CABLE POSITIONS:
SEE BoM 00 ft | zi = iss. 3VRNFS DATA SHEETS Rev 01
Saudi Electricity Company
SG
Ly gS Aya gaa AS)
SEC DISTRIBUTION MATERIALS SPECIFICATION
32-SDMS-01, Rev. 02
DATE: 31-10-2007G
9.0 DATA SCHEDULE
NON-EXTENCIBLE RING MAIN UNIT, SF6, 17.5 kV. (VRN-FS)
(Sheet 1 of 3)
SEC Inguiry No. __ Item No.
REF. SEC VENDOR
SEC. SPECIFIED PROPOSED
Lees VALUE VALUES
4.0 | DESIGN AND CONSTRUCTION REQUIREMENTS
4.1___ | GENERAL
1. RMU Type Indoor / Outdoor Indoor/Outdoor
2. RMU Configuration 3-Way / 4-Way 3.Way
3. Tee-off Fuse / Breaker Breaker
4. Fuse-switch with shunt coil Yes/No ‘Not applicable
'5._Term. fastener for Ring switch MI6 M16
6. Term, fastener for Tee-Of MI2 12
42-44 | GENERAL
1. Service Voltage 13.8 KV EE
2. Maximum Operating Voltage 17.5 kV 47.5KV
3. Rated Frequency 60 Hz 60H2
4, Rated Current of Load Break
(As per clause 4.3) 400. 400A(upto 630A)
5. Rated Current of Fuse :
Switches (As per clause 4.3) 200A. eveneeeee:
6. Short circuit withstand current —
Ring switches (1 sec.) 21kA
7, Rated Making Current of =R
Ring switches (peak) SOKA
'& Rated Making Current of
Earthing Switches (peak) SO kA See
9. Rated Making Current of
Fuse Switch (peak) SOkA
10. Impulse Withstand Voltage 95kV |
11. Power Frequency Withstand AS Be
Voltage (1 min.) (o1-sD) Soty
12. Internal Are fault withstand ae an
for 1 second 8 ae ot |
KO wR AF
DK 1211 Tencean =~ Page 17 of 25,VRNFS DATA SHEETS Rev 01
Saudi Electricity Company Gg ely gl ys geal AS
32-SDMS-01, Rev. 02
SEC DISTRIBUTION MATERIALS SPECIFICATION
DATE: 31-10-2007G
9.0 DATA SCHEDULE
NON-EXTENCIBLE RING MAIN UNIT, SF6, 17.5 kV (VRN- FS)
(Sheet 2 of 3)
SEC Inquiry No. Item No.
45.3 | CIRCUIT BREAKER TYPE
1. Service Voltage 13.8kV 13.8kV
2. Maximum Operating Voltage IT.SKV 17.5KV
3. Rated Frequency 60 Hz ‘60Hz
4. Rated Current of CB 200 A 250A
5. Rated Short circuit level (1's) 21 kA 21K
6. Rated Making Current SOKA 50KA
7. Re-striking Voltage Ratio 14 15
8. Duty Cycle O-1-€0-t-CO__[0-3min-CO-3min-CO
9. Making time ms Not applicable
10.Opening time ms 55ms
11. Are Duration ms ams
12. Total Breaking Time ms 67ms
13. Operating Mechanism Spring Charged | Spring Charged
[45.2 | DIMENSIONS OF FUSE =
1. Overall Length of Fuse 442 mm Not applicable
2. Overall Diameter mm Not applicable
49 TERMINATION / CABLE BOX
Cable box size Refer GA attached
Vertical distance (bushing to 750mm
4.10 | ENCLOSURE FOR OUTDOOR UNITS
1. Overall Dimensions of Width x Depth x Height | Co DMS
Completely Assembled RMU (xm xm xm)
2. Degree of Protection ‘As per 01-SDMS-01 SPS
3. Finish Method 7/2 GAL* Paint
4. Finish Color RAL 7033 [1 |* _RAL?033 _ |
Cee
Ec ww
DKA211 SerrencemPage 18 of 25VRNFS DATA SHEETS_Rev 01
Saudi Electricity Company G sly gS Aya penal Asc)
32-SDMS-01, Rey. 02
DATE: 31-10-2007G
SEC DISTRIBUTION MATERIALS SPECIFICATION
9.0 DATA SCHEDULE,
NON-EXTENCIBLE RING MAIN UNIT, SF6, 17.5 kV
(Sheet 3 of 3)
SEC Inquiry No. ____ tem No.
A, ADDITIONAL TECHNICAL INFORMATION OR FEATURES SPECIFIED BY
SEC:
ADDITIONAL SUPPLEMENTARY DATA OR FEATURES PROPOSED BY
BIDDER/VENDOR/SUPPLIER:
C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDORY SUPPLIER:
LIST OF DEVIATIONS & CLAUSES TO WHICH EXCEPTIONS ARE TAKEN
BY THE BIDDER/VENDOR/SUPPLIER: (USE SEPARATE SHEET IF
NECESSARY)
MANUFACTURER OF VENDOR / SUPPLIER
QUIPMEN
Name of Company
Location and Office
Address
‘Name and Signature of
‘Authorize
Representative
Official Seal / Stamp
DKA211 Page 19 of 25