C1400D5 - Specs
C1400D5 - Specs
Model: C1400 D5
Frequency: 50 Hz
Fuel type: Diesel
Standby Prime
Fuel consumption kVA (kW) kVA (kW)
Ratings 1400 (1120) 1250 (1000)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 24 41 59 77 22 38 54 69
L/hr 91 158 224 291 84 144 203 263
Fuel flow
Maximum fuel flow, L/hr 625
Maximum fuel inlet restriction, mm Hg 203
Maximum fuel inlet temperature, °C 70
power.cummins.com
©2019 Cummins Inc. | DS44-CPGK (09/19)
Air Standby rating Prime rating
Combustion air, m3/min 104.8 96.3
Maximum air cleaner restriction, kPa 6.2
Exhaust
Exhaust gas flow at set rated load, m3/min 240.7 223.6
Exhaust gas temperature, °C 525 520
Maximum exhaust back pressure, kPa 6.7
power.cummins.com
©2019 Cummins Power Generation Inc. | DS44g-CPGK A055S601 (09/19)
Genset outline
Open set
Enclosed set
Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.
Alternator data
Ratings definitions
Emergency Standby Limited-Time Running Prime Power (PRP): Base Load (Continuous)
Power (ESP): Power (LTP): Power (COP):
Applicable for supplying Applicable for supplying Applicable for supplying Applicable for supplying
power to varying electrical power to a constant power to varying electrical power continuously to a
load for the duration of electrical load for limited load for unlimited hours. constant electrical load for
power interruption of a hours. Limited-Time Prime Power (PRP) is in unlimited hours. Continuous
reliable utility source. Running Power (LTP) is in accordance with ISO 8528. Power (COP) is in
Emergency Standby Power accordance with ISO 8528. Ten percent overload accordance with ISO 8528,
(ESP) is in accordance with capability is available in ISO 3046, AS 2789,
ISO 8528. Fuel stop power accordance with ISO 3046, DIN 6271 and BS 5514.
in accordance with AS 2789, DIN 6271 and
ISO 3046, AS 2789, BS 5514.
DIN 6271 and BS 5514.
power.cummins.com
©2019 Cummins Power Generation Inc. | DS44g-CPGK A055S601 (09/19)
Formulas for calculating full load currents:
©2019 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
DS44-CPGK (09/19)
Specification sheet
Diesel
generator set
KTA50 series
engine
1250 kVA - 1675 kVA 50 Hz
1120 kW - 1545 kW 60 Hz
Description
This Cummins® commercial generator set is a Control system - Standard PowerCommand®
fully integrated power generation system, electronic control provides total system
providing optimum performance, reliability, and integration including remote start/stop, precise
versatility for stationary Standby, Prime Power, frequency and voltage regulation, alarm and
and Continuous duty applications. status message display, AmpSentryTM
protection, output metering, auto-shutdown.
Features
Cooling system - Standard integral set-
Cummins heavy-duty engine - Rugged 4-cycle
mounted radiator system, designed and tested
industrial diesel delivers reliable power, low
for rated ambient temperatures, simplifies facility
emissions and fast response to load changes.
design requirements for rejected heat.
Permanent Magnet Generator (PMG) - Offers
Enclosures - Optional weather-protective and
enhanced motor starting and fault clearing short
sound-attenuated enclosures are available.
circuit capability.
Warranty and service - Backed by a
Alternator - Several alternator sizes offer
comprehensive warranty and worldwide
selectable motor starting capability with low
distributor network.
reactance 2/3 pitch windings; low waveform
distortion with non-linear loads, fault clearing ISO8528-5 G3 Capable – Refer to factory for
short-circuits capability, and class F or H site and configuration specific transient
insulation. performance specification.
Emissions
Standby rating Prime rating compliance Data sheets
50 Hz 60 Hz 50 Hz 60 Hz TA Luft –
50 Hz 60 Hz
Model kVA (kW) kW (kVA) kVA (kW) kW (kVA) EU Stage
DS44-
C1400 D5 1400 (1120) 1250 (1000)
CPGK
DS46-
C1675 D5 1675 (1340) 1400 (1120)
CPGK
DS47-
C1675 D5A 1675 (1340) 1500 (1200)
CPGK
DS84-
C1250 D6 1270 (1588) 1120 (1400)
CPGK
DS85-
C1500 D6 1545 (1931) 1286 (1608)
CPGK
power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Generator set specifications
Governor regulation ISO 8528 part 1
Voltage regulation, no load to full load ± 1%
Random voltage variation ± 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
EMC compatibility BS EN61000-6-4 / BS EN61000-6-2
Engine specifications
Design 4 cycle, V-block, turbocharged and after-cooled
Bore 158.8 mm (6.25 in.)
Stroke 158.8 mm (6.25 in.)
Displacement 50 L (3067 in3)
Cylinder block engine Sixteen-cylinder vee formation, direct injection, four-cycle diesel
Battery capacity 1800 amps at ambient temperature 32 ºF (0 °C)
Battery charging alternator 55 amps
Starting voltage 24 Volts, negative ground
Fuel system Direct injection
Fuel filter Dual spin on paper element fuel filters with standard water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on paper element full flow and bypass lube oil filters
Standard cooling system 104 ºF (40 ºC) ambient radiator
Alternator specifications
Design Brushless, 4 pole, drip proof revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise
Exciter type Permanent Magnet Generator (PMG)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load < 1.5%. Non distorting balanced linear load < 5%
Telephone Influence Factor (TIF) < 50% per NEMA MG1-22.43
Telephone Harmonic Factor (THF) No load < 1.5%. Non distorting balanced linear load < 5%
Available voltages
50 Hz Line – Neutral/Line – Line 60 Hz Line – Neutral/Line – Line
• 220/380* • 1905/3300 • 219/380 • 2400/4160
*Derate may be applicable at this voltage. Please consult the factory for details.
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
PowerCommand 3.3 control system Engine data
• DC voltage
• Engine speed
• Lube oil pressure and temperature
• Coolant temperature
• Comprehensive FAE data (where applicable)
Other data
The PowerCommand 3.3 control system is an integrated • Genset model data
microprocessor based generator set control system • Start attempts, starts, running hours, kW hours
providing voltage regulation, engine protection, alternator • Load profile (operating hours at % load in 5%
protection, operator interface and isochronous governing. increments)
AmpSentry – Includes integral AmpSentry protection,
• Fault history
which provides a full range of alternator protection functions
that are matched to the alternator provided. • Data logging and fault simulation (requires InPower)
Power management – Control function provides battery Standard control functions
monitoring and testing features and smart starting control Digital governing (optional)
system.
• Integrated digital electronic isochronous governor
Advanced control methodology – Three phase sensing,
full wave rectified voltage regulation, with a PWM output for • Temperature dynamic governing
stable operation with all load types. Digital voltage regulation
Communications interface – Control comes standard with • Integrated digital electronic voltage regulator
PCCNet and Modbus interface. • 3-phase, 4-wire Line-to-Line sensing
Regulation compliant – Prototype tested: UL, CSA, UKCA • Configurable torque matching
and CE compliant. AmpSentry AC protection
Service – InPower™ PC-based service tool available for • AmpSentry protective relay
detailed diagnostics, setup, data logging and fault
simulation. • Over current and short circuit shutdown
Reliable design – The control system is designed for • Over current warning
reliable operation in harsh environment. • Single and three phase fault regulation
Multi-language support • Over and under voltage shutdown
Operator panel features • Over and under frequency shutdown
Operator panel features – The operator panel, in addition • Overload warning with alarm contact
to the alternator, displays the Utility/AC Bus data. • Reverse power and reverse Var shutdown
Operator/display functions • Field overload
• 320 x 240 pixels graphic LED backlight LCD Engine protection
• Auto, manual, start, stop, fault reset and lamp test/panel • Battery voltage monitoring, protection and testing
lamp switches • Over speed shutdown
• Alpha-numeric display with pushbuttons • Low oil pressure warning and shutdown
• LED lamps indicating genset running, remote start, not in • High coolant temperature warning and shutdown
auto, common shutdown, common warning, manual run
• Low coolant level warning or shutdown
mode, auto mode and stop
Paralleling control functions • Low coolant temperature warning
• Digital frequency synchronization and voltage matching • Fail to start (over crank) shutdown
• Isochronous kW and kVar load sharing controls • Fail to crank shutdown
• Droop kW and kVar control • Cranking lockout
• Sensor failure indication
• Sync check
• Low fuel level warning or shutdown
• Extended paralleling (peak shave/base load)
• Fuel-in-rupture-basin warning or shutdown
• Digital power transfer control (AMF) provides load
transfer operation in open or closed transition or soft • Full authority electronic engine protection
(ramping) transfer mode Control functions
Alternator data • Time delay start and cool down
• Line-to-Neutral and Line-to-Line AC volts • Real time clock for fault and event time stamping
• 3-phase AC current • Exerciser clock and time of day start/stop
• Frequency • Data logging
• kW, kVar, power factor kVA (three phase and total) • Cycle cranking
• Load shed
• Configurable inputs and outputs (4)
• Remote emergency stop
Options
• Auxiliary output relays (2)
power.cummins.com
©2020 Cummins Inc. | SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a
reliable utility source. Emergency Standby Power
(ESP) is in accordance with ISO 8528. Fuel Stop
power in accordance with ISO 3046, AS 2789,
DIN 6271 and BS 5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant
electrical load for limited hours. Limited-Time
This outline drawing is to provide representative configuration
Running Power (LTP) is in accordance with
details for model series only.
ISO 8528.
Prime Power (PRP): See respective model data sheet for specific model outline
drawing number.
Applicable for supplying power to varying electrical
load for unlimited hours. Prime Power (PRP) is in Do not use for installation design
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046,
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a
constant electrical load for unlimited hours.
Continuous Power (COP) in accordance with
ISO 8528, ISO 3046, AS 2789, DIN 6271 and
BS 5514.
Model Dim ‘A’ (mm) Dim ‘B’ (mm) Dim ‘C’ (mm) Set weight* dry (kg) Set weight* wet (kg)
C1400 D5 5105 2000 2238 9190 9613
C1675 D5 5811 2033 2330 10348 10967
C1675 D5A 5811 2033 2330 10348 10967
C1250 D6 5105 2000 2238 9190 9613
C1500 D6 5811 2033 2330 10348 10967
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.
©2020 Cummins Inc. All rights reserved. Cummins is a registered trademark of Cummins Inc. PowerCommand, AmpSentry, InPower and “Our energy working for you.” are trademarks of
Cummins Inc. Other company, product, or service names may be trademarks or service marks of others. Specifications are subject to change without notice.
SS16-CPGK (KTA50) - MARKUP-UKCA-UPDATE (02/22)
Basic Engine Model: Curve Number:
Cummins Inc. FR6250
G-DRIVE
KTA50-G3
K50
QSB
Columbus, Indiana 47202-3005
Engine Critical Parts List: Date: 1
EXHAUST EMISSIONS DATA SHEET CPL : 2227 30 JUN 12
Displacement : 50.3 litre (3067 in3) Bore : 159 mm (6.25 in.) Stroke : 159 mm (6.25 in.)
No. of Cylinders : 16 Aspiration : Turbocharged and Aftercooled
Emission Certification : N/A
Note: mg/m3 and PPM numbers are measured dry and corrected to 5% O2 content.
Data was taken from a single engine test according to the test methods, fuel specification, and reference conditions stated above and is subject to engine-to-engine variability. Tests conducted with alter-
nate test methods, instrumentation, fuel, or reference conditions can yield different results.
2
PI734C
WINDING 312
CONTROL SYSTEM SEPARATELY EXCITED BY P.M.G.
PROTECTION IP23
WINDING LEADS 6
MAIN STATOR RESISTANCE 0.00126 Ohms PER PHASE AT 22°C STAR CONNECTED
R.F.I. SUPPRESSION BS EN 61000-6-2 & BS EN 61000-6-4,VDE 0875G, VDE 0875N. refer to factory for others
WAVEFORM DISTORTION NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 5.0%
1 BEARING 2 BEARING
50 Hz 60 Hz
COOLING AIR 2.69 m³/sec 5700 cfm 3.45 m³/sec 7300 cfm
VOLTAGE STAR 380/220 400/231 415/240 440/254 416/240 440/254 460/266 480/277
kVA BASE RATING FOR REACTANCE
1505 1550 1550 1520 1705 1815 1855 1890
VALUES
Xd DIR. AXIS SYNCHRONOUS 3.18 2.96 2.75 2.40 3.86 3.67 3.43 3.21
X'd DIR. AXIS TRANSIENT 0.19 0.18 0.17 0.15 0.23 0.22 0.21 0.20
X''d DIR. AXIS SUBTRANSIENT 0.14 0.13 0.12 0.11 0.17 0.16 0.15 0.14
Xq QUAD. AXIS REACTANCE 2.05 1.91 1.77 1.55 2.49 2.37 2.22 2.07
X''q QUAD. AXIS SUBTRANSIENT 0.29 0.27 0.25 0.22 0.35 0.33 0.31 0.29
XL LEAKAGE REACTANCE 0.04 0.03 0.03 0.03 0.04 0.04 0.04 0.04
X2 NEGATIVE SEQUENCE 0.20 0.19 0.18 0.15 0.25 0.23 0.22 0.21
X0 ZERO SEQUENCE 0.02 0.02 0.02 0.02 0.03 0.03 0.03 0.03
REACTANCES ARE SATURATED VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
T'd TRANSIENT TIME CONST. 0.135s
T''d SUB-TRANSTIME CONST. 0.01s
T'do O.C. FIELD TIME CONST. 2.23s
Ta ARMATURE TIME CONST. 0.02s
SHORT CIRCUIT RATIO 1/Xd
3
PI734C
50 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
APPROVED DOCUMENT
4
PI734C
60 Winding 312
Hz THREE PHASE EFFICIENCY CURVES
APPROVED DOCUMENT
5
PI734C
Winding 312
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
APPROVED DOCUMENT
10
0
0 500 1000 1500 2000 2500 3000 3500
LOCKED ROTOR kVA
60
Hz 380V 416V 440V 460V 480V
30
25
.
20
PER CENT TRANSIENT VOLTAGE DIP
15
10
0
0 500 1000 1500 2000 2500 3000 3500 4000
LOCKED ROTOR kVA
6
PI734C
SYMMETRICAL
ASYMMETRICAL
CU RR E NT (Am p s)
10000
APPROVED DOCUMENT
1000
0.001 0.01 0.1 1 10
TIME (secs)
Sustained Short Circuit = 5,400 Amps
60 100000
Hz
SYMMETRICAL
ASYMMETRICAL
CU RR E NT (Am p s)
10000
1000
0.001 0.01 0.1 1 10
TIME (secs)
7
PI734C
Winding 312 / 0.8 Power Factor
RATINGS
Class - Temp Rise Cont. F - 105/40°C Cont. H - 125/40°C Standby - 150/40°C Standby - 163/27°C
50Hz Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
kVA 1400 1445 1445 1415 1505 1550 1550 1520 1570 1615 1615 1590 1615 1660 1660 1630
kW 1120 1156 1156 1132 1204 1240 1240 1216 1256 1292 1292 1272 1292 1328 1328 1304
Efficiency (%) 95.4 95.5 95.6 95.8 95.2 95.4 95.5 95.7 95.1 95.2 95.4 95.6 95.0 95.1 95.3 95.5
kW Input 1174 1210 1209 1182 1265 1300 1298 1271 1321 1357 1354 1331 1360 1396 1393 1365
60Hz Star (V) 416 440 460 480 416 440 460
APPROVED DOCUMENT 480 416 440 460 480 416 440 460 480
kVA 1590 1690 1725 1760 1705 1815 1855 1890 1770 1890 1930 1970 1820 1945 1985 2025
kW 1272 1352 1380 1408 1364 1452 1484 1512 1416 1512 1544 1576 1456 1556 1588 1620
Efficiency (%) 95.3 95.4 95.5 95.6 95.2 95.2 95.3 95.4 95.1 95.1 95.2 95.3 95.0 95.0 95.2 95.3
kW Input 1335 1417 1445 1473 1433 1525 1557 1585 1489 1590 1622 1654 1533 1638 1668 1700