e o Fike INSTRUCTIONS RESET MULTI-TOOL DESCRIPTION Fike has designed a new Reset Tool (02-14782), this tool can be used on any of the operators / actuators shown the chart below and replaces the three existing tools. These operators / actuators are unique and have previously required different tools for reset. The Fike Reset Multi-Tool (02-14782) sa ‘multipurpose tool that ald in the resetting of all these operators, ‘Adcitional functionality includes a pin to reset PROINERT pneumatic actuators ‘and threaded knob for PROINERT blanking plug removal. ‘TOOL EQUIVALENCY CHART Part No. vo Iveo DFIA piva uvo eee I mare 70-286 x x a x 70-312 x 1671-0166 x x 02-14782 x x x x x x Ei wo fke.com Form to. 06-53, October, 2016 This document is only intended to be a guideline and is not applicable to net all situations. Information subject to full disclaimer at http://www. fike.com, Fike RESET INSTRUCTIONS FOR IVO ~ IVPO ~DFIA~ DIVA- UVO y | Prnertensed (res Posten) > Puno Remove the Operator from the Fike valve by removing Retaining Clip. 2} Remove Safety Pin and pul the Manual Strike Button knob untiit resets (interal cick is heard) Ssfetyin. SY 3] Align the forked end of the anvil handle around the grooved end ofthe Operator tip When retin UVO its commences to use the adetiona Pin Tool Pin Too! st 4) Squeeze reset too! handles untll Operator Pin resets (clicks into place) IMPORTANT NOTE: Check that Operator Pin is reset to ensure device is armed before Inserting on a suppression valve, via Fike com Ferm No, 06833, October, 2036 This document is only intended to be a guideline and is not applicable to all situations. Information subject to full disclaimer at http://www.fike.com/disclaimer rc Fike RESET INSTRUCTIONS FOR PNEUMATIC ACTUATOR 2) Remove Pin Tool fom Reset Multi-Tool 2}, Remove the Operator from the Fike valve by removing Retaining Cin Pneumatic Astor 3) Slide Pin Tool over the tip ofthe Preumatic Actuator. 44) Push the Pin Too! in by hand to depres the internal latching ball IMPORTANTNOTE: Do not attempt to force the tip ofthe Pneumatic ‘etuator to reset. t wl retract on its own once the Internal latch balls moved with the Pn "pEatendes Fired Postion) IMPORTANTNOTE: Check that Operator Pin is eset to ensure device is armed before inserting on a suparession valve. Poeumati Actuator A. ‘preset (armed Postion) won Fke cor Form No, 05838, October, 2036 This document is only intended to be a guideline and is not applicable to set all situations. Information subject to full disclaimer at Fike INSTRUCTIONS FOR BLANKING PLUG REMOVAL 41) Remove Knob from the Reset Multi-Tool 2} Remove the Retaining Clip from the PROINERT Vahee. 3) Thread knob into Blanking Plug, 4) Pui Knob to remove Blanking Plug. ‘The PROINERT Valve is now ready for an operator. whe com Fo No, 06833, October, 2016 This document is only intended to be a guideline and is not applicable to we all situations. Information subject to full disclaimer at http://www. fike.com/disclaimer

You might also like