Professional Documents
Culture Documents
FLS EP Filter INSTRUCTION MANUAL
FLS EP Filter INSTRUCTION MANUAL
INSTRUCTION MANUAL
RAMSINGSVEJ 30 - 2500 VALBY - DENMARK 100 GLENBOROUGH DRIVE – 77057-3611 HOUSTON - USA CARRETERA DE LA COURUNA KM. 17-8 – 28230 LAS ROZAS – SPAIN ESPACE INDUSTRIEL, NORD – 80084 AMIENS CÉDEX 2 - FRANCE
50001-08 2
SECTION A
1. INTRODUCTION......................................................................................................... 4
6. SPECIFICATIONS .................................................................................................... 54
6.1 Signals............................................................................................................... 54
6.2 Voltage supply................................................................................................... 54
6.3 Environment ...................................................................................................... 54
3 50001-08
SECTION B
7. INTRODUCTION....................................................................................................... 55
9. CONFIGURATION .................................................................................................... 56
SECTION A
In Fig. 1.1 is outlined the HV power supply consisting of a control cabinet, where PIACS
DC is mounted, and a high voltage tank containing an oil-cooled high-voltage trans-
former/rectifier.
The control unit regulates the average value of the precipitator current in a closed loop
control system. The current is measured by means of (5) a current shunt
(mA-signal). The precipitator current and thereby the corona power is regulated by means
of two antiparallel thyristors controlling the AC voltage applied to the high-voltage trans-
former. The secondary voltage of transformer is rectified in a monophasic bridge rectifier
and then applied directly to the electrostatic precipitator with a negative polarity.
5 50001-08
It is well-known that the corona power is limited by the sparks occurring in the precipitator.
These are detected using the precipitator voltage, that is measured by a voltage divider
(kV-signal) (6). Apart from a safe spark detection, one of the most important tasks of
PIACS DC is a rapid recovery of the voltage level after a spark without unnecessary block-
ing of the precipitator current and without occurrence of multiple sparks. These functions
are performed by an interface PC board (1) and a microprocessor PC board (2).
Then, the task of PIACS DC consists in the determination of the optimal firing angle to the
thyristor, in every single half-cycle of the line frequency. This firing command is transmitted
as a frequency signal to a firing angle control board (4) where it is transformed to firing
pulses to be applied to the two antiparallel thyristors.
The man/machine interface is carried out via a keyboard/display (3). Besides, PIACS DC
comprises a number of other important functions, which are built into the control unit. They
will be described in Chapter 3, CONTROL STRATEGY OF THE HV POWER SUPPLY.
50001-08 6
• Direct measurement of the average, minimum (trough), and peak value of the
precipitator voltage
• Automatic turn on from the CPU (e.g. in case of line voltage dips)
• Power Off Rapping (POR), is used together with rapping of collecting plates
The main elements of the control unit are shown in Fig. 2.1:
Externally, there are a control panel (1) consisting of a keyboard (2), a display window (3),
start/stop buttons (4), and panel instruments (5). See Chapter 4, OPERATING INSTRUC-
TIONS for details.
Fixed to the front plate (7) there are two PC boards (PCBs). Closest to the front plate is
placed the microprocessor PC board CU19 (8) on which a 16-characters liquidcrystal dis-
play (9) is mounted.
Fixed to PCB CU19 with four plastic spacers (10) is mounted the interface PCB CS28.1
(11) with the components side facing against the control panel (1).
The keyboard (2) is implemented with membrane contacts (12) and is connected to an
Euro-connector (16) in PCB CU19 (64 pins) via a flat cable (17). Communication with the
outside world takes place via two SUB-D connectors, one having 25 pins (18) and the
other one 37 pins (19).
50001-08 8
The two PC boards (8) and (11) are interconnected electrically via a Euro-connector (13),
which is mounted in the middle of both PC boards.
In order to protect the two PC boards from mechanical shock as well as dust and electro-
magnetic interference (EMI), these are covered by a metallic cover (14), which is fixed to
the front plate with three screws (15).
This part of the control unit is connected to the remaining part and to the main circuit of the
HV power supply as shown in Fig. 2.2.
Voltage
Supply
AA30.1
Thyristors
Relay
Control
System
Internal
Signals
External Signals
Fig. 2.2, PIACS DC connection diagram
The control panel with the two PC boards (CU19 and CS28.1) is connected to a terminal
and distribution PC board (HX02) via two multicore cables, terminated by SUB-D connec-
tors in both ends. The connectors X5 and X13 have 25 pins, while X6 and X14 have 37
pins.
The firing order from the microprocessor circuit is transmitted via the interface board to the
terminal strip X15 and further to the firing angle control PC board (AA30.1). This PCB
transforms the firing command to firing pulses, which are then applied to the phase control
thyristors. The firing pulse transformers are mounted on PC board AA30.1.
9 50001-08
The PC boards CU19 and CS28.1 are energized from a separate 24 V transformer wind-
ing like the PC board AA30.1. As shown in the example of Fig. 2.2 the relay control system
may in some cases be energized from a 220 V winding, but this depends on the particu-
lar plant. The AC supply can also be taken from a 24 V winding.
The external signals, e.g. the alarms from the HV tank, remote indication, remote control,
etc. are connected to the terminal strip X12 on the PC board HX02. Besides, there are two
BNC-connectors X17 and X19, which are intended for the connection of the unit to a su-
pervisory control computer.
Fig. 2.3 shows an example of an electric diagram of the control unit where all the signals
the PIACS DC can handle are shown. As the connection to the HV power supply depends
on the type used, please consult the delivered plant documentation for a complete descrip-
tion.
.1
Start-up
The start-up (1) begins when the main contactor is energized. During the first two seconds
the firing pulses to the thyristors are blocked; after that, the precipitator voltage is raised to
an adjustable starting value (parameter UDC start) during one half-cycle of the line fre-
quency.
Then the DC-current is increased at a rate of 200%/min. (100% corresponds to the rated
current). The starting sequence finishes when an adjustable current limit (8) (parameter I
DC Limit) is reached, or when a type 1 spark (2) or a type 2 spark (6) takes place.
Figure 3.1 shows an example of a start-up sequence finished by a type 1 spark. See sec-
tion 3.2 concerning spark detection.
11 50001-08
Current Setback
After that, the current is raised at a rate (5) corresponding to the desired spark rate (pa-
rameter Spk Set Rt). The rate of rise (5) is calculated internally in the PIACS DC and
corresponds to the product of the selected current setback and the spark rate (Set-Back
x Spk Set Rt).
In case of type 2 spark (6), the firing pulses to the thyristors are blocked during an adjust-
able time (parameter t-Quench); after that, the reaction is like in case of type 1 sparks.
After the recovery time, the current is increased at the rate of rise calculated internally (5).
If no spark occurs, the current is limited by the selected upper limit (8).
In case of fast changes in the operating conditions of the precipitator, many sparks may
occur in a short time, reducing the current to a low value. When the disturbance disap-
pears, it may take a relatively long time before the current can assume its normal value.
This is the case, particularly if the selected rate of rise is low. Therefore, the automatic
control includes the so-called FRM-function (Fast Ramp Mode), which increases the
DC-current fast at a rate corresponding to 200%/min. The FRM-function is activated, if no
sparks occur during an adjustable waiting time t-FRM (parameter t-FastRamp).
If the absolute value of the precipitator voltage (│uF│) falls and crosses the undervoltage
limit (11), as seen in Fig. 3.2.b, a 20 ms timer is started (12). The undervoltage limit is de-
termined automatically as 0.5 x UDC low.lim.
50001-08 12
If the precipitator voltage does not exceed the undervoltage limit (11) before the timing in-
terval (12) elapses, a type 2 spark is detected (Fig. 3.2.b). As mentioned before, in case of
type 2 sparks, a blocking period for the firing pulses determined by the parameter
t-Quench is initiated. After sparks, the DC-current is increased to the reduced value dur-
ing the so-called recovery time. During this period, the precipitator voltage is regulated as
shown in Fig. 3.3.
After that, there is a change from voltage control to current control (15). The rise of the av-
erage voltage to the value (17), corresponding to the reduced current value, takes place
during the selected recovery time (16). In this example it corresponds to five half-cycles
(parameter t-Recovery).
In the first of the three half-cycles where the voltage rise takes place, the aimed voltage
level (14) can be adjusted by the parameter RecoverCurve. It indicates at the same time
the recovery method used:
If the measurement of the peak voltage is not possible, the control unit changes automati-
cally to recovery after the mean voltage. (See description of STATUS messages).
In case of a new spark during the voltage recovery period the automatic control will con-
sider this as a type 2 spark. After the subsequent quench-time (parameter t-Quench) has
elapsed, the aim in the next three half-cycles, is to raise the precipitator voltage to a level
of approximately 75% of the original level (13).
Fig. 3.4 shows the primary current (iP) and the absolute value (│uF│) of the precipitator
voltage, in relation to the AC line voltage (uN). It is seen that the primary current may con-
sist of an auxiliary and a main current pulse.
The current in this example is blocked during one half-cycle (T/2). When the auxiliary pulse
is required in order to avoid saturation of the core of the HV transformer, it typically leads
the main current pulse by 120°.
Another way to avoid saturation of the core is by using limitation of the firing angle used for
the main pulse. This is explained in section 3.10.
50001-08 14
The waveforms are periodical and are repeated with a cycle time corresponding to the in-
terval between two main current pulses equal to Nec x T/2. Nec is always an odd number
of half-cycles in order to avoid direct current in the AC power line. This is adjustable with
the parameter Nec min. This setting is limited by an upper limit determined by the pa-
rameter Nec max (max. value 25).
During EC-operation, the max. attainable current is the rated current multiplied by a factor
K = 1.5/Nec. The adjusted current limit and current setback are therefore automatically
corrected by the same factor when changing from DC-operation to EC- operation and
vice-versa.
The distance between the auxiliary firing (1) and the main firing (2) is adjustable by means
of the parameter α Aux/Main, and there is also a lower limit for the auxiliary firing (pa-
rameter α Aux.Min.). A value larger than 175° disables the auxiliary firing, making pos-
sible the activation of the back-corona detector (parameter BC Measure.). See also sec-
tion 3.5.
When changing to a lower degreee of intermittence, the firing angle is instantaneously in-
creased in order to avoid sparks (parameter α Nec Change).
After a spark, the precipitator voltage is increased using a single current pulse, to a level
determined by the parameter RecoverCurve, in the same way as during DC-operation.
Afterwards the thyristors are blocked during a number of half-cycles corresponding to the
current degree of intermittence. In the following main firing the firing angle is delayed in
order to avoid spark (parameter α EC Spark).
15 50001-08
The value Ubs is the average of the last two minimum values before the spark and Uas is
the average of the third and fourth minimum values after the spark (but second and third
minimum values for Nec > 1).
Back corona occurs when Uas > Ubs, but the control unit includes a sensitivity factor (fBC)
and hysteresis (h) in the detection procedure. This means that the degree of intermittence
will change automatically as follows:
If the result of a detection procedure causes a reduction of Nec, a new detection proce-
dure is initiated immediately.
The back corona detector is activated periodically with an adjustable frequency deter-
mined by parameter BC Measure.. The activation is not possible if the setting of parame-
ter α Aux.Min. is ≤ 175°. By setting BC Measure. to 0, the back corona detector is
deactivated. In this case, the intermittence degree is equal to the parameter
Nec min.
For the measurement of Ubs and Uas, the average value of four sparks is taken. In case of
double spark, defined as two sparks closer than 0.3 s, the value of the second spark is
disregarded.
Every time the periodical detection is activated, the parameter t-Fast Ramp is set to 10 s
thus allowing the current to increase rapidly to the spark level. In this situation it is possible
to choose between two states:
The first state is standard, while the second allows the current to increased up to rated
value.
However, if no sparks occur the thyristors are blocked during an adjustable time (parame-
ter t-Block BC), and the back corona detection is performed in the same way than in
case of sparks.
The operating parameters pertaining to the normal set, have to be adjusted to the best col-
lection efficiency, e.g. under easy operating conditions where back corona is not present.
The HRM-parameters have to be adjusted to the best collection efficiency at high dust re-
sistivity. When the +12 V of the control unit is applied to the optional input 1 (IN1) via a
relay contact, the condition for selecting the HRM-parameters, is that the parameter HRM
function is set to 1. When this is 0, the normal set is always the valid one.
This takes place by choosing between two current limits as shown below:
The activation occurs if the parameter RCO function is set to 1 and the rapping control
is commanding rapping of the collecting plates. This is not valid if the control unit is com-
manding continuous rapping.
The use of the option RCO function set to 1 excludes the simultaneous use of the op-
tion POR function set to 1.
50001-08 18
2) External signal
• the simultaneous use of the option "Power Off Rapping", activated externally (i.e.
POR function set to 2).
• the simultaneous use of Cont.Rap.Mode in the rapping control system set to 1.
• If the parameter POR function is set to 1 or 3, it starts a count of the number of rap-
ping cycles commanded by the timer 1 (but not in case of continuous rapping).
• The use of POR function equal to 1 or 3 excludes the simultaneous use of RCO
function equal to 1.
2) External signal
• If the parameter POR function is set to 2, it starts a count of the numbers of rapping
cycles by detecting the activation of the option input 2 (IN2). It means that during rap-
ping, the external rapping system has to connect a relay contact between the +12V of
the control unit and IN2.
The function is controlled by the parameteren POR Period (adjustable between 1 and
500), which permits to choose the rapping "n" where POR has to take place.
19 50001-08
t-ON + t-OFF
The blocking period takes place immediately after the time delay has
elapsed and it has a duration determined by the parameter t-ON POR (adjustable be-
tween 10 and 200 s).
• If the parameter t-ON is changed, the parameter t-delay POR is changed accord-
ingly by the automatic control unit.
50001-08 20
The use of the parameter VOL-function set to 2 excludes the use of the option
Rap.Sync.Mode in the rapping control.
When Manual Mode is active, the current is not reduced after sparks and therefore the
spark rate cannot be controlled. For this reason, the automatic control must not be left in
this mode of operation. An automatic change to normal current control takes place if the
keyboard is not operated in a period of 3 minutes.
When Manual α Mode is active, the spark rate cannot be controlled; therefore, the
automatic control may not be left in this state. An automatic change to normal current con-
trol takes place if the keyboard is not operated in a period of 3 minutes.
This mode of operation is indicated by displaying the text WARN.: TEST MODE
instead of I DC, and by displaying TEST on characters 3 to 7 when the key
STATUS
is pressed.
This test mode is automatically reset 18 hours after its activation or after the power to the
control unit has been switched off. In case of automatic reset the main contactor is tripped
automatically and the parameter is set to 0.
Manual reset is possible at any time by setting the parameter Manual Mode to 0.
21 50001-08
After the connection of the main contactor, the current is regulated from 0 to the selected
upper limit, at the normal rate of rise. The current is kept at this level independently of the
voltage level; i.e. no tripping occurs in this undervoltage condition after the normal time
limit of 30 s has elapsed.
This range can be limited to 120°, in such a way that the earliest firing occurs at 60°. This
can be used in certain cases to avoid saturation of the HV transformer.
The parameter α Aux.Min. is used for activation of this facility, and the firing range is
calculated by means of the parameter α Aux/Main plus an offset of 30°. The activation
of the auxiliary firing occurs only if the parameter α Aux.Min. is less than 175°.
176° Reserved
give a normal firing range with DC operation (Nec = 1), but in case of EC operation (Nec ≥
3), it is limited to 126° (96°+ 30°) corresponding to an earliest firing of 3 ms (at 50 Hz).
50001-08 22
4. OPERATING INSTRUCTIONS
The operation of the control unit takes place from a control panel as shown in Fig. 4.1 be-
low.
The HV power supply is switched on and off by means of pushbuttons (1) lighted by built-
in LEDs.
Parameter readouts and entering of new parameter values are carried out via a keyboard
(2) with membrane keys.
The readouts are normally displayed on a 16-characters digital display (3). The mean cur-
rent and the mean voltage can also be read on analog panel instruments (4).
Further, there is a window (5) for LED indication of faults detected internally by the micro-
processor and a field (6) for indication of rated values (current and voltage) and identifica-
tion of the precipitator bus-section controlled by the PIACS DC.
23
50001-08
4.1 Start/stop
A prior condition for switching the HV power supply on, is that no external or internal
alarms are reported. These alarms are shown blinking on the display. If the unit is not
ready to start and an alarm message is shown, this can only be removed by pressing the
ENTER/
RESET
key after the cause of the fault has been corrected (see section 4.4).
Alarms messages can be temporarily removed, e.g. by pressing a parameter key. But they
will be again displayed automatically after 20 s without use of the keyboard, or after press-
ing a read-only key or STATUS.
Note that the message INTERLOCKING is automatically reset when the activation signal
disappears.
The HV power supply can be turned on by pressing the ON button I , unless remote op-
eration has been selected.
The HV power supply is turned off by pressing the OFF button O . The OFF button has a
mechanical interlock to prevent remote start. If the "alternative wiring" has been used in
connection with stop caused by alarms, the display will show INTERLOCKING when button
O is pressed, as described in manual 50101.
When the HV power supply is turned off, O is lighted and I is off. The order is re-
versed when the HV power supply is in operation; then I is lighted, deflections are ob-
served in the panel instruments and the precipitator current is shown on the display.
The ON and OFF buttons activate auxiliary relays that form part of the relay command
system of the precipitator. These are shown in the electric diagrams for the respective in-
stallation. Remote operation can also be performed via the relay command system.
The keyboard (2) is the operator's direct access to communication with the microprocessor
control. As a safety measure against erroneous settings, the access to parameter changes
is limited to three access levels:
All the parameters can be displayed without any kind of access limitation. All measuring
values and status indications (7) as well as level 1 and level 2 parameters, have a dedi-
cated key. Level 3 parameters require a code (see section 4.3.4). When a key is pressed,
a "beep" sound is always emitted.
During use of the operating keys (8) the following messages may be displayed:
PASSWORD
ENTER PASSWORD
When the key is pressed the display shows:
When an illegal password is entered, the display ILLEGAL PASSWORD
shows:
When more digits than programmed are entered, TOO MANY DIGITS
the display shows:
When a parameter value outside the allowed range ILLEGAL VALUE
is entered, the display shows:
When pressing a key not expected in a given se- ILLEGAL KEY
quence, the display shows:
This message is displayed, e.g. when the user attempts to change a level 3 parame-
ter from level 1.
The value will remain displayed, until a new keystroke displays other values or parameters
or until a period of 3 min. without entries has elapsed. The following values and messages
can be observed on the display:
25
50001-08
I DC mA
U DC kv 1th keystroke
Spark-Rate /m
H FRM BC 3 13 A1
STATUS It shows the status of the control unit, i.e. the various
events that may occur during operation, alone or simulta-
neously. Here are shown some of the possible messages.
A complete survey is given on the next page.
50001-08 26
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
H _ F R M _ B C _ 1 • 1 3 ^ A 1
1: type 1 spark
2: type 2 spark
After that, the setting can be changed by entering the new value and then pressing the key
ENTER/
RESET
.
As an indication of accept of a new setting, the display is turned off during one second
which is perceived as a blinking.
The parameter with the new setting is shown on the display during 3 minutes.
If the keyboard is not operated in this period of time the display automatically changes and
shows the precipitator current.
For the sake of clarity, related parameters are grouped under the same key. This key acti-
vates a scrolling stack that shows the parameters in a definite sequence.
I DC Limit mA
HRM I Lim. mA
Set-Back mA
HRM SetBck mA
Spk Set Rt /m
HRM Spk Rt /m
BC Measure. /h
This key shows and sets the frequency for the back corona
detection measurements. The frequency can be adjusted be-
BACK tween 1 and 60 times/hr, but only if
CORONA α Aux.Min. > 175°. The detector is put out of operation
by entering the value 0.
t-Recovery ms
HRM t-Rec. ms
t-FastRamp s
t-Quench ms
TIME
SETTINGS
t-Recovery sets the recovery time after a spark in the
range 40 to 1000 ms. HRM t-Rec. is the valid one when the
HRM-function is active.
t-FastRamp sets the waiting time for fast regulation of the
precipitator current, in case sparks do not occur. The setting
range is 2 to 300 s.
t-Quench sets the blocking time for the firing pulses after
type 2 sparks. The setting range is 5 to 500 ms.
Nec min
0: Local control/setting
1: Remote control/setting
2: Both Local and Remote control/setting
Parameter changes at level 2 require entering of a password. The password is 222 and it
is entered by means of following keystrokes:
PASSWORD 2 2 2 ENTER/
RESET
As an indication that the user is at this level, the message Level 2 is shortly displayed
and thereafter the parameter setting is shown blinking at 1.5 Hz.
The parameter to be changed is displayed by pressing its respective key, as shown before
and the new value is entered.
ENTER/
RESET
Finally, the value is stored by pressing in the same way as in case of level 1 pa-
rameters.
A return to level 1 occurs automatically if the keyboard is not operated within 3 min. or by
PASSWORD
ENTER/
RESET
pressing followed by .
In this case there is not a dedicated key and the parameters can only be displayed by en-
tering a code. Level 3 parameters are considered as factory settings and eventual
changes are reserved to FLS Airtech specialists; therefore the display text is only shown
in English. The parameters can only be displayed by means of following keystrokes:
PASSWORD
X ENTER/
RESET
where X is the parameter code (one or two digits), whose value is shown in the follow-
ing survey:
50001-08 32
Level 3 parameters
CODE DISPLAY FUNCTION DESCRIPTION
1 Language: It sets the desired language on the display. Level 3
parameters are only shown in English. Settings be-
tween 0 and 99. See section 4.5.4.
2 Frequency Hz This parameter is set to the line frequency of the
plant. Only 50 and 60 Hz are allowed.
3 IDC rated mA This parameter is set to the rated current of the HV
power supply.
Adjustable between 50 and 2500 mA.
4 IDC ScaleFac It indicates the scaling factor of rated current
IDC rated related to full scale value for a current
measurement (1 V mean value). The standard value
is 1.00 but values between 0.75 and 1.25 can be
selected in case of special client demands.
5 UDC Rated kV The parameter is set to the rated voltage of the HV
power supply. Adjustable between 60 and 150 kV.
6 UDC upp.lim kV If this limits is exceeded for more than 1 s an over-
voltage alarm is repported. Adjustable between 15
and 150 kV.
7 UDC low.lim kV It indicates the limit used for the alarm "undervoltage
during 30 s", and it is also used as undervoltage
limit in the detection of type 2 sparks (50% of the
parameter value). Adjustable between 2 and 15 kV.
8 UDC start kV It determines the aimed level for the precipitator
voltage immediately after the connection of the main
contactor. Further, it determines a lower voltage limit
used in the voltage recovery after sparks (50% of
the parameter value).
Adjustable between 10 and 55 kV.
9 Spec.reduc. mA It determines an aditional current reduction that is
added to the normal setback, in case of a spark is
closer than 0.5 s from the preceeding one. Adjust-
able in mA between 1 and 25% of the rated current.
10 RCO I Lim mA It indicates the current limit valid when the RCO-
function is active. Adjustable between 0 and rated
current. It can be used in connection with the rap-
ping of the collecting plates
(RCO function), or CO-monitoring. In the last
case a typical setting is 0.01 mA/m2 of collecting
plate surface. See also the ESP operating instruc-
tions.
33
50001-08
The following 3 parametere are primarily used as readouts and so they have no influ-
ence in the automatic control.
60 µP-Error This flag (which can only assume the values 0 and
1) shows 1 after a fault detected in the µP-system.
The condition is that the fault has been corrected
and the HV power supply has been put into opera-
tion again.
70 Ty1 Spk This readout shows the number of type 1 sparks.
The maximum value is 299.999.999 and the
counter can be reset by entering 0.
71 Ty2 Spk This readout shows the number of type 2 sparks.
The maximum value is 299.999.999 and the
counter can be reset by entering 0.
87 t-ON POR s It determines the duration of the blocking interval
when the POR-function is activated. Adjustable
between 10 and 200 s.
88 POR period rc It indicates the time interval between 2 POR-
blocking intervals expressed as the number of
rapping cycles (rc).
Adjustable between 1 and 500 rc.
89 t-delay POR s Time delay before the blocking interval can occur.
Adjustable between 0 and 200 s.
When a particular level 3 parameter is shown on the display, the subsequent parame-
ENTER/
RESET
ters can be displayed merely by pressing .
Changing of parameter values requires the use of password. This is entered by means
of the following keystrokes:
PASSWORD
X X
X X ENTER/
RESET
Afterwards the display will shortly show Level 3, and the parameters readouts will be
shown blinking at 1.5 Hz. A particular parameter is displayed by using its parameter code
shown in the above table. The new value is entered in the normal way and is stored by
ENTER/
RESET
pressing . While staying at level 3, level 1 and level 2 parameters can be displayed
and changed in the usual way without leaving level 3.
Return to level 1 occurs automatically if the keyboard is not operated in a period of 3 min-
PASSWORD
ENTER/
RESET
utes. Return to level 1 can also take place by pressing followed by .
37
50001-08
When using the existing facilities for remote control (start/stop) via the serial communica-
tion bus (PIACS Bus), sometimes the so-called "alternative wiring" has to be employed.
See a separate manual for more details.
In case of fault or interlock activation, the respective contact will open deenergizing relay
(e), and causing the disconnection of the main contactor. Moreover, the fault indication is
transmitted to the microprocessor PC board via the interface PC board (CS28.1), as the
+12 V disappears from the alarm input in question. Afterwards, an alarm message is
shown on the display (blinking at a frequency of 1.5 Hz) and the microprocessor discon-
nects relay (e) too, via the relay contact shown in Fig. 4.2 as "CPU-alarm". See section
4.4.
Because relay (e) is disconnected directly by the alarm signalling contact, extra safety is
obtained. When the cause of the fault has been corrected, the alarm message on the dis-
ENTER/
RESET
play can be reset by pressing . This is not necessary when the cause of the discon-
nection has been an interlock.
In case of simultaneous alarms, only the first registered alarm will be indicated on the dis-
play. The display will show the next alarm message after the first fault has been corrected
and the respective alarm message has been reset.
There are some internal alarms, detected by the microprocessor, which results in the a
disconnection of the relay contact "CPU-alarm".
All the alarms and interlocks are described in the following survey:
4.5 Miscellaneous
a) Storage
PASSWORD
2 7 X X X ENTER/
RESET
b) Call
The optimal set of parameters can be called at level 2 or 3. At one of these levels, the
following should be entered:
PASSWORD
9 2 2 2 ENTER/
RESET
In this case, the control unit itself will set the parameters (both the normal and optimal
set of parameters) to the pre-programmed values.
41
50001-08
SYSTEM_INIT
Note that the pre-programmed values are not adjusted to suit the particular precipitator
plant. The rated values of the T/R set, for instance, will be set to 90 kV, 1000 mA and
50 Hz. Therefore, a "system initialisation" should always be followed by a control of all
the parameters. Afterwards, they should be stored as an optimal set of parameters.
This function can also be activated from the keyboard. Being at operator level 3 the
following should be entered:
PASSWORD
2 5
7 X X X ENTER/
RESET
where X X X is the level 3 password and the display will also show:
SYSTEM_INIT
4.5.3 Messages
a) Line voltage disturbances
After certain voltage disturbances described in the EMC directive, the control unit will
command an automatic reconnection. This reconnection affects the main contactor of the
T/R set and the rapping systems, respectively.
This automatic reconnection takes place only when local start from the PIACS DC is al-
lowed. This reconnection can be disabled by setting parameter nr. 44
Autostart En. to 0.
In case of reconnection the display shows AUTOMATIC START. This message disap-
pears, when any key is pressed.
b) µP-fault
When the fault µP CHECK ERROR has occurred, after reset, the HV power supply can be
started again. If the keyboard is not operated during 3 minutes, the display will show µP
ERROR WARNNING and the red LED will flash (position 5 in Fig. 4.1). This indicates that
the microprocessor system is not 100% in order and operation can proceed under special
attention. Besides, the keyboard can be operated in the normal way. If only the red LED is
flashing, the position of the jumpers J5 and J6 has to be checked.
c) Test mode
This operation mode is also indicated on the display as TEST when the key
STATUS
is pressed.
50001-08 42
The number of languages implemented depends on the version of the component D17 on
PC board CU19. Therefore, please consult the documentation for the particular plant for
more details.
If the EPROM D17 is not mounted, or the desired language code is not implemented in it,
the texts are displayed in English.
43 50001-08
5.1 Commissioning
a) PC board CU19
50001-08 44
* Only J5, J6 and S1 can be controlled without dismounting the PC boards. Therefore,
jumpers J1 to J4 should only be checked in case of unnormal operation.
J5 and J6 are mounted on the back of the PC boards. When the jumper is not
mounted, this corresponds to a virtual mounting in position 1 - 2.
Change-over switch S1: is used for setting the communication speed in the serial
line; its standard position is 2. For more details please
consult the respective manual (50101).
b) PC board CS28.1
Remote Remote
indication IDC indication UDC
Signal range J1 J2 J3 J4 J5 J6
4 – 20 mA* A A A A A A
0 – 20 mA A A B A A B
0 – 10 V B B B B B B
*) Standard jumper position
F1 are "picofuses", serie 275, and consists of 4 pieces located in a row with F1/1 on the
top.
The signals for remote indication of UDC and IDC are galvanic isolated from the other
electronic circuits, but not mutually.
Pot. R75 and 138: are used for calibration of the panel instruments on the control
panel (factory adjustment).
Pot. R85: adjusts the sensitivity of the spark detector according to the follow-
ing curve:
47 50001-08
c) PC board AA30.1
Jumper J1 Jumper J2
1-2 2-3
When line frequency is 60 Hz Manual firing angle control by R30
2-3* 1-2*
When line frequency is 50 Hz Aut. firing angle control by PIACS DC
*) Standard position
Pot. R30: adjusts the firing angle, when J2 enables this function. (Stan-
dard setting is 3).
Some functions can be tested when the control unit is energized and the main contactor is
disconnected. But if the main contactor becomes energized without pressing the start but-
ton, the AC supply has to be turned off and the control system must be checked.
50001-08 48
IDC ScaleFac
A HV power supply delivered by FLS Airtech uses a current signal level of 1 V at rated cur-
rent. Therefore, the parameter has to be set to 1.00.
When upgrading HV power supplies from other manufacturers, special demands may be
met; e.g. in a T/R set with a rated current of 800 mA, 1V could correspond to 1000 mA
(fuld scale value). In this case the parameter has to be set to a value equal to the relation
between the rated current and the full scale value:
UDC upp.lim
This parameter monitors the maximum permissible average value of the precipitator volt-
age. The main contactor is disconnected if the voltage has been higher than the set level
more than 1 s.
Use 90 % of U DC rated as initial setting. If the maximum average voltage during opera-
tion is known, use this value plus 10 kV as setting.
49 50001-08
These two parameters determines the proportional and the integral factor respectively, in
the PI controller used in the automatic control of the precipitator current. This controller is
realized in the software of the unit. The 2 parameters have to be set in a way that the regu-
lation is fast and the overshoot is acceptable.
RecoverCurve
By means of this parameter it is possible to choose the aimed voltage level used for the
regulation of the precipitator voltage after sparks.
A high parameter value gives a high voltage level and viceversa. A criterion for the optimi-
zation of this setting is that it may not cause multiple sparking, i.e. a new spark during the
voltage recovery after the previous one. A spark occurring in the recovery period is indi-
cated as type 2 spark on the display (character nr. 16).
A correct setting depends on rated voltage and the capacitance of the precipitator bus-
section.
The setting is about 15° as standard, (or 915° in case the voltage recovery is performed
according the peak value). See section 3.2.
- about 5° lower if high current density is installed, i.e. > 0,5 mA/m2 (the current density is
the rated currrent divided by the bus-section collecting plate area).
- about 5° higher in case of high precipitator capacity, i.e. small duct spacing (e.g. 250
mm) or special discharge electrode type or configuration (e.g. 2 electrodes pr. plate).
These parameters can only be used during EC operation and have the purpose of avoid-
ing saturation of the HV transformer. α Aux/Main determines the time interval between
the auxiliary and the main firing angle of the thyristors, and
α Aux.Min. determines a lower limit for the auxiliary firing angle.
A high value of α Aux/Main and a low value of α Aux.Min. give a greater effect, but
the waveform of the precipitator voltage is less pulsating (lower riple). α Aux.Min. >
175° (preset value) puts the auxiliary firing out of operation, which causes a more pulsating
precipitator voltage (higher riple). This setting is necessary if the minimum (trough) value of
the precipitator voltage has to be measured or/and the back corona detector has to be
used. The consequence is that some types of HV transformers get saturated. See section
3.10 about the correct setting in order to avoid saturation.
α EC Spark
This parameter determines the number of degrees by which the firing angle is delayed af-
ter spark (EC operation), just after the voltage recovery. In order to obtain a faster reaction
after spark, α EC Spark has to be as small as possible.
50001-08 50
t-Block BC
This parameter determines the thyristors blocking time used in detection of back corona
when sparks do not occur. In case of severe back corona, the parameter value should be
increased if the PIACS DC does not detect its presence.
Autostart En.
This parameter activates an automatic reconnection of the main contactor after a short
drop of the line voltage, according to the European regulations in force. See section
4.5.3.a. These reconnection of the HV power supply and rappers is enabled when the pa-
rameteren is set to 1.
The recommended setting for Autostart En. is 1 and this may only be changed to 0 in
case of the client demands it.
Normally, most of the detected sparks should be type 1. It is recommended to check that
these are real and they are not caused by a too sensitive setting of the potentiometer R85.
This can be controlled by:
• Turning R85 c.c.w., which gives a less sensitive detection. If the precipitator cur
rent level gets higher, with an stable display of current and voltage (i.e. neither
real og false spark are detected), this should be considered as indication that the
setting of R85 was too sensitive.
The precipitator current has to be reduced after a spark. The adjusted reduction may be
STATUS
increased so as to see clearly that it is actually taking place. Press to verify that
mainly type 1 sparks are occurring.
Measure the spark rate and if the FRM-function is not activated between the sparks, the
measured value should correspond to the adjusted value.
51 50001-08
a) Undervoltage
b) Overvoltage
The HV power supply is brought back to its normal state and the overvoltage alarm is con-
trolled in the following way:
This control is normally performed by observing the panel instruments and the status mes-
sages on the display (see section 4.3.1).
Finally, check the parameters in such a way that their settings correspond to the existing
or expected operating conditions and then store them as an optimal set of parameters
(see section 4.5.1).
50001-08 52
5.2 Troubleshooting
The control unit can control HV power supplies of different manufactures. Therefore, the
user is referred to the respective instruction in case of faults which lie outside the unit.
In case of faults in the control unit, the troubleshooting procedure should be based on lo-
calizing the problem in one of the three PC boards which the control unit consists of. After
that, the faulty PC board should be replaced.
It is a prior condition that the AC supply voltages delivered by transformer in the control
cabinet are in order (see Fig. 2.3 and the system documentation) and the various connec-
tors are correctly mounted.
It is important to be able to determine if the fault exists inside or outside the control unit.
The control unit makes it possible to distinguish if the fault resides in the inter-
face/microprocessor part, in the remaining part of the HV power supply or in the electro-
static precipitator.
As mentioned in section 5.1.1 c) the firing PC board AA30.1 can control the firing angle of
the thyristors directly with potentiometer R30, when jumper J2 is mounted in position 2-3.
An internal oscillator is used and it can vary the firing angle between 165° og 33°. A late
firing (towards 165°) is obtained when R30 is turned clockwise. (CW).
If the precipitator current can be controlled by turning R30, the fault resides on the PC
boards CU19 or CS28.1.
However, it is also possible to check if fuses F2 and F3 (on PCB CS28.1) are burnt, by
measuring the 24 VDC between terminals X15-20 and 21 on terminal PC board HX01. As
alternative, the following visual check can be performed:
• If F3 is burnt, the panel instruments show full scale deflection and alarm MAINS
SYNC.FAIL. is given.
• If F2 is burnt, the panel instruments deflects in the wrong direction and analog
measurements on the display are showing between 50 and 200% of rated values.
• If both F2 and F3 are burnt, there is no light in the ON/OFF pushbuttons and alarm
HIGH P OIL TANK is given.
On PCB CS28.1 are located 4 pcs. fuses F1 for protection of internal circuits. Therefore,
they are not important during troubleshooting, because in case of burn-up the PC boards
CS28.1 or CU19 are considered to be defective. Therefore, the following procedure must
be followed only in case the service personnel is familiarized with the circuits of the sys-
tem.
• If the output lines for remote indication or data communication had been ex
posed to external voltage sources, fuses F1/1, F1/3 and F1/2 may be burnt.
To determine in which of the two PC boards the fault has occurred, the following main rule
can be utilized:
53 50001-08
If the man/machine communication is working, i.e. if the display and keyboard is in order
and no microprocessor faults have been reported, the fault very probably resides in the
interface PC board CS28.1; vice-versa if the man/machine communication does not work,
then the fault is located in the PC board CU19.
When requiring assistance from FLS Airtech, it is important to indicate the version num-
ber of the software. This can be displayed by means of folowing keystrokes:
PASSWORD
1 X
6 0 ENTER/
RESET
6. SPECIFICATIONS
6.1 Signals
Current input: +1 V at rated current
Voltage signal:
Signal amplitude -10 V at rated voltage
Input impedance 1.5 MΩ (pure resistive)
Voltage divider:
Type resistive/capacitive or pure resistive
Note: The "local start" relays (for HV power supply and rappers) gives only a start impulse.
6.3 Environment
Ambient temperature: - -25°C to 70°C (storage)
0°C to 45°C (operation)
Relative humidity: IEC 654-1 group B2
Max. height above sea level: 2000 m
55 50001-08
SECTION B
Functionally, the rapping control is a subsystem, but is fully integrated into the control of the HV
power supply.
As the lay-out in each case depends on the particular precipitator plant, for a complete description,
please consult the electrical documentation.
8. CONTROL STRATEGY
The rapping control consists mainly of two time sequence functions (timers), where the operation
RAPPING
and pause periods can be set individually by means of parameters grouped under the key.
Each timer has an output to a command relay (c or d in Fig. 7.1), which can control the rapping mo-
tors for discharge and collecting systems or vibrators for gas distribution screens. Besides, the op-
eration of the motors can be determined by commands ordering forced pause or operation.
9. CONFIGURATION
The two timers have a configuration number corresponding to the rapping motors they control. The
configuration is performed by means of the level 3 parameters RAPtimer1: and RAPtimer2:,
having parameter codes 83 and 84, respectively. Following possibilities exist:
• The timer may have assigned names from M0 to M9M9M9, by entering a number between 0
and 999 for the respective configuration parameter.
• M0 means that the timer is not used, i.e. its output is not active. The control unit does not ac-
cept numbers in the range 1 - 999, that are multiplum of 10. For instance, following combina-
tions are possible:
RAPPING
Then the parameter texts belonging to key will be:
t-OFF M1 m
t-ON M1 s
t-OFF M2 m and
t-ON M2 s
57 50001-08
10. OPERATION
The activation takes place, when parameter Cont.Rap.Mode is set to 1 and +12V are applied to
the optional input IN2 via a contact relay.
If Cont.Rap.Mode is set to 1 and IN2 is not activated, the operation and pause periods will be de-
termined by the respective parameter in the usual way.
The use of Cont.Rap.Mode equal to 1 excludes the possibility of using the option
RCO function and POR function equal to 2 in the control of the HV power supply.
If the parameter Rap.Sync.Mode (setting 0 or 1) is set to 1 and IN3 is activated, the pause period
in the timer controlling M1 will continue so long as IN3 is active. If the timer is on its operation period
when IN3 is activated, it will remain in operation.
The synchronization function should be used carefully in order to avoid a pemanent blocking of the
rapping system in a particular bus section of the electrostatic precipitator.
The use of Rap.Sync.Mode equal to 1 excludes the possibility of using the option VOL Function
equal to 2 in the control of the HV power supply.
50001-08 58
However, this function can only be fully utilized, if the rapping of all the precipitator fields is turned
on simultaneously. The asynchronous start is obtained by adding the value of the parameter
t-DELAY-ON (setting range 0 to 720 min.) to the first pause period after turning the rapping sys-
tems on.
If the parameter t-DELAY-OFF (setting range 0 to 720 min.) has been set to a value greater than
0, the control unit will activate the delayed OFF function approximately 5 s after the HV power sup-
ply is turned off, provided that the rapping systems has not been turned off.
Activation of the delayed OFF-function means that the rapping systems are continuously operating
during the adjusted time t-DELAY-OFF, after which they will be in continuous pause.
The delayed OFF function is reset if the HV power supply is turned on, or if the rapping systems are
turned off. The delayed OFF function is not activated if the normal continuous operation is acti-
vated.
59 50001-08
If the automatic control of the rapping systems has received an alarm, the respective text is shown
RAPPING
blinking when is pressed or if the keyboard has not been operated during 3 min.
The following scrolling stack functions are obtained with a normal timer configuration, after pressing
RAPPING
key :
The 1st keystroke shows the status of the rapping system control, which may be
or an alarm message in case the system is in the alarm state. A detailed description follows.
The 2nd and 4th keystroke give the pause periods for the two timers. Continuous operation is ob-
tained by setting them to 0 min. The longest pause period is 720 min.
The 3rd and 5th keystroke give the operation period of the timers, which can be set between 0 and
400 s. Setting them to 0 gives a permanent pause state. It is not possible to set a timer to continu-
ous operation and permanent pause at the same time.
The permanent pause state may be chosen only as a temporary setting, e.g. during the measure-
ment of I-V characteristics. This setting is not longer valid after a start-up following an interruption of
the line voltage.
50001-08 60
The first field indicates the status of the rapping system control, field two and three indicates timer 1
and timer 2 status, respectively, while the fourth field is reserved.
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
R U N O N O F F _ _ _
Parameter survey
a) Timer function 1 OK
b) Timer function 2 OK
e) Ready to start (alarm)
Q) Safety switches
When using the remote control facilities regarding start and stop via the serial communication bus,
in certain cases the so-called "alternative wiring" has to be used. See a separate manual for more
details (50101).
The basic principle is the same as in the control of the HV power supply, i.e. an electrical interlock
circuit which is monitored by the control unit.
If there are no alarms or other interlocks, the relay (e) will be energized.
Of particular interest in this monitoring system are the contacts (a) and (b), which are intended for
monitoring of the rapping systems operation, both the feedback signal from the main contactors as
well as thermal overload and a possible monitoring with a speed monitor.
63 50001-08
A timer is started when a start command is given, or if a previously registered activation signal dis-
appears. If the activation signal has not arrived before the time determined by ALARM-DELAY has
elapsed, the CPU will indicate an alarm via relay (e). See Fig. 11.
The mentioned alarms are also shown blinking on the display when the status of the rapping sys-
tem control is read out.
Note that the 2 alarm messages 1) and 2) are determined by the configuration parameters RAP-
timer1: and RAPtimer2:.
In case of RAPtimer1: for instance is configured to control M4 and M5, the alarm message dis-
played is FAILURE M4M5.
50001-08 64
Then the interlock system can be tested. Disconnect the signal on the terminal strip and check the
alarm message on the display and check that the system cannot be started.
Set operation and pause periods to a small value and check these.
Disconnect the monitoring signal during operation and check the alarm.
The parameter settings at delivery are carried out based on the expected conditions of operation
and the precipitator operating instructions. The operation period (ON time) should normally have a
duration corresponding to a complete revolution of the rapping shaft.
The optimal set of parameters is stored as described for the control of the HV power power supply.
See section 4.5.1.
13. SPECIFICATIONS
These are described in Section A covering the control of the HV power supply. See Chapter 6.
---o0o---