Professional Documents
Culture Documents
4 Feb 9, 2018
Revision History
Revision Date Remark
1.0 2013-10-08 the first edition
1.1 2015-08-03 the first update
1.2 2017-01-01 the second update
1.3 2017-10-01 the third update
1.4 2018-02-07 the fourth update
1. Safety Information
Caution !
Before installing the product, please read the instructions.
Please check if all the control power, current, voltage are off before
connecting or taking apart.
1. Safety Information
2. Introduction ························································································ 1
2.1. Summary ··········································································································· 1
2.2. Main functions and features ······································································· 1
The pre-set sequences are available to set five times, and for both phase and ground, the
combined operations are possible within the range of 5 instantaneous or 5 times delayed
operating. The first interruption of a fault regarding instantaneous operation, is done
quickly and instantaneously, so that even the fuses in the system do not operate. After
setting time, it recloses back on. And the next interruption has a definite or inverse time
delay. Thus downstream fuses or other protection devices in the network have the chance
to operate and isolate the affected network section, restoring normal operation in the
remaining work. Therefore reclosers make the range of fault section to be limited.
Mainly Reclosers which are installed in overhead distribution line, provide the measurement
of electric current flowing in the distribution line. In case of load current occurrence and
fault detection, it opens and recloses repeatedly according to setting sequence, and at the
sametime, it transmits the status/receives the command to/from HOST and remote controls
of opening/reclosing to minimize the accident. Besides, it stores the whole events in
distribution line, provides the fault causes, and it performs remote monitoring and controls
by transmitting data through DNP3.0, IEC60870-5-101, IEC60870-5-104 protocols.
- 1 -
- Additionally user defined 4 types of curves available
- 3 steps protection characteristics implementable, established with definite time elements
and high-current elements
◆ Measuring Function
- Current, voltage magnitude and phase angle
- Symmetrical component about 3-phase voltage and current
- Active, reactive, apparent power, and power factor
- Active and reactive energy
- Frequency
- Power quality information : THD, sag/swell, harmonic 2~32th
◆ Control Function
- Recloser switch Open / Close control
- Battery Test control
- Preparatory control
- 2 -
◎ Fault Event
It stores and manages various fault information(occurred time, type of fault, operation
relaying element) during distribution line accidents up to 1024 cases in time sequence.
3. Technical Data
3.1. Power and Input/Output
◆ Power Supply
- 3 -
◆ Voltage Input
6 channels
(Va,Vb,Vc, Rated voltage : 4V (Max : ~8V) Under 0.1VA
Vr,Vs,Vt)
◆ Digital Input
Debounce Delay
Opto-Isolation 10 Port DC 24V Input Biased
(1~500ms)
◆ Digital Output
100mA/250VAC 5A/250VAC
Function Description
Input Physical input, virtual input,
Output Physical output, virtual output
AND For two inputs, AND gate
OR For two inputs, OR gate
NOT For one inputs, NOT gate
NAND For two inputs, NAND gate
XOR For two inputs, XOR gate
SR Latch of Set / Reset
Timer Timer with settings of Set, Reset, On/Off Delay Timer
D Flip-Flop To maintain froze the input signal for one PLC cycle
- 4 -
3.2. Environmental
Items Spec
Radiated -
IEC60255-22-4 10V/m
electromagnetic field
- 5 -
3.3. Communication
◆ System Interface Port1
Items Spec
DCD(1), RX(2), TX(3), DTR(4), GND(5)
9 Pin Signal
DSR(6), RTS(7), CTS(8), NC(9)
RS232C Speed 1200, 2400, 4800, 9600, 19200, 38400
Items Spec
RX(2), TX(3), GND(5)
9 Pin Signal
RTS(7), CTS(8),
RS232C Speed 1200, 2400, 4800, 9600, 19200, 38400
- 6 -
◆ System Interface Port3(option)
Items Spec
10/100 Base-T
Ethernet
Tr Isolation Circuit
◆ Maintenance Port(USB-A)
Items Spec
3.4. Measurements
kW,kVar,kVA 2% 0~99MW
THD 2% 0~200%
- 7 -
3.5. Mechanical Performance and Size
◆ Weight : 3.5 kg
◆ FRONT VIEW
- 8 -
◆ SIDE VIEW
310.00
343.00
91.00
- 9 -
◆ TOP VIEW
1.0.0t
84.0
225.0
260.0
- 10 -
◆ REAR VIEW
180.0
120.0
- 11 -
◆ Terminal Arrangement
RS232C(SCADA PORT)
RS232C(SCADA PORT)
DI (Status) Connector
DO (Control) Connector
ETHERNETConnector
AI(Voltage) Connector
AI(Current) Connector
- 12 -
◆ Pin Assignment(Up Side View)
1) Control Power Connector
4 3
24G 24VIN
2 1
FG FG
2) DI (Status) Connector
14 13 12 11 10 9 8
DI10 DI9 DI8 DI7
DI_COM3 DI_COM2 DI_COM1 (Handle
(Spare2) (Spare1) (Gas Low) Lock)
7 6 5 4 3 2 1
DI6 DI5 DI4 DI3 DI2 DI1
(Door (Charger DI_COM1
Open) Fail) (Batt Low) (AC Loss) (Close) (Open)
3) DO (Control) Connector
12 11 10 9 8 7
DO6- DO6+ DO3- DO3+
(Rec (Rec DO4- DO4+
Close) Close) (Bat Test-) (Bat Test+)
6 5 4 3 2 1
DO5- DO5+ DO2- DO2+ DO1- DO1+
(Rec (Rec
Open) Open) (Close-) (Close+) (Open-) (Open+)
4) AI(Voltage) Connector
10 9 8 7 6
V6 V4 V_COM V_COM V2
5 4 3 2 1
V5 V_COM V_COM V3 V1
5) AI(Current) Connector
6 5 4 3 2 1
IN(0)- IN(0)+ Icom IC IB IA
- 13 -
V6 V4 V_COM V_COM V2
V5 V_COM V_COM V3 V1
◆ Pin Assignment
- 14 -
IN(0)- IN(0)+ Icom IC IB IA
INTERNAL PANEL
0
13
DOOR
MS CONNECTOR
MODEM
CABLE HOLE
VENTILATOR
- 15 -
◆ Controller PCB
215.00
205.00
103.90
112.50
235.00
121.10
112.50
- 16 -
◆ Battery Check PCB
90.0 5.0
R7.0
10.0
50.0 50.0
87.0
R5.5
100.0
- 17 -
4. Installation Instructions
4.1. Front Panel and names of each part
3
4 5
7 10
8 9
11 14
12 13
15
16
- 18 -
2) LCD
It shows EPIC-R300’s measuring, setting, stored information, and search information.
It is convenient 20*4 character module LCD to move the screen through controling
manipulation button.
5) Manipulation Button
Button which controls LCD screen.
- Menu(M) Button : Button which moves to upper menu
- Up(▲) Button : Button which increases set value or moves the menu upwards
- Down(▼) Button : Button which decreases set value or moves the menu downwards
- Enter(⤶) Button : Button which enters the menu or saves set value
- 19 -
- Trip Info Freq LED : LED which shows the recloser operates by frequency protection
elements
- Power flow LED(Reverse) : LED which shows whether forward or reverse power
flow
- 20 -
15) Maintenance Port (USB-A)
It is USB-A port for maintenance. It uses MODBUS-RTU protocol as well as a special S/W
provided by NEOPIS.
o REMOTE CONTROL (R/C) Button : It is a button which selects remote and local control
mode. If you push the button, remote and local mode select are toggled. If REMOTE LED
is on, which means remote control mode is on so it is not possible to operate on local.
In order for local control, push the button to turn off REMOTE LED. Then operate at the
local as using OPEN/ CLOSE button on the side.
o OPEN Button : It is a button to open Recloser on local. If OPEN LED is turned on,
which means Recloser’s status is changed.
o CLOSE Button : It is a button to close Recloser on Local. CLOSE LED is turned off when
Recloser’s status is changed.
Buttons Function
Return to upper menu
Menu(M)
Cancel setting
Increase set value
Up(▲)
Move to upwards of menu
Decrease set value
Down(▼)
Move to downwards of menu
Move to lower menu
Enter(⤶) Save set value
Choose set value
- 21 -
4.2.2 LCD Display during Power Up
When EPIC-R300’s power is connected, the product name, EPIC-R300, and company name
is on LCD for a second. Then measuring screen shows voltage and current.
E P I C R 3 0 0
N E O P I S
Without controling key, the main measurement menu always returns to top screen 10
minutes later.
[ R/ C Con t r o l l e r ] Ia : 0 . 0 0 0. 00 / 0. 0 0
S e q N: 0 R /C : U n k n o wn Ib : 0 . 0 0 0. 00 / 0. 0 0
Rc l T : 0 Re s e t T : 0 Ic : 0 . 0 0 0. 00 / 0. 0 0
< No t Re a d y > In : 0 . 0 0 <AB C / RS T >
- 22 -
4.2.3 LCD Menu Operation
DI Status DI status
- 23 -
Fast Curve Setting fast operating value curve
Setting fast operating value control
Fast Multiplier
multiplier
Fast Time Add Set fast operating value time delayed
Set fast operating value min. response
Fast Min Response
time
Fast Reset Time Set fast reset time of definite time
- 24 -
Save Set Save the operation setting
- 25 -
Set operating angle directional
3I0 Angle
current
- 26 -
Reset Time Set reset time of reclosing counter
SEF SEF Rec Time 3rd Set 3rd reclosing operating time(SEF)
Reclose
SEF Rec Time 4th Set 4th reclosing operating time(SEF)
Time
Set reset time of reclosing
SEF Reset Time
counter(SEF)
Save Set Set SEF reclose setting
- 27 -
O-V Pickup Set pickup level for over voltage
- 28 -
CT Ratio Set CT ratio
- 29 -
Check Day Set auto checking day for battery
- 30 -
Set ground current level for Analog
Ground Current
High Alarm function
Set phase voltage level for Analog
Phase Voltage
High Alarm function
Set system power level for Analog
Alm System Power
High Alarm function
Select whether Analog High Alm
Enable High Alarm
function is available
Save config set value for Analog High
Save Config
Alarm
Set phase current level for Analog
Phase Current
Low Alarm function
Set ground current level for Analog
Ground Current
Low Alarm function
Set phase voltage level for Analog
Analog Phase Voltage
Low Alarm function
Low
Set system power level for Analog
Alm System Power
Low Alarm function
Select whether analog low alm
Enable Low Alarm
function is available
Save config set value for Analog Low
Save Config
Alarm
Door Open Contact Set contact type for door open(DI6)
Set condition of AC POWER LED
Miscell AC POWER LED
On(DI3)
aneous
Config Insulator Type Set type of insulator
Communica Mode RTS Off Delay Set RTS off delay time
tion m CTS Timeout Set CTS set timeout time
Control DCD Timeout Set DCD Set timeout time
- 31 -
Unsol Response Delay Set unsolicited response transmission
delay
- 32 -
PSTN Modem Select PSTN mode type, PPP, dialup
or SMS
Auto Hangup Time Set Auto hangup time
- 33 -
5. LCD Menu
5.1. Display
5.1.1. Display operation
Moving on display items is like below.
[ D I S P L A Y M E N U ]
-> 1 . P o w e r
2 . E n e r g y
3 . V o l t a g e / C u r r e n t
4 . T H D
5 . P h a s e D i f f
6 . R e s e t / S W C o u n t
7 . F a u l t C o u n t
8 . V I W e a r C o u n t
9 . D I S t a t u s
1 0 . S e l f - D i a g n o s i s
1 1 . D e v i c e I n f o
- 34 -
becomes clear to 0.
3) Voltage/Current : display items like Voltage (Va, Vb, Vc) and Current (Ia, Ib, Ic)’s
Positive Sequence, Negative Sequence, Zero Sequence
4) THD : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s Total Harmonic Distortion value
(measure up to h=2~32th)
5) Phase Diff : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s phase difference
6) Reset / SW Count : display Power On Reset Count and Watchdog Reset Count. display
the number of Switch’s On/Off
7) Fault Count : display each phase’s fault count and total fault count
9) DI Status : DI Status display. it shows 4 items at once. In order to see the next item,
use Up/Down Key to move. Display items are below,
- Open, Close, Handle Lock, External AC Fail, Over Discharge, Door, Charger fail
- Spare1,2, DI status. If DI status is Enable it shows 1.
12) Device Info : device’s information(name of the device, manufacturer, program version,
Web site display
- 35 -
⓵ 1st TRIP - 1st FAST TCC ⓶ 1ST RECLOSE INTERVAL
⓷ 2 ND
TRIP - 2 ND
FAST TCC ⓸ 2ND RECLOSE INTERVAL
⓹ 3rd TRIP - 1ST SLOW TCC ⓺ 3rd RECLOSE INTERVAL
⓻ 4th TRIP - 2nd SLOW TCC ⓼ 4th RECLOSE INTERVAL
⓽ 5 th
TRIP - 3 rd
SLOW TCC ⓾ LOCKOUT
The following figure shows the successful reclosing case that Recloser operates twice of
fast action and inputted. After the lapse of set-Reset Time, Recloser returns, and then
display of LED and LCD are changed from Progress into Ready status. If a fault occurs
again during Reset Time, when the counts of reclosing action reaches to total counts
which shall be calculated from remaining fault counts, the Recloser becomes locked out.
- 36 -
Recloser) after fault current. After detecting zero voltage, EPIC-R300 generates FI. With
protective device’s reclosing success, normal current and voltage are returned. If FI Auto
Reset was set, FI is reset automatically.
If not, push FI reset button on the front or it is reset with transmitted FI reset order in
remote. R300 is designed to generate FI not only for the case that R300 becomes tripped
itself against a fault, but also that other protection devices are tripped.
- Temporary Fault
- Permanent
Fault
Protection set value divides into 4 Groups to manage. Choose applied group through
Active Group setting.
- 37 -
[ S e t t i n g ME N U ] [ F u n c S e t t i n g ]
→ 1 . F u n c G r o u p 1 → 1 . P h a s e F a u l t
2 . F u n c G r o u p 2 2 . G r o u n d F a u l t
3 . F u n c G r o u p 3 3 . S E F F a u l t
4 . F u n c G r o u p 4 4 . T r i p & R e c l o s e
5 . S e l e c t G r o u p 5 . A u x i l i a r y F u n c
- 38 -
Trip Direction OFF/FWD/REV OFF Selection of phase fault direction
Set positive sequence voltage
3V1 Threshold 0~100 20 1 %
operating value
Fault Set positive sequence current
3I1 Threshold 0~100 20 1 %
Direction operating value
Set positive sequence current
3I1 Angle 0~359 300 1 °
operating angle
Dir Block OC NO/YES NO Set direction function block
1) Fast Operation
This menu is for setting “FAST” among Recloser’s operation sequence
2) Delay Operation
This menu is for setting “Delay” among Recloser’s operation sequence
3) Delay DT Protection
This menu is for setting Delay Definite Time regardless of targeted section among
Recloser’s operation sequence
4) HCT Protection
This menu is for setting the protection against the high current trip of Recloser
- 39 -
6) Inrush Restraint
When the circuit breaker is putted in order to supply the electricity to a load, Inrush
current is generated in a short time. Inrush restraint is a function to prevent Recloser’s
mis-operation of fault detection elements due to that kind of inrush current at the time of
energization in the line. Inrush restraint can be achieved by two methods ; multiplier can
be applied to pick-up current, and another way is, in case that 1st and 2nd harmonics
contents of generated current is over the constant current, to restrain current for the
setting time.
In order to detect Phase Fault, setting items and ranges are like below. The order to set is
like below.
1) Choose the menu with Up/Down Key. Press Enter Key to enter the menu.
[[ FF uu nn cc SS ee tt t t i i nngg] ] [ P h a s e F a u l t ]
->1
→ 1 . P
P hh aa ss ee FF aa uu l l t t → 1 . Op L e vv e l & T i me
2 . G
G rr oo uu nn dd FF aa uu l l t t 2 . B l o c k F l t P i c k u p
3 . SS EE FF FF aa uu l l tt 3 . F a u l t D i r e c t i o n
4 . TT rr ii pp &
& RR ee cc l l oos s ee
5 . A
A uu xx ii ll ii aa rr yy FF uunnc c
2) On Phase Fault menu, choose the setting item you want with Up/Down Key. Press Enter
Key to enter the setting item.
[ O P L e v e l & T i m e ] [ P i c k u p L e v e l ]
→1 . P i c k u p L e v e l S E T : 4 0 0 A
2 . F a s t C u r v e
3 . F a s t Mu l t i p l i e r ( 1 0 - 2 0 0 0 A : 1 A )
4 . F a s t T i m e A d d
5 . F a s t Mi n R e s p o n s e
6 . F a s t R e s e t T i m e
7 . D e l a y C u r v e
8 . D e l a y Mu l t i P l i e r
9 . D e l a y T i m e A d d
1 0 . D e l a y Mi n R e s p
1 1 . D e l a y R e s e t T i m e
1 2 . D e l a y D T L e v e l
1 3 . D e l a y D T T i m e
1 4 . H C T L e v e l
1 5 . H C T T i m e
1 6 . F u n c I n U s e
1 7 . S a v e S e t
- 40 -
3) Change set value with Up/Down Key. Press Enter Key to confirm. If you want to cancel
the changed set value, press M Key.
4) When the setting is completed, choose 17. Save Set to save the set value in backup
memory and come out from the item. Then the set value is applied to the device.
[ O P L e v e l & T i m e ]
→1 . P i c k u p L e v e l [ U p d a t e S e t t i n g ]
2 . F a s t C u r v e
3 . F a s t Mu l t i p l i e r → P r e s s E n t e r
4 . F a s t T i m e A d d
5 . F a s t Mi n R e s p o n s e
6 . F a s t R e s e t T i m e
7 . D e l a y C u r v e
8 . D e l a y Mu l t i P l i e r
9 . D e l a y T i m e A d d
1 0 . D e l a y Mi n R e s p
1 1 . D e l a y R e s e t T i m e
1 2 . D e l a y D T L e v e l
1 3 . D e l a y D T T i m e
1 4 . H C T L e v e l
1 5 . H C T T i m e
1 6 . F u n c I n U s e
1 7 . S a v e S e t
- 41 -
Delay DT Level 25~10000 OFF 1 A Set operating value at delay DT level
Delay DT Time 0.01~2 2.00 0.01 sec Set operating time at delay DT time
Set operating value at high current
HCT Level 25~10000 OFF 1 A
trip level
Set operating time at high current
HCT Time 0.01~1 0.04 0.01 sec
trip time
Func In Use NO/YES YES Set phase fault operation functions
A multiplier to prevent the
mis-recognizing as a fault by
Cold Load Multi 1~10 2 1
increasing a multiply of pick-up level
under cold load condition.
Set the return current of restraining
Return Normal I 0~30 0.3 0.01 sec
operation against cold load
Cold Load Time 0~180 3 1 min Set restraining time of cold load
Use Cold Load NO/YES NO Set cold load Use/Not use
Block flt
A multiplier to prevent the
Pickup mis-recognizing as a fault by
Inrush Multiply 1~10 2 1
increasing a multiple of pick-up level
under inrush condition
Inrush Time 0~30S 0.02 0.01 sec Set restraining time of Inrush
Use Inrush NO/YES NO Set inrush Use/Not use
2nd Harmonic 1-50 20 1 % A level of regarding 2nd harmonic as inrush
Use 2nd
0.02~1 0.02 0.01 sec Set 2nd harmonics Use/Not use
Harmonic
Trip Direction OFF/FWD/REV OFF Selection of ground fault direction
3V0 Threshold 0~100 20 1 % Set zero sequence voltage operating value
Fault
3I0 Threshold 0~100 20 1 % Set zero sequence current operating value
Direction
3I0 Angle 0~359 300 1 ° Set zero sequence current operating angle
Dir Block OC NO/YES NO Set direction function block
To detect SEF Fault, setting items and ranges are like below.
3I0 Pickup 0.1~20 5.0 0.1 A Set 3I0 current operation value
-3V0 Pickup 0~80 30 1 % Set 3V0 voltage operation value
Op Level
SEF Reset Time 0.00~1.00 0.00 0.01 sec Set SEF reset time of definite time
& Time
OFF/ALARM/
Func In Use OFF Set SEF fault operation functions
TRIP
- 42 -
Inrush Multiply 1~10 2 1 Set inrush control multiplier
Inrush Time 0~30 0.02 0.01 sec Set inrush operating time
Block Flt Use Inrush NO/YES NO Set phase fault inrush Use/Not use
Pickup 2nd Harmonic 1~50% 20 1 % Set 2nd harmonic inrush control level
2nd_H Detect Time 0.02~1 0.02 0.01 sec Set 2nd harmonic time level
Use 2nd Harmonic NO/YES NO Set 2nd harmonic inrush Use/Not use
Fault Op Angle 0~345 90 1 ° Set operating angle
Direction Op Time 0.1~30 1.0 0.1 sec Set operating time
5) Sequence Coordination
When operating with 2 or more Recloser connected in series in distribution line, in order
to prevent the operation of all Reclosers’ being opened at the same time which are
installed both in power supply side and in load side, the Sequence Coordination function
is used to. This function is that, when multiple Reclosers in load side are connected to
- 43 -
one Recloser on the power supply side, only the Recloser experienced a fault is set to
perform the opening operation.
As shown below, if the Recloser in power supply is Active state in Sequence Coordination
mode, in case of line fault, while Recloser in power supply detects the fault current and
operates the opening delayed action, it returns to normal situation by the operation of
Recloser in load side, and then Recloser in power supply will increase the operation
sequence only by one time. Therefore, only sequence of Recloser(power supply side) is in
progress without opening operation, so that even when load Recloser operates to delay
action, Recloser from supply side does not progress the other instantaneous actions in
sequence, but operates to delay action in the same way with load Recloser. If the
reclosing function is restrained, the Sequence Coordination function does not work.
1) All Reclosers both in supply side and the load must be set at same instantaneous time,
delay characteristics and the same minimum operating Pickup current value. (If the
minimum operating pickup current is wrongly set, the pickup value of power supply must
be larger than the load)
3) Recloser in supply should resume 100ms or more of delay time than load Recloser, or
the value of the minimum operating pickup current must be larger than that of load
Recloser.
4) The reset time of power supply Recloser must be set longer than the longest reclosing
time of the load Recloser. This is to prevent Recloser in supply side to be reset mode
during reclosing of load Recloser.
- 44 -
The setting items and ranges of Trip & Recloser are as follows.
2) Sync Check : To check the voltage synchronization of the Source and Load side.
Once the voltages of the Source side and Load side are maintained for the set time,
within the setting range, the Sync Check is “OK”.
- 45 -
If the voltages of Source and Load sides are out of phase setting range, Sync Fail occurs
and then sync LED operates.
9) Close Interlock : Settings associated with the function of inhibiting the input depending
on the situation of power system, when Recloser is applied.
For the case of Live Load function with “Enable”, it inhibits the input only when the
voltage is applied to both Source side and Load side. And, in case of Sync Fail function
with “Enable”, it inhibits the input when the synchronization of voltage on the Source side
and Load side is not suitable.
10) Loop Automation : When a fault occurs in a distribution line, protection device
- 46 -
perfoms protecton operation and the load in the lower side of protection devise will
experience a power outage. Thus, the blackout range of the distribution line are spread
to normal condition section as well as fault occurrence section.
For coping with those case, loop control function will operate in the way of separating the
fault section, and supplying power to normal section, then it helps to minimize the outage
time.
EPIC-R300 provides those loop control function which is operable in service only by using
the information about voltage, current, and operating state.
Depending on the configuration of recloser being installed, 3 modes of loop control can
be selected.
- Feeder recloser : the recloser is installed near the substation or inside.
- Midpoint recloser : installation point is between feeder recloser and tie recloser.
- Tie-point recloser : the recloser are usually installed at tie point where two distribution
lines are interconnected.
1) feeder recloser
Protection elements are generally operate when downstream fault occurs in the distribution
line. If it detects voltage loss at power supply, recloser will trip after set time.
In both cases that trip by protection elements and remote operation, loop control function
is automatically stopped.
2) Mid point recloser
Protection elements are generally operate when downstream fault occurs in the distribution
line. If, due to the action at power source side, it detects voltage loss at both sides, it
shall be automatically changed into another setting group after set time.
After downstream recloser or tie point recloser’s operation, the power supply starts to
provide from reverse side. For this moment, the reclosing action shall be hold for a certain
period of time.
3) Tie-point recloser
When voltage loss is detected in the set side, it close after the set time.
After closing, when the fault is detected, it stops and holds reclosing for a sertain period
of time.
The operation by protection elements is possible after normalization of reclosing element.
The activated operation group shall be changed according to feeding direction or setting
- 47 -
- “Tie SW open time”
This is the time required to open a “Tie Sw open” in order to repair the distribution lines
to the normal state, if power is supplied from both Tie Sw after the fault is recovered.
- “Tie Sw Source”
It is used to determine the conditions of Tie Sw closing.
BOTH : If any loss for both side, it operates after Tie Sw closing time.
ABC : ABS side is power side, and when RST side is de-energized, then it closes after the
close time.
RST : RST side is power side, when RST side is de-energized, then it closes after the close
time.
1) Feeder recloser trips when the voltage at power supply side is lost.
2) Mid recloser changes to Alt group setting when the voltage of power supply and load
side is dead due to the trip of protection device at power supply, and also changes to
the single shot mode which does not operate reclosing.
3) Tie recloser closes if one side voltage is lost.
4) Feeder recloser closed when the voltage at power supply become live after it is
repaired.
5) Mid recloser closes when the voltage is supplied to both side.
6) Tie recloser opens when the voltage is supplied to both ends.
<Table 5-5> Auxiliary Function
Category Item Range Default Step Unit Explanation
Voltage setting to reset phase
Volt On 50~90 90 1 %
loss(standard on rating voltage)
Voltage setting to set phase
Volt Off 35~75 75 1 %
Open Line loss(standard on rating voltage)
Detect If voltage is kept under volt off
Delay Off 0.1~30 30 0.1 sec
during delay time
Show whether open line detect
Use Func NO/YES YES
function is available
Phase Off 5~60 5 1 ° degree setting to check phase sync
Delay Time 0.1~30 30 0.1 sec delay time setting to check phase sync
Sync Check
Show whether sync check function is
Use Func NO/YES YES
available
Live Line Volt Level 10~90 30 1 % Set voltage level monitoring operation
Detect Detect Time 0.05~1 0.10 0.01 sec Set voltage level operating time
I2/I1 Pickup 30~100% 50 1 % Set negative current operating level
Delay Time 0.1~10 10.0 0.1 sec Set negative OC operation time
Negative I1 Threshold 5~200 10 1 A Set Positive current threshold value
OC 2nd Harmonic Blk OFF/ALM/TRIP OFF Select 2nd Harmonic block/ non-block
Set negative OC fault operation
Func In Use OFF/ALM/TRIP OFF
functions, No Use/Alarm/Trip
- 48 -
U-V Pickup 30~98 75 1 % Set pickup level for under voltage
Under U-V Op Time 0.1~100 3 0.1 sec Set operation time for under voltage
Voltage Set whether under voltage function is
Use Func OFF/ALM/TRIP OFF
available
O-V Pickup 102~150 120 1 % Set pickup level for over voltage
Over O-V Op Time 0.1~100 3 0.1 sec Set operation time for over voltage
Voltage Set whether over voltage function is
Use Func OFF/ALM/TRIP OFF
available
U-F Pickup 47~59.98 49.8 0.01 Hz Set pickup level for under frequency
Set operation time for under
Under U-F Op Time 0.1~60 1 0.1 sec
frequency
Frequency
Set whether under frequency function
Use Func OFF/ALM/TRIP OFF
is available
O-F Pickup 50.02~63.00 60.02 0.01 Hz Set pickup level for over frequency
Over O-F Op Time 0.1~60 1 0.1 sec Set operation time for over frequency
Frequency Set whether over frequency function is
Use Func OFF/ALM/TRIP OFF
available
Close Live Load NO/YES NO Select whether live load is available
Interlock Sync Fail NO/YES NO Select whether sync fail is available
OFF/FEEDER/MI
Loop Selection OFF Select operating mode for the recloser
D/TIE
Deadbus Open Set open time for determining
0~600 0 1 sec
Time distribution line’s dead line state
Tie Sw Open
0~600 0 1 sec Set open time for tie sw
Time
Tie Sw Source BOTH/ABC/RST BOTH Select whether Tie sw source is ABC or RST
Loop
Tie Sw Close
Automation 0~600 0 1 sec Set close time for tie sw
Time
Rec Block Time 0~600 60 1 sec Set Reclosing Blocking Time
Set whether restoration after clearing
Enable Restore Disable/Enable Disable
fault
Rec Close Time 0~600 30 1 sec Set recloser closing time after open
Set delta I level to restore for Tie
Tie On Delta I 5~95 5 1 %
recloser after fault
[ P r i ma r y G r o u p ]
S E T : 1
( 1 - 4 : 1 )
- 49 -
5.3. Configuration Menu
It provides menus for analog current and voltage input related setting, Debounce Time
setting to prevent DI chattering, DO output pulse adjustment related setting, Event Log
information setting and clear related setting.
5.3.1. Analog
Analog voltage / current input related setting items and ranges are like below.
2) On Analog menu, choose the item you want with Up/Down Key. Press Enter Key to
enter the item.
- 50 -
[ A n a l o g Me n u ]
->1 . L i n e C o n f i g
2 . F r e q u e n c y
3 . R a t e d V o l t
4 . C T r a t i o
5 . N CTT r a t i o
6 . A v g I n t e r v a l
7 . S e l e c t F I R e s e t
8 . D i s p l a y V o l t a g e
9 . P h a s e P o s i t i o n
1 0 . P h a s e R o t a t i o n
1 1 . S o u r c e S i d e
1 2 . E n e r g y L o g D u t y
1 3 . C l o s i n g D e l a y [ L I N E C O N F I G ]
1 4 . C h e c k V f o r F I S E T : 3 P 4 W
1 5 . R e c l a i m T f o r F I
1 6 . I mp o r t K e y D e l a y ( 3 P 4 W/ 3 P 3 W)
1 7 . F a i l V S e n s o r
1 8 . S a v e C o n f i g
3) Change set value with Up/Down Key. Press Enter Key to check. If you want to cancel
the changed set value, press M Key.
4) After change, choose 18. Save Config to save the set value in backup memory and
come out from the item. Then the set value is applied to the device.
[ A n a l o g Me n u ]
->1 . L i n e C o n f i g
2 . F r e q u e n c y
3 . R a t e d V o l t
4 . C T r a t i o
5 . N CTT r a t i o
6 . A v g I n t e r v a l
7 . S e l e c t F I R e s e t
8 . D i s p l a y V o l t a g e
9 . P h a s e P o s i t i o n
1 0 . P h a s e R o t a t i o n
1 1 . S o u r c e S i d e
1 2 . E n e r g y L o g D u t y
1 3 . C l o s i n g D e l a y [ U p d a t e S e t t i n g ]
1 4 . C h e c k V f o r F I
1 5 . R e c l a i m T f o r F I - > P r e s s E n t e r
1 6 . I mp o r t K e y D e l a y
1 7 . F a i l V S e n s o r
1 8 . S a v e C o n f i g
- 51 -
5.3.2. DI Debounce Time
It is a menu to set debounce time to prevent DI Chattering. It is available to set on each channel.
During set time, DI status value should be kept to be considered with the changed value.
- 52 -
Ib Gain Adjust 10~2000 0 1 A Adjust current Ib’s gain
Ic Gain Adjust 10~2000 0 1 A Adjust current Ic’s gain
In Gain Adjust 10~2000 0 1 A Adjust current In’s gain
Va Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Va’s gain
Vb Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vb’s gain
Vc Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vc’s gain
Vr Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vr’s gain
Vs Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vs’s gain
Vt Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vt’s gain
Delete save gain data in backup
Clear Gain Data
memory
The way to set is identical with 5.3.1
5.3.6. Waveform
Settings associated with the condition of capturing the waveform and storing it.
“1. sample rate” : to select the sample rate which saves a waveform per one cycle.
“2. Record size” : to select the length of the waveform.
“3. Pre-cycle” : to set the stotage size before a failure occurance as a ratio of the total
size.
“4. Post-cycle” : to set the stotage size after a failure occurance as a ratio of the total
size.
*option
Item Range Default Step Unit Explanation
Auto-Check Day 1~31 1 1 day Set auto checking day for battery
Detect Batt-Low 18.7~24.0 21.6 0.1 V Set voltage level for battery low
Cut-Off Voltage 18.7~23.0 20.8 0.1 V Set voltage level for battery cutoff
Cut-Off Delay 1~600 60 1 s Set delay time for battery cutoff
- 53 -
5.3.8. V/I Unbalance
Settings relating to the level and operating time for detecting the unbalance of Voltage
and Current.
5.3.9. Sag/Swell
Settings related to the level and operating time to detect Sag, Swell, and Interruption.
5.3.11. VI Wear
Select VI type which is used in the recloser, and it displays residual contact wear for each
phase’ VI and total operation times.
- 54 -
Item Range Default Step Unit Explanation
Set the type of the VI used in the
Max Op Count 1000~10000 2000 1
recloser
Set alarm level for residual contact
Alarm Level 0~100 45 1 %
wear
Duty Factor A 0~100 100 1 % Set duty factor for A phase’s VI
Duty Factor B 0~100 100 1 % Set duty factor for B phase’s VI
Duty Factor C 0~100 100 1 % Set duty factor for C phase’s VI
Delete save wear information in
Clear Wear Info
backup memory
- 55 -
<Table 5-19> Misc. Config
Item Range Default Step Unit Explanation
Door Open Contact N.O(A)/N.C(B) N.O(A) Set contact type for door open(DI6)
AC Fail/AC
AC POWER LED AC Fail Set contact type for AC POWER(DI3)
Normal
Insulator Type Mold/SF6-GAS Mold Set contact type for Gaslow(DI7)
- 56 -
<Table 5-21> DNP Config
Item Range Default Step Unit Explanation
D/L Retry 0~2 0 1 Set the number of data link layer retry
- 57 -
5.4.5. IEC104 Config
It is a menu to set IEC870-5-104 communication related item.
<Table 5-23> IEC104 Config
Item Range Default Step Unit Explanation
Conn Timeout(t0) 1~255 30 1 sec Set connection timeout
APDU Timeout(t1) 1~255 15 1 sec Set APDU timeout
Ack Timeout(t2) 1~255 10 1 sec Set ack timeout
Test Period(t3) 1~255 20 1 sec Set time period
Select whether spontaneous
Xmt Spontaneous Disable/Enable Disable
response function is available
Max Xmt I-APDU(k) 1~32767 15 1 Set max transmitting I-APDU
Max Rcv I-APDU(w) 1~32767 10 1 Set max receiving I-APDU
The way to set is identical with 5.3.1
- 58 -
5.4.9. SMS Config
Settings for using the SMS(short message service).
1) Press Enter Key to change the time. Then the cursor blinks on the year you want to change.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
2) To change the month, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 7
T i m e : 1 4 : 3 0 : 2 6
- 59 -
3) To change the date, press Enter Key then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 1 1
4) To change the time, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 3 0 : 2 6
5) To change the minute, press Enter Key. Then the cursor blinks.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 2 6
6) To change the second, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 1 1
7) After changing, press Enter Key then the menu below shows. Press Enter Key again
then the edited time is saved.
[ U p d a t e S e t t i n g ]
- > P r e s s E n t e r
- 60 -
5.6. Event View Menu
It is a menu to check various recorded information in EPIC-R300. Event List shows in a
chronological order from the latest one. You can check information with Up/Down Key.
There is information of Event List and maximum number of storage below.
- 61 -
APPENDIX A. - COMTRADE File’s Formats
The COMTRADE record generated by your device consist of two files: the configuration
file (*.cfg) and the data file (*.dat). These files are structured as described in IEEE Power
Engineering Society C37.111 COMTRADE data format. Please refer to the IEC website for
the most up-to-date COMTRADE data format information.
- 62 -
- 63 -
Configuration field details
The following table describes the channel identifier(ch_id) and channel phase identification
(ph) values:
- 64 -
Example - configuration file
- 65 -
APPENDIX B. TC Curve
1. TC Curve
The EPIC-R300 supports analog recloser curves, IEC curves, ANSI/IEEE curves, and KEPCO
curves, The list is as follows.
No. 1 2 3 4 5 6 7 8 9 10
TC Curve A B C D E K L M N P
No. 11 12 13 14 15 16 17 18 19 20
TC Curve R T V W Y Z 1 2 3 4
No. 21 22 23 24 25 26 27 28 29 30
TC Curve 5 6 7 8 8* 9 11 13 14 15
No. 31 32 33 34 35 36 37 38 39 40
No. 41 42 43 44 45 46 47 48 49 50
◆ TC curve equation
The equation of TC curve supported by EPIC-R300 is as follows.
×
- I = Fault current
- I> = Pick up current setting value
- k = Multiplier setting value
Standard Curve A B C
Normal Inverse(NI) 0.14 0.02
Very Inverse(VI) 13.5 1
IEC Extremely Inverse(EI) 80 2
Long-time Inverse(LI) 120 1
Short-time Inverse(SI) 0.05 0.04
Moderately Inverse(MI) 0.0515 0.114 0.02
Very Inverse(VI) 19.61 0.491 2
IEEE/ANSI
Extremely Inverse(EI) 28.2 0.1217 2
Normal Inverse(NI) 0.0086 0.0185 0.02
Long-time Inverse(U8) 5.95 0.18 2
ANSI
Short-time Inverse(U2) 0.2394 0.0169 0.02
Normal Inverse(NI) 0.011 0.042 0.02
ES
Very Inverse(VI) 3.985 0.1084 1.95
- 66 -
2. TC Curve 1~4
1
2
3
102 4
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 67 -
3. TC Curve 5~8
5
6
7
102 8
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 68 -
4. TC Curve 8*~13
8*
9
11
102 13
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 69 -
5. TC Curve 14~18
14
15
16
102 18
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 70 -
6. TC Curve A~D
A
B
C
102 D
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 71 -
7. TC Curve E~M
E
K
L
102 M
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 72 -
8. TC Curve N~T
N
P
R
102 T
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 73 -
9. TC Curve V~Z
V
W
Y
102
Z
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 74 -
10. TC Curve IEC NI~SI
IEC NI
IEC VI
IEC EI
104 IEC LI
IEC SI
103
102
Time[sec]
101
100
10-1
100 101
Current In Multiplies of Setting
- 75 -
11. TC Curve IEEE MI~NI
IEEE MI
IEEE VI
IEEE EI
103 IEEE NI
102
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 76 -
12. TC Curve ANSI U8, U2
ANSI U8
ANSI U2
103
102
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 77 -
13. TC Curve ES NI, VI
ES NI
ES VI
102
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 78 -
14. TC Curve KEPCO N1~N4
N1
N2
N3
102 N4
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 79 -
15. TC Curve DEF 1S, 10S
DEF 1S
DEF 10S
101
Time[sec]
100
10-1
100 101
Current In Multiplies of Setting
- 80 -
- 81 -