Industrial Electronics Laboratory Manual
Industrial Electronics Laboratory Manual
1
CONTENTS
1
SCR & DIAC CHARACTERISTICS
2
IGBT & MOSFET CHARACTERISTICS
3 AC VOLTAGE CONTROLLER USING TRIAC-DIAC
4
TEMPERATURE SENSOR
5
HUMIDITY SENSOR
6
MOTOR START/STOP CONTROL PROGRAM
7 CONTROL SYSTEM FOR MOTORS WITH EMERGENCY BACKUP
EXPERIMENT NO. 1
SCR AND DIAC CHARACTERISTICS
CHARACTERISTICS OF SCR:
AIM: To plot the characteristics of an SCR and to find the forward resistance, holding
current and latching current.
APPARATUS:
SCR & DIAC Characteristics Study unit.
THEORY:
A Silicon Controlled Rectifier (SCR) is a four layer, three terminals and three junction
device, which is basically a rectifier with a control terminal called Gate. Like diode, it is also
a uni-directional device and forward conduction is from anode to cathode. Since SCR use
silicon for its construction so it is called silicon controlled rectifier. Where it operates as a
rectifier, it is mainly used as a switch.
There are three terminals namely Anode (A), Cathode (K), and Gate (G). Four layers, with
alternatively
P-type and N-type silicon semiconductors forming three junctions. If SCR is forward biased
with G=0,the Junctions J1 and J3 are forward biased and J2 is reverse biased .If +VAK is
small, leakage current flows (IFX) until +VAK is large enough to cause reverse biased
junction J2 to break down. The forward voltage at this point is called forward break over
voltage VF (BR).
If a negative voltage is applied to anode and a positive voltage is applied to cathode of the
SCR, the junction J2 is forward biased and J1 and J2 are reverse biased with very small
leakage current flow called reverse blocking current. If the reverse voltage is now increased,
J1 and J3 break down in the zener or avalanche mode and IR is not limited, hence SCR could
be damaged or destroyed. The region of the reverse characteristics before reverse breakdown
is called reverse blocking region.
CIRCUIT DIAGRAM:
I. V – I Characteristics:
Ron-State = ΔVAK/ΔIA Ω.
Tabular Column:
1) Apply about 20 V between Anode and Cathode by varying VA. Keep the
load potentiometer RL at minimum position. The device must be in the OFF state
with gate open.
2) Gradually increase Gate voltage - Vg till the device turns ON. This is the
minimum gate current ( Ig min) required to turn ON the device.
3) Adjust the gate voltage to a slightly higher. Set the load potentiometer at the
maximum resistance position. The device should comes to OFF state, otherwise
decrease VA till the device comes to OFF state.
RESULT: The values of VAK and IAK are noted down, graph is plotted and SCR forward resistance, latching
and holding currents are found.
APPARATUS:
SCR & DIAC Characteristics Study unit.
CIRCUIT DIAGRAM:
PROCEDURE:
6) At a particular value of voltage the device conducts. This can be noticed by the sudden
increase of Ammeter reading.
7) This is the device breakdown voltage, vary VL further and note down the corresponding V/I
readings in the tabular column.
Note :- If Voltage from V1 is not sufficient to turn on Diac, connect V1 and V2 supplies in
series (connect V1- to V2 +)and use V1 + as + and V2 – as – .
Tabular Column:
RESULT: The values of VAK and IAK are noted down, graph is plotted and SCR forward
resistance, Latching and Holding Currents are found.
CONCLUSION:
EXPERIMENT NO. 2
IGBT AND MOSFET CHARACTERISTICS
AIM: To plot the static characteristics of MOSFET & IGBT.
APPARATUS:
IGBT & MOSFET Characteristics Study Unit.
Characteristics of MOSFET:
THEORY:
In n-channel depletion type MOSFET with gate positive with respect to source ID, VDS and
VGS are drain current, drain source voltage and gate-source voltage. A plot of variation of ID with VDS
for a given value of VGS gives the Drain characteristics or Output characteristics. If VGS & VDS are
positive,
ID is positive for n channel MOSFET and VGS is negative for depletion mode. VGS is positive for
enhancement mode.
MOSFET can be operated in three regions
• Cut-off region,
• Saturation region (pinch-off region) and
• Linear region.
In the linear region ID varies linearly with VDS. i.e., increases with increase in VDS. Power
MOSFETs are operated in the linear region for switching actions. In saturation region ID almost
remains constant for any increase in VDS.Transfer characteristic gives the variation of ID with VGS for
a given value of VDS. ID is the drain current with shorted gate. As curve extends on both sides VGS
can be negative as well as positive.
TransConductance Characteristics:
PROCEDURE:
down ID and VGS readings for every 0.5 Volts. and enter in the tabular column.
3) The minimum gate voltage VGS which is required for conduction to start in the MOSFET
Source. If VGS is greater than VGS(Th), the Drain current depends on magnitude of the
IDEAL GRAPH :
Drain Characteristics:
PROCEDURE:
region and ID is directly proportional to VDS. If VDS is more than Vp, constant ID flows from the
device and this operating region is called constant current region.
4) Repeat the above for different values of VGS and note down ID V/S VDS 5) Draw the graph of I D
V/S VDS for different values of VGS.
IDEAL GRAPH :
Characteristics of IGBT
Theory:
An output characteristic is a plot of collector current IC versus collector to emitter voltage VCE
for given values of gate to emitter voltage VGE. A plot of collector current IC versus gate-emitter
voltage VGE for a given value of VCE gives the transfer characteristic. Figure below shows the transfer
characteristic. The Controlling parameter is the gate-emitter voltage VGE in IGBT. If VGE is less than
the threshold voltage VT then IGBT is in OFF state. If VGE is greater than the threshold voltage VT
then the IGBT is in ON state. IGBTs are used in medium power applications such as ac and dc motor
drives, power supplies and solid state relays.
Transfer Characteristics:
PROCEDURE:
4) Repeat the same for different values of Vc and draw the graph of Ic V/S VGE.
TABULAR COLUMN:
Collector Characteristics:
PROCEDURE:
1) Initially set V2 to VGE1= 5 Volts. Slowly vary V1 and not down IC and VGE. For a Particular value
of VGE1 there is a pinch off voltage ( Vp) between Collector and Emitter as Shown in figure.
2) If VGE is lower than Vp, the device works in the constant resistance region and IC is directly
proportional to VGE. If VGE is more than Vp, constant IC flows from the device and this operating
region is called constant current region.
3) Repeat the above for different values of VGE and note down IC values. 4) Draw the graph of IC V/S
VGE for different values of VGE.
TABULAR COLUMN:
RESULT: The transfer characteristics & collector characteristics are obtained and their
respective graphs are plotted and output resistance and Trans conductance are found.
CONCLUSIONS:
EXPERIMENT NO. 3
AC VOLTAGE CONTROLLER USING TRIAC-DIAC
AIM: To study the static characteristics of RC Half and Full wave firing circuit .
APPARATUS:
THEORY:
AC VOLTAGE CONTROLLERS
If a Thyristor switch is connected between AC supply and load, the power flow can be controlled by
varying the rms value of AC voltage applied to the load, and this type of power circuit is known as an
AC voltage controller. The most common application of AC voltage controller are; Industrial heating,
on- load transformer tap changing, light controls, speed control of polyphase induction motors and AC
magnet controls. For power transfer, two types of control are normally used :
1. On – Off control
2. Phase – angle control
In On – Off control, thyristor switches connect the load to the AC source for a few cycles of input
voltage and then disconnect it for another few cycles. This is trivial in nature and will not be discussed
here.
In Phase control, thyristor switches connect the load to the AC source for a portion of each type of
input voltage. This mode of control will be the subject of discussion in this section.
Since the input voltage is AC, thyristors are line commutated; and phase – control thyristors, (converter
grade thyristors), which are relatively inexpensive and slower than fast – switching thyristors, are
normally used. For applications upto 400Hz, if TRIAC’s are available to meet the voltage and current
ratings of a particular application, TRIAC’s are more commonly used.
Connection diagram:
3) Switch ON the mains supply, vary the firing angle potentiometer and observe the variation in
lamp brightness and also note down the voltage variation across the lamp.
RESULT:-AC voltage controller using TRIAC and DIAC have been rigged up and output waveforms
have been plotted.
CONCLUSIONS:
EXPERIMENT NO. 4
TEMPERATURE SENSOR
DESCRIPTION
The AD590 is an excellent sensor for temperature-to-current conversion due to its good linearity with a
transduction ratio of 1(A/((K.
The circuit of Figure 1 is the AD590 transduction circuit with two different transduction outputs, the
10mV/((K at U1 PIN6 and the 100mV/¢J at Vo15. The U1 acts as a voltage follower. The output of U1
can obtain the voltage of 10mV/((K by adjusting the R2 for R2+R3=10K).
In many applications, the Celsius scale is more convenient than absolute temperature. The relationship
of these two temperature scales is ((K =((C+273.2, and 273.2((K =0((C. In other words, if the
temperature is at 273.2((K (0((C), the output voltages at Vf1 and U1 should be 2.732V and 0V,
respectively. In order to yield the 2.732V stabilized voltage, a voltage regulator which consist of R6,
CR1, R7, R8, R9 and U3 is used.
A digital thermometer shown in Figure 2 is built with the AD590 transducer module and the 7135 A/D
converter. Since the transduction output of the AD590 transducer is 100mV/¢J, such that the full-scale
voltage of the A/D converter must be set to 20V.
PROCEDURE
B. Digital thermometer
Figure shows the functional blocks of module KL-62001. The transducer output (0 to +5VDC) applies
to inputs of the 12-bit A/D converter, and then is converted to digital signals to the PIO chip or the
single-chip microcomputer 8031 according to control signals. The PIO chip is a interface for
transmitting the digital signals to a buffer card in a personal computer. The RS-232 is a
communication-interface for communication between the single-chip 8031 and serial ports of the
personal computer. Refers to the KL-62001 USER'S MANUAL for details.
2. Using 25-pin cable, connect the RS-232 interface to any serial port of personal computer.
3. Set the AD590 Transducer Module KL-64005 on the Trainer KL-62001.
4. Repeat Steps 2 to 3 from section A.
5. Set the DIP switches to the value of 4095.
6. Turn on KL-62001.
7. Complete Table 3.
LOW and the alarm buzzer is turned on. Previous Steps are used to display the temperature
9. Connect the SINGLE CHIP & EPROM OUT CONTROL CTRL to the GND.
10. Boot the computer using the KL-62001 disk.
At A> type
CD BASIC <ENTER>
Then type
(YOURBASIC) <ENTER>
At OK type
LOAD "KLPLOTER <ENTER>
At OK type
RUN <ENTER>
(i) 1<ENTER>
(b) Change the temperature values and observe the temperature curve on the screen.
RESULTS
Table 1
Table 2
EXPERIMENT NO. 5
HUMIDITY SENSOR
DESCRIPTION
The circuit of Figure 1 is a humidity transducer circuit for this experiment. This circuit consists of four
sections:
The first section is an oscillator consisted of U5 and U6.The U6, Wein oscillator, generates a sine
wave. The U5 acts as an amplitude limiter to limit the sine wave at 250 Hz and 0.5 Vrms. The second
section serves amplification, filtering, and rectification. It consists of U4, C1, and CR2. The magnitude
of negative output is proportional to sensed humidity. The R17 is for gain adjustment and the R14 is for
zero level calibration. Figure 2 shows the characteristic of humidity sensor.
In Figure 1, we measure the output voltage of Vo16 using DMM or AD converter. Using DMM, the
voltage reading must divide by 100 mV to obtain the value of humidity. Using AD converter, the
readout represents the value of humidity. The operating range of HOS201 is from 55 to 100 %RH and a
tolerance of ©Υ3 %RH.
PROCEDURE
A. Basic measurement
1. Set the Humidity Transducer Module KL-64005 Block 16 on the Trainer KL-62001. Supply the
power.
2. Using scope, measure and record the signal at Vf2.
B. Impedance measurement
1. Connect the DMM probes to HOS201 lead wires.
1. Set the Humidity Transducer Module KL-64005 Block 16 on the Trainer KL-62001. supply the
power.
2. Connect the HUMIDITY SENSOR leads to SENSOR IN.
3. Repeat Step 2 in experiment B.
4. Complete Table 2.
5. Plot V sensor16 vs. humidity, Vu4, pin6 vs. humidity, and Vo16 vs. humidity curves.
D. Computer control
1. Complete the following connections:
CONCLUSIONS:
EXPERIMENT NO. 6
MOTOR START/STOP CONTROL PROGRAM
Theory
Introduction to PLCs
A programmable logic controller (PLC) or programmable controller is a digital computer
used for automation of electromechanical processes, such as control of machinery on factory assembly
lines, amusement rides, or lighting fixtures. PLCs are used in many industries and machines. Unlike
general purpose computers, the PLC is designed for multiple inputs and output arrangements, extended
temperature ranges, immunity to electrical noise, and resistance to vibration and impact. Programs to
control machine operation are typically stored in battery-backed or non-volatile memory. A PLC is an
example of a real time system since output results must be produced in response to input conditions
within a bounded time, otherwise unintended operation will result
The main difference from other computers is that PLCs are armored for severe conditions (such as dust,
moisture, heat, cold) and have the facility for extensive input/output (I/O) arrangements. These connect
the PLC to sensors and actuators. PLCs read limit switches, analog process variables (such as
temperature and pressure), and the positions of complex positioning systems. Some use machine vision.
On the actuator side, PLCs operate electric motors, pneumatic or hydraulic cylinders, magnetic relays,
solenoids, or analog outputs. The input/output arrangements may be built into a simple PLC, or the
PLC may have external I/O modules attached to a computer network that plugs into the PLC.
PLCs are well-adapted to a range of automation tasks. These are typically industrial processes in
manufacturing where the cost of developing and maintaining the automation system is high relative to
the total cost of the automation, and where changes to the system would be expected during its
operational life. PLCs contain input and output devices compatible with industrial pilot devices and
controls; little electrical design is required, and the design problem centers on expressing the desired
sequence of operations. PLC applications are typically highly customized systems so the cost of a
packaged PLC is low compared to the cost of a specific custom-built controller design. On the other
hand, in the case of mass-produced goods, customized control systems are economic due to the lower
cost of the components, which can be optimally chosen instead of a "generic" solution, and where the
non-recurring engineering charges are spread over thousands or millions of units.
Programmable controllers are widely used in motion control, positioning control and torque control.
Some manufacturers produce motion control units to be integrated with PLC so that G-code (involving
a CNC machine) can be used to instruct machine movements.[citation needed]
PREPARATION
1) PC (FXGPWIN Installed)
2) PC (GMWIN Installed)
RELATED KNOWLEDGE
ACTIVATION CONDITION
1) Build motor’s start circuit by using two input switches (start, stop). (Output consists of
output coil for electronic contact maker, operation lamp, and stop lamp.) Initially stop lamp
must glow.
2) If start input switch is turned on, motor gets started, and then operation lamp turns on
whereas stop lamp turns off.
3) If one turns on stop lamp during operation, motor stops, and lamp turns on, and operation
lamp turns off.
4) PLC I/O MAP is configured below.
PROGRAM PRACTICE
1) Execute the GMWIN and open the Project window and the program window. 2)
Write a program using PLC I/O MAP 3) Write ladder program as shown
below.
1) To verify what was mentioned above, one uses a simulator, which is characteristic of
GLOFA t perform an experiment to check whether there is any abnormality in the circuit
and its activation.
2) Simulator starts when one clicks the icon on Basic tool bar. When one clicks on this
icon, firstly following window opens
If one clicks OK than simulator starts and we can use inputs and outputs of simulator to monitor our
program.
LAB TASK
1) Implement the above lab in FXGPWIN and also configure the hardware.
2) Also mentioned that in what sequence the hardware is connected.
3) Also implement the above ladder with set and reset command as discussed in class (in
GMWIN).
Conclusion
EXPERIMENT NO. 7
CONTROL SYSTEM FOR MOTORS WITH EMERGENCY BACKUP
PURPOSE OF EXPERIMENT
PREPARATION
1) FXGP-WIN
RELATED KNOWLEDGE
ACTIVATION CONDITION
1) Build motor’s start/stop circuit by using four input switches (operation, stop).
2) PLC I/O MAP is configured below.
PROGRAM PRACTICE
1) Execute the FXGP-WIN and open the Project window and the program window. 2)
Write a program using PLC I/O MAP
3) Write ladder program as shown below.
Execute the program by converting and then writing to the plc. Follow the steps used in the previous
lab.
EXPERIMENT NO. 8
WATER LEVEL CONTROL SYSTEM
PURPOSE OF EXPERIMENT
PREPARATION
2) FXGP-WIN
RELATED KNOWLEDGE
ACTIVATION CONDITION
3) Build motor’s start/stop circuit by using four input switches (operation, stop).
4) PLC I/O MAP is configured below.
Inputs
Outputs
4) Execute the FXGP-WIN and open the Project window and the program window. 5)
Write a program using PLC I/O MAP
6) Write ladder program as shown below.
LADDER DIAGRAM
CONCLUSION
EXPERIMENT NO. 9
MOTORS LOAD DISTRIBUTION CONTROL SYSTEM
PURPOSE OF EXPERIMENT
PREPARATION
3) FXGP-WIN
RELATED KNOWLEDGE
ACTIVATION CONDITION
5) Build motor’s start/stop circuit by using four input switches (operation, stop).
6) PLC I/O MAP is configured below.
Inputs
Outputs
CONCLUSIONS:
EXPERIMENT NO. 10
TIMERS USING PLC
A driven coil sets internal PLC contacts (NO and NC contacts available). Various timer resolutions are
possible, from 1 to 100 msec, but availability and quantity vary from PLC to PLC.
Selectable timers taken from the main range of 100 msec timers.
Timers operate by counting clock pulses (1, 10 and 100 msec). The timer output contact is
activated when the count data reaches the value set by the constant K. The overall duration or
elapsed time, for a timers operation cycle, is calculated by multiplying the present value by the
timer resolution, i.e.
A 10 msec timer with a present value of 567 has actually been operating for:
567 10 msec
567 0.01 sec = 5.67 seconds
Timers can either be set directly by using the constant K to specify the maximum duration or
indirectly by using the data stored in a data register (ex. D). For the indirect setting, data
registers which are battery backed/ latched are usually used; this ensures no loss of data during
power down situations. If however, the voltage of the battery used to perform the battery
backed service, reduces excessively, timer malfunctions may occur.
On certain programmable controllers, driving a special auxiliary coil redefines approximately half
of the 100 msec timers as 10 msec resolution timers. The following PLC’s and timers are subject
to this type of selection.
- FX0, FX0S driving M8028 ON, timers T32 to 55 (24 points) are changed to 10 msec resolution.
- FX0N driving M8028 ON, timers T32 to 62 (31 points) are changed to 10 msec resolution.
1. Build buzzer’s start/stop circuit by using one input switch, a 1ms timer and a buzzer as an
output.
2. Execute the FXGP-WIN and open the Project window and the program window.
3. Write ladder program as shown below.
In this example, the Output Y0 will be ON for 1 sec and then OFF for 1 sec. It will be used to describe
how a PLC ladder can be produced, modified and tested. Then using a Mitsubishi FX2NPLC, the
program will be downloaded, run and monitored
The ladder diagram for the circuit and its explanation is given below.
1. Line 0
(a) On closing the input switch X0, the timer T0 will be enabled via the normally closed
contact of timer T1.
(b) Timer T0 will now start timing out, and after 1 sec, the Timer will operate. This
means:
(i) Any T0 normally open contacts -jj-, will close.
(ii) Any T0 normally closed contacts -j / j-, will open.
2. Lines 5 and 9
There are two T0 contacts, which are both normally open, therefore both of them will
close, causing the following to occur:
(a) Timer T1 will become enabled and start timing out.
(b) Output Y0 will become energized, i.e. output Y0 will turn ON.
3. Line 5
LAB ASSIGNMENT
CONCLUSIONS: