Generator set data sheet

Model: C1400 D5
Frequency: 50 Hz
Fuel type: Diesel

Spec sheet: SS16-CPGK


Sound data sheet: MSP-2040
Cooling data sheet: MCP 2072

Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 1400 (1120) 1250 (1000)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 24 41 59 77 22 38 54 69
L/hr 91 158 224 291 84 144 203 263

Engine Standby rating Prime rating


Engine manufacturer Cummins
Engine model KTA50-G3
Configuration Cast iron, 60 º V16 cylinder
Aspiration Turbocharged and after-cooled
Gross engine power output, kWm 1227 1097
BMEP at set rated load, kPa 1951 1744
Bore, mm 159
Stroke, mm 159
Rated speed, rpm 1500
Piston speed, m/s 7.9
Compression ratio 13.9:1
Lube oil capacity, L 152
Overspeed limit, rpm 1725 ±50
Regenerative power, kW 116
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 625
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70

power.cummins.com
©2019 Cummins Inc. | DS44-CPGK (09/19)
Air Standby rating Prime rating
Combustion air, m3/min 104.8 96.3
Maximum air cleaner restriction, kPa 6.2

Exhaust
Exhaust gas flow at set rated load, m3/min 240.7 223.6
Exhaust gas temperature, °C 525 520
Maximum exhaust back pressure, kPa 6.7

Standard set-mounted radiator cooling


Ambient design, °C 40
Fan load, kWm 46
Coolant capacity (with radiator), L 424
Cooling system air flow, m3/sec @ 12.7 mm H2O 27.6
Total heat rejection, Btu/min 44000 38500
Maximum cooling air flow static restriction mm H2O 12.7

Optional set-mounted radiator cooling


Ambient design, °C 50
Fan load, kWm 46
Coolant capacity (with radiator), L 424
Cooling system air flow, m3/sec @ 12.7 mm H2O 27.6
Maximum cooling air flow static restriction mm H2O 12.7

Optional set-mounted radiator cooling


Ambient design, °C 55
Fan load, kWm 46
Coolant capacity (with radiator), L 424
Cooling system air flow, m3/sec @ 12.7 mm H2O 27.6
Maximum cooling air flow static restriction mm H2O 12.7

Weights* Open Enclosed


Unit dry weight kgs 9190 17002
Unit wet weight kgs 9613 17425
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions mm 5105 2000 2238
Enclosed set standard dimensions (with exhaust stack)
12192 2438 2896 (3233)
mm

power.cummins.com
©2019 Cummins Power Generation Inc. | DS44g-CPGK A055S601 (09/19)
Genset outline

Open set

Enclosed set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

Alternator data

Connection Temp rise ºC Duty Alternator Voltage


Wye, 3-phase 150/125 S/P PI734B 380-440 V
Wye, 3-phase 105* P PI734B 380-440 V
Wye, 3-phase 125/105 S/P HVSI804R 6300-6600 V
Wye, 3-phase 125/105 S/P HVSI804R 10000 V
Wye, 3-phase 125/105 S/P HVSI804R 10500-11000 V
Wye, 3-phase 125/105 S/P MVSI804R 3300 V

*Option available only through ETO (Engineering to Order)

Ratings definitions

Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.

power.cummins.com
©2019 Cummins Power Generation Inc. | DS44g-CPGK A055S601 (09/19)
Formulas for calculating full load currents:

Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.73 x 0.8 Voltage

For more information contact your local Cummins distributor


or visit power.cummins.com

©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS44-CPGK (09/19)
Specification sheet

Diesel
generator set
KTA50 series
engine
1250 kVA - 1675 kVA 50 Hz
1120 kW - 1545 kW 60 Hz
Description
This Cummins® commercial generator set is a Control system - Standard PowerCommand®
fully integrated power generation system, electronic control provides total system
providing optimum performance, reliability, and integration including remote start/stop, precise
versatility for stationary Standby, Prime Power, frequency and voltage regulation, alarm and
and Continuous duty applications. status message display, AmpSentryTM
protection, output metering, auto-shutdown.
Features
Cooling system - Standard integral set-
Cummins heavy-duty engine - Rugged 4-cycle
mounted radiator system, designed and tested
industrial diesel delivers reliable power, low
for rated ambient temperatures, simplifies facility
emissions and fast response to load changes.
design requirements for rejected heat.
Permanent Magnet Generator (PMG) - Offers
Enclosures - Optional weather-protective and
enhanced motor starting and fault clearing short
sound-attenuated enclosures are available.
circuit capability.
Warranty and service - Backed by a
Alternator - Several alternator sizes offer
comprehensive warranty and worldwide
selectable motor starting capability with low
distributor network.
reactance 2/3 pitch windings; low waveform
distortion with non-linear loads, fault clearing ISO8528-5 G3 Capable – Refer to factory for
short-circuits capability, and class F or H site and configuration specific transient
insulation. performance specification.

Emissions
Standby rating Prime rating compliance Data sheets
50 Hz 60 Hz 50 Hz 60 Hz TA Luft –
50 Hz 60 Hz
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) EU Stage
DS44-
C1400 D5 1400 (1120) 1250 (1000)
CPGK
DS46-
C1675 D5 1675 (1340) 1400 (1120)
CPGK
DS47-
C1675 D5A 1675 (1340) 1500 (1200)
CPGK
DS84-
C1250 D6 1270 (1588) 1120 (1400)
CPGK
DS85-
C1500 D6 1545 (1931) 1286 (1608)
CPGK

power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Generator set specifications
Governor regulation ISO 8528 part 1
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMC compatibility BS EN61000-6-4 / BS EN61000-6-2

Engine specifications
Design 4 cycle, V-block, turbocharged and after-cooled
Bore 158.8 mm (6.25 in.)
Stroke 158.8 mm (6.25 in.)
Displacement 50 L (3067 in3)
Cylinder block engine Sixteen-cylinder vee formation, direct injection, four-cycle diesel
Battery capacity 1800 amps at ambient temperature 32 ºF (0 °C)
Battery charging alternator 55 amps
Starting voltage 24 Volts, negative ground
Fuel system Direct injection
Fuel filter Dual spin on paper element fuel filters with standard water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on paper element full flow and bypass lube oil filters
Standard cooling system 104 ºF (40 ºC) ambient radiator

Alternator specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise
Exciter type Permanent Magnet Generator (PMG)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1-22.43
Telephone Harmonic Factor (THF) No load < 1.5%. Non distorting balanced linear load < 5%

Available voltages
50 Hz Line – Neutral/Line – Line 60 Hz Line – Neutral/Line – Line
• 220/380* • 1905/3300 • 219/380 • 2400/4160

• 230/400 • 3640/6300 • 254/440 • 7200/12470

• 240/415 • 3810/6600 • 277/480 • 7620/13200

• 254/440 • 6350/11000 • 347/600 • 7970/13800

*Derate may be applicable at this voltage. Please consult the factory for details.

Generator set options


Engine Alternator Warranty
• Heavy duty air filter • Alternator heater • 5 years for Standby application
• Water jacket heater 220/240 V • High humidity isolation • 2 years for Prime application
• Oil sampling valve • Exciter voltage regulator (PMG)
• UK built engine and alternator • Hardened Beaning Cartridge
Silencer
• 9 dB attenuation critical silencer
Enclosure Control panel • 25 dB residential – delivered loose
• High-cube 40ft container • 3 pole main circuit breaker
• 4 pole main circuit breaker
Cooling
• Antifreeze 50/50 (Ethylene glycol)

*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
PowerCommand 3.3 control system Engine data
• DC voltage
• Engine speed
• Lube oil pressure and temperature
• Coolant temperature
• Comprehensive FAE data (where applicable)
Other data
The PowerCommand 3.3 control system is an integrated • Genset model data
microprocessor based generator set control system • Start attempts, starts, running hours, kW hours
providing voltage regulation, engine protection, alternator • Load profile (operating hours at % load in 5%
protection, operator interface and isochronous governing. increments)
AmpSentry – Includes integral AmpSentry protection,
• Fault history
which provides a full range of alternator protection functions
that are matched to the alternator provided. • Data logging and fault simulation (requires InPower)
Power management – Control function provides battery Standard control functions
monitoring and testing features and smart starting control Digital governing (optional)
system.
• Integrated digital electronic isochronous governor
Advanced control methodology – Three phase sensing,
full wave rectified voltage regulation, with a PWM output for • Temperature dynamic governing
stable operation with all load types. Digital voltage regulation
Communications interface – Control comes standard with • Integrated digital electronic voltage regulator
PCCNet and Modbus interface. • 3-phase, 4-wire Line-to-Line sensing
Regulation compliant – Prototype tested: UL, CSA, UKCA • Configurable torque matching
and CE compliant. AmpSentry AC protection
Service – InPower™ PC-based service tool available for • AmpSentry protective relay
detailed diagnostics, setup, data logging and fault
simulation. • Over current and short circuit shutdown
Reliable design – The control system is designed for • Over current warning
reliable operation in harsh environment. • Single and three phase fault regulation
Multi-language support • Over and under voltage shutdown
Operator panel features • Over and under frequency shutdown
Operator panel features – The operator panel, in addition • Overload warning with alarm contact
to the alternator, displays the Utility/AC Bus data. • Reverse power and reverse Var shutdown
Operator/display functions • Field overload
• 320 x 240 pixels graphic LED backlight LCD Engine protection
• Auto, manual, start, stop, fault reset and lamp test/panel • Battery voltage monitoring, protection and testing
lamp switches • Over speed shutdown
• Alpha-numeric display with pushbuttons • Low oil pressure warning and shutdown
• LED lamps indicating genset running, remote start, not in • High coolant temperature warning and shutdown
auto, common shutdown, common warning, manual run
• Low coolant level warning or shutdown
mode, auto mode and stop
Paralleling control functions • Low coolant temperature warning
• Digital frequency synchronization and voltage matching • Fail to start (over crank) shutdown
• Isochronous kW and kVar load sharing controls • Fail to crank shutdown
• Droop kW and kVar control • Cranking lockout
• Sensor failure indication
• Sync check
• Low fuel level warning or shutdown
• Extended paralleling (peak shave/base load)
• Fuel-in-rupture-basin warning or shutdown
• Digital power transfer control (AMF) provides load
transfer operation in open or closed transition or soft • Full authority electronic engine protection
(ramping) transfer mode Control functions
Alternator data • Time delay start and cool down
• Line-to-Neutral and Line-to-Line AC volts • Real time clock for fault and event time stamping
• 3-phase AC current • Exerciser clock and time of day start/stop
• Frequency • Data logging
• kW, kVar, power factor kVA (three phase and total) • Cycle cranking
• Load shed
• Configurable inputs and outputs (4)
• Remote emergency stop
Options
• Auxiliary output relays (2)

power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a
reliable utility source. Emergency Standby Power
(ESP) is in accordance with ISO 8528. Fuel Stop
power in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
This outline drawing is to provide representative configuration
Running Power (LTP) is in accordance with
details for model series only.
ISO 8528.
Prime Power (PRP): See respective model data sheet for specific model outline
drawing number.
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in Do not use for installation design
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours.
Continuous Power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and
BS 5514.

Model Dim ‘A’ (mm) Dim ‘B’ (mm) Dim ‘C’ (mm) Set weight* dry (kg) Set weight* wet (kg)
C1400 D5 5105 2000 2238 9190 9613
C1675 D5 5811 2033 2330 10348 10967
C1675 D5A 5811 2033 2330 10348 10967
C1250 D6 5105 2000 2238 9190 9613
C1500 D6 5811 2033 2330 10348 10967
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.

Codes and standards


The CE marking is only valid
when equipment is used in a
fixed installation application.
This generator set is designed Material compliance declaration
in facilities certified to ISO 9001 is available upon request.
and manufactured in facilities
certified to ISO 9001 or The UKCA marking is only valid
ISO 9002. when equipment is used in a
fixed installation application.
Material compliance declaration
is available upon request.
All enclosed products are
This generator set has been
designed to meet or exceed EU
2000/14/EC noise legislation 2000/14/EC ISO 8528 designed to comply with
ISO 8528 standards.
step 2006.

For more information contact your local Cummins distributor


or visit power.cummins.com

©2020 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Basic Engine Model: Curve Number:
Cummins Inc. FR6250
G-DRIVE
KTA50-G3
K50
QSB
Columbus, Indiana 47202-3005
Engine Critical Parts List: Date: 1
EXHAUST EMISSIONS DATA SHEET CPL : 2227 30 JUN 12

Displacement : 50.3 litre (3067 in3) Bore : 159 mm (6.25 in.) Stroke : 159 mm (6.25 in.)
No. of Cylinders : 16 Aspiration : Turbocharged and Aftercooled
Emission Certification : N/A

Engine Speed Standby Power Prime Power Continuous Power

Limited Time Unlimited Time


RPM kWm hp kWm hp
kWm hp kWm hp
1500 1227 1645 1150 1541 1097 1470 900 1206
1800 1380 1850 1300 1742 1220 1635 1000 1340

Exhaust Emissions Data @ 1500 RPM


Standby Power Prime Power Continuous Power
Component g/BHP-h mg/m3 PPM g/BHP-h mg/m3 PPM g/BHP-h mg/m3 PPM
HC (Total Unburned Hydrocarbons) 0.13 55 110 0.12 50 100 0.1 42 90
NOx (Oxides of Nitrogen as NO2) 12 6100 2880 11 5500 2590 9 4500 2140
CO (Carbon Monoxide) 2.8 1400 1060 2.7 1400 1020 2.6 1300 930
PM (Particulate Matter) 0.08 40 - 0.09 35 - 0.11 55 -
SO2 (Sulfer Dioxide) 0.12 56 28 0.12 58 26 0.13 56 28

Exhaust Emissions Data @ 1800 RPM


Standby Power Prime Power Continuous Power
Component g/BHP-h mg/m3 PPM g/BHP-h mg/m3 PPM g/BHP-h mg/m3 PPM
HC (Total Unburned Hydrocarbons) 0.12 45 90 0.12 45 100 0.13 50 100
NOx (Oxides of Nitrogen as NO2) 12.70 6300 3040 11.3 5700 2760 9.7 4800 2290
CO (Carbon Monoxide) 1.00 480 400 0.08 360 290 0.5 250 190
PM (Particulate Matter) 0.06 30 - 0.07 35 - 0.06 30 -
SO2 (Sulfer Dioxide) 0.12 59 29 0.12 58 28 0.13 56 28

Note: mg/m3 and PPM numbers are measured dry and corrected to 5% O2 content.

Test Methods and Conditions:


Steady-State emissions recorded per ISO8178-1 during operation at rated engine speed (+/- 2%) and stated constant load (+/-2%) with engine temperatures, pressures, and emission rates stabilized.
Fuel Specifications:
46.5 Cetane Number, 0.035 Wt. % Sulfur; Reference ISO8178-5, 40CFR86.1313-98 Type 2-D and ASTM D975 No. 2-D.
Reference:
25°C (77°F) Air Inlet Temperature, 40°C (104°F) Fuel Inlet Temperature, 100 kPa (29.53 in Hg) Barometric Pressure; 10.7 g/kg (75 grains H2O/lb) of dry air Humidity (required for NOx correction): Intake
Restriction set to maximum allowable limit for clean filter; Exhaust Back Pressure set to maximum allowable limit.

Data was taken from a single engine test according to the test methods, fuel specification, and reference conditions stated above and is subject to engine-to-engine variability. Tests conducted with alter-
nate test methods, instrumentation, fuel, or reference conditions can yield different results.

Data subject to change without notice.


PI734C - Winding 312
APPROVED DOCUMENT
Technical Data Sheet
PI734C
SPECIFICATIONS & OPTIONS
STANDARDS TERMINALS & TERMINAL BOX
Stamford industrial generators meet the requirements of BS Standard generators feature a main stator with 6 ends
EN 60034 and the relevant sections of other national and brought out to the terminals, which are mounted on the
international standards such as BS5000, VDE 0530, NEMA frame at the non-drive end of the generator. A sheet steel
MG1-32, IEC60034, CSA C22.2-100, AS1359. terminal box contains the AVR and provides ample space
Other standards and certifications can be considered on for the customers' wiring and gland arrangements. It has
request. removable panels for easy access.

DESCRIPTION SHAFT & KEYS


The STAMFORD PI range of synchronous ac generators are All generator rotors are dynamically balanced to better
brushless with a rotating field. They are separately excited than BS6861:Part 1 Grade 2.5 for minimum vibration in
by the STAMFORD Permanent Magnet Generator (PMG). operation. Two bearing generators are balanced with a
This is a shaft mounted, high frequency, pilot exciter which half key.
provides a constant supply of clean power via the Automatic
Voltage Regulator (AVR) to the main exciter. The main INSULATION/IMPREGNATION
exciter output is fed to the main rotor, through a full wave The insulation system is class 'H', and meets the
bridge rectifier, protected by surge suppression. requirements of UL1446.
All wound components are impregnated with materials
VOLTAGE REGULATORS APPROVED DOCUMENT and processes designed specifically to provide the high
The PI range generators, complete with a PMG, are available build required for static windings and the high mechanical
with one of two AVRs. Each AVR has soft start voltage build strength required for rotating components.
up and built in protection against sustained over-excitation,
which will de-excite the generator after a minimum of 8 QUALITY ASSURANCE
seconds. Generators are manufactured using production
Underspeed protection (UFRO) is also provided on both procedures having a quality assurance level to
AVRs. The UFRO will reduce the generator output voltage BS EN ISO 9001.
proportional to the speed of the generator below a pre-
settable level. NOTE ON REGULATION
The stated voltage regulation may not be maintained in
The MX341 AVR is two phase sensed with a voltage the presence of certain radio transmitted signals. Any
regulation of ± 1 %. (see the note on regulation). change in performance will fall within the limits of Criteria
'B' of EN 61000-6-2:2001. At no time will the steady-state
The MX321 AVR is 3 phase rms sensed with a voltage voltage regulation exceed 2%.
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled DE RATES
recovery from step loads. An over voltage protection circuit All values tabulated on page 8 are subject to the following
will shutdown the output device of the AVR, it can also trip an reductions
optional excitation circuit breaker if required. As an option,
short circuit current limiting is available with the addition of 5% when air inlet filters are fitted.
current transformers. 10% when IP44 Filters are fitted.
3% for every 500 metres by which the operating altitude
Both the MX341 and the MX321 need a generator mounted exceeds 1000 metres above mean sea level.
current transformer to provide quadrature droop 3% for every 5°C by which the operational ambient
characteristics for load sharing during parallel operation. temperature exceeds 40°C.
Provision is also made for the connection of the STAMFORD
power factor controller, for embedded applications, and a Note: Requirement for operating in an ambient
remote voltage trimmer. temperature exceeding 60°C must be referred to the
factory.
WINDINGS & ELECTRICAL PERFORMANCE
All generator stators are wound to 2/3 pitch. This eliminates
triplen (3rd, 9th, 15th …) harmonics on the voltage waveform
and is found to be the optimum design for trouble-free supply
of non-linear loads. The 2/3 pitch design avoids excessive
neutral currents sometimes seen with higher winding pitches. Note: Continuous development of our products entitles us to
A fully connected damper winding reduces oscillations during change specification details without notice, therefore they must
paralleling. This winding, with the 2/3 pitch and carefully not be regarded as binding.
selected pole and tooth designs, ensures very low levels of
voltage waveform distortion. Front cover drawing is typical of the product range.

2
PI734C
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.

A.V.R. MX341 MX321

VOLTAGE REGULATION ±1% ± 0.5 % With 4% ENGINE GOVERNING

SUSTAINED SHORT CIRCUIT REFER TO SHORT CIRCUIT DECREMENT CURVES (page 7)

INSULATION SYSTEM CLASS H

PROTECTION IP23

RATED POWER FACTOR 0.8

STATOR WINDING DOUBLE LAYER LAP

WINDING PITCH TWO THIRDS

WINDING LEADS 6

MAIN STATOR RESISTANCE 0.00126 Ohms PER PHASE AT 22°C STAR CONNECTED

MAIN ROTOR RESISTANCE


APPROVED DOCUMENT 1.85 Ohms at 22°C

EXCITER STATOR RESISTANCE 17.5 Ohms at 22°C

EXCITER ROTOR RESISTANCE 0.063 Ohms PER PHASE AT 22°C

R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others

WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%

MAXIMUM OVERSPEED 2250 Rev/Min

BEARING DRIVE END BALL. 6228 C3

BEARING NON-DRIVE END BALL. 6319 C3

1 BEARING 2 BEARING

WEIGHT COMP. GENERATOR 3018 kg 2967 kg

WEIGHT WOUND STATOR 1445 kg 1445 kg

WEIGHT WOUND ROTOR 1257 kg 1195 kg


2
WR² INERTIA 37.3309 kgm 36.33 kgm2
SHIPPING WEIGHTS in a crate 3091kg 3036kg

PACKING CRATE SIZE 194 x 105 x 154(cm) 194 x 105 x 154(cm)

50 Hz 60 Hz

TELEPHONE INTERFERENCE THF<2% TIF<50

COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm

VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE
1505 1550 1550 1520 1705 1815 1855 1890
VALUES
Xd DIR. AXIS SYNCHRONOUS 3.18 2.96 2.75 2.40 3.86 3.67 3.43 3.21

X'd DIR. AXIS TRANSIENT 0.19 0.18 0.17 0.15 0.23 0.22 0.21 0.20

X''d DIR. AXIS SUBTRANSIENT 0.14 0.13 0.12 0.11 0.17 0.16 0.15 0.14

Xq QUAD. AXIS REACTANCE 2.05 1.91 1.77 1.55 2.49 2.37 2.22 2.07

X''q QUAD. AXIS SUBTRANSIENT 0.29 0.27 0.25 0.22 0.35 0.33 0.31 0.29

XL LEAKAGE REACTANCE 0.04 0.03 0.03 0.03 0.04 0.04 0.04 0.04
X2 NEGATIVE SEQUENCE 0.20 0.19 0.18 0.15 0.25 0.23 0.22 0.21
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03

REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.135s
T''d SUB-TRANSTIME CONST. 0.01s
T'do O.C. FIELD TIME CONST. 2.23s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd

3
PI734C
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

4
PI734C
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES

APPROVED DOCUMENT

5
PI734C
Winding 312

Locked Rotor Motor Starting Curve


50
Hz 346V 380V 400V 415V 440V
30

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15
APPROVED DOCUMENT

10

0
0 500 1000 1500 2000 2500 3000 3500
LOCKED ROTOR kVA

60
Hz 380V 416V 440V 460V 480V
30

25
.

20
PER CENT TRANSIENT VOLTAGE DIP

15

10

0
0 500 1000 1500 2000 2500 3000 3500 4000
LOCKED ROTOR kVA

6
PI734C

Three-phase Short Circuit Decrement Curve. No-load Excitation at Rated Speed


Based on star (wye) connection.
50
Hz 100000

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

APPROVED DOCUMENT

1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 5,400 Amps

60 100000
Hz

SYMMETRICAL

ASYMMETRICAL
CU RR E NT (Am p s)

10000

1000
0.001 0.01 0.1 1 10
TIME (secs)

Sustained Short Circuit = 6,100 Amps


Note 1 Note 2
The following multiplication factors should be The following multiplication factor should be used to convert the
used to adjust the values from curve between values calculated in accordance with NOTE 1 to those applicable
time 0.001 seconds and the minimum current to the various types of short circuit :
point in respect of nominal operating voltage :
50Hz 60Hz 3-phase 2-phase L-L 1-phase L-N
Voltage Factor Voltage Factor Instantaneous x 1.00 x 0.87 x 1.30
380v x 1.00 416v x 1.00 Minimum x 1.00 x 1.80 x 3.20
400v x 1.05 440v x 1.06 Sustained x 1.00 x 1.50 x 2.50
415v x 1.09 460v x 1.10 Max. sustained duration 10 sec. 5 sec. 2 sec.
440v x 1.16 480v x 1.15 All other times are unchanged
The sustained current value is constant irrespective
of voltage level
Note 3
Curves are drawn for Star (Wye) connected machines.

7
PI734C
Winding 312 / 0.8 Power Factor

RATINGS

Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C

50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440

kVA 1400 1445 1445 1415 1505 1550 1550 1520 1570 1615 1615 1590 1615 1660 1660 1630

kW 1120 1156 1156 1132 1204 1240 1240 1216 1256 1292 1292 1272 1292 1328 1328 1304

Efficiency (%) 95.4 95.5 95.6 95.8 95.2 95.4 95.5 95.7 95.1 95.2 95.4 95.6 95.0 95.1 95.3 95.5

kW Input 1174 1210 1209 1182 1265 1300 1298 1271 1321 1357 1354 1331 1360 1396 1393 1365

60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480

kVA 1590 1690 1725 1760 1705 1815 1855 1890 1770 1890 1930 1970 1820 1945 1985 2025

kW 1272 1352 1380 1408 1364 1452 1484 1512 1416 1512 1544 1576 1456 1556 1588 1620

Efficiency (%) 95.3 95.4 95.5 95.6 95.2 95.2 95.3 95.4 95.1 95.1 95.2 95.3 95.0 95.0 95.2 95.3

kW Input 1335 1417 1445 1473 1433 1525 1557 1585 1489 1590 1622 1654 1533 1638 1668 1700

DIMENSIONS

8
APPROVED DOCUMENT

Head Office Address:


Barnack Road, Stamford
Lincolnshire, PE9 2NB
United Kingdom
Tel: +44 (0) 1780 484000
Fax: +44 (0) 1780 484100

www.cumminsgeneratortechnologies.com

Copyright 2010, Cummins Generator Technologies Ltd, All Rights Reserved


Stamford and AvK are registered trade marks of Cummins Generator Technologies Ltd
Cummins and the Cummins logo are registered trade marks of Cummins Inc.

PI7C-312-TD-EN-SG-A