Seismic and Wind
Seismic and Wind
Na = 1.0
By R&P:
Nv = 1.12
Low‐Rise Buildings ( h ≤ 18m ) : Component and Cladding Simplified Procedure
by R&P:
Adjustment factor, λ = 1.455
Purlin Loads
SDL = 0.387 KN/m
LL = 0.455 KN/m
WL1 = 1.749 KN/m (windward pressure)
WL2 = 4.873 KN/m (leeward suction Zone 2)
= 2.926 KN/m (leeward suction Zone 1)
a= 0.900
Superimposed Deadloads (T204-2):
Topchord:
Roofing & Insulation: 0.125
Purlin LC100x50x15x2 (2"x4"x2.0mm C-Purlin) 3.417kg/m
weight (kg/m) = 3.417
(weight*9.81/1000)/S = 0.042
Ceiling & Utilities: 0.358
0.5251 KPa x truss spacing = 1.181 KN/m
Bottom chord:
Ceiling & Utilities: 0.358 KPa x truss spacing = 0.806 KN/m
Liveload (T205-3) 0.6 KPa x truss spacing x CosƟ = 1.27974 KN/m
Windleft / Windright
windward (pressure) = 3.779 KN/m (all zones)
leeward (suction) = 7.623 KN/m (zone 1)
10.793 KN/m (zone 2)
Truss Loads
Deadload = 1.181 KN/m (topchord)
= 0.806 KN/m (bottomchord)
Liveload = 1.280 KN/m (topchord)
Windward = 3.779 KN/m (pressure)
Leeward = 7.623 KN/m (suction, Zone 1)
= 10.793 KN/m (suction, Zone 2)