You are on page 1of 1

Technical Offer: 0951/17-B

Earthing Transformer (Neutral Point Coil) with IP21 enclosure

Dry type impregnated technology, Natural air cooling (AN).


Ambient temperature < 40°C; altitude < 1000 m ; humidity < 90%, INDOOR APPLICATION.
In accordance with CEI 60076-6 standard.

Network Frequency: 60 Hz Network voltage: 480V (without tapping)


Permanent current in neutral: 350A (116A for each phase) P=96.5kVA
Fault current in the neutral: ≤2000 A during 10 seconds
Coupling: Zn

Additional resistance in neutral supplied separately: 0.00968 ohm at 350A permanent and 2000A 10sec. in
IP21 enclosure.
Permanent losses in this resistance = 1.2kW (see the dimensions of the resistance in the attached drawing).

Thermal insulation class : H


Temperature rise class : H
Winding material : Aluminium
Rated Voltage insulation level : 1.1 kV
Total losses (at 115 °C): 3 kW (exact value to be confirmed after order)

Connections HT:
From top.
Dismountable plate for cable glands (cable glands not included)
Enclosure:
- RAL 9003 (BCV Standard)
- Index of protection : IP21 IK07 – For indoor application
- Equipped with Lifting lugs

Accessories: - Rating Plate - Bi-directional rollers


Drawing language, Rating plate and test reports: English

Dimensions IP21 (+/- 10% Tolerance) :


Length= 1310 mm ; Width = 900 mm ; Height = 1340 mm ; Weight = 360 Kg

ZI Allée des Justices Filiale de Schneider Electric Industries S.A.


85200 Fontenay-le-Comte - France N° ident TVA : FR 69 572 029 874
Tél. 33 (0)2 51 53 22 00 Siège social : 85200 Fontenay-le-Comte - France
Fax 33 (0)2 51 51 06 45 S.A.S. au capital de 476 560 €

Siret: 572 029 874 000 60 RCS La Roche-sur-Yon 572 029 874 - NAF 2711