e o
Fike INSTRUCTIONS
RESET MULTI-TOOL
DESCRIPTION
Fike has designed a new Reset Tool (02-14782), this tool can be used on any of
the operators / actuators shown the chart below and replaces the three
existing tools. These operators / actuators are unique and have previously
required different tools for reset. The Fike Reset Multi-Tool (02-14782) sa
‘multipurpose tool that ald in the resetting of all these operators,
‘Adcitional functionality includes a pin to reset PROINERT pneumatic actuators
‘and threaded knob for PROINERT blanking plug removal.
‘TOOL EQUIVALENCY CHART
Part No. vo Iveo DFIA piva uvo eee I mare
70-286 x x a x
70-312 x
1671-0166 x x
02-14782 x x x x x x Ei
wo fke.com Form to. 06-53, October, 2016
This document is only intended to be a guideline and is not applicable to net
all situations. Information subject to full disclaimer at
http://www. fike.com,Fike
RESET INSTRUCTIONS FOR IVO ~ IVPO ~DFIA~ DIVA- UVO
y
| Prnertensed (res Posten)
>
Puno
Remove the Operator from the Fike valve by removing Retaining Clip.
2} Remove Safety Pin and pul the Manual Strike Button knob untiit resets
(interal cick is heard)
Ssfetyin. SY
3] Align the forked end of the anvil handle around the grooved end ofthe Operator tip
When retin UVO its commences
to use the adetiona Pin Tool
Pin Too! st
4) Squeeze reset too! handles untll Operator Pin resets (clicks into place)
IMPORTANT NOTE: Check that Operator Pin is reset to ensure device is armed before
Inserting on a suppression valve,
via Fike com
Ferm No, 06833, October, 2036
This document is only intended to be a guideline and is not applicable to
all situations. Information subject to full disclaimer at
http://www.fike.com/disclaimer
rcFike
RESET INSTRUCTIONS FOR PNEUMATIC ACTUATOR
2) Remove Pin Tool fom Reset Multi-Tool
2}, Remove the Operator from the Fike valve by removing Retaining Cin Pneumatic Astor
3) Slide Pin Tool over the tip ofthe Preumatic Actuator.
44) Push the Pin Too! in by hand to depres the internal latching ball
IMPORTANTNOTE: Do not attempt to force the tip ofthe Pneumatic
‘etuator to reset. t wl retract on its own once the
Internal latch balls moved with the Pn
"pEatendes Fired Postion)
IMPORTANTNOTE: Check that Operator Pin is eset to ensure device is
armed before inserting on a suparession valve.
Poeumati Actuator
A.
‘preset (armed Postion)
won Fke cor Form No, 05838, October, 2036
This document is only intended to be a guideline and is not applicable to set
all situations. Information subject to full disclaimer atFike
INSTRUCTIONS FOR BLANKING PLUG REMOVAL
41) Remove Knob from the Reset Multi-Tool
2} Remove the Retaining Clip from the PROINERT Vahee.
3) Thread knob into Blanking Plug,
4) Pui Knob to remove Blanking Plug.
‘The PROINERT Valve is now ready for an operator.
whe com Fo No, 06833, October, 2016
This document is only intended to be a guideline and is not applicable to we
all situations. Information subject to full disclaimer at
http://www. fike.com/disclaimer