Professional Documents
Culture Documents
I. General
This Meeting was convened following an agreement made during the SEERC Management Board in Kyiv last
June. The Conveners of two established RWGs 02 and 03 invited the RWG Members who have been nominated
by NCs. The RWG 02 Convener obtained the following nominations:
Slovenia: Maks Babuder (maks.babuder@eimv.si)
Marko Hrast (marko.hrast@eles.si)
Aleksander Polajner (aleksander.polajner@eles.si)
3. Brief survey of work done by former CIGRE WGs related to this issue
In autumn 1980 the CIGRÉ SC 31 established an Ad Hoc Task Force on Static Var Compensators as a part of
WG 31-01. The pertaining ToR aimed its endeavours to preparing of an international survey on operational
experiences and was assembled of different experts coming from utilities, manufacturers, research
organizations and universities. The main intention was to obtain a practical guidance for application. In
1986 the Brochure 25 entitled STATIC VAR COMPENSATORS was prepared and published by WG 38-01
Task Force No.2 giving application principles for:
- Voltage Control
- Load Balancing
- Power Transfer Capacity Increase
- Transient Stability Improvement
- Improvement of System Damping
- Subsynchronous Resonance Damping and
- Reduction of Temporary and Line Energisation Overvoltages
Later on the CIGRÉ Task Force No. 3 of WG 38-01 “Reactive Power Compensation Analysis and Planning
Procedure” issued in 1987 the Brochure 27: METHODS FOR REACTIVE POWER OPTIMIZATION where an
exhaustive list of references is given emphasizing among other related features, the Voltage control and
stability and Voltage quality. In 1989 the Brochure 30 REACTIVE POWER COMPENSATION ANALYSES AND
PLANNING PROCEDURES was published which has been prepared by the same Task Force No. 3.
In 1993 as a result of the Task Force No.4 of CIGRÉ WG 38.05 the publishing of the Brochure 77 ANALYSIS
AND OPTIMIZATION OF SVC USE IN TRANSMISSION SYSTEMS followed.
During last two decades numerous CIGRÉ Brochures dealing with system voltage control have been
published. Brochure 144 STATIC SYNCHRONOUS COMPENSATOR (STATCOM) conceived by Working Group
14.19 and published in the year 2000 represents a continuation of the Brochure 25. Power handling
capability and other advances of commercially available GTO thyristors made possible the development of
new controllable reactive power sources with operating characteristics similar to that of rotative
synchronous compensators. This analogy contributed to its new name Static Synchronous Compensator
(STATCOM).
All of these CIGRÉ expert groups focussed on the system voltage profile control which endeavours
continued after reorganizing of CIGRÉ and led to establishing of the WG B4.35 within the SC B-4 HVDC and
Power Electronics. As result of this group work the Brochure 242 THYRISTOR CONTROLLED VOLTAGE
REGULATORS was published in 2004. It is worth to mention that at the end of this report a Comparison of
the hybrid thyristor-type OLTC with conventional OLTCs was made.
Despite this advantages and favourable environment but caused by important limitations and obstacles the
widespread application of power electronic equipment in the transmission system didn’t take place. Its
high cost and lower reliability remains a serious obstacle and it gives to the use of mechanically switched
compensators a decisive advantage.
The generated power volatility of greater part of renewable sources on one hand and the open energy
market environment on the other may jeopardize the power system stability and cause serious problems
in reducing transmission capability notably the cross border capacities.
One RWG 02 Member reported on the last CIGRÉ SC A2 Colloquium on 20TH – 25TH of last September where
Shunt Reactor Reliability was considered and discussed. Australia and Great Britain reported on most
frequent shunt reactor failures.
On the same occasion the A3 Workshop and Tutorial was organized dealing with Shunt Reactor Switching.
It seems that the controlled switching is commonly used because of frequent (daily) reactor on/off
switching.
Transmission System voltage control represent today an important issue touching and affecting R&D
interests of several SC activities.
6. Future work
The participants expressed their feelings about the importance of voltage profile control in all parts of the electric
power system aiming to integrate all influencing factors and particularly striving to activate and stimulate interest
of all concerned. From formal and informal discussions it seems reasonable to continue intensive exchange of
experiences between RWG members. The convener will contact the SEERC MB representatives to nominate new
RWG Members and contact all already assigned members who were not able to attend this meeting.
Maks Babuder
ATTACHMENT 1
Page 1/1
TEİAŞ
Turkish Electricity Transmission Corporation
Transmission Planning and Coordination Division
Main structure of the grid; 400kV lines and substations; were started to be built in mid 1970s. Construction of
400kV lines has started from far east located Hydro-Electric Power Plants, HEPPs to the load centres, İstanbul
region passing through Ankara, the capital city via long lines total length up to ~1000km. Such long lines
required shunt reactor at both end at the intermediate substations for initial switching and light load operation.
We have used mono phase reactor ranging of 97MVAR @380kV to 122MVAR @380kV. Single phase reactors
are practical at that time for the HEPP switchyards which are far from main transportation network and contain
large site area. These shunt reactors are bus bar connected by breaker or line connected with or without breaker.
Development of our 400kV network for the last 45 years, different sizes of shunt reactors were used in the grid
where most of them are three phase. They have sizes as 97MVAR, 122MVAR, 146MVAR and 166MVAR
respectively. If any substation contains a line longer than ~150km-~170km, we utilize a shunt reactor to apply
line switching successfully, generally at both ends. Recently in large cities, increasing utilization of underground
cable also requires shunt reactors in the substations. We have introduced the first on-load tap changing 400kV
shunt reactor in our grid a few years ago. This reactor is 160-250MVAR @ 420kV with # of 25 on load taps.
Below is the brief definition of this shunt reactor from the draft specification.
"This specification covers the design, manufacturing, testing, supply, transport assistance for installation
and commissioning of 3-phase shunt reactors provided with tapped windings and on-load tap-changer, with
variable MVAR output from 160 to 250MVAR at 420kV.
Shunt reactors (SRs) shall be 3-phase units, 50Hz, oil immersed, outdoor type, natural oil and forced air
cooling (ONAN/ONAF).
SRs shall be provided with all the herein specified accessories and with current transformers (CTs)
bushing type, mounted on the line and neutral terminals for measuring and protection.
SRs shall be connected to the end of a 420kV line or to a 420kV substation bus-bar, via an SF6-420kV
circuit breaker (CB) provided with independent operating mechanisms for each pole and specified for switching
off SRs. A synchronizing relay will initiate at appropriate instants the opening of CB separately for each pole, to
perform SR current interruption without risk of dangerous over-voltages due to current chopping.
Surge arresters with suitable ratings shall be connected to the HV terminals of SRs and also to neutral
terminal if this is specified to be grounded via a reactor.
In case of 1-phase-to-Gr fault in a line directly compensated by dedicated SR, the pole of CB of SR
connected to the line faulty phase (or all the 3 poles of CB) may be automatically opened and reclosed after 4 or
5 seconds, if the faulty phase of line has been successfully reclosed. If reclosing is unsuccessful, the SR will be de-
energized with the line.
SRs shall comply with the following characteristics which shall be the minimum requirements.
ATTACHMENT 3
Page 2/2
Some shunt reactors are utilized at power plants in order to permit generator to operate at overexcited mode for
better machine stability even there is no voltage problem. The planned Nuclear Power Plant, NPP is also to be
designed to contain at least two large size shunt reactors.
154kV network also equipped with some reactor (5MVAR-20MVAR) where grid Short Circuit Power is less. In
154kV lines, line energizing does not require reactor thereof all shunt reactors are bus bar connected at this voltage
level.
ATTACHMENT 4
Page 1/1
Marko Hrast M. Sc.
Eles d.o.o. (TSO of Slovenia)
Transmission Network Infrastructure
The base of Slovenian electric power network consists of 220 kV and 400 kV network. Due to relatively small size
of network (cca. 3000 km) and geographical position in the middle of European electric power system it has strong
interconnection with neighbouring countries on both voltage levels. The power flow through the network depends
on many factors: the hydrology and hydro power production in Western Balkan, sporadic production of wind
energy from North Europe, low consumption during night and weekends.
These oscillations of power flow through our network and also in the neighbouring counties create non-
controllable increases of voltage in the 220 kV and 400 kV network. During past five years on 400 kV network the
voltage exceed the maximum allowed voltage in the network on average 800 hours per year. In 2013 the problem
of exceeded voltage phenomena reached 2700 hours in the most critical point of the network. Such a situation
represents violation of grid operation rules and brings problems with accelerated ageing of insulation of all kind of
high voltage equipment. It is obvious that there is a need for some measures to diminish such risks in the network
and on the equipment.
There are several possible solutions which can be more or less successful in particular situations. The first step is to
switch off the lines during low load situation under certain conditions. These measures can be done when there are
lines with double circuits and multiple line interconnections in the same direction. Nevertheless such measure
means that security and reliability criteria are violated. The second measure in our network is the use of phase-
shifting transformer with which the power flow during low load can be increased and voltage can be brought in the
required values. This solution has been used quite successfully during past 12 months.
Since the problem of exceeded voltages arisen the long term solution has been studied. The most known and
technologically and economically convenient is the use of variable shunt reactors (VSR), which has be studied in
our case. The project of installation of two VSR is in progress. Other possible solutions which can be used are
installations of synchronous compensators and the new generations of static var compensators (SVC). These two
solutions are currently being studied.
ATTACHMENT 5
Page 1/1
Božidar Filipović-Grčić, PHD
On behalf of the Croatian TSO and Croatian CIGRÉ NC
Overview of problems with the voltage profile in 220 kV and 400 kV transmission network in Croatia and
proposal for possible solutions.
Transients caused by shunt reactor switching (overvoltages and restrike phenomena during de-energization
and inrush currents due to energization).
Overview of controlled switching technology and circuit breaker characteristics for shunt reactor switching.
Experiences with measurements and simulations of shunt reactor switching transients in 110 kV network in
Croatia (modelling of electric arc in EMTP software).
Experiences with simulations of transients when switching variable shunt reactor (VSR) in 400 kV network.
Comparison of compensation solutions with VSR and SVC solutions in the transmission network.
Overview of PhD thesis which are currently in progress on Faculty of Electrical Engineering and Computing,
University of Zagreb.
1) Title: Power system interconnection reactive power flow control
Expected scientific contributions:
- Method of managing the flow of reactive power to the interconnection transmission lines with defined allowed
values of reactive power flows at the ends of transmission lines.
- The model for determining the minimum correction limit of reactive power flows on interconnection transmission
lines when there are no good solutions from the optimization procedure.
- Experimental verification of the model for the control of reactive power flow to the interconnection transmission
lines.
2) Title: Parameter and switching sequence selection of variable shunt reactors (VSR) in high voltage network
Expected scientific contributions:
- The method of parameter selection of VSR on the basis of a sensitivity analysis of voltage conditions in high
voltage transmission network.
- A mathematical model for the analysis of transients due to switching of VSR in the transmission network.
- The algorithm of optimal selection of VSR switching sequence with aim to reduce mechanical and electrical
stress of high voltage equipment.
ATTACHMENT 6
Page 1/12
ATTACHMENT 6
Page 2/12
ATTACHMENT 6
Page 3/12
ATTACHMENT 6
Page 4/12
ATTACHMENT 6
Page 5/12
ATTACHMENT 6
Page 6/12
ATTACHMENT 6
Page 7/12
ATTACHMENT 6
Page 8/12
ATTACHMENT 6
Page 9/12
ATTACHMENT 6
Page 10/12
ATTACHMENT 6
Page 11/12
ATTACHMENT 6
Page 12/12