You are on page 1of 87

User Manual Document Version 1.

4 Feb 9, 2018
Revision History
Revision Date Remark
1.0 2013-10-08 the first edition
1.1 2015-08-03 the first update
1.2 2017-01-01 the second update
1.3 2017-10-01 the third update
1.4 2018-02-07 the fourth update
1. Safety Information

Caution !
Before installing the product, please read the instructions.

Please make sure if the product is broken before installing.

Please check if all the control power, current, voltage are off before
connecting or taking apart.

The terminal has a high current and high voltage so it can be


life-threatening when you touch it directly.

The setting should be done along the distribution line configuration.


The machine shows wrong information or malfunction caused by a
different setting from the distribution line configuration.

Connect the side connector along correct connector number with


current/voltage/DO/DI.

The appliance’s earthing terminal should be earthed to ground.


CONTENTS

1. Safety Information

2. Introduction ························································································ 1
2.1. Summary ··········································································································· 1
2.2. Main functions and features ······································································· 1

3. Technical Data ··················································································· 3


3.1. Power and Input/Output ·············································································· 3
3.2. Environmental ·································································································· 5
3.3. Communication ······························································································· 6
3.4. Measurements ································································································· 7
3.5. Mechanical Performance and Size ····························································· 8

4. Installation Instructions ···································································· 18


4.1. Front Panel and names of each part ······················································· 18
4.2. LCD Control and Setting ············································································· 21
4.2.1 Button Function ····················································································································· 21
4.2.2 LCD Display during Power Up ·························································································· 22
4.2.3 LCD Menu Operation ·········································································································· 23
4.2.4. LCD Menu Items ·················································································································· 23
4.3. Order of Installation Test Operation ························································ 33

5. LCD Menu ··························································································· 34


5.1. Display ··············································································································· 34
5.1.1. Display operation ················································································································· 34
5.1.2. Display Menu ························································································································ 34
5.2. Protection Setting Menu ·············································································· 35
5.2.1. Operation Principle of Recloser ······················································································· 35
5.2.2. Operation Principle of FI ··································································································· 36
5.2.3. Phase Fault ···························································································································· 38
5.2.4. Ground Fault ························································································································· 41
5.2.5. SEF Fault ································································································································· 42
5.2.6. Trip & Reclose ······················································································································ 43
5.2.7. Auxiliary Func ························································································································ 45
5.2.8. Select Group ·························································································································· 49
5.3. Configuration Menu ······················································································· 50
5.3.1. Analog ····································································································································· 50
5.3.2. DI Debounce Time ·············································································································· 52
5.3.3. DO Pulse Width ··················································································································· 52
5.3.4. Backup Set / Clear ·············································································································· 52
5.3.5. Analog Gain Adjust ············································································································· 52
5.3.6. Waveform ······························································································································· 53
5.3.7. Check Auto Battery ············································································································· 53
5.3.8. V/I Unbalance ······················································································································· 53
5.3.9. Sag/Swell ································································································································ 54
5.3.10. THD Alarm ··························································································································· 54
5.3.11. VI Wear ································································································································ 54
5.3.12. Analog High Alm ··············································································································· 54
5.3.13. Analog Low Alm ················································································································ 55
5.3.14. Misc. Config ························································································································ 55
5.4. Communication Menu ··················································································· 56
5.4.1. SCADA Port ··························································································································· 56
5.4.2. Modem Control ···················································································································· 56
5.4.3. DNP Config ····························································································································· 56
5.4.4. IEC101 Config ························································································································· 57
5.4.5. IEC104 Config ························································································································· 58
5.4.6. TCP/IP Config ·························································································································· 58
5.4.7. PSTN Modem ·························································································································· 58
5.4.8. PPP Config ······························································································································· 58
5.4.9. SMS Config ······························································································································ 59
5.4.10. Time Sync Option ·············································································································· 59
5.5. Time Set Menu ······························································································· 59
5.6. Event View Menu ··························································································· 61

APPENDIX A. COMTRADE File’s Formats ··········································· 62


APPENDIX B. RECLOSER Characteristic Curve ·································· 66
1. TC Curve ·················································································································· 66
2. TC Curve 1~4 ······································································································· 67
3. TC Curve 5~8 ······································································································· 68
4. TC Curve 8*~13 ··································································································· 69
5. TC Curve 14~18 ·································································································· 70
6. TC Curve A~D ······································································································ 71
7. TC Curve E~M ····································································································· 72
8. TC Curve N~T ······································································································ 73
9. TC Curve V~Z ······································································································ 74
10. TC Curve IEC NI~SI ···························································································· 75
11. TC Curve IEEE MI~NI ························································································· 76
12. TC Curve ANSI U8, U2 ······················································································ 77
13. TC Curve ES NI, VI ····························································································· 78
14. TC Curve KEPCO N1~N4 ·················································································· 79
15. TC Curve DEF 1S, 10S ······················································································· 80
2. Introduction
2.1. Summary
Reclosers are used in distribution system. In case of line fault, due to temporarily
overcurrent, Reclosers can break and make currents several times, thus avoiding longer
network interruptions due to temporary faults. But, in case of permanent fault, because
fault current is still detected after trip and reclosing actions of pre-set sequences, Recloser
is locked out finally as opened.

The pre-set sequences are available to set five times, and for both phase and ground, the
combined operations are possible within the range of 5 instantaneous or 5 times delayed
operating. The first interruption of a fault regarding instantaneous operation, is done
quickly and instantaneously, so that even the fuses in the system do not operate. After
setting time, it recloses back on. And the next interruption has a definite or inverse time
delay. Thus downstream fuses or other protection devices in the network have the chance
to operate and isolate the affected network section, restoring normal operation in the
remaining work. Therefore reclosers make the range of fault section to be limited.

Mainly Reclosers which are installed in overhead distribution line, provide the measurement
of electric current flowing in the distribution line. In case of load current occurrence and
fault detection, it opens and recloses repeatedly according to setting sequence, and at the
sametime, it transmits the status/receives the command to/from HOST and remote controls
of opening/reclosing to minimize the accident. Besides, it stores the whole events in
distribution line, provides the fault causes, and it performs remote monitoring and controls
by transmitting data through DNP3.0, IEC60870-5-101, IEC60870-5-104 protocols.

2.2. Main functions and features


◆ Protection Function
- Fault Detection about phase and ground fault
- SEF(Sensitive Earth Fault) used on non-grounded network
- Inrush current control function during fault detection
- In case of Cold Load, Fault Pickup Level adjustment
- Phase Loss Detection
- Phase Sync Fail Detection about source and load voltage
- Automatic breaking and reclosing by detecting phase and ground fault
- Detecting fault and monitoring the status in distribution line
- Built-in 50 types of recloser curves including IEC, ANSI/IEEE, McGraw Edison Recloser
curve
- Equiped with 4 types of curves(N1, N2, N3, N4) developed by Korea Electric Power
Research Institute(KEPRI, under KEPCO)

- 1 -
- Additionally user defined 4 types of curves available
- 3 steps protection characteristics implementable, established with definite time elements
and high-current elements

◆ Measuring Function
- Current, voltage magnitude and phase angle
- Symmetrical component about 3-phase voltage and current
- Active, reactive, apparent power, and power factor
- Active and reactive energy
- Frequency
- Power quality information : THD, sag/swell, harmonic 2~32th

◆ Control Function
- Recloser switch Open / Close control
- Battery Test control
- Preparatory control

◆ State Monitoring Function


- Recloser Open / Close status
- Handle locked status
- Gas pressure low status(option)
- External AC low status
- Battery overcharge status
- Door Open
- Spare status 1,2
- Over dischager
- Chager fail

◆ Various Communication Interface


- System Interface Port : RS232C
DNP3.0
IEC60870-5-101
- System Interface Port(option) : Ethernet
DNP3.0 over TCP/IP
IEC60870-5-104
- Maintenance Port : USB-A
MODBUS RTU

◆ Various Event Information


◎ Operation Event
It stores and manages events occurred during operation such as control(On, Off, Trip)event
and diagnosis event up to 30,000 cases in time sequence.

- 2 -
◎ Fault Event
It stores and manages various fault information(occurred time, type of fault, operation
relaying element) during distribution line accidents up to 1024 cases in time sequence.

◆ Fault Wave Storage Function


It saves and manages the latest fault 160Cycle(16Sample standard) sample data up to 6
cases. The user can use save fault wave to analyze the cause of faults.

◆ Convenient interface for users


Through RS232 communication port, it is convenient to manage various set values and
stored measuring information search on PC.(using company supplied S/W)

◆ Self-diagnosis and Backup functions during power-off


EPIC-R300 operates self-diagnosis such as CPU check, memory error diagnosis, I/O
diagnosis, and control power diagnosis. It saves warning output and diagnosis event on
occasion of failure. Therefore the user can have a speedy response.

3. Technical Data
3.1. Power and Input/Output
◆ Power Supply

Voltage input Power consumption

DC 24V within 10W

◆ Current Input(Ground System)

Channel Rating input Input burden

4 channels Rated current(Ia,Ib,Ic) : 1A (Max:12A)


Under 1VA
(Ia,Ib,Ic,In) Rated current(In) : 1A (Max:12A)

◆ Current Input(Non-Ground System)

Channel Rating input Input burden

4 channels Rated current(Ia,Ib,Ic) : 1A (Max:12A)


Under 1VA
(Ia,Ib,Ic,I0) Rated current(I0) : 1A (Max:12A)

- 3 -
◆ Voltage Input

Channel Rating input Input burden

6 channels
(Va,Vb,Vc, Rated voltage : 4V (Max : ~8V) Under 0.1VA
Vr,Vs,Vt)

◆ Digital Input

Input Type Point Number Input Circuit Others

Debounce Delay
Opto-Isolation 10 Port DC 24V Input Biased
(1~500ms)

◆ Digital Output

Control contact (Photomos) Normal contact

100mA/250VAC 5A/250VAC

2EA 4EA, 8EA(option)

Purpose : Recloser Open / Close Purpose : Battery Test / Spare

◆ Logic Functions (option)


EPIC-R300 provides logic function. It can output the information about inside device with
DO, DI, etc, which are processed by using the functions of AND, OR, NOT, Timer, SR
Latch, etc, with DO, DI. And it can also be passed to the upper system through
communication.
Basic logic function is as shown below table.

Function Description
Input Physical input, virtual input,
Output Physical output, virtual output
AND For two inputs, AND gate
OR For two inputs, OR gate
NOT For one inputs, NOT gate
NAND For two inputs, NAND gate
XOR For two inputs, XOR gate
SR Latch of Set / Reset
Timer Timer with settings of Set, Reset, On/Off Delay Timer
D Flip-Flop To maintain froze the input signal for one PLC cycle

- 4 -
3.2. Environmental
Items Spec

Operating -25 ~ 85℃


Temperature
Storage -40 ~ 95℃

Humidity < 95% RH

Altitude < 4000m

Insulation Resistance DC500V, > 100MΩ

Dielectric Withstand AC 60Hz 2000V/1Min

IEC60255-5 6kV : Current


Impulse
IEC60255-5 4kV : Voltage, Power, DIO
High Frequency
IEC60255-22-1 2.5kV
Disturbance

EFT/Burst IEC60255-22-4 Class A : 4kV

Radiated -
IEC60255-22-4 10V/m
electromagnetic field

ESD 60255-22-2: Contact(6kV), Air(8kV)

EMI IEC 60255-25

Vibration IEC 60255-21-1 class 2

- 5 -
3.3. Communication
◆ System Interface Port1

Items Spec
DCD(1), RX(2), TX(3), DTR(4), GND(5)
9 Pin Signal
DSR(6), RTS(7), CTS(8), NC(9)
RS232C Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

support DNP3.0 Subset Level3

DNP3.0 multi-frame transmission


Protocol
Enable / Disable Unsolicited Response for each class

Save Event which is not transmitted

support single character NACK


IEC60870
-5-101 Regular update about measurement data
Protocol
capable to set address size

◆ System Interface Port2(can select RS232c or RS485)

Items Spec
RX(2), TX(3), GND(5)
9 Pin Signal
RTS(7), CTS(8),
RS232C Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

9 Pin Signal 485+(6), 485-(9)

RS485 Speed 1200, 2400, 4800, 9600, 19200, 38400

Opto-Isolation Circuit (Dielectric level : 1kV)

MODBUS-RTU Slave Mode : To communicate with SCADA

- 6 -
◆ System Interface Port3(option)

Items Spec
10/100 Base-T
Ethernet
Tr Isolation Circuit

DNP3.0 over Network Access Protocol for DNP3.0


TCP/IP
Using standard TCP/IP network
Protocol
(connection-oriented secure data transmission)

Network Access Protocol for IEC60870-5-101


IEC60870
-5-104 Application layer is based on IEC60870-5-101
Protocol Using standard TCP/IP network
(connection-oriented secure data transmission)

◆ Maintenance Port(USB-A)

Items Spec

4 Pin Signal VCC(1), D-(2), D+(3), GND(4)


USB-A
Speed 38400bps
setting, measuring, confirmation function of stored information
MODBUS (failure information, driving information, Wave)
-RTU
Maximum 120 point Read at once
Protocol
Supply special SW for Maintenance

3.4. Measurements

Items Accuracy Range

Voltage 1% 40kV (Including PT ratio)

Current 1% 12,000A (Including CT ratio)

kW,kVar,kVA 2% 0~99MW

Power Factor 2% 0~±1

Frequency ±0.01Hz 45~65Hz

kWh, kVarh 2% 0~999999999kW

THD 2% 0~200%

- 7 -
3.5. Mechanical Performance and Size
◆ Weight : 3.5 kg
◆ FRONT VIEW

<Figure 3-1> Front View

- 8 -
◆ SIDE VIEW

310.00
343.00

91.00

<Figure 3-2> Side View

- 9 -
◆ TOP VIEW

1.0.0t
84.0
225.0
260.0

<Figure 3-3> Top View

- 10 -
◆ REAR VIEW

180.0

120.0

<Figure 3-4> Rear View

- 11 -
◆ Terminal Arrangement

RS232C(SCADA PORT)

RS232C(SCADA PORT)

Control Source Connector

DI (Status) Connector

DO (Control) Connector

ETHERNETConnector
AI(Voltage) Connector

AI(Current) Connector

<Figure 3-5> Terminal Arrangement

- 12 -
◆ Pin Assignment(Up Side View)
1) Control Power Connector
4 3
24G 24VIN
2 1
FG FG

2) DI (Status) Connector
14 13 12 11 10 9 8
DI10 DI9 DI8 DI7
DI_COM3 DI_COM2 DI_COM1 (Handle
(Spare2) (Spare1) (Gas Low) Lock)
7 6 5 4 3 2 1
DI6 DI5 DI4 DI3 DI2 DI1
(Door (Charger DI_COM1
Open) Fail) (Batt Low) (AC Loss) (Close) (Open)

3) DO (Control) Connector
12 11 10 9 8 7
DO6- DO6+ DO3- DO3+
(Rec (Rec DO4- DO4+
Close) Close) (Bat Test-) (Bat Test+)
6 5 4 3 2 1
DO5- DO5+ DO2- DO2+ DO1- DO1+
(Rec (Rec
Open) Open) (Close-) (Close+) (Open-) (Open+)

4) AI(Voltage) Connector
10 9 8 7 6
V6 V4 V_COM V_COM V2
5 4 3 2 1
V5 V_COM V_COM V3 V1

5) AI(Current) Connector
6 5 4 3 2 1
IN(0)- IN(0)+ Icom IC IB IA

- 13 -
V6 V4 V_COM V_COM V2

V5 V_COM V_COM V3 V1
◆ Pin Assignment

<Figure 3-6> Pin Assignment


RS232C RS232C
RS485 Port (SCADA Port)

- 14 -
IN(0)- IN(0)+ Icom IC IB IA

DO3- DO3+ DI10 DI9 DI8 DI7


DO6- DO6+ DO4- DO4+ (Bat Test-) (Bat Test+) DI_COM3 (Spare2)
DI_COM2 (Spare1)
DI_COM1 (GasLow) (HandleLock) 24G 24VIN
DO5- DO5+ DO2- DO2+ DO1- DO1+ DI6 DI5 DI_COM1 DI4 DI3 DI2 DI1
(Close-) (Close+) (Open-) (Open+) (Door Open) (Charger Fail) (Batt Low) (ACLoss) (Close) (Open) FG FG
◆ Assembly Drawing

INTERNAL PANEL

0
13

DOOR

MS CONNECTOR
MODEM
CABLE HOLE

VENTILATOR

<Figure 3-7> Assembly Drawing

- 15 -
◆ Controller PCB

215.00
205.00

103.90
112.50

235.00

121.10
112.50

<Figure 3-8> Controller PCB

- 16 -
◆ Battery Check PCB

90.0 5.0

R7.0
10.0

50.0 50.0

87.0

R5.5

5.0 20.0 25.0 25.0 20.0 5.0


27.0

100.0

<Figure 3-9> Battery Check PCB

- 17 -
4. Installation Instructions
4.1. Front Panel and names of each part

3
4 5

7 10

8 9
11 14
12 13

15

16

<Figure 4-1> Front Panel Configuration

1) Operation Status LED


- Run LED : LED which shows CPU’s operation state
- Error LED : LED which shows device’s diagnosis fail
- AC Power LED : LED which shows external power
- Battery Low : LED which shows low battery voltage
- Handle Lock : LED which show Recloser’s handle lock status
- Gas Low : LED which show Recloser’s gas low status only SF6 gas insulation type(option)

- 18 -
2) LCD
It shows EPIC-R300’s measuring, setting, stored information, and search information.
It is convenient 20*4 character module LCD to move the screen through controling
manipulation button.

3) System Communication LED


LED which shows communication state when EPIC-R300 communicates with host system.
- RX LED : Receiving
- TX LED : Transmitting
- RTS LED : Request transmission to Modem

4) ALT SET Button


Button which select function group. LED on, EPIC-R300’s operate by primary group. LED
off, by reverse group.

5) Manipulation Button
Button which controls LCD screen.
- Menu(M) Button : Button which moves to upper menu
- Up(▲) Button : Button which increases set value or moves the menu upwards
- Down(▼) Button : Button which decreases set value or moves the menu downwards
- Enter(⤶) Button : Button which enters the menu or saves set value

6) Distribution Fault Status LED


LED which shows fault on Distribution Line. It shows distribution line’s source and whether
it is load’s voltage, and whether it is synchronous.
- Live Source LED : LED which shows whether it supplies voltage on source side
- Live Load LED : LED which shows whether it supplied voltage on load side
- Phase Sync. Fail LED : LED which shows synchronous fail of phase A/R or B/S or C/T voltage
- Phase A/B/C Loss LED : LED which show phase loss of phase A/B/C on source side
- Phase R/S/T Loss LED : LED which show phase loss of phase R/S/T on load side
- Phase A LED : A Phase Fault LED
- Phase B LED : B Phase Fault LED
- Phase C LED : C Phase Fault LED
- Phase N LED : N Phase Fault LED
- Phase SEF LED : Zero Phase Fault LED on Non-Ground System
- Recloser Ready LED : LED which shows recloser and a control are ready to start a new
auto-reclosing sequence
- Recloser Cycle LED : LED which shows reclosing sequence is in progress
- Recloser Lockout LED : LED which shows recloser goes to lockout with open
- Trip Info Min LED : LED which shows the measured phase current is over the set
minimum operating current
- Trip Info Volt LED : LED which shows the recloser operates by voltage protection
elements

- 19 -
- Trip Info Freq LED : LED which shows the recloser operates by frequency protection
elements
- Power flow LED(Reverse) : LED which shows whether forward or reverse power
flow

7) Non Reclosing Button


It is used to set whether to allow auto-reclosing sequence after the trip due to
overcurrent and protection elements. Push the button to toggle current functionality. When
the indicator turns on, reclosing operation is restricted.

8) Protection Blocked Button


It is used to restrict operation of all protection elements. It can be temporarily used to
restrict operation of all protection elements. Push the button to toggle current
functionality.

9) Ground Trip Blocked Button


It is used to set whether operation of protection elements for ground overcurrent and SEF.
Push the button to toggle current functionality. When the indicator turns on, operation of
protection elements for ground overcurrent and SEF is restricted.

10) Fault Reset Button


It is a button to reset fault and diagnosis signal LED. It reset actual fault
information with LED.

11) Battery Test Button and LED


It is a button to test battery and battery charger circuit. It shows the test result on Battery
Low LED. If battery low LED is on, which means test fail.

12) Lamp Test Button


It is a button to test LEDs. When push lamp test button, all of the LEDs are turn on.

13) Control Lock Button


It is a button to prevent control operation when doing open / close REC switch on local
or remote when turn on control lock LED. If the control lock LED is on, the protection
function of Recloser also becomes locked. Push control lock button to turn off control lock
LED and then use open / close button to operate.

14) Hot Line Tag


When Activating hot line tag function
- Operation of all protection elements is set to be single shot mode.
- It operates by fast curve.
- It restricts closed operation for the recloser from all sources.
- Tag can be only removed by the tagging source.

- 20 -
15) Maintenance Port (USB-A)
It is USB-A port for maintenance. It uses MODBUS-RTU protocol as well as a special S/W
provided by NEOPIS.

16) Switch Control Button and LED


It is a button to control Recloser and LED to show the state.

o REMOTE CONTROL (R/C) Button : It is a button which selects remote and local control
mode. If you push the button, remote and local mode select are toggled. If REMOTE LED
is on, which means remote control mode is on so it is not possible to operate on local.
In order for local control, push the button to turn off REMOTE LED. Then operate at the
local as using OPEN/ CLOSE button on the side.

o OPEN Button : It is a button to open Recloser on local. If OPEN LED is turned on,
which means Recloser’s status is changed.

o CLOSE Button : It is a button to close Recloser on Local. CLOSE LED is turned off when
Recloser’s status is changed.

4.2. LCD Control and Setting


4.2.1 Button Function

Buttons Function
Return to upper menu
Menu(M)
Cancel setting
Increase set value
Up(▲)
Move to upwards of menu
Decrease set value
Down(▼)
Move to downwards of menu
Move to lower menu
Enter(⤶) Save set value
Choose set value

- 21 -
4.2.2 LCD Display during Power Up
When EPIC-R300’s power is connected, the product name, EPIC-R300, and company name
is on LCD for a second. Then measuring screen shows voltage and current.

◆ Power Up for 1 second on LCD Display


It is the screen of EPIC-R300. A second later, LCD top display shows.

E P I C R 3 0 0
N E O P I S

<Figure 4-2> LCD Display

◆ LCD Top Display


This Top Menu is that displays Recloser’s operation state. Using up/down button, you can
move to the main measurement menu which shows the measured value of current and
voltage. The menu items for Recloser’s operation state are as follows.

- SeqN : Current reclosing counts


- R/C Status : Open/Close/Unknown
- Rcl T : Reclosing time remained
- Reset T : Return time remained
- R/C Ready, Progress, Lockout state

Without controling key, the main measurement menu always returns to top screen 10
minutes later.

[ R/ C Con t r o l l e r ] Ia : 0 . 0 0 0. 00 / 0. 0 0
S e q N: 0 R /C : U n k n o wn Ib : 0 . 0 0 0. 00 / 0. 0 0
Rc l T : 0 Re s e t T : 0 Ic : 0 . 0 0 0. 00 / 0. 0 0
< No t Re a d y > In : 0 . 0 0 <AB C / RS T >

<Figure 4-3> Recloser’s Operation State Menu

- 22 -
4.2.3 LCD Menu Operation

<Figure 4-4> LCD Menu in Top Menu

4.2.4. LCD Menu Items


Next, it is a list of overall menu items. Menu is divided into main menu and lower menu.

<Table 4-1. LCD Menu>


Main menu Lower menu Contents

Top menu Display operation state of Recloser

Main Measurement Menu Display voltage and current measured


Active/reactive/apparent power,
Power
power factor, frequency
Energy Active, reactive energy
Voltage and current’s symmetrical
Voltage / Current
component
Voltage and current’s total harmonic
THD
distortion
Voltage and current’s phase
Phase Diff
difference
Power On/Off count, watchdog reset
Reset / SW Count
Display count, switch Open/Close count
total and individual phase’s fault
Fault Count
count
VI Wear Count It displays residual contact wear

DI Status DI status

Self-Diagnosis self-diagnosis state

Comm Monitoring It displays communication packets

Device Info device information

Protection Func Phase Op Level &


Pickup Level Setting operating level for phase fault
Set Group Fault Time

- 23 -
Fast Curve Setting fast operating value curve
Setting fast operating value control
Fast Multiplier
multiplier
Fast Time Add Set fast operating value time delayed
Set fast operating value min. response
Fast Min Response
time
Fast Reset Time Set fast reset time of definite time

Delay Curve Set delay curve-operating value

Delay Multiplier Set delay control multiplier

Delay Time Add Set delay time added

Delay Min Resp Set delay min. response time

Delay Reset Time Set delay reset time of definite time

Delay DT Level Set operating value at definite time


Set operating time for operating value at
Delay DT Time
definite time
Set operating value at high current trip
HCT Level
level
Set operating time at high current trip
HCT Time
time
Func In Use Set phase fault operation functions

Save Set Save the operation setting


A multiplier to prevent the
1~4
mis-recognizing as a fault by increasing
Cold Load Multi
a multiply of pick-up level under cold
load condition.
Return Normal I Set cold load return current

Cold Load Time Set restraining time of cold load

Use Cold Load Set cold load Use/Not use

Block Flt Inrush Multiply Set inrush control multiplier


Pickup
Inrush Time Set inrush operating time

Use Inrush Set phase fault inrush Use/Not use

2nd Harmonic Set 2nd harmonic inrush control level

2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Trip Direction Set trip direction in fault section


Set positive sequence voltage pickup
3V1 Threshold
level
Fault Set positive sequence current pickup
3I1 Threshold
Direction level
Set operating angle directional
3I1 Angle
current
Dir Block OC Set fault direction block

- 24 -
Save Set Save the operation setting

Pickup Level Set operating level for ground fault

Fast Curve Set fast operating value curve


Set fast operating value control
Fast Multiplier
multiplier
Fast Time Add Set fast operating time delay added
Set fast operating value min.
Fast Min Response
response time
Fast Reset Time Set fast reset time of definite time

Delay Curve Set delay operating value curve


Set delay operating value control
Delay Multiplier
multiplier
Op Level &
Delay Time Add Set delay operating value delay time added
Time
Set delay operating min. response
Delay Min Resp
time
Delay Reset Time Set delay reset time of definite time

Delay DT Level Set operating value at definite time


Set operating time for operating
Delay DT Time
value at definite time
Set operating value at high current trip
HCT Level
level
Set operating time at high current trip
HCT Time
time
Ground
Func In Use Set phase fault operation functions
Fault
Save Set Save the operation setting
A multiplier to prevent the
mis-recognizing as a fault by
Cold Load Multi
increasing a multiply of pick-up level
under cold load condition.
Return Normal I Set cold load return current

Cold Load Time Set restraining time of cold load

Use Cold Load Set cold load Use/Not use

Block Flt Inrush Multiply Set inrush control multiplier


Pickup
Inrush Time Set inrush operating time

Use Inrush Set phase fault inrush Use/Not use

2nd Harmonic Set 2nd harmonic inrush control level

2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Trip Direction Set trip direction in fault section


Fault
3V0 Threshold Set zero phase voltage pickup level
Direction
3I0 Threshold Set zero phase current pickup level

- 25 -
Set operating angle directional
3I0 Angle
current

Dir Block OC Set fault direction block

Save Set Save the operation setting

Set zero phase current operating


3I0 Pickup
value
Set zero phase voltage operating
-3V0 Pickup
value
Op Level &
Time SEF Reset Time Set SEF reset time of definite time

Func In Use Set SEF operating functions

Save Set Save the operation setting

Inrush Multiply Set inrush control multiplier

Inrush Time Set inrush operating time


SEF
Fault Use Inrush Set phase fault inrush Use/Not use
Block Flt
2nd Harmonic Set 2nd harmonic inrush control level
Pickup
2nd_H Detect Time Set 2nd harmonic time level

Use 2nd Harmonic Set 2nd harmonic inrush Use/Not use

Save Set Save the operation setting

Op Angle Set SEF operating angle


Fault
Op Time Set SEF operating time
Direction
Save Set Save the operation setting
Set phase fault sequence operating
Phase Oper Cnt
counts
Set fast operating counts for phase
Phase Rec Phase Fast Cnt
fault
Count Set HCT operating section for phase
Phase HCT Cnt
fault
Save Set Save phase fault operation setting
Set ground fault sequence operating
GND Oper Cnt
counts
Set fast operating counts for ground
GND Rec GND Fast Cnt
fault
Count Set HCT operating section for ground
Trip & GND HCT Cnt
fault
Reclose
Save Set Save ground fault operation setting
Set SEF fault sequence operating
SEF Oper Cnt
counts
SEF Rec
SEF Fast Cnt Set fast operating counts for SEF fault
Count
Save Set Save SEF fault operation setting

Rec Time 1st Set 1st reclosing operating time

Reclose Rec Time 2nd Set 2nd reclosing operating time


Time
Rec Time 3rd Set 3rd reclosing operating time

Rec Time 4th Set 4th reclosing operating time

- 26 -
Reset Time Set reset time of reclosing counter

Save Set Set reclose time setting

SEF Rec Time 1st Set 1st reclosing operating time(SEF)

SEF Rec Time 2nd Set 2nd reclosing operating time(SEF)

SEF SEF Rec Time 3rd Set 3rd reclosing operating time(SEF)
Reclose
SEF Rec Time 4th Set 4th reclosing operating time(SEF)
Time
Set reset time of reclosing
SEF Reset Time
counter(SEF)
Save Set Set SEF reclose setting

Single Shot Time Set single shot time


Reclosing Set sequence coordination Use/Not
Seq Coordination
Option use
Save Set Save operating setting

Volt On Set open line voltage on level

Volt Off Set open line voltage off level


Open Line
Delay Off Set open line delay time setting
Detect
Set whether open line function is
Use Func
available
Save Set save open line set value
Set sync check phase difference
Phase Off
permission setting
Set sync check phase difference delay
Delay Time
Sync Check time setting
Set whether sync check function is
Use Func
available
Save Set save sync check set value

Volt Level Set live line voltage on level


Live Line
Auxiliary Detect Time Set live line detecting delay time
Detect
Func
Save Set save live line set value
Set reverse phase current operation
I2/I1 Pickup
value
Set reverse phase current operation
Delay Time
time
Negative I1 Threshold Set Positive current threshold value
OC
2nd Harmonic Blk Select 2nd Harmonic block/ non-block

Func In Use Set negative OC operating functions

Save Set Save the operation setting

U-V Pickup Set pickup level for under voltage

U-V Op Time Set operation time for under voltage


Under
Voltage Set whether under voltage function is
Use Func
available
Save Set Save under voltage set value

- 27 -
O-V Pickup Set pickup level for over voltage

O-V Op Time Set operation time for over voltage


Over
Voltage Set whether over voltage function is
Use Func
available
Save Set Save over voltage set value

U-F Pickup Set pickup level for under frequency


Set operation time for under
U-F Op Time
Under frequency
Frequency Set whether under frequency function
Use Func
is available
Save Set Save under frequency set value

O-F Pickup Set pickup level for over frequency

O-F Op Time Set operation time for over frequency


Over
Frequency Set whether over frequency function
Use Func
is available
Save Set Save over frequency set value

Live Load Select whether live load is available


Close
Sync Fail Select whether sync fail is available
Interlock
Save Set Save close interlock set value
Select operating mode for the
Loop Selection
recloser
Set open time for determining
Deadbus Open Time
distribution line’s dead line state
Tie Sw Open Time Set Open time for tie sw
Select whether Tie sw source is ABC or
Tie Sw Source
RST

Loop Tie Sw Close Time Set close time for tie sw


Automation
Rec Block Time Set Reclosing Blocking Time
Set whether restoration after clearing
Enable Restore
fault
Rec Close Time Set recloser closing time after open
Set delta I level to restore for Tie
Tie On delta I
recloser after fault
Save Set Save loop automation set value

Primary Group Select a group which will be actvated


Select whether auto group function is
Sel Auto Group
available
Select
Reverse Group Select a alternative group
Group
Save Sel Group Save select group set value

Default Fact Set Set all settings to factory settings

Line Config Set 3P4W / 3P3W


Configurat- Frequency Set frequency(50/60Hz)
Analog
ion
Rated Volt Set rated voltage

- 28 -
CT Ratio Set CT ratio

NCT Ratio Set NCT ratio

Avg Interval Set average value process interval

Select FI Reset Set FI reset way(Auto / Manual)


Selection of line to phase voltage and
Display Voltage
line to line voltage
Phase Position Select phase position
Select whether phase rotation is ABC
Phase Rotation
or ACB
Select which side will be power
Source Side source between ABC side and RST
side
Energy log duty Set duty time for energy logging

Closing delay Set delay time to close CB


Select whether to consider voltage
Check V for FI
when FI set
Reclaim T for FI Set reclaim time for FI clear
Set Delay about Important Key(ALT
Important Key Delay
SET, CLOSE, OPEN)
V Sensor Fail Delay Set delay time for Voltage Sensor Fail

I Cut Level Set level for current cutting

V Cut Level Set level for voltage cutting

Save Config Save analog configuration setting


DI
DI1~ DI10 Set DI1~10 debounce time
Debou
nce
Save Config Set save DI debounce Configuration
Time
DO DO1~DO6 Set DO1~DO6 pulse width
Pulse
Width Save Config Save DO pulse width setting

Set Switch Cnt Set number of switch operation

Backup Clear Event Clear event information


Set/Cle
ar Clear Fault Clear fault information

Clear Oper Count Clear operation information

Ia~In, Va~Vt Adjust analog gain


Analog
Gain Save Config Save analog gain config setting
Adj
Clear Gain Data Clear analog gain config setting

Set sample rate when capturing


Sample Rate
waveform
Record Size Set record size of waveform
Wavefo
rm Pre Cycle Set pre cycle number of waveform

Post Cycle Set post cycle number of waveform

Save Config Save waveform config setting

- 29 -
Check Day Set auto checking day for battery

Check Check Hour Set auto checking hour for battery


Auto
Check Min Set auto checking minute for battery
batt
Save config set value for battery auto
Save Config
checking
Auto-Check Day Set auto checking day for battery

Check Detect Batt-Low Set voltage level for battery low


Auto
Cut-Off Voltage Set voltage level for battery cutoff
batt(op
tion) Cut-Off Delay Set delay time for battery cutoff
Save config set value for battery auto
Save Config
checking
V Unbalance Set unbalance level for voltage

V Unbalance Time Set unbalance time for voltage


V/I
Unbala I Unbalance Set unbalance level for current
nce
I Unbalance Time Set unbalance time for current

Save Config Save V/I unbalance set value

Sag Level Set pickup level for sag

Sag Time Set operation time for sag

Swell Level Set pickup level for swell


Sag/Sw
Swell Time Set operation time for swell
ell
Interrupt Level Set pickup level for interruption

Interrupt Time Set operation time for interruption

Save Config Save config set value for Sag/Swell

V THD Alarm Level Set alarm level for voltage THD

V THD Alarm Time Set alarm time for voltage THD


THD
I THD Alarm Level Set alarm level for current THD
Alarm
I THD Alarm Time Set alarm time for current THD

Save Config Save config set value for THD alarm


Set the type of the VI used in the
Max Op Count
recloser
Set alarm level for residual contact
Alarm Level
wear
Duty Factor A Set duty factor for A phase’s VI
VI
Wear Duty Factor B Set duty factor for B phase’s VI

Duty Factor C Set duty factor for C phase’s VI

Save Config Save config set value for VI Wear

Clear Wear Info Clear wear information

Analog Set phase current level for Analog


Phase Current
High High Alarm function

- 30 -
Set ground current level for Analog
Ground Current
High Alarm function
Set phase voltage level for Analog
Phase Voltage
High Alarm function
Set system power level for Analog
Alm System Power
High Alarm function
Select whether Analog High Alm
Enable High Alarm
function is available
Save config set value for Analog High
Save Config
Alarm
Set phase current level for Analog
Phase Current
Low Alarm function
Set ground current level for Analog
Ground Current
Low Alarm function
Set phase voltage level for Analog
Analog Phase Voltage
Low Alarm function
Low
Set system power level for Analog
Alm System Power
Low Alarm function
Select whether analog low alm
Enable Low Alarm
function is available
Save config set value for Analog Low
Save Config
Alarm
Door Open Contact Set contact type for door open(DI6)
Set condition of AC POWER LED
Miscell AC POWER LED
On(DI3)
aneous
Config Insulator Type Set type of insulator

Save Confg Save config set value for Misc. config

Baud Rate Set Baud rate

Parity Set serial communication Parity

Slave D/L Addr Set DNP slave or IEC-101 D/L address

ASDU Common Addr Set IEC870 ASDU Common address


SCADA
Port Select Protocol Set communication protocol
Select Protocol map, full map or user
Select Map
map
Clear User Map Clear downloaded user map

Save SCADA Port Save SCADA port related setting

Comm Line Set modem communication line

Communica Mode RTS Off Delay Set RTS off delay time
tion m CTS Timeout Set CTS set timeout time
Control DCD Timeout Set DCD Set timeout time

Save Modem Ctrl Save modem control related setting

D/L Retry Set data link layer retry

D/L Timeout Set data link layer timeout

D/L Confirm Set data link layer confirm


DNP
Config A/L Retry Set application layer retry

A/L Timeout Set application layer timeout

Unsol Response Class Set unsolicited response transmission


class

- 31 -
Unsol Response Delay Set unsolicited response transmission
delay

Unsol Resend Delay Set unsolicited resend transmission


delay when no ACK
SBO Timeout Set select before operation timeout

Master Address Set master address for unsolicited


response
Frame Interval Set link layer frame interval

DNP Port Num Set DNP-TCP Port Number


Select whether clear event or not
Cls Evt when RST
after device restart
Select whether save event only after
Event Time Sync
time sync or save event always
Select whether with time or without
BI Change Default Variation
time when sending BI event data
Select whether with time or without
AI Change Default Variation
time when sending AI event data
Save DNP Set Save DNP related setting

Link Addr Size Set link address size

Common Addr Size Set common address size

IOA Size Set Information Object address size

COT Size Set COT address size

Time Format Select Time Format, CP24, CP56 or


NO
IEC101
Config Single Character N/ACK Set 1-character ACK, NACK function

Arm Timeout Set arm timeout

Analog Data Type Set analog data type

Scan Analog Change Set scan analog change information

Scan Binary Change Set scan binary change information

Save IEC Set Save IEC101 related setting

Conn Timeout(t0) Set connection timeout

APDU Timeout(t1) Set APDU timeout

Ack Timeout(t2) Set ack timeout

IEC104 Test Period(t3) Set time period

Config Select whether spontaneous response


Xmt Spontaneous
function is available
Max Xmt I-APDU(k) Set max transmitting I-APDU

Max Rcv I-APDU(w) Set max receiving I-APDU

Save IEC104 Set Save IEC104 related setting

IP Address Set IP address

Subnet Mask Set subnet mask bit set


TCP/IP
Gateway Set gateway address
Config
NTP Server Set NTP server address

Save TCPIP Set Save TCP/IP related setting

- 32 -
PSTN Modem Select PSTN mode type, PPP, dialup
or SMS
Auto Hangup Time Set Auto hangup time

PSTN Dial Timeout Set dial timeout


Config
Attempt Delay Set dial attempt delay time

Max Attempts Set dial max attempt

Save PSTN Set Save PSTN related setting

Our IP Addr Set our IP address

Their IP Addr Set their IP address


PPP
DNS1 IP Addr Set DNS1 IP address
Config
DNS2 IP Addr Set DNS2 IP address

Save PPP Set Save PPP related setting

Trip Enable Set sending trip information

FI Enable Set sending FI information

SMS Open Enable Set sending open information


Config
Door Open Enable Set sending door information

AC fail Enable Set sending AC fail information

Save SMS Set Save SMS related setting

SNTP sync Enable Select whether to enable SNTP

Time SNTP sync Period Set SNTP cycle duty


sync
option Select Time Zone Select time zone

Save TimeSync Set Save TimeSync related setting

Time Set Time setting


Fault Event Fault event

Op Event Display Operation event

Demand I Display Demand current


Event View
Demand P Display Demand power
Max Demand I Display Max demand current
Max Demand P Display Max demand Power

4.3. Order of Installation Test Operation


① Check if the connection is right. Turn On the control power.
② Check CT/PT rate on System Config. Menu. If necessary, adjust it following CT/PT rate control.
③ Check connection system on System Config. Menu. If necessary, adjust it.
④ Check & Control Alarm contact’s setting state on DO Config. Menu. If necessary, adjust it.
⑤ On Relay setting menu, check if Relays are correctly setting. If necessary, adjust it.
⑥ After all adjustments, EPIC-R300 works properly.
⑦ If RUN LED on front panel blinks regularly and SYS-FAIL LED is turned off, which
means it works properly.

- 33 -
5. LCD Menu
5.1. Display
5.1.1. Display operation
Moving on display items is like below.

<Figure 5-1> Display Operation

5.1.2. Display Menu


Display menu shows measuring value(voltage, current, phase, symmetrical component),
operation count, fail count, DI status, self-diagnosis, and status information.

[ D I S P L A Y M E N U ]
-> 1 . P o w e r
2 . E n e r g y
3 . V o l t a g e / C u r r e n t
4 . T H D
5 . P h a s e D i f f
6 . R e s e t / S W C o u n t
7 . F a u l t C o u n t
8 . V I W e a r C o u n t
9 . D I S t a t u s
1 0 . S e l f - D i a g n o s i s
1 1 . D e v i c e I n f o

<Figure 5-2> Display Menu

1) Power : Active / Reactive / Apparent Power, Power Factor, Frequency display

2) Energy : Active / Reactive Energy display (kWh). If it is over 999999999kWh, then it

- 34 -
becomes clear to 0.

3) Voltage/Current : display items like Voltage (Va, Vb, Vc) and Current (Ia, Ib, Ic)’s
Positive Sequence, Negative Sequence, Zero Sequence

4) THD : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s Total Harmonic Distortion value



 

   (measure up to h=2~32th)


5) Phase Diff : display Voltage(Va, Vb, Vc) and Current(Ia, Ib, Ic)’s phase difference

6) Reset / SW Count : display Power On Reset Count and Watchdog Reset Count. display
the number of Switch’s On/Off

7) Fault Count : display each phase’s fault count and total fault count

8) VI Wear Count : display residual contact wear for each phase’VI

9) DI Status : DI Status display. it shows 4 items at once. In order to see the next item,
use Up/Down Key to move. Display items are below,
- Open, Close, Handle Lock, External AC Fail, Over Discharge, Door, Charger fail
- Spare1,2, DI status. If DI status is Enable it shows 1.

10) Self-Diagnosis : device’s self-diagnosis information display

11) Comm Monitoring


It displays communication packets

12) Device Info : device’s information(name of the device, manufacturer, program version,
Web site display

5.2. Protection Setting Menu


5.2.1 Operation Principle of Recloser
The figure below shows the case of lockout state that, when set with 2F3D of reclosing
sequence, Recloser operates twice of fast operation and 3 times of delay operation against
fault, and then locked out as opened.

- 35 -
⓵ 1st TRIP - 1st FAST TCC ⓶ 1ST RECLOSE INTERVAL
⓷ 2 ND
TRIP - 2 ND
FAST TCC ⓸ 2ND RECLOSE INTERVAL
⓹ 3rd TRIP - 1ST SLOW TCC ⓺ 3rd RECLOSE INTERVAL
⓻ 4th TRIP - 2nd SLOW TCC ⓼ 4th RECLOSE INTERVAL
⓽ 5 th
TRIP - 3 rd
SLOW TCC ⓾ LOCKOUT

<Figure 5-3> Permanent fault for Recloser Sequence

The following figure shows the successful reclosing case that Recloser operates twice of
fast action and inputted. After the lapse of set-Reset Time, Recloser returns, and then
display of LED and LCD are changed from Progress into Ready status. If a fault occurs
again during Reset Time, when the counts of reclosing action reaches to total counts
which shall be calculated from remaining fault counts, the Recloser becomes locked out.

⓵ 1st TRIP - 1st FAST TCC ⓶ 1ST RECLOSE INTERVAL


⓷ 2ND TRIP - 2ND FAST TCC ⓸ 2ND RECLOSE INTERVAL
⓹ 3rd TRIP - 1ST SLOW TCC

<Figure 5-4> Temporary fault for Recloser Sequence

5.2.2 Operation Principle of FI


If there is a fault on distribution line, protection device(CB, Recloser) does tripping to
protect the system. Then EPIC-R300, Feeder RTU, operates Protection function to detect the
fault, through which it is possible to explore fault section. It is a menu to set and manage
related set value. The basic principle of operation is like a picture below. If there is
permanent or temporary Fault, it detects zero voltage with protective device(CB or

- 36 -
Recloser) after fault current. After detecting zero voltage, EPIC-R300 generates FI. With
protective device’s reclosing success, normal current and voltage are returned. If FI Auto
Reset was set, FI is reset automatically.

If not, push FI reset button on the front or it is reset with transmitted FI reset order in
remote. R300 is designed to generate FI not only for the case that R300 becomes tripped
itself against a fault, but also that other protection devices are tripped.

- Temporary Fault

<Figure 5-5> Temporary Fault

- Permanent

Fault

<Figure 5-6> Permanent Fault

Protection set value divides into 4 Groups to manage. Choose applied group through
Active Group setting.

- 37 -
[ S e t t i n g ME N U ] [ F u n c S e t t i n g ]
→ 1 . F u n c G r o u p 1 → 1 . P h a s e F a u l t
2 . F u n c G r o u p 2 2 . G r o u n d F a u l t
3 . F u n c G r o u p 3 3 . S E F F a u l t
4 . F u n c G r o u p 4 4 . T r i p & R e c l o s e
5 . S e l e c t G r o u p 5 . A u x i l i a r y F u n c

<Figure 5-7> Setting Menu- Func Group

5.2.3. Phase Fault


In order to detect phase fault, setting items and ranges are like below.

<Table 5-1> Detecting phase fault

Category Item Range Default Step Unit Explanation

Pickup Level 10~2000 400 1 A Set operation level


Fast Curve 1~50 A Curve Set fast curve
Set a multiplier of fast operating
Fast Multiplier 0.05~2 1.00 0.01
curve.
Set operating delayed time under fast
Fast Time Add 0.00~1.00 0.00 0.01 sec
curve condition
Fast Min Set min. operating response time
0.00~1.00 0.00 0.01 sec
Response under fast curve condition
Fast Reset Time 0.00~1.00 0.00 0.01 sec Set fast reset time of definite time
Delay Curve 1~50 B Curve Set delay curve
Set a multiplier of delay operating
Op Level Delay Multiplier 0.05~2 1.00 0.01
curve.
& Time Set operating delayed time under
Delay Time Add 0.00~1.00 0.00 0.01 sec
delay curve condition
Set minimum operating response time
Delay Min Resp 0.00~1.00 0.00 0.01 sec
under delay curve condition
Delay Reset Time 0.00~1.00 0.00 0.01 sec Set delay reset time of definite time
Delay DT Level 25~10000 OFF 1 A Set operating value at delay DT level
Delay DT Time 0.01~2 2.00 0.01 sec Set operating time at delay DT time
Set operating value at high current
HCT Level 25~10000 OFF 1 A
trip level
Set operating time at high current
HCT Time 0.01~1 0.04 0.01 sec
trip time
Func In Use NO/YES YES Set phase fault operation functions
A multiplier to prevent the
mis-recognizing as a fault by
Cold Load Multi 1~10 2 1
increasing a multiply of pick-up level
under cold load condition.
Set the return current of restraining
Return Normal I 0~30 0.3 0.01 sec
operation against cold load
Cold Load Time 0~180 3 1 min Set restraining time of cold load
Use Cold Load NO/YES NO Set cold load Use/Not use
Block flt
A multiplier to prevent the mis-
Pickup recognizing as a fault by increasing a
Inrush Multiply 1~10 2 1
multiple of pick-up level under inrush
condition
Inrush Time 0~30S 0.02 0.01 sec Set restraining time of Inrush
Use Inrush NO/YES NO Set inrush Use/Not use
A level of regarding 2nd harmonic as
2nd Harmonic 1-50 20 1 %
inrush
Use 2nd Harmonic 0.02~1 0.02 0.01 sec Set 2nd harmonics Use/Not use

- 38 -
Trip Direction OFF/FWD/REV OFF Selection of phase fault direction
Set positive sequence voltage
3V1 Threshold 0~100 20 1 %
operating value
Fault Set positive sequence current
3I1 Threshold 0~100 20 1 %
Direction operating value
Set positive sequence current
3I1 Angle 0~359 300 1 °
operating angle
Dir Block OC NO/YES NO Set direction function block

1) Fast Operation
This menu is for setting “FAST” among Recloser’s operation sequence

2) Delay Operation
This menu is for setting “Delay” among Recloser’s operation sequence

3) Delay DT Protection
This menu is for setting Delay Definite Time regardless of targeted section among
Recloser’s operation sequence

4) HCT Protection
This menu is for setting the protection against the high current trip of Recloser

5) Cold load Operation


If a load has not been powered for a prolonged period, and when the power has again
resumed i.e. by input of circuit breaker, this can impose a higher current than the pickup
value of time-delay overcurrent protection, which could exceed normal settings. These
conditions can exists for an extended period and must not be interpreted as a fault. In
other words, this function is recognized as Cold load circumstance, when no current
measured in the Recloser is maintained for 5 minutes(300sec). If the measured current is
less than the multiples of pick-up, Recloser does not recognize it as a failure. If it is larger
than the multiples of pick-up, Recloser regards the situation as an actual fault, and
performs the same reclosing sequence same as normal operation.

<Figure 5-8> ColdLoad

- 39 -
6) Inrush Restraint
When the circuit breaker is putted in order to supply the electricity to a load, Inrush
current is generated in a short time. Inrush restraint is a function to prevent Recloser’s
mis-operation of fault detection elements due to that kind of inrush current at the time of
energization in the line. Inrush restraint can be achieved by two methods ; multiplier can
be applied to pick-up current, and another way is, in case that 1st and 2nd harmonics
contents of generated current is over the constant current, to restrain current for the
setting time.
In order to detect Phase Fault, setting items and ranges are like below. The order to set is
like below.

1) Choose the menu with Up/Down Key. Press Enter Key to enter the menu.
[[ FF uu nn cc SS ee tt t t i i nngg] ] [ P h a s e F a u l t ]
->1
→ 1 . P
P hh aa ss ee FF aa uu l l t t → 1 . Op L e vv e l & T i me
2 . G
G rr oo uu nn dd FF aa uu l l t t 2 . B l o c k F l t P i c k u p
3 . SS EE FF FF aa uu l l tt 3 . F a u l t D i r e c t i o n
4 . TT rr ii pp &
& RR ee cc l l oos s ee
5 . A
A uu xx ii ll ii aa rr yy FF uunnc c

<Figure 5-9> Setting menu

2) On Phase Fault menu, choose the setting item you want with Up/Down Key. Press Enter
Key to enter the setting item.

[ O P L e v e l & T i m e ] [ P i c k u p L e v e l ]
→1 . P i c k u p L e v e l S E T : 4 0 0 A
2 . F a s t C u r v e
3 . F a s t Mu l t i p l i e r ( 1 0 - 2 0 0 0 A : 1 A )
4 . F a s t T i m e A d d
5 . F a s t Mi n R e s p o n s e
6 . F a s t R e s e t T i m e
7 . D e l a y C u r v e
8 . D e l a y Mu l t i P l i e r
9 . D e l a y T i m e A d d
1 0 . D e l a y Mi n R e s p
1 1 . D e l a y R e s e t T i m e
1 2 . D e l a y D T L e v e l
1 3 . D e l a y D T T i m e
1 4 . H C T L e v e l
1 5 . H C T T i m e
1 6 . F u n c I n U s e
1 7 . S a v e S e t

<Figure 5-10> Phase Fault-Pickup Level

- 40 -
3) Change set value with Up/Down Key. Press Enter Key to confirm. If you want to cancel
the changed set value, press M Key.
4) When the setting is completed, choose 17. Save Set to save the set value in backup
memory and come out from the item. Then the set value is applied to the device.
[ O P L e v e l & T i m e ]
→1 . P i c k u p L e v e l [ U p d a t e S e t t i n g ]
2 . F a s t C u r v e
3 . F a s t Mu l t i p l i e r → P r e s s E n t e r
4 . F a s t T i m e A d d
5 . F a s t Mi n R e s p o n s e
6 . F a s t R e s e t T i m e
7 . D e l a y C u r v e
8 . D e l a y Mu l t i P l i e r
9 . D e l a y T i m e A d d
1 0 . D e l a y Mi n R e s p
1 1 . D e l a y R e s e t T i m e
1 2 . D e l a y D T L e v e l
1 3 . D e l a y D T T i m e
1 4 . H C T L e v e l
1 5 . H C T T i m e
1 6 . F u n c I n U s e
1 7 . S a v e S e t

<Figure 5-11> Phase Fault-Save Set

5.2.4. Ground Fault


In order to detect ground fault, setting items and ranges are like below.

<Table 5-2> Detecting ground fault

Category Item Range Default Step Unit Explanation

Pickup Level 5~2000 400 1 A Set operation level

Fast Curve 1~50 1 Curve Set fast curve


Fast Multiplier 0.05~2 1.00 0.01 Set a multiplier of fast operating curve.
Set operating delayed time under fast
Fast Time Add 0.00~1.00 0.00 0.01 sec
curve condition
Fast Min Set min. operating response time
0.00~1.00 0.00 0.01 sec
Response under fast curve condition
Op Level &
Fast Reset Time 0.00~1.00 0.00 0.01 sec Set fast reset time of definite time
Time
Delay Curve 1~50 8 Curve Set delay curve
Delay Multiplier 0.05~2 1.00 0.01 Set a multiplier of delay operating curve.
Set operating delayed time under
Delay Time Add 0.00~1.00 0.00 0.01 sec
delay curve condition
Set minimum operating response time
Delay Min Resp 0.00~1.00 0.00 0.01 sec
under delay curve condition
Delay Reset
0.00~1.00 0.00 0.01 sec Set delay reset time of definite time
Time

- 41 -
Delay DT Level 25~10000 OFF 1 A Set operating value at delay DT level
Delay DT Time 0.01~2 2.00 0.01 sec Set operating time at delay DT time
Set operating value at high current
HCT Level 25~10000 OFF 1 A
trip level
Set operating time at high current
HCT Time 0.01~1 0.04 0.01 sec
trip time
Func In Use NO/YES YES Set phase fault operation functions
A multiplier to prevent the
mis-recognizing as a fault by
Cold Load Multi 1~10 2 1
increasing a multiply of pick-up level
under cold load condition.
Set the return current of restraining
Return Normal I 0~30 0.3 0.01 sec
operation against cold load
Cold Load Time 0~180 3 1 min Set restraining time of cold load
Use Cold Load NO/YES NO Set cold load Use/Not use
Block flt
A multiplier to prevent the
Pickup mis-recognizing as a fault by
Inrush Multiply 1~10 2 1
increasing a multiple of pick-up level
under inrush condition
Inrush Time 0~30S 0.02 0.01 sec Set restraining time of Inrush
Use Inrush NO/YES NO Set inrush Use/Not use
2nd Harmonic 1-50 20 1 % A level of regarding 2nd harmonic as inrush
Use 2nd
0.02~1 0.02 0.01 sec Set 2nd harmonics Use/Not use
Harmonic
Trip Direction OFF/FWD/REV OFF Selection of ground fault direction
3V0 Threshold 0~100 20 1 % Set zero sequence voltage operating value
Fault
3I0 Threshold 0~100 20 1 % Set zero sequence current operating value
Direction
3I0 Angle 0~359 300 1 ° Set zero sequence current operating angle
Dir Block OC NO/YES NO Set direction function block

The way to set is identical with 5.2.3

5.2.5. SEF Fault


SEF(Sensitive Earth Fault) fault is used when ground fault current is small in ungrounded
system. Next it is operation diagram about operation area. Like the picture, +-90° becomes
operation area by setting’s op-Angle. When earth current and voltage volume is over the
set value with a fault and earth current’s phase is in operation area based on earth
voltage, then it is picked up as fault. If this condition is kept during operation time, SEF
Fault is set.

To detect SEF Fault, setting items and ranges are like below.

<Table 5-3> Detecting Set Fault


Category Item Range Default Step Unit Explanation

3I0 Pickup 0.1~20 5.0 0.1 A Set 3I0 current operation value
-3V0 Pickup 0~80 30 1 % Set 3V0 voltage operation value
Op Level
SEF Reset Time 0.00~1.00 0.00 0.01 sec Set SEF reset time of definite time
& Time
OFF/ALARM/
Func In Use OFF Set SEF fault operation functions
TRIP

- 42 -
Inrush Multiply 1~10 2 1 Set inrush control multiplier
Inrush Time 0~30 0.02 0.01 sec Set inrush operating time
Block Flt Use Inrush NO/YES NO Set phase fault inrush Use/Not use
Pickup 2nd Harmonic 1~50% 20 1 % Set 2nd harmonic inrush control level
2nd_H Detect Time 0.02~1 0.02 0.01 sec Set 2nd harmonic time level
Use 2nd Harmonic NO/YES NO Set 2nd harmonic inrush Use/Not use
Fault Op Angle 0~345 90 1 ° Set operating angle
Direction Op Time 0.1~30 1.0 0.1 sec Set operating time

<Figure 5-12> Operation Diagram of SEF

The way to set is identical with 5.2.3

5.2.6. Trip & Reclose


1) Phase Rec Count
This is the menu for setting the counts of reclosing operation against phase fault.

2) GND Rec Count


This is the menu for setting the counts of reclosing operation against GND fault.

3) SEF Rec Count


This is the menu for setting the counts of reclosing operation against SEF fault.

4) Single Shot Operation


In single shot operation, Recloser goes directly to lockout after a trip, and will not reclose.
This operation occurs in two cases ; one is the case when Recloser disable in the front,
the controller goes to lockout without reclosing. and another case is that, after Recloser is
put, the fault occurs during the Single Shot setting time, then it goes to trip and
locked-out.

5) Sequence Coordination
When operating with 2 or more Recloser connected in series in distribution line, in order
to prevent the operation of all Reclosers’ being opened at the same time which are
installed both in power supply side and in load side, the Sequence Coordination function
is used to. This function is that, when multiple Reclosers in load side are connected to

- 43 -
one Recloser on the power supply side, only the Recloser experienced a fault is set to
perform the opening operation.

As shown below, if the Recloser in power supply is Active state in Sequence Coordination
mode, in case of line fault, while Recloser in power supply detects the fault current and
operates the opening delayed action, it returns to normal situation by the operation of
Recloser in load side, and then Recloser in power supply will increase the operation
sequence only by one time. Therefore, only sequence of Recloser(power supply side) is in
progress without opening operation, so that even when load Recloser operates to delay
action, Recloser from supply side does not progress the other instantaneous actions in
sequence, but operates to delay action in the same way with load Recloser. If the
reclosing function is restrained, the Sequence Coordination function does not work.

The following rules apply to the Sequence coordination

1) All Reclosers both in supply side and the load must be set at same instantaneous time,
delay characteristics and the same minimum operating Pickup current value. (If the
minimum operating pickup current is wrongly set, the pickup value of power supply must
be larger than the load)

2) All Reclosers must have the same reclosing Time.

3) Recloser in supply should resume 100ms or more of delay time than load Recloser, or
the value of the minimum operating pickup current must be larger than that of load
Recloser.

4) The reset time of power supply Recloser must be set longer than the longest reclosing
time of the load Recloser. This is to prevent Recloser in supply side to be reset mode
during reclosing of load Recloser.

<Figure 5-13> Sequence Coordination

- 44 -
The setting items and ranges of Trip & Recloser are as follows.

<Table 5-4> Setting for Trip&Recloser


Category Item Range Default Step Unit Explanation
Counts of reclosing operation against
Phase Oper Cnt 1~5 4 1
phase fault
Phase Set fast operation section among
Rec Phase Fast Cnt 0~5 2 1 counts of reclosing operation against
Count phase fault
Counts of HCT operation against
Phase HCT Cnt 0~5 0 1
phase fault
Counts of reclosing operation against
GND Oper Cnt 1~5 4 1
ground fault
Set fast operation section among
GND Rec
GND Fast Cnt 0~5 2 1 counts of reclosing operation against
Count
ground fault
Counts of HCT operation against
GND HCT Cnt 0~5 0 1
ground fault
Counts of reclosing operation against
SEF Oper Cnt 1~5 4 1
SEF fault
SEF Rec
Set fast operation section among
Count
SEF Fast Cnt 0~5 2 1 counts of reclosing operation against
SEF fault
Rec Time 1st 0.3~180 2.0 0.1 sec Set 1st reclosing operation time
Rec Time 2nd 1~180 10 1 sec Set 2nd reclosing operation time
Reclose
Rec Time 3rd 1~180 15 1 sec Set 3rd reclosing operation time
Time
Rec Time 4th 1~180 30 1 sec Set 4th reclosing operation time
Reset Time 2~300 30 1 sec Set reclosing return time
SEF Rec Time 1st 0.3~180 2.0 0.1 sec Set 1st SEF reclosing operation time
SEF SEF Rec Time 2nd 1~180 10 1 sec Set 2nd SEF reclosing operation time
Reclose SEF Rec Time 3rd 1~180 15 1 sec Set 3rd SEF reclosing operation time
Time SEF Rec Time 4th 1~180 30 1 sec Set 4th SEF reclosing operation time
SEF Reset Time 2~300 30 1 sec Set SEF reclosing return time
Single Shot Time 0~180 10 1 sec Set single shot time
Reclosing
Set sequence coordination Use/Not
Option Seq Coordination NO/YES NO
use

5.2.7 Auxiliary Func


This function is for monitoring and additional functions of distribution line, key functions
are as follows.

1) Open Line Detect : To set the Phase Loss in distribution line


When phase voltage is maintained below a set value of voltage off for over delay time, it
is determined as Phase Loss. As the phase voltage grows more than setting value, the
Phase Loss is turned off. The percentage of voltage off in Open Line Detect shall be set
equal to or lower than the Live Line Detect voltage level. This is to avoid monitoring the
Open Line when 3 phase voltages are less than Live Line.

2) Sync Check : To check the voltage synchronization of the Source and Load side.
Once the voltages of the Source side and Load side are maintained for the set time,
within the setting range, the Sync Check is “OK”.

- 45 -
If the voltages of Source and Load sides are out of phase setting range, Sync Fail occurs
and then sync LED operates.

3) Live Line Detect : Setting for monitoring live line


Any of the phase from 3 phase voltage from source side is over Voltage On, Hot Line
Source LED light will be on and determines the Source side as Hot Line.
Load side also operates in the same principle.

4) Negative OC : Protection function for reverse phase current.


The setting items and ranges of Auxiliary Function are as follows.

5) Under Voltage : Settings associated with under voltage protection


If you select “3. Use Func” as TRIP, when low-voltage occurs, it trips circuit breaker, and
does not perform any reclosing operation. If you select it as Alarm, it does not trip the
circuit breaker, and record the alarm status in operating information, and it transmits to
the host system over the communication.

6) Over Voltage : Setting associated with over voltage protection


If you select “3. Use Func” as TRIP, when over-voltage occurs, it trips circuit breaker, and
does not perform any reclosing operation. If you select it as Alarm, it does not trip the
circuit breaker, and record the alarm status in operating information, and it transmits to
the host system over the communication.

7) Under Frequency : Settings associated with low-frequency protection


If you select “3. Use Func” as TRIP, when low-frequency occurs, it trips circuit breaker, and
does not perform any reclosing operation. If you select it as Alarm, it does not trip the
circuit breaker, and record the alarm status in operating information, and it transmits to
the host system over the communication.

8) Over Frequency : Settings associated with over-frequency protection


If you select “3. Use Func” as TRIP, when over-frequency occurs, it trips circuit breaker, and
does not perform any reclosing operation.
If you select it as Alarm, it does not trip the circuit breaker, and record the alarm status
in operating information, and it transmits to the host system over the communication.

9) Close Interlock : Settings associated with the function of inhibiting the input depending
on the situation of power system, when Recloser is applied.
For the case of Live Load function with “Enable”, it inhibits the input only when the
voltage is applied to both Source side and Load side. And, in case of Sync Fail function
with “Enable”, it inhibits the input when the synchronization of voltage on the Source side
and Load side is not suitable.

10) Loop Automation : When a fault occurs in a distribution line, protection device

- 46 -
perfoms protecton operation and the load in the lower side of protection devise will
experience a power outage. Thus, the blackout range of the distribution line are spread
to normal condition section as well as fault occurrence section.

For coping with those case, loop control function will operate in the way of separating the
fault section, and supplying power to normal section, then it helps to minimize the outage
time.
EPIC-R300 provides those loop control function which is operable in service only by using
the information about voltage, current, and operating state.

Depending on the configuration of recloser being installed, 3 modes of loop control can
be selected.
- Feeder recloser : the recloser is installed near the substation or inside.
- Midpoint recloser : installation point is between feeder recloser and tie recloser.
- Tie-point recloser : the recloser are usually installed at tie point where two distribution
lines are interconnected.

1) feeder recloser
Protection elements are generally operate when downstream fault occurs in the distribution
line. If it detects voltage loss at power supply, recloser will trip after set time.
In both cases that trip by protection elements and remote operation, loop control function
is automatically stopped.
2) Mid point recloser
Protection elements are generally operate when downstream fault occurs in the distribution
line. If, due to the action at power source side, it detects voltage loss at both sides, it
shall be automatically changed into another setting group after set time.
After downstream recloser or tie point recloser’s operation, the power supply starts to
provide from reverse side. For this moment, the reclosing action shall be hold for a certain
period of time.
3) Tie-point recloser
When voltage loss is detected in the set side, it close after the set time.
After closing, when the fault is detected, it stops and holds reclosing for a sertain period
of time.
The operation by protection elements is possible after normalization of reclosing element.
The activated operation group shall be changed according to feeding direction or setting

- “Dead bus open time”


The loop automation operates when the distribution line is in dead state.
It can be determined by using setting value based on voltage whether distribution line is
dead or not.
The state of loop automation shall be determined as “dead” only when the dead bus state
is maintained for a set time.
The voltage values of all sources and load side shall not exceed the set values.

- 47 -
- “Tie SW open time”
This is the time required to open a “Tie Sw open” in order to repair the distribution lines
to the normal state, if power is supplied from both Tie Sw after the fault is recovered.

- “Tie Sw Source”
It is used to determine the conditions of Tie Sw closing.
BOTH : If any loss for both side, it operates after Tie Sw closing time.
ABC : ABS side is power side, and when RST side is de-energized, then it closes after the
close time.
RST : RST side is power side, when RST side is de-energized, then it closes after the close
time.

Loop Operation procedure

Feeder MID Tie


CB CB
REC REC REC

1) Feeder recloser trips when the voltage at power supply side is lost.
2) Mid recloser changes to Alt group setting when the voltage of power supply and load
side is dead due to the trip of protection device at power supply, and also changes to
the single shot mode which does not operate reclosing.
3) Tie recloser closes if one side voltage is lost.
4) Feeder recloser closed when the voltage at power supply become live after it is
repaired.
5) Mid recloser closes when the voltage is supplied to both side.
6) Tie recloser opens when the voltage is supplied to both ends.
<Table 5-5> Auxiliary Function
Category Item Range Default Step Unit Explanation
Voltage setting to reset phase
Volt On 50~90 90 1 %
loss(standard on rating voltage)
Voltage setting to set phase
Volt Off 35~75 75 1 %
Open Line loss(standard on rating voltage)
Detect If voltage is kept under volt off
Delay Off 0.1~30 30 0.1 sec
during delay time
Show whether open line detect
Use Func NO/YES YES
function is available
Phase Off 5~60 5 1 ° degree setting to check phase sync
Delay Time 0.1~30 30 0.1 sec delay time setting to check phase sync
Sync Check
Show whether sync check function is
Use Func NO/YES YES
available
Live Line Volt Level 10~90 30 1 % Set voltage level monitoring operation
Detect Detect Time 0.05~1 0.10 0.01 sec Set voltage level operating time
I2/I1 Pickup 30~100% 50 1 % Set negative current operating level
Delay Time 0.1~10 10.0 0.1 sec Set negative OC operation time
Negative I1 Threshold 5~200 10 1 A Set Positive current threshold value
OC 2nd Harmonic Blk OFF/ALM/TRIP OFF Select 2nd Harmonic block/ non-block
Set negative OC fault operation
Func In Use OFF/ALM/TRIP OFF
functions, No Use/Alarm/Trip

- 48 -
U-V Pickup 30~98 75 1 % Set pickup level for under voltage
Under U-V Op Time 0.1~100 3 0.1 sec Set operation time for under voltage
Voltage Set whether under voltage function is
Use Func OFF/ALM/TRIP OFF
available
O-V Pickup 102~150 120 1 % Set pickup level for over voltage
Over O-V Op Time 0.1~100 3 0.1 sec Set operation time for over voltage
Voltage Set whether over voltage function is
Use Func OFF/ALM/TRIP OFF
available
U-F Pickup 47~59.98 49.8 0.01 Hz Set pickup level for under frequency
Set operation time for under
Under U-F Op Time 0.1~60 1 0.1 sec
frequency
Frequency
Set whether under frequency function
Use Func OFF/ALM/TRIP OFF
is available
O-F Pickup 50.02~63.00 60.02 0.01 Hz Set pickup level for over frequency
Over O-F Op Time 0.1~60 1 0.1 sec Set operation time for over frequency
Frequency Set whether over frequency function is
Use Func OFF/ALM/TRIP OFF
available
Close Live Load NO/YES NO Select whether live load is available
Interlock Sync Fail NO/YES NO Select whether sync fail is available
OFF/FEEDER/MI
Loop Selection OFF Select operating mode for the recloser
D/TIE
Deadbus Open Set open time for determining
0~600 0 1 sec
Time distribution line’s dead line state
Tie Sw Open
0~600 0 1 sec Set open time for tie sw
Time
Tie Sw Source BOTH/ABC/RST BOTH Select whether Tie sw source is ABC or RST
Loop
Tie Sw Close
Automation 0~600 0 1 sec Set close time for tie sw
Time
Rec Block Time 0~600 60 1 sec Set Reclosing Blocking Time
Set whether restoration after clearing
Enable Restore Disable/Enable Disable
fault
Rec Close Time 0~600 30 1 sec Set recloser closing time after open
Set delta I level to restore for Tie
Tie On Delta I 5~95 5 1 %
recloser after fault

5.2.8. Select Group


It is a menu to set currently applied Primary Group among 4 setting groups.
Default value is set 1. If Sel Auto Group is selected as “YES”, it selects automatically the
primary group and reverse group, depending on the power flow. If the current flows from
load side to source side, side flows from Load side to power side, the reverse group is
applied.
[ S e t t i n g ME N U ]
1 . F u n c G r o u p 1
[ S e l G r o u p Me n u ]
2 . F u n c G r o u p 2
> 1 . P r i ma r y G r o u p
3 . F u n c G r o u p 3
2 . S e l A u t o G r o u p
4 . F u n c G r o u p 4
3 . R e v e r s e G r o u p
> 5 . S e l e c t G r o u p

[ P r i ma r y G r o u p ]
S E T : 1

( 1 - 4 : 1 )

<Figure 5-14> Setting Menu

- 49 -
5.3. Configuration Menu
It provides menus for analog current and voltage input related setting, Debounce Time
setting to prevent DI chattering, DO output pulse adjustment related setting, Event Log
information setting and clear related setting.

5.3.1. Analog
Analog voltage / current input related setting items and ranges are like below.

<Table 5-6> Setting for Analog voltage / current


Item Range Default Step Unit Explanation
Line Config 3P4W/3P3W 3P4W Distribution line’s connection
Frequency 50/60 60Hz Distribution line’s frequency
Rated Voltage 3.8~21 13.2 0.01 kV Distribution line’s rated voltage
CT ratio 100~2000 1000 1 CT ratio
NCT ratio 100~2000 1000 1 NCT ratio
Avg Interval 5-15 15 5 min Average process time about demand value
Way to FI reset
Select FI Reset Auto/Man Man
Refer 5.2.2
Display voltage L-N/L-L L-N Selection of line to phase voltage and line to line voltage
ABC/ACB/BCA/
Phase Position ABC Select phase position
BAC/CAB/CBA
Phase Rotation ABC/ACB ABC Select whether phase rotation is ABC or ACB
Select which side will be power source between
Source Side ABC/RST ABC
ABC side and RST side
Energy Log Duty Week/Month Week Set duty time for energy logging
Closing Delay 0~300 0 1 sec Set delay time to close CB
Check V for FI NO/YES YES Select whether to consider voltage when FI set
Reclaim T for FI 0~120 2 1 sec Set reclaim time for FI
Import Key Delay 1~5 1 1 sec Set import key delay
Fail V Sensor 0~120 10 1 sec Set delay time for voltage sensor fail
I Cut Level 0~10 0.1 0.1 % Set level for current cutting
V Cut Level 0~50 10 1 % Set level for current cutting

The order to set is like below.


1) Choose the menu with Up/Down Key. Press Enter Key to enter the menu.
[ C o n f i g Me n u ]
-> 1 . A n a l o g
2 . D I D e b o u n c e T i m e
3 . D O P u l s e T i m e
4 . B a c k u p S e t / C l e a r
5 . A n a l o g G a i n A d j
6 . Wa v e f o r m
7 . C h e c k A u t o B a t t
8 . V / I U n b a l a n c e
9 . S a g / S w e l l
1 0 . T H D A l a r m

<Figure 5-15> Config Menu

2) On Analog menu, choose the item you want with Up/Down Key. Press Enter Key to
enter the item.

- 50 -
[ A n a l o g Me n u ]
->1 . L i n e C o n f i g
2 . F r e q u e n c y
3 . R a t e d V o l t
4 . C T r a t i o
5 . N CTT r a t i o
6 . A v g I n t e r v a l
7 . S e l e c t F I R e s e t
8 . D i s p l a y V o l t a g e
9 . P h a s e P o s i t i o n
1 0 . P h a s e R o t a t i o n
1 1 . S o u r c e S i d e
1 2 . E n e r g y L o g D u t y
1 3 . C l o s i n g D e l a y [ L I N E C O N F I G ]

1 4 . C h e c k V f o r F I S E T : 3 P 4 W

1 5 . R e c l a i m T f o r F I
1 6 . I mp o r t K e y D e l a y ( 3 P 4 W/ 3 P 3 W)

1 7 . F a i l V S e n s o r
1 8 . S a v e C o n f i g

<Figure 5-16> Analog Menu-Line Config

3) Change set value with Up/Down Key. Press Enter Key to check. If you want to cancel
the changed set value, press M Key.

4) After change, choose 18. Save Config to save the set value in backup memory and
come out from the item. Then the set value is applied to the device.
[ A n a l o g Me n u ]
->1 . L i n e C o n f i g
2 . F r e q u e n c y
3 . R a t e d V o l t
4 . C T r a t i o
5 . N CTT r a t i o
6 . A v g I n t e r v a l
7 . S e l e c t F I R e s e t
8 . D i s p l a y V o l t a g e
9 . P h a s e P o s i t i o n
1 0 . P h a s e R o t a t i o n
1 1 . S o u r c e S i d e
1 2 . E n e r g y L o g D u t y
1 3 . C l o s i n g D e l a y [ U p d a t e S e t t i n g ]

1 4 . C h e c k V f o r F I
1 5 . R e c l a i m T f o r F I - > P r e s s E n t e r

1 6 . I mp o r t K e y D e l a y
1 7 . F a i l V S e n s o r
1 8 . S a v e C o n f i g

<Figure 5-17> Analog Menu-Save Config

- 51 -
5.3.2. DI Debounce Time
It is a menu to set debounce time to prevent DI Chattering. It is available to set on each channel.
During set time, DI status value should be kept to be considered with the changed value.

<Table 5-7> DI Debounce Setting


Item Range Default Step Unit Explanation
DI_1 1~500 10 1 ms DI 1’s debounce time setting
DI_2 1~500 10 1 ms DI 2’s debounce time setting
DI_3 1~500 10 1 ms DI 3’s debounce time setting
... ... ... ... ... ...
DI_10 1~500 10 1 ms DI 10’s debounce time setting
The way to set is identical with 5.3.1

5.3.3. DO Pulse Width


It sets DO1~6’s on pulse output time.

<Tabel 5-8> DI Pulse Setting


Item Range Default Step Unit Explanation
DO_1 10~2000 500 10 ms DO 1’s pulse width time setting
DO_2 10~2000 500 10 ms DO 2’s pulse width time setting
DO_3 10~2000 500 10 ms DO 3’s pulse width time setting
DO_4 10~2000 500 10 ms DO 4’s pulse width time setting
DO_5 10~2000 500 10 ms DO 5’s pulse width time setting
DO_6 10~2000 500 10 ms DO 6’s pulse width time setting
The way to set is identical with 5.3.1

5.3.4. Backup Set / Clear


It is a menu operating switch operation count, Event data clear, Fault data and clear.

<Table 5-9> Backup Set / Clear


Item Range Default Step Unit Explanation
Set Switch Cnt 0~65535 0 1 Set the number of switch operation
Delete saved event information in backup
Clear Event NO/YES NO
memory
Clear Fault NO/YES NO Delete save fault information in backup memory
Delete save operation information in backup
Clear Oper Count NO/YES No
memory
The way to set is identical with 5.3.1

5.3.5. Analog Gain Adjust


It is a menu to adjust analog voltage / current volume gain. EPIC-R300 is set in calibration
about voltage / current signal input from factory. However if measuring value is different
because of external sensor’s error, use the menu to adjust.

<Table 5-10> Analog Gain Adjust


Item Range Default Step Unit Explanation
Ia Gain Adjust 10~2000 0 1 A Adjust current Ia’s gain

- 52 -
Ib Gain Adjust 10~2000 0 1 A Adjust current Ib’s gain
Ic Gain Adjust 10~2000 0 1 A Adjust current Ic’s gain
In Gain Adjust 10~2000 0 1 A Adjust current In’s gain
Va Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Va’s gain
Vb Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vb’s gain
Vc Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vc’s gain
Vr Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vr’s gain
Vs Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vs’s gain
Vt Gain Adjust 1~66 13.2 0.01 kV Adjust voltage Vt’s gain
Delete save gain data in backup
Clear Gain Data
memory
The way to set is identical with 5.3.1

5.3.6. Waveform
Settings associated with the condition of capturing the waveform and storing it.
“1. sample rate” : to select the sample rate which saves a waveform per one cycle.
“2. Record size” : to select the length of the waveform.
“3. Pre-cycle” : to set the stotage size before a failure occurance as a ratio of the total
size.
“4. Post-cycle” : to set the stotage size after a failure occurance as a ratio of the total
size.

<Table 5-11> Waveform


Item Range Default Step Unit Explanation
Set sample rate when capturing
Sample rate 16/32/64/128 32 sample
waveform
Record size 20~600 20 1 cycle Set record size of waveform
Pre-cycle 10~50 10 1 % Set pre-cycle number of waveform
Post-cycle 10~50 10 1 % Set post cycle number of waveform

5.3.7. Check Auto Battery


To automatically set the cycle of testing battery.

<Table 5-12> Check Auto


Item Range Default Step Unit Explanation
Check Day 1~31 1 1 day Set auto checking day for battery
Check Hour 0~23 0 1 hour Set auto checking hour for battery
Check Minute 0~59 0 1 minute Set auto checking minute for battery

*option
Item Range Default Step Unit Explanation
Auto-Check Day 1~31 1 1 day Set auto checking day for battery
Detect Batt-Low 18.7~24.0 21.6 0.1 V Set voltage level for battery low
Cut-Off Voltage 18.7~23.0 20.8 0.1 V Set voltage level for battery cutoff
Cut-Off Delay 1~600 60 1 s Set delay time for battery cutoff

- 53 -
5.3.8. V/I Unbalance
Settings relating to the level and operating time for detecting the unbalance of Voltage
and Current.

<Table 5-13> V/I Unbalance


Item Range Default Step Unit Explanation
V unbalance 0~100 0 1 % Set unbalance level for voltage
V unbalance time 0.1~60 0.1 0.1 sec Set unbalance time for voltage
I unbalance 0~100 0 1 % Set unbalance level for current
I unbalance time 0.1~60 0.1 0.1 sec Set unbalance time for current

5.3.9. Sag/Swell
Settings related to the level and operating time to detect Sag, Swell, and Interruption.

<Table 5-14> Sag/Swell


Item Range Default Step Unit Explanation
Sag Level 50~99 90 1 % Set pickup level for sag
Sag Time 0.02~10 1.0 0.01 sec Set operation time for sag
Swell Level 101~150 120 1 % Set pickup level for swell
Swell Time 0.02~10 1.0 0.01 sec Set operation time for swell
Interrupt Level 10~50 10 1 % Set pickup level for interruption
Interrupt Time 0.02~10 1.0 0.01 sec Set operation time for interruption

5.3.10. THD Alarm


Settings relating to the alarm level and operating time of the Voltage/Current’s THD(Total
Harmonic Distortion).

<Table 5-15> THD Alarm


Item Range Default Step Unit Explanation
V THD Alarm Level 1~100 3 1 % Set alarm level for voltage THD
V THD Alarm Time 0.02~60.00 0.02 0.01 sec Set alarm time for voltage THD
I THD Alarm Level 1~100 3 1 % Set alarm level for current THD
I THD Alarm Time 0.02~60.00 0.02 0.01 sec Set alarm time for current THD

5.3.11. VI Wear
Select VI type which is used in the recloser, and it displays residual contact wear for each
phase’ VI and total operation times.

<Table 5-16> VI Wear

- 54 -
Item Range Default Step Unit Explanation
Set the type of the VI used in the
Max Op Count 1000~10000 2000 1
recloser
Set alarm level for residual contact
Alarm Level 0~100 45 1 %
wear
Duty Factor A 0~100 100 1 % Set duty factor for A phase’s VI
Duty Factor B 0~100 100 1 % Set duty factor for B phase’s VI
Duty Factor C 0~100 100 1 % Set duty factor for C phase’s VI
Delete save wear information in
Clear Wear Info
backup memory

5.3.12. Analog High Alm


Settings relating to the alarm level and operating time of the Voltage/Current’s THD(Total
Harmonic Distortion).

<Table 5-17> Analog High Alm


Item Range Default Step Unit Explanation
Set phase current level for Analog
Phase Current 1~16000 400 1 A
High Alarm function
Set ground current level for Analog
Ground Current 1~16000 400 1 A
High Alarm function
Set phase voltage level for Analog
Phase Voltage 1~38000 13200 1 V
High Alarm function
Set system power level for Analog
System Power 1~54000 5280 1 kV
High Alarm function
Select whether Analog High Alm
Enable High Alarm Disable/Enable Disable
function is available

5.3.13. Analog Low Alm


Settings relating to the alarm level and operating time of the Voltage/Current’s THD(Total
Harmonic Distortion).

<Table 5-18> Analog Low Alm


Item Range Default Step Unit Explanation
Set phase current level for Analog
Phase Current 1~15999 110 1 A
Low Alarm function
Set ground current level for Analog
Ground Current 1~15999 110 1 A
Low Alarm function
Set phase voltage level for Analog
Phase Voltage 1~37999 510 1 V
Low Alarm function
Set system power level for Analog
System Power 1~53999 0 1 kV
Low Alarm function
Select whether analog low alm
Enable Low Alarm Disable/Enable Disable
function is available

5.3.14. Misc. Config


Settings relating to the miscellaneous config(Door contact, AC POWER LED, Insulator
Type...).

- 55 -
<Table 5-19> Misc. Config
Item Range Default Step Unit Explanation
Door Open Contact N.O(A)/N.C(B) N.O(A) Set contact type for door open(DI6)
AC Fail/AC
AC POWER LED AC Fail Set contact type for AC POWER(DI3)
Normal
Insulator Type Mold/SF6-GAS Mold Set contact type for Gaslow(DI7)

5.4. Communication Menu


It is a menu to set communication port to connect with upper system.
On this menu there are communication port setting in connection with SCADA system,
modem control signal setting in connection with modem, DNP3.0, IEC60870-5-101,
IEC60870-5-104, TCP/IP protocol related setting.

5.4.1. SCADA Port


It is a menu to set communication port in connection with SCADA system.

<Table 5-19> SCADA Port


Item Range Default Step Unit Explanation
Port connected with SCADA’s
Baud Rate 1200~38400 9600 bps
communication speed setting
Parity NO/EVEN/ODD NO Serial communication parity setting
Slave/DL Address 0~65534 2 1 DNP slave or IEC-101 D/L address setting
ASDU Comm
0~65534 2 1 ASDU common address setting
Addr
DNP/DNP-TCP/IEC- DNP3.0 and DNP-TCP and IEC870-5-101
Select Protocol DNP
101/IEC-104/ protocol and IEC870-5-104 protocol setting
Select Map Full Map/User Map Full Map Protocol map type setting

Clear User Map Delete saved user map in backup memory

The way to set is identical with 5.3.1

5.4.2. Modem Control


It is a menu to set modem control signal to connect SCADA system and modem.

<Table 5-20> Modem Control


Item Range Default Step Unit Explanation
Comm Line 2 / 4 4 Modem communication line setting
RTS Off Delay 10~500 100 10 ms After TX completion, delay setting for RTS Off
CTS Time out 0~255 3 1 s After RTS enable, CTS waiting time setting
DCD Time out 0.1~30 10 0.1 s TX waiting time when DCD is enable on 2 Line
The way to set is identical with 5.3.1

5.4.3. DNP Config


It is a menu to set DNP3.0 communication related items.

- 56 -
<Table 5-21> DNP Config
Item Range Default Step Unit Explanation
D/L Retry 0~2 0 1 Set the number of data link layer retry

D/L Timeout 1~255 3 1 s Set data link layer timeout


NO/YES/ SOMETI
D/L Confirm Choose if data link layer ask confirm is used
SOMETIME ME
A/L Retry 0~2 0 1 Set the number of application link layer retry
A/L Timeout 1~255 10 1 s Set application layer timeout
After power on, choose if unsolicited response
Unsol Resp Class NO/YES NO
is set
Unsol Resp Delay 0~60 1 1 s Unsolicited response delay time setting

Unsol Resend Dly 0~60 1 1 s Unsolicited response delay time setting


After selection, if set timeout is over for
SBO Timeout 1~255 5 1 s
operation order, select is lifted
Master Addr 0~65534 65534 1 Upper master’s address setting
If D/L timeout confirm is NO, choose link
Frame Interval 10~500 20 10 ms
frame’s interval
DNP Port Num 0~65534 20000 1 Set DNP-TCP Port Num
Disable/Enabl Select whether Clear Event when Reset
Cls Evt when RST Disable
e function is available
Disable/Enabl Select whether Event Time Sync function is
Event Time Sync Disable
e available
With
Without
BI Chg Dflt Var time/Without Select whether with time or without time
time
time
With
Without
AI Chg Dflt Var time/Without Select whether with time or without time
time
time
The way to set is identical with 5.3.1

5.4.4. IEC101 Config


It is a menu to set IEC870-5-101 communication related item.

<Table 5-22> IEC101 Config


Item Range Default Step Unit Explanation
Link Addr Size 0~2 2 1 Data link address size
Common Addr Size 1~2 2 1 Common address size
IOA Size 1~3 2 1 Information object address size
COT Size 1~2 1 1 COT address size

Time Format CP24/CP56/NO CP56 Select Time Fomat, CP24, CP56


or NO

Single Char N/ACK Disable/Enable Disable Set character ACK, NACK


information
Arm Timeout 1~255 5 1 s Set arm timeout
NORMAL/SCALE
Analog Data Type NORMAL Set analog data type
/FLOAT

Scan Analog Chg Disable/Enable Disable Set scan analog change


information

Scan Binary Chg Disable/Enable Disable Set scan binary change


information
The way to set is identical with 5.3.1

- 57 -
5.4.5. IEC104 Config
It is a menu to set IEC870-5-104 communication related item.
<Table 5-23> IEC104 Config
Item Range Default Step Unit Explanation
Conn Timeout(t0) 1~255 30 1 sec Set connection timeout
APDU Timeout(t1) 1~255 15 1 sec Set APDU timeout
Ack Timeout(t2) 1~255 10 1 sec Set ack timeout
Test Period(t3) 1~255 20 1 sec Set time period
Select whether spontaneous
Xmt Spontaneous Disable/Enable Disable
response function is available
Max Xmt I-APDU(k) 1~32767 15 1 Set max transmitting I-APDU
Max Rcv I-APDU(w) 1~32767 10 1 Set max receiving I-APDU
The way to set is identical with 5.3.1

5.4.6. TCP/IP Config


It is a menu to set TCP/IP address to connect SCADA system by Ethernet.

<Table 5-24> TCP/IP Config


Item Range Default Step Explanation
IP Address 0~255 0.0.0.0 1 Set IP address of FTU
Subnet Mask 0~255 255.255.255.0 1 Set subnet mask bits
Gateway 0~255 192.168.0.0 1 Set gateway address
NTP Server 0~255 192.168.0.0 1 Set NTP Server address
The way to set is identical with 5.3.1

5.4.7. PSTN Modem


Settings required to connect to the PSTN network.

<Table 5-25> PSTN Modem


Item Range Default Step Unit Explanation
PSTN Modem NO/PPP/Dialup/SMS NO Select PSTN mode type,PPP, dialup or SMS
Auto Hangup Time 0~255 30 1 sec Set Auto hangup time
Dial Timeout 10~255 90 1 sec Set dial timeout
Attempt Delay 10~3600 60 1 sec Set dial attempt delay time
Max Attempts 1~5 3 1 sec Set dial max attempt
The way to set is identical with 5.3.1

5.4.8. PPP Config


Settings for using the PPP(Point to Point Protocol).

<Table 5-26> PPP Config


Item Range Default Step Explanation
Our IP address 0~255 192.168.0.0 1 Set our IP address
Their IP address 0~255 192.168.0.0 1 Set their IP address
DNS1 IP address 0~255 192.168.0.0 1 Set DNS1 IP address
DNS2 IP address 0~255 192.168.0.0 1 Set DNS2 IP address
The way to set is identical with 5.3.1

- 58 -
5.4.9. SMS Config
Settings for using the SMS(short message service).

<Table 5-27> SMS Config


Item Range Default Step Explanation
Trip Enable NO/YES NO Set sending trip information
FI Enable NO/YES NO Set sending FI information
Open Enable NO/YES NO Set sending open information
Door Open Enable NO/YES NO Set sending door information
AC fail Enable NO/YES NO Set sending AC fail information
The way to set is identical with 5.3.1

5.4.10. Time Sync Option


Settings for using the Time Sync Option.
<Table 5-28> Time Sync Option
Item Range Default Step Unit Explanation
SNTP Enable NO/YES NO Select whether to enable SNTP
SNTP Period 1~24 1 1 hour Set SNTP cycle duty
UTC-12:00 ~ UTC+09:0
Select Time Zone Select time zone
UTC+14:00 0 SEOUL
The way to set is identical with 5.3.1

5.5. Time Set Menu


It is a menu to set time on the device. Like a picture below, RTC present time is on 2
upper lines and time for editing is on 2 down lines. The order to change the time you
want is like below.

1) Press Enter Key to change the time. Then the cursor blinks on the year you want to change.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6

<Figure 5-18> Time Set-year

2) To change the month, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 7
T i m e : 1 4 : 3 0 : 2 6

<Figure 5-19> Time Set-month

- 59 -
3) To change the date, press Enter Key then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 1 1

<Figure 5-20> Time Set-day

4) To change the time, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 3 0 : 2 6

<Figure 5-21> Time Set-hour

5) To change the minute, press Enter Key. Then the cursor blinks.

Press Up/Down Key to change.

N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 2 6

<Figure 5-22> Time Set-minute

6) To change the second, press Enter Key. Then the cursor blinks.
Press Up/Down Key to change.
N o w : 2 0 1 2 / 0 9 / 2 7
T i m e : 1 4 : 3 0 : 2 6
E d i t : 2 0 1 3 / 1 0 / 2 9
T i m e : 1 5 : 2 2 : 1 1

<Figure 5-23> Time Set-second

7) After changing, press Enter Key then the menu below shows. Press Enter Key again
then the edited time is saved.
[ U p d a t e S e t t i n g ]

- > P r e s s E n t e r

<Figure 5-24> Update Setting

- 60 -
5.6. Event View Menu
It is a menu to check various recorded information in EPIC-R300. Event List shows in a
chronological order from the latest one. You can check information with Up/Down Key.
There is information of Event List and maximum number of storage below.

<Table 5-30> Event View Menu


Event Items Description Max Event Num

Fault Event Save Fault Event history 512


Save Operation Event history
Op Event (save operation history about Power On, DO/DI 20,480
operation, setting, Fault/Pickup operation)
Demand I Average current during Demand time 255

Demand P Average electricity during Demand time 255

Max Demand I Record maximum Demand I value for a day 63

Max Demand P Record maximum Demand P value for a day 63

- 61 -
APPENDIX A. - COMTRADE File’s Formats
The COMTRADE record generated by your device consist of two files: the configuration
file (*.cfg) and the data file (*.dat). These files are structured as described in IEEE Power
Engineering Society C37.111 COMTRADE data format. Please refer to the IEC website for
the most up-to-date COMTRADE data format information.

Configuration File Format


The configuration file is an ASCII text file that contains the information necessary to
interpret the data (*.dat) file. The configuration file will have the same filename as the
data file but with the .cfg file extension, and will be included in every COMTRADE record.
For more details refer to the IEEE COMTRADE data format documentation.

Configuration file layout


The configuration (*.cfg) file is laid out as follows:

Configuration file fields


The configuration (*.cfg) file fields are described in following table:

- 62 -
- 63 -
Configuration field details
The following table describes the channel identifier(ch_id) and channel phase identification
(ph) values:

Data file format


The data (*.dat) file contains the sample number, time stamp and data values of each
channel, for each sample in the file. The data file has the same name as the configuration
file but with a .dat file extension, and contains binary formatted data.

Data file layout


The data (*.dat) file layout is as follows:

Data file fields


The data (*.dat) fields are described in the following table:

- 64 -
Example - configuration file

- 65 -
APPENDIX B. TC Curve
1. TC Curve
The EPIC-R300 supports analog recloser curves, IEC curves, ANSI/IEEE curves, and KEPCO
curves, The list is as follows.

No. 1 2 3 4 5 6 7 8 9 10

TC Curve A B C D E K L M N P

No. 11 12 13 14 15 16 17 18 19 20

TC Curve R T V W Y Z 1 2 3 4

No. 21 22 23 24 25 26 27 28 29 30

TC Curve 5 6 7 8 8* 9 11 13 14 15

No. 31 32 33 34 35 36 37 38 39 40

TC Curve 16 18 IEC NI IEC VI IEC EI IEC LI IEC SI IEEE MI IEEE VI IEEE EI

No. 41 42 43 44 45 46 47 48 49 50

TC Curve IEEE NI ANSI U2 ANSI U8 ES NI ES VI KEPCO N1 KEPCO N2 KEPCO N3 KEPCO N4

◆ TC curve equation
The equation of TC curve supported by EPIC-R300 is as follows.

  
        × 
   
   
  
- I = Fault current
- I> = Pick up current setting value
- k = Multiplier setting value

Standard Curve A B C
Normal Inverse(NI) 0.14 0.02
Very Inverse(VI) 13.5 1
IEC Extremely Inverse(EI) 80 2
Long-time Inverse(LI) 120 1
Short-time Inverse(SI) 0.05 0.04
Moderately Inverse(MI) 0.0515 0.114 0.02
Very Inverse(VI) 19.61 0.491 2
IEEE/ANSI
Extremely Inverse(EI) 28.2 0.1217 2
Normal Inverse(NI) 0.0086 0.0185 0.02
Long-time Inverse(U8) 5.95 0.18 2
ANSI
Short-time Inverse(U2) 0.2394 0.0169 0.02
Normal Inverse(NI) 0.011 0.042 0.02
ES
Very Inverse(VI) 3.985 0.1084 1.95

- 66 -
2. TC Curve 1~4

1
2
3
102 4

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 67 -
3. TC Curve 5~8

5
6
7
102 8

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 68 -
4. TC Curve 8*~13

8*
9
11
102 13

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 69 -
5. TC Curve 14~18

14
15
16
102 18

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 70 -
6. TC Curve A~D

A
B
C
102 D

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 71 -
7. TC Curve E~M

E
K
L
102 M

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 72 -
8. TC Curve N~T

N
P
R
102 T

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 73 -
9. TC Curve V~Z

V
W
Y
102
Z

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 74 -
10. TC Curve IEC NI~SI

IEC NI
IEC VI
IEC EI
104 IEC LI
IEC SI

103

102
Time[sec]

101

100

10-1

100 101
Current In Multiplies of Setting

- 75 -
11. TC Curve IEEE MI~NI

IEEE MI
IEEE VI
IEEE EI
103 IEEE NI

102

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 76 -
12. TC Curve ANSI U8, U2

ANSI U8
ANSI U2
103

102

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 77 -
13. TC Curve ES NI, VI

ES NI
ES VI

102

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 78 -
14. TC Curve KEPCO N1~N4

N1
N2
N3
102 N4

101
Time[sec]

100

10-1

100 101
Current In Multiplies of Setting

- 79 -
15. TC Curve DEF 1S, 10S

DEF 1S
DEF 10S

101
Time[sec]

100

10-1
100 101
Current In Multiplies of Setting

- 80 -
- 81 -

You might also like