
Page 19
PROTECTIVE GRILLE
(optional)
MPreC® LMPRD OD
with terminal box and cover
for defined oil drainage

MTraB® DB200T MTraB® DB200D-T MTraB® DB200 G


for transformers in rated power twin design, for transformers in with γ control for oven and
classes >40 to ≤200 MVA, rated power classes >200 MVA, cavern transformers as well as
Additional information Additional information β control β control and filter heating GSU machine transformers
www.reinhausen.com/messko-mprec www.reinhausen.com/messko-mtrab

10 11
MESSKO® MFloC® MESSKO® MLog®
Flow monitor for the oil-water-cooling circuit of transformers Transport monitoring: Measuring, saving, and transmitting
transport conditions worldwide

The MESSKO® MFloC® flow indicator MESSKO® MLog® reliably monitors the
­monitors the flow of coolant through the transport and condition of goods of all
oil-water-cooling circuit of transformers. types.
It reliably detects and reports a pump
failure as soon as it occurs.

MLog® IM100 Premium Control

MFloC ® MFl100-O
For insulating oil with DN100 flange and terminal
Advantages
box with terminal strip II Saves and displays acceleration/shock II No hazardous goods labeling required
forces (X, Y, and Z-axes), ambient tem- II Resistant to UV rays, sea water, and oil
perature, and humidity II Resistant to water spray and dust as per
II Temperature measurement from –40 IP 65, no additional protective housing
Advantages to +125 °C required
II Specially formed, spoon-shaped paddle II Suitable for all common pipe diameters II Humidity measurement from 0 to II Intuitive user interface and PC software
II To increase the reliability in laminar as and flow directions 100 % RH II USB port
Matching accessories
well as non-laminar (turbulent) flows II Easy assembly II Storage capacity of up to one year and II Manipulation-proof data format
II Operational from –50 to +80 °C II Convenient adaptation for different flow efficient power supply with commercially II Calibration and update service
II For cooling media from –30 to +120 °C directions with swiveling display part available batteries
II Laminated safety glass with built-in II Easy to exchange
MLOG ANALYSER
UV filter
SOFTWARE
II Guaranteed leaktight connection to the
coolant circuit thanks to separation of
Variants and options
the transmitter and display parts II LCD display, black/white
II Global positioning via GPS
II GSM module to send status and alarm messages via SMS (worldwide)
MOUNTING PLATE II Bluetooth interface for wireless data transmission
Variants and options II 2 digital inputs: <0.8 V, >2.4 V
II For mineral-based insulating oil as per IEC 60296, alternative insulating oil or water II 2, 4, or 6 universal inputs (0–5 V DC)
II With standard flange (DN100–DN300) or retrofit flange
II Terminal box with terminal strip, ANSI or MIL connector
II Different housing colors and dials
Sample configurations
II Offshore configuration ASSEMBLY KIT

Sample configurations

LR14 BATTERIES
MLog® IM50 Basic Control MLog® IM100 Premium Control
Complementary products
with GPS positioning and with display, 2 digital and up to
temperature, humidity, and 6 universal inputs, Bluetooth
acceleration measurement interface, and GSM module
MESSKO® MSafe

Transport monitoring
Buchholz relay USB CABLE
Flow indicator

Page 16

MFloC ® MFl100-W MFloC ® MFl100-O MR


for water with flange DN100 and with IEC- or ANSI-compliant
terminal box with terminal strip design

Additional information Additional information


www.reinhausen.com/messko-mfloc www.reinhausen.com/messko-mlog

12 13
MESSKO® MTeC® EPT303 MESSKO® MTeC® EPT303 FO
Forward-looking temperature management system for Pinpoint temperature management with fiber optic technology
transformers
The MESSKO® MTeC® EPT303 FO combines
The modularly expandable, digital control the advantages of the base module from
unit MESSKO® MTeC® EPT303 impresses the MTeC® EPT303 series with state-of-
with highly intelligent solutions in the the-art fiber optic temperature measure-
areas of safety, functionality and user- ment technology. As the measurements
friendliness: from the modern design of the can be taken directly in the windings,
user interface and the optional MESSKO® MTeC® EPT303 FO using fiber Bragg grating temperature management is always based
MControl® with touch display to compli- technology on highly precise hot spot temperature
MTeC® EPT303 - the dawning of a new age in ance with all conventional communication values.
transformer temperature management standards.
Advantages
II Fiber optic measurement using fiber II Up to 32 MSpot® sensors can be used
Bragg grating technology II Stainless steel flange suitable for use
II Multiple measuring head with 3 mea- offshore
surement points per MSpot® sensor II Extremely stable connecting lead made
II Sensors do not suffer from the effects of up of 8 fiber optic cables in one armor
aging
Advantages
II Simple parameterization, intuitive user to twice) and the load measurement in
Variants and options
guidance and individual configuration up to 3 phases II Variants and options available as for the MTeC® EPT303 (see page 14)
of the user interface thanks to a modern II Measurement of the ambient tempera- II Please note: Upgrading and retrofitting not possible
design and operating concept ture and oil level
II User interface in 8 languages guarantees II 2 additional, freely selectable
safe use worldwide temperature differences
II Minimum risk of setting incorrect pa-
rameters due to a 3-level role concept
II Activation of up to 7 freely
configurable cooling stages MESSKO® MTeC® EPT202
and the simulation mode II Optional load-dependent or periodic
II Freely configurable alarm levels, triggers activation, or intermittent cooling group Robust solution for intelligent cooling control
and warning instructions change adjustable
II No software installation for II All conventional communications stan- The MESSKO® MTeC® EPT202 is a cooling
customers thanks to the unit's built-in dards come standard: DNP3, IEC 60870, control system that is both rugged and
operating system and the ability to call IEC 61850, Modbus cost-effective. It includes all necessary
up the application in any conventional II Calculation and display of
functions for independently protect-
web browser estimated remaining service life
II Precise determination of the winding ing and extending the service life of the
temperature thanks to measurement of transformer for years to come. Both the
the top oil temperature (carried out up top oil temperature and load current are
Matching accessories Matching accessories measured. The hot spot temperature and
the estimated remaining service life of the
MTeC ® EPT202 for DIN rail mounting transformer are calculated using these two
Variants and options values.
Pt100 TEMPERATURE
II Visualization and operation on one user interface thanks to optional MESSKO® MControl®
SENSOR
MESSKO® MControl® 7-inch color touch display Page 23
II Maximum measuring accuracy as the MSpot® sensors and combinable FO module
Page 20 Advantages
make it possible to take measurements directly in the windings using fiber optics (see II Measurement/display of oil temperature dent cooling stage activation
Monitoring and analysis systems

Monitoring and analysis systems


MESSKO® MTeC® EPT303 FO on page 15) II Winding and ambient temperature II Parameterization of individual cooling
II Flexibility in terms placement for integration into existing control cabinets thanks to display stages possible
modular design II Remaining service life calculation in ac- II Load cycle mode for uniform fan load
II Available as a standalone product or integrated into a customized cordance with the IEC and ANSI standard II Information on the status, alarm and
Compatible products Compatible products
control cabinet solution II Internal data storage for up to 32,000 trip visible on the device LEDs
II Option for upgrading and retrofitting data records II Analog outputs for remote transmission
II Cooling-type dependent and load-depen- of measurement values
MESSKO®
MESSKO MTO
®
control cabinet systems
Page 24
oil level indicator Variants and options
Page 8
II DIN rail mounting, control panel mounting or installation in 19-inch plug-in housing
Matching accessories II Supply voltage of 100 to 240 V AC with 50 to 400 Hz or 100 to 353 V DC
II Input range of temperature sensor and analog output for oil temperature
selectable from -20 to +160 °C
Additional information Additional
Additional information
information II Analog output for winding temperature 0 to +180 °C
www.reinhausen.com/messko-mtec www.reinhausen.com/messko-mtec
www.messko.de II Option for upgrading and retrofitting
14 15
MESSKO® MSafe® MESSKO® MSense®
Buchholz relay for protecting power transformers and reactors Oil analysis sensor of persistent quality

The MESSKO® MSafe® Buchholz relay is With hydrogen, carbon monoxide, and
used as a central protective device for moisture in the insulating oil of power
fluid-filled transformers and reactors transformers, the MESSKO® MSense®
with an oil conservator. product family monitors the primary
It triggers in the case of gas accumulation, early indicators of possible damage in the
abrupt increase of the flow rate, as well as transformer with thermal or electrical
the loss of oil. As a result potential dam- causes.
ages to the transformer are avoided early. Continual functional safety and reliable
measurements are ensured by components
MSafe® MBR25 which are just as robust as they are tech-
With nominal flange diameter DN25, 4-hole nically refined and by the new 2-stage
measurement procedure directly in the
MESSKO® MSense®
oil flow.
with ball valve for installation directly
Advantages on the transformer tank or piping False alarms, downtimes, and results
II High quality materials provide long II Additional functional safety provided by to the cooling system distorted by environmental influences
service life solid floats are therefore a thing of the past.
II Helium leak test for oil and gas tightness II Two main switching contacts (NO con-
II Avoids false tripping via dry-reed mag- tact, NC contact, or changeover contact)
netic switch II Test line connection/remote verification
Advantages
II Switches can be replaced without having II Long-term functional safety thanks to II Needs-based parameterization using the
to access the oil circuit capillary gas extraction unit, stainless MESSKO® MSeT® software provided
steel pipe to protect the measuring tech- II Manual sampling directly at the point of
nology, and robust housing measurement using integrated Luer lock
II High-precision measurements thanks to connection
Variants and options semiconductor sensors, capacitive mois- II Two free DGA and moisture analyses in
II DN25, DN50, or DN80 connecting flange ture sensor, inert measurement chamber, the MESSKO lab included
II Two or four switching contacts (NO contact, NC contact, or changeover contact) 2-stage measurement procedure directly II Installation options for all common
II Response speed of flap valve 0.65 m/s to 3 m/s in the oil flow equipment scenarios: Initial fitting and
II Mineral-based insulating oil as per IEC 60296 or alternative insulating oil II Interfaces to all common SCADA systems retrofitting
II M25 or NPT 1/2" threaded cable glands for continuous remote monitoring II Rapid on-site assistance from global,
II Offshore configuration II The internal memory makes available for quality-certified service network
II Inspection glass cover long-term analyses all measurements
II Manual reset for function test from up to 4 years in the past
II Remote verification of operational readiness via a compressed-air line (optional)
Variants and options
Sample configurations II Monitoring of the most important early indicators:
Matching accessories x1.5 - Hydrogen and moisture
x2.5 - Hydrogen, Carbon monoxide and moisture
II Integrated display on housing
II Installation with flange screw connection for direct inlet
or using oil loop for retrofitting (optional)
GAS SAMPLER II Offshore version
II Optional: MESSKO® MSense® protocol converter - converting data from Modbus RTU to
the following protocols: DNP 3.0, Modbus TCP, and IEC 61850-8-1 MMS
Monitoring and analysis systems

Monitoring and analysis systems


MSafe® MBR80 II Housing color RAL 7033 or RAL 7038
with nominal flange diameter
DN80, 4-hole GAS QUICK TEST Complementary products
For verifying
Sample configurations
H2 and CO levels
MESSKO® PrimeLab®
Gas-in-oil analysis for
transformers and tap
changers
Page 25

Additional information Additional information MESSKO® MSense®


www.reinhausen.com/messko-msafe www.reinhausen.com/messko-msense without display

16 17
MESSKO® MCTA-5 MESSKO® MPreC® TEST BENCH
CT current simulator for verifying and setting CT current-operated Mobile test bench for pressure relief devices
temperature measurements at transformers
Combinable products
The MESSKO MCTA-5 CT current simulator
®
The MESSKO® MPreC® test bench tests and
is used in testing facilities for commission- MESSKO® TRASY2 logs the accuracy and functionality of new
ing or maintenance work. Using this device Temperature measuring and used pressure relief devices.
CT currents are simulated at the switched system Commissioning, maintaining, and ser­vicing
off transformer to verify and adjust mea- Page 4 these devices become much easier as a
result.
suring instruments via the created thermal
image.
MESSKO® COMPACT
Temperature measuring
MESSKO® MCTA-5
system
CT current simulator
Page 5

Advantages MESSKO® BeTech


II Mobile application II Alternating current adjustable via a Thermometer
II Constant alternating current c­ ontrol button, display window for Page 6 MPreC® test bench
(adjustable from 0 to 5 A) up to 40 VA ­displaying information with installed pressure relief device
load
II Housing with built-in handle
ZT-F2.1
TEMPERATURE Advantages
­TRANSMITTER
II For use in a laboratory or testing facility, II Pressure ranges and number of test
Page 20
or for commissioning or maintenance cycles individually selectable
work II Intuitive MESSKO® MPreC® test bench
II V4A stainless steel and IP 65 control unit software in English and Chinese for
for applications involving extreme ambi- ­reliable evaluation, processing, and
ent conditions administration of data
II Measuring range 4 psi to 30 psi II Graphic display, saving and printing of
II Ambient conditions –10 to +50 °C test results
MESSKO® MZT1650S II Straightforward commissioning and easy
and safe operation
Calibration bath for checking temperature sensors
Combinable products
The MESSKO® MZT1650S is a highly precise
calibration bath for checking and verifying
temperature sensors at the transformer or MESSKO® TRASY2
in the laboratory. Temperature measuring
system
Page 4

MESSKO® COMPACT
Temperature measuring
MPreC® test bench
system
with fitted cover hood
Page 5 Combinable products
Testing, measuring, and service systems

Testing, measuring, and service systems


MESSKO® MZT1650S
Calibration bath MESSKO® BeTech MESSKO® MPreC®
thermometer Pressure relief device
Page 6 Page 10

Advantages
II Compact, mobile unit for carrying out II Easy to operate thanks to an intuitive
on-site checks user interface
II Lightweight and easy to transport in the II Sample holder in integrated liquid bath
service and transport case
II Programmable temperature profile

Additional information Additional information


www.reinhausen.com/messko www.reinhausen.com/messko

18 19
TEMPERATURE MEASUREMENT Suitable for

Suitable for IgT-MU II Used to convert and separate direct current or direct voltage MESSKO® COMPACT
MEASURING TRANSDUCER into a load-independent direct current and direct voltage signal Temperature measuring system
Page 5
ZT-F2.1 II Core component of the MESSKO TRASY2 temperature measuring
®
MESSKO TRASY2
®

TEMPERATURE TRANSMITTER system Temperature measuring system


II Variety of functions, depending on the connection Page 4

MTraB® DATA LOGGER II For recording the functional operating sequence of the dehydrating MESSKO® MTraB®
breather over time to determine the air circulation of the trans- Maintenance-free dehydrating
former and/or tap changer breather
MOUNTING WELL II Mounting well for placing the oil thermometer in the thermometer MESSKO® TRASY2 II Data readouts via mobile computer Page 11
pocket as per DIN 42 554 Temperature measuring system II Easy evaluation of data using supplied software for optimizing the
II With leadthrough to immersion tube for the temperature sensor of Page 4 operational readiness and service life of the transformer
the indicator thermometer

COMBI WELL II Mounting well for placing the oil thermometer in the thermometer PQ96/PQ144
pocket as per DIN 42 554 Moving coil meter
II With leadthrough to immersion tube for the temperature sensor of Page 22
the indicator thermometer
II Integrated Pt100 laboratory resistor as per DIN 43 760 facilitates MEASURED VALUE DISPLAYS
remote transmission of measured values
Suitable for
Pt100 TEMPERATURE SENSOR PQ96/PQ144
Moving coil meter EI100/160 II Analog pointer instrument with digital LCD display MESSKO® TRASY2
Page 22 ELECTRONIC INDICATOR II For installation in a control cabinet or directly on the transformer Temperature measuring system
MESSKO® MTeC® EPT202 II Displays the temperature or a percentage output of any sensor Page 4
Thermometer with intelligent II Input signal 4–20 mA, supply voltage 24 V DC MESSKO® COMPACT
fan control II Can be used in conjunction with the TT30 signal converter Temperature measuring system
Page 15 Page 5
MESSKO® MTO
Oil level indicator
Page 8

EI100 ELECTRONIC INDICATOR II Analog pointer instrument with digital LCD display MESSKO® MTO
WITH BRACKET II For installation in a control cabinet using a bracket Oil level indicator

REMOTE TRANSMISSION AND PROCESSING


II Displays the temperature or a percentage output of any sensor Page 8
II Input signal 4–20 mA, supply voltage 24 V DC MESSKO® MMK

OF MEASURED VALUES
II Can be used in conjunction with the TT30 signal converter Oil level indicator
Page 9

Suitable for EI100 ELECTRONIC INDICATOR II Analog pointer instrument with digital LCD display MESSKO® MTO
WITH CLAMPING BRACKET II For installation in a control cabinet using a clamping bracket Oil level indicator
TT30 SIGNAL CONVERTER II For converting a variety of sensor signals into process signals MESSKO® TRASY2 II Displays the temperature or a percentage output of any sensor Page 8
II Adaptable, on the input side, to different mechanical and electrical Temperature measuring system II Input signal 4–20 mA, supply voltage 24 V DC
sensors Page 4 II Can be used in conjunction with the TT30 signal converter
II Maximum safety and functionality at the transformer when com- MESSKO® COMPACT
bined with mechanical base units Temperature measuring system D1272AT DIGITAL INDICATOR II Remote digital indicator of oil or winding temperature MESSKO® TRASY2
II Connects to control room systems for process monitoring while Page 5 II Connects to the analog output (Pt100 or 4–20 mA) of the Temperature measuring system
safety-relevant mechanical switching functions are maintained combi well or to the ZT-F2.1 temperature transmitter Page 4
II Current bus technology
II Two freely adjustable limit contacts and different output signals MESSKO® COMPACT
(4–20 mA, 0–5 V, 0–10 V) for further signal processing optionally Temperature measuring system
Pt-MU II Converts the signal of a Pt100 temperature sensor into a MESSKO® TRASY2
available Page 5
MEASURING TRANSDUCER standardized signal proportional to the temperature Temperature measuring system
MESSKO® BeTech
II Connects to the Pt100 connectors in the ZT-F2.1 transformer Page 4
Thermometer
temperature transmitter or to the combi well, for example MESSKO® BeTech
Page 6
II Conditions the output signals of these devices for further Thermometer
Accessories

Accessories
processing via a computer or for electric/electronic display Page 6
II For transferring measured values across large distances or distur- PQ96/PQ144
bance fields Moving coil meter
Page 22

Additional information Additional information


www.reinhausen.com/messko www.reinhausen.com/messko

20 21
Suitable for
PROTECTIVE DEVICES
PQ96/PQ144 II Remote analog indication of oil or winding temperature MESSKO TRASY2
®
Suitable for
MOVING COIL METER II Connects to the analog output (Pt100 or 4–20 mA) of the Temperature measuring system
combi well or to the ZT-F2.1 temperature transmitter Page 4
PROTECTIVE GRILLE II Constructed from V4A stainless steel MESSKO® MTraB®
MESSKO® COMPACT
Maintenance-free dehydrating
Temperature measuring system
breather
Page 5
Page 11

INSECT GRILLE II Constructed from V4A stainless steel MESSKO® MTraB®


For stainless steel filter Maintenance-free dehydrating
breather
Page 11

POWER SUPPLY
FOOT STEP PROTECTION II Constructed from galvanized steel MESSKO® TRASY2
Suitable for Temperature measuring system
Page 4
SNT36 POWER SUPPLY II Wide-range power supply unit for input voltages of 85 to 270 V AC MESSKO® TRASY2 MESSKO® COMPACT
and 110 to 400 V DC Temperature measuring system Temperature measuring system
II Output 24 V DC Page 4 Page 5
MESSKO® COMPACT
Temperature measuring system
Page 5
MESSKO® BeTech
Thermometer
Page 6
MESSKO® MTO
Oil level indicator MATCHING ACCESSORIES
Page 8
ZT-F2.1 TEMPERATURE TRANSMITTER Suitable for
Page 20
COMBI WELL MESSKO® MLOG® ANALYSER II Configure the MESSKO® MLog® transport monitor from a PC MESSKO® MLog®
Page 20 SOFTWARE II Evaluate recorded data Transport monitor
II Optional 3-level password protection Page 13
PSLC242 POWER SUPPLY II Turn-key, unregulated power supply unit MESSKO® TRASY2
II For installation on 35 mm DIN rail profile and bolting to an Temperature measuring system MOUNTING PLATE II Constructed from V4A stainless steel MESSKO® MLog®
a­ ssembly and support surface Page 4 Transport monitor
II For line voltages of 230 V AC and 115 V AC MESSKO® COMPACT Page 13
II Output with sustained short circuit-proof protection and potential- Temperature measuring system
free as per VDE 0551 Page 5 MULTI-BALLAST TX II Conversion of the CT current MESSKO® TRASY2
II Compatible with tropical environments thanks to resin encapsula- MESSKO® BeTech Multi-ballast transformer Temperature measuring system
tion Thermometer Page 4
Page 6 MESSKO® COMPACT
MESSKO® MTO Temperature measuring system
Oil level indicator Page 5
Page 8 MESSKO® BeTech
Thermometer
Page 6

MControl® II Configure and visualize parameters on site without MESSKO® MTeC EPT303
any service computer Digital temperature
II Full visualization convenience regardless of the degree management system
of expansion Page 14
Accessories

Accessories
Additional information Additional information
www.reinhausen.com/messko www.reinhausen.com/messko

22 23
MESSKO® CONTROL CABINET SYSTEMS MESSKO® PrimeLab®
Customized control cabinet solutions for special customer requirements Gas-in-oil analysis for transformers and tap changers

MESSKO develops application and PrimeLab® gas-in-oil analysis from MESSKO


customer-specific control cabinets and is a safe, reliable, and proven method for
control cabinet systems to meet individual assessing the internal status of transform-
requirements and configurations. ers and oil-filled electrical equipment.
To this end, special attention is paid to
ensuring that all modules and components
are arranged in a maintenance-friendly
and ergonomic fashion as soon as initial
design work for the control cabinet begins.
PrimeLab® sampling kit

Advantages
II Complete sampling kit with sampling II Efficient, early error detection
guide II Malfunctions and downtime are avoided
II Easy and clean sample taking II Comprehensive test reports and graphi-
II Analysis in modern MESSKO oil labora- cal formatting of the data
tory II Derivation of economically sensible
II Information provided about the status courses of action, maintenance schedules
of transformers, tap changers, and other (oil conditioning), and counter-measures
Individual control cabinet solutions – equipment (cooling)
the full-service package from MESSKO® II Verification of the measuring accuracy of
multi-gas sensors in monitoring systems

Advantages
II Customer-specific solutions – from plan- II Ongoing compliance with current stan-
Range of tests available for oil sample provided
ning through to production dards and guidelines II Concentration of fault gases dissolved in oil (DGA) as per IEC 60567
II Production based on electrical wiring II High-quality, reliable materials (H2, CO, CO2, O2, N2, CH4, C2H6, C2H4, C2H2, C3H8, C3H6)
diagrams drafted in house or by the II Operation possible even under extreme II Moisture analysis (water concentration in insulating oil) as per IEC 60814
customer ambient conditions II Disruptive discharge voltage (min. 30 kV) as per DIN EN 60156
II Maintenance-friendly and logically II Single contact appointed to offer profes- II Dielectric loss (tan δ) as per IEC 60247
organized arrangement of modules and sional assistance throughout the entire II Permittivity (dielectric number) as per IEC 60247
components project II Specific electrical DC resistance as per IEC 60247
II Easy to upgrade and expand, and II Comprehensive functional test prior to II Electrical conductivity
lightweight construction thanks to the delivery II Total solid matter count as per DIN IEC 60422, appendix C
modular system II Wear metal content (Fe, Cr, Sn, Al, Ni, Cu, Pb, Mo)
II Additive content (Ca, Mg, Zn, P, Ba, B)
II Impurity content (Si, K, Na, Li)
II Viscosity at 40 and 100 °C
II Viscosity index
II Degree of oxidation
II Appearance (visual inspection)
II Color number
II Neutralization number
II Surface tension
II Total particulate count via microscopical counting
II Flashpoint as per DIN EN ISO 2719, DIN 51758
II Pour point as per DIN ISO 3016, ASTM D97
II Furfurol/furan content as per DIN EN 61198
Services

Services
II Degree of depolymerization (DP) of paper insulation as per DIN EN 61198
II Polychlorinated biphenyl (PCB) content as per DIN EN 12766-2
II Corrosive sulfur content as per ASTM D 127
II Density at 15 °C as per DIN EN ISO 12185

Additional information Additional information


www.reinhausen.com/messko-systemsandprojects www.reinhausen.com/messko-primelab

24 25
MESSKO® –
WORLDWIDE CONNECTED
Messko GmbH
Gewerbegebiet An den Drei Hasen
Messko-Platz 1
61440 Oberursel, Germany

Phone: +49 6171 6398-0


Fax: +49 6171 6398-98
E-mail: messko-info@reinhausen.com

www.reinhausen.com/messko

Maschinenfabrik Reinhausen GmbH


Falkensteinstrasse 8
93059 Regensburg, Germany

Phone: +49 941 4090-0


Fax: +49 941 4090-7001
E-mail: info@reinhausen.com

www.reinhausen.com

Experience the
MESSKO® product world.
www.reinhausen.com/messko

Please note:
The data in our publications may differ from
the data of the devices delivered. We reserve
the right to make changes without notice.

IN2064/09/01 EN – MESSKO® Product Catalogue –


MS99085006 – 08/16 –

© Messko GmbH 2016

THE POWER BEHIND POWER.

You might also like